Error Code P2
Error Code P2
M 2-2.3 BMS-2 / P2
20
TRAINING
M 2-2.3 BMS-2 / P2
Code 1 Code 2 Description Reason Solution Shown as Function
33. 01 Power supply > 35V Feed voltage higher than 35V Check feed line, reduce voltage
02 Check feed line, increase voltage (check quality and Flashing code
Power supply < 8V Feed voltage lower than 35V
size of wires)
04-09 undefined
10 Voltage on dump valve not correct, System
Not allowed power on dump valve Check valve for damages or shortcut, check wiring Flashing code
valve might be damaged emergency stop
12 Shortcut in emergency loop Shortcut in emergency loop Check all connected users Flashing code
15 Shortcut on one or more digital outputs
Shortcut on digital output 1-6 Check connected end users. Therefore disconnect Flashing code
1-6
all users and reset system. Then reconnect one by
16 Shortcut on one or more digital outputs System
Shortcut on digital output 7-12 one to find out the faulty user. Check faulty user. Flashing code
7-12 emergency stop
17 Error on digital output 1
Error on digital output 1 Check end user on output 1 Flashing code
feed back error
34. 01-08 Check valve (Danfoss module, Nordhydraulic
Feedback error on analogue outputs Feed power to valve not correct. System
magnetic coils). Flashing code
1-8 (power supply to valve). Defective valve. emergency stop
Check wiring for quality/damages.
35. 01-08 Check valve (Danfoss module, Nordhydraulic
Feedback error on analogue outputs Analogue signal to valve not correct. System
magnetic coils). Flashing code
1-8 (signal to valve). Defective valve. emergency stop
Check wiring for quality/damages.
50. 01-16 Lever 1-16 (analogue channel) active Lever 1-16 activated during start up or Bring lever back to neutral position, restart system. System
Flashing code
during start up. lever defective. If code stays, check lever. emergency stop
51. 01-16
Error on analogue channel 1-16 No safety contact (digital) available. Check lever (Joystick) System
Flashing code
(Comparison analogue/digital AK-DK) Lever damaged. Change if required. emergency stop
52. 01-08 Check valve (Danfoss module, Nordhydraulic
System
Valve error 1-8 (error input) Error signal from valve 1-8. magnetic coils). Change if required. Flashing code
emergency stop
Check wiring for quality/damages.
63. 01 Relay K0 in receiver is not in neutral Reset system.
Error input from start locking.
position. If code stays, change relay.
System
02 Flashing code
Start locked digital channel (switch) Bring switch to neutral position, restart system. emergency stop
Error on start locked digital channel.
not in neutral position during start up. Change switch if defective.
21