Design of 38 Mega Watts Steam Power Plant in Majayjay Laguna
Design of 38 Mega Watts Steam Power Plant in Majayjay Laguna
Design of 38 Mega Watts Steam Power Plant in Majayjay Laguna
PROJECT BACKGROUND
For each economical development of one nation, there is always an increase in the needs
for energy. As the economy in the Philippines grow, the demand in energy also arises due to the
increasing needs of big companies for energy and electricity. The needs in energy is very essential
on every aspect of people’s life, from small devices up to the large equipments, people are using
energy to make it work. To address the increasing needs in power generation, Power plants are built
to sustain the energy needs of our society. Some Power plants sources of energy to create electricity
are scarce and limited, that’s why engineers look for ways to create energy from renewable and
natural energy sources. Fossil fuels are non-renewable, that is, they draw on finite resources that
will eventually dwindle, becoming too expensive or too environmentally damaging to retrieve. In
contrast, the many types of renewable energy resources-such as hydro, wind and solar energy-are
constantly replenished and will never run out.
Each and every year, as the population and economic status of the Philippines grow, the
demand in energy also increases. Based from the latest data of the Department of Energy, the total
dependable generating capacity in the Philippines in the year 2016 was 19,097 MW. The outlook for
electricity demand in energy for the year 2017 and 2018 will also increase as the economy and
population increases. Among the different energy sources which are the Coal, Oil-based, Natural
Gas and Renewable Energy sources, the two that produces a large share of energy is the Coal and
the Renewable Energy. The Philippines depends too much energy from Coal which generates
36.5% of the Philippines total electricity and the Renewable energy sources from Geothermal, Hydro
and Biomass, solar and wind produces 31.4% of the Philippines total electricity. With these data, we
can see that the Philippines are mostly dependent on the Coal which is a non-renewable energy
source.
The Philippines are known for many renewable sources because of its rich natural
resources. These energy sources can be used to generate electricity. From our natural energy
sources, we can solve the continuous needs for energy demand and also help to preserve our
environment. This natural and renewable energy sources also has good sustainability that ensures
1
the good future for our country or society. In selecting the most suitable power plant to be designed,
many trade-offs and multiple constraints are considered especially in the effects of the power plant
on the economy, environment and the sustainability.
Laguna covers a total area of 1,917.85 km2 (740.49 sq mi) occupying the north-central
section of the CALABARZON region in Luzon. The province is situated southeast of Metro
Manila, south of Rizal, west of Quezon, north of Batangas and east of Cavite. Laguna is the third
largest province in the CALABARZON region and the 63rd largest in the entire country. The
municipalities of Cavinti and the city of San Pablo have the largest land areas with
203.58 km2 (78.60 sq mi) and 197.56 km2 (76.28 sq mi), respectively. The municipality
of Victoria has the smallest land area with 57.46 km2 (22.19 sq mi)
(https://wikivisually.com/wiki/Laguna_(province).
2
Table 1.1.1 Statistics of Laguna Province, Philippines
(https://en.wikipedia.org/wiki/Laguna_(province)
Laguna is powered by electric companies namely MERALCO and FLECO (Laguna Electric
Cooperative, Inc. ). The First Laguna Electric Cooperative, Inc. (FLECO) was incorporated and
registered with the National Electrification Administration (NEA) on April 3, 1973 under Presidential
Decree 269. The operation of FLECO commenced on September 1, 1973 when it took-over the
seven (7) private electric franchises and municipal systems, namely: Siniloan Electric which
covered the towns of Siniloan, Pangil, Pakil, Mabitac and Sta. Maria; Pagsanjan Electric System;
Paete Electric Service; Lumban Electric System; Kalayaan Electric System; Cavinti Electric System
and Calim &. Jamilano Electric Co., which served the town of Famy. Initially, FLECO contracted a
3
loan with NEA used chiefly as payment for taken-over private systems, rehabilitation of old lines,
and service expansion (http://fleco.com.ph/).
(http://124.83.47.8/Fleco%20Online%20Bills/aboutus.php)
4
1.2 STATEMENT OF THE PROBLEM
The constant increase in the needs of power also means that more generation of energy is
needed. Power plants are the main source of immense energy and power. From these, we can satisfy
the continuous increase in the demand of electricity. The most common sources of energy that are
used in the Philippines is Coal, but considering the scarcity and the near depletion of this energy
source, renewable energy and natural gases are also considered in designing the most suitable
power plant.
The designers chose to design a 38 Mega Watts Steam Power Plant to provide sufficient
energy source for the area of Laguna and the municipalities near it. The power plant will be situated
in the municipality of Majayjay, Laguna. The researchers chose this location to increase the energy
production in this area with the help of FLECO and MERALCO electric cooperatives in the distribution
of power for the costumers. In the Distribution Development Plant (DDP) prepared by the Department
of Energy (DOE) clearly shows the annual projected peak demand from 2010 to 2019. The table
shows that FLECO has an increasing need for additional power in the upcoming years.
(https://www.doe.gov.ph/distribution-development-plan)
The proposed power plant design is Steam Power Plant using Coal, Oil or Natural Gas as
energy sources. The study will also consider choosing the best energy source among Coal, Oil and
Natural Gas in terms of its advantage on its sustainability, economical and environmental aspects.
Choosing the most suitable energy source for the steam power plant will be based from the research
and computations made by the researchers. The trade-offs and multiple constraints that will be
considered will highly affect the decision in which type of energy source the steam power plant will
use. Since power plants have a long life, this trade-offs and multiple constraints will affect the design
on the long term that’s why it is very important to consider those factors in selecting a power plant to
design.
5
Table 1.2.1 Energy/Power Management Distribution Development Plan
(https://www.doe.gov.ph/distribution-development-plan)
6
1.3 Projects Objectives
General Objectives:
Specific Objectives:
To design a steam power plant using conventional energy sources such as Coal, Oil and
Natural Gas.
To determine factors and conditions for the selection of the suitable energy source for the
steam power plant that would produce better efficiency and production of power.
To design a steam power plant from the best energy source considering the trade-offs and
multiple constraints and standards.
1.) Manila Electric Company or Meralco (Manila Electric Railroad And Light Company)
2.) Franchise areas of FLECO (First Laguna Electric Cooperative, Inc.)
Cavinti
Pagsanjan
Paete
Pakil
Pangil
Siniloan
Famy
Mabitac
Sta. Maria
7
1.5 Project Scope and Limitations
This project objective is to design two proposed steam power plants with a capacity of 21
MW situated in area of Majayjay, Laguna with an immense potential source of energy namely Coal
and Oil.
For Design Alternative 1: Coal-Fired Steam Power Plant, the following main components to
be included in the design are turbines, boiler, furnace, condenser, steam reheater,
superheater, economizer, steam preheater, stack, condenser and cooling system. The
prospective power plant is planned to be installed at Laguna. The difference of coal-powered
from oil-powered is that the design include furnace and it uses chain grate.
For Design Alternative 2: Oil-Fired Steam Power Plant, the following main components to
be included in the design are turbines, boiler, condenser, steam reheater, superheater,
economizer, steam preheater, stack, condenser and cooling system. The prospective power
plant is planned to be installed at Laguna. The difference of oil-powered from coal-powered
is that the design doesn’t include furnace and it does not use chain grate, instead it uses
burner for combustion.
For Design Alternative 3: Natural Gas-Fired Steam Power Plant, the following main
components to be included in the design are turbines, boiler, condenser, steam reheater,
superheater, economizer, steam preheater, stack, condenser and cooling system. The
prospective power plant is planned to be installed at Laguna. The design of this power plant
is the same from the oil-fired steam power plant; the only difference is the fuel used and the
combustion of fuel.
Among the proposed design, the most suitable energy source that is sustainable, and will
be appropriate to the budget and environment will be preferred for the selection of the final design of
power plant. Also, the designers will consider the computations, trade-offs and multiple constraints
in choosing the best suitable steam power plant.
8
1.6 Project Development
Design alternatives
Applying Trade-offs
Coal-Fired Steam Power
Plant Choosing between what is more
Oil-Fired Steam Power Plant efficient, economical,
Natural Gas-Fired Steam environmental, and sustainable in
Power Plant the 3 alternatives declared
Design Inputs
9
CHAPTER 2
DESIGN INPUTS
2.1 Design Description
The design of steam power plant powered by different alternative sources will be installed in
Majayjay, Laguna. The project aims to design and install a Steam Power plant powered by different
alternative sources to help the electric providers in Laguna such as Meralco and FLECO to cope up
with the increasing demand of electricity in the province.
Laguna covers a total area of 1,917.85 km2 (740.49 sq mi) occupying the north central
section of the CALABARZON region in Luzon. Laguna is the third largest province in the
CALABARZON region and the 63rd largest in the entire country.
10
(http://www.tageo.com/index-e-rp-v-33-d-m3357869.htm)
The Figure shows the geographic area where the power plant will be situated. It is among
one of the municipalities of the province of Laguna.
Laguna’s natural resources are water with about 300 million gallons of underground water
recharged by at least seven principal watersheds. It has Asia’s 3rd biggest lake-the Laguna de
Bay- which ably supplies the Province’s fresh water resource requirements and form part of the
people’s livelihood.
Laguna is nestled in the foothills of three mountains namely, Mount Makiling, Mount Banahaw, and the Sierra Madre
Range that not only provide attraction for the tourism industry and
11
sources of many forest-based products, but also serve as stewards for the clean air that
Laguna generously share. The soil is heaven for those seeking opportunities in agriculture and
horticulture given its richness and fertility.
2.4 Demography
2.4.1 Population
12
2.5 Topography
Laguna Island Philippines has a total area of 175,973 hectares (or about 1,759.7
square kms.), the third largest province in Region IV. Its size is approximately 3.75 percent
of the whole Region IV and about 0.58 percent of the total land area of the country. The
provincial capital is Santa Cruz.
13
2.6 Area Analysis
The power plant is located in the area of Majayjay, Laguna and the total land area and
land used by the power plant is shown on the table. This is the proposed area allocation for the
steam power plant design.
Table 2.6.1 Area analysis of the Steam Power Plant
L A N D U S E
S P A C E A L L O C . A R E A
AREA ALLOWANCE 1 0 , 0 0 0 s q . m
To come up with the best power plant energy source from the three alternatives, the
researchers considered the information released by the Department of Energy (DOE). The DOE
released sufficient and enough data which becomes the standard in choosing the best from the 3
power plant alternative sources to be installed in Majayjay, Laguna.
14
2.7.1 COAL–FIRED STEAM POWER PLANT
.
Coal-fired steam power plant is a good alternative in deciding what power plant to
design because of the advantages it possesses. Coal costs very low price in production and
available in most of the countries. Though abundant, coal is a dirty energy source and is
responsible for global warming emissions. Coal also has significant and harmful
consequences for the environment since burning coal releases toxins such as carbon
dioxide into the atmosphere. Also, coal-fired steam power plant demands heavy water
resources which are suitable in the area of Laguna since it has rich water resources. Overall,
considering coal as a fuel is not good environmentally but is very good economically since
it has the cheapest fuel.
Design Alternative 1:
o Coal-fired Power Plant will run using a fuel with the following composition:
C – 84.05%
H2 – 4.5%
O2 – 6%
N2 – 1.17%
S – 0.55%
Ash – 3.73%
15
Natural Gas use a fossil fuel whose emissions also contribute to global warming,
making it a far less attractive climate solution than lower-and zero-carbon alternatives. But
since the other alternatives also contribute to global warming, this alternative is also good
but problems may arise in the sustainability and availability of the natural gasses.
Design Alternative 3:
o Natural Gas-fired Power Plant will run using natural gas which is almost 100%
Methane with the Higher heating value of 15.4 Kwh/kg (CH
16
2.8 Schematic Diagram
2.7.1 Steam Power Plant Diagram
Nomenclature:
A. Steam Boiler P. Cooling tower
B. Furnace Q. Generator
C. Ash pit R. Transformer
D. Super heater S. Main transformer
E. Economizer T. Pump
F. Air preheater U. Condensate pump
G. Stack V. Boiler feed pump
H. High pressure turbine W. Steam trap
I. Steam reheater X. Forced draft fan
J. Low pressure turbine Y. Atmospheric pressure
K. Condenser Z. Hot saturated air
L. Low pressure heater
M. Deaerator A`. Spray nozzle
N. High pressure heater
B`. Baffles
O. Heat exchanger
17
2.9 Steam Power Plant Parts and Two Types of Boiler:
Components
1. Fire-tube boiler:
2.9.1 Steam Turbine
Here, water partially fills a boiler
barrel with a small volume left above to
accommodate the steam (steam space).
Fire-tube boilers usually have a
comparatively low rate of steam
production, but high steam storage
capacity. Fire-tube boilers mostly burn
solid fuels, but are readily adaptable to
those of the liquid or gas variety.
Steam Turbine is one of the most
important prime movers for generating
electricity. This falls under the category of
power producing turbo-machines. In the
turbine, the energy level of the working
fluid goes on decreasing along the flow
stream.
2.9.2 Boiler
18
2. Water-tube boiler:
In this type, tubes filled with water are arranged inside a furnace in a number of possible
configurations; often the water tubes connect large drums, the lower ones containing water and the
upper ones, steam and water. In other cases, such as a mono-tube boiler, water is circulated by a
pump through a succession of coils. This type generally gives high steam production rates, but less
storage capacity than the above Water tube boilers can be designed to exploit any heat source and
are generally preferred in high-pressure applications since the high-pressure water/steam is
contained within small diameter pipes which can withstand the pressure with a thinner wall.
2.9.3 Furnace
A furnace is a device used for high-temperature heating. The name derives from Greek word
fornax, which means oven. The term furnace can also refer to a direct fired heater, used in boiler
applications in chemical industries or for providing heat to chemical reactions for processes like
cracking, and are part of the Standard English names for many metallurgical furnaces worldwide.
The heat energy to fuel a furnace may be supplied directly by fuel combustion, by electricity such as
the electric arc furnace, or through induction heating in induction furnaces.
Power plant furnaces may have a reheater section containing tubes heated by hot flue gases
outside the tubes. Exhaust steam from the high pressure turbine is passed through these heated
tubes to collect more energy before driving the intermediate and then low pressure turbines.
19
2.9.5 Superheater
A superheater is a device used to convert saturated steam or wet steam into dry steam used
in steam engines or in processes, such as steam reforming. There are three types of superheaters
namely: radiant, convection, and separately fired. A superheater can vary in size from a few tens of
feet to several hundred feet (a few meters to some hundred meters).
In a steam engine, the superheater re-heats the steam generated by the boiler, increasing
its thermal energy and decreasing the likelihood that it will condense inside the engine. Superheaters
increase the thermal efficiency of the steam engine, and have been widely adopted. Steam which
has been superheated is logically known as superheated steam; non-superheated steam is called
saturated steam or wet steam.
2.9.6 Economizer
Economizers are commonly used as part of a heat recovery steam generator in a combined cycle power
plant. In an HRSG, water passes through an economizer, then a boiler and
20
then a superheater. The economizer also prevents flooding of the boiler with liquid water
that is too cold to be boiled given the flow rates and design of the boiler. A common application of
economizers in steam power plants is to capture the waste heat from boiler stack gases (flue gas)
and transfer it to the boiler feed water. This raises the temperature of the boiler feed water, lowering
the needed energy input, in turn reducing the firing rates needed for the rated boiler output.
Economizers lower stack temperatures which may cause condensation of acidic combustion gases
and serious equipment corrosion damage if care is not taken in their design and material selection.
An air preheater (APH) is a general term used to describe any device designed to heat air
before another process with the primary objective of increasing the thermal efficiency of the process.
They may be used alone or to replace a recuperative heat system or to replace a steam coil.
The purpose of the air preheater is to recover the heat from the boiler flue gas which
increases the thermal efficiency of the boiler by reducing the useful heat lost in the flue gas. As a
consequence, the flue gases are also conveyed to the flue gas stack or chimney at a lower
temperature, allowing simplified design of the conveyance system and the flue gas stack. It also
allows control over the temperature of gases leaving the stack.
2.9.8 Feed Water Heater (Low Pressure Heater and High Pressure Heater)
A feedwater heater is a power plant component used to pre-heat water delivered to a steam
generating boiler. Preheating the feedwater reduces the irreversibility involved in steam. This
reduces generation and therefore improves the thermodynamic efficiency of the system. This
reduces plant operating costs and also helps to avoid thermal shock to the boiler metal when the
feedwater is introduced back into the steam cycle.
In a steam power plant, feedwater heaters allow the feedwater to be brought up to the
saturation temperature very gradually. This minimizes the inevitable irreversibility associated with
heat transfer to the working fluid. The energy used to heat the feedwater is usually derived from
steam extracted between the stages of the steam turbine. Therefore, the steam that would be used
to perform expansion work in the turbine (and therefore generate power) is not utilized for that
21
purpose. The percentage of the total cycle steam mass flow used for the feedwater heater is termed
the extraction fraction and must be carefully optimized for maximum power plant thermal efficiency
since increasing this fraction causes a decrease in turbine power output.
2.9.9 Deaerator
A deaerator is a device that is widely used for the removal of oxygen and other dissolved
gases from the feed water to steam-generating boilers. In particular, dissolved oxygen in boiler feed
water will cause serious corrosion damage in steam systems by attaching to the walls of metal piping
and other metallic equipment and forming oxides (rust). Dissolved carbon dioxide combines with
water to form carbonic acid that causes further corrosion.
The deaerators in the steam generating systems of most thermal power plants use low
pressure steam obtained from an extraction point in their steam turbine system. However, the steam
generators in many large industrial facilities such as petroleum refineries may use whatever low
pressure steam is available.
2.9.10 Stack
A flue-gas stack is a type of chimney, a vertical pipe, channel or similar structure through
which combustion product gases called flue gases are exhausted to the outside air. Flue gases are
produced when coal, oil, natural gas, wood or any other fuel is combusted in an industrial furnace, a
power plant's steam-generating boiler, or other large combustion device. The flue gas stacks are
often quite tall, up to 400 meters or more, so as to disperse the exhaust pollutants over a greater
area and thereby reduce the concentration of the pollutants to the levels required by governmental
environmental policy and environmental regulation.
2.9.11 Condenser
A condenser is a commonly used term for a water-cooled shell and tube heat exchanger
installed on the exhaust steam from a steam turbine in stations. These condensers are heat
exchangers which convert steam from its gaseous to its liquid state at a pressure below atmospheric
pressure. Where cooling water is in short supply, an air-cooled condenser is often used. An air-
cooled condenser is however, significantly more expensive and cannot achieve as low a steam
turbine exhaust pressure (and temperature) as a water-cooled condenser.
Condensers are also used in applications and industries other than the condensing of steam
turbine exhaust in power plants. In thermal power plants, the purpose of a condenser is to condense
the exhaust steam from a steam turbine to obtain maximum efficiency, and also to convert the turbine
exhaust steam into pure water (referred to as steam condensate) so that it may be reused in the
steam generator or boiler as boiler feed water.
22
2.9.12 Cooling Tower
A cooling tower is a heat rejection device which rejects waste heat to the atmosphere
through the cooling of a water stream to a lower temperature. Cooling towers may either use the
evaporation of water to remove process heat and cool the working fluid to near the wet-bulb air
temperature or, in the case of closed circuit dry cooling towers, rely solely on air to cool the working
fluid to near the dry-bulb air temperature.
2.9.13 Piping
Within the industry, piping design is a system of pipes used to convey fluids from one location
to another. The engineering discipline of piping design studies the efficient transportation of fluid.
The in-line components, known as fittings, valves, and other devices, typically sense and control the
pressure, flow rate and temperature of the transmitted fluid, and usually are included in the field of
Piping Design or Piping Engineering. Piping systems are documented in piping and instrumentation
diagrams (P&IDs). If necessary, pipes can be cleaned by the tube cleaning process.
Pipes for steam systems are commonly manufactured from carbon steel to ASME B 16.9
A106. The same material may be used for condensate lines, although copper tubing is preferred in
some industries. For high temperature superheated steam mains, additional alloying elements, such
as chromium and molybdenum, are included to improve tensile strength and creep resistance at high
temperatures. Typically, pipes are supplied in 6 meters length.
P o i n t Pressure/Temperature
2 9 M P a / 4 3 0 ° C
3 6 . 5 M P a
4 6 . 5 M P a / 4 2 0 ° C
5 4 . 5 M P a
6 2 . 5 M P a
7 0 . 5 M P a
8 0 . 0 1 M P a
23
Table 2-1: Pressure Assumptions for Steam Power Plant
In order to find the best design, multiple constrains and trade-offs must be considered and
these will be applied in the type of fuel used in running the power plant. Three types of fuel are
considered namely coal, oil, and natural gas. The following data will be used in determining the
weight of fuel used, weight of gas, and percentage of carbon dioxide in the power plant’s emissions.
24
CHAPTER 3
Upon designing a power plant, there are many factors, constraints and trade-offs to be
considered. These factors may hinder the design to attain the best possible result because of the
limitations and constraints of the design. The proponents will design thermal and mechanical system
to meet desired needs within realistic constraints such as economical, environmental, and
sustainability. The constraints in this project will serve as a media for the evaluation of the parameters
and limitations of the trade-offs laid by the designers to choose the best trade-off to be implemented
within the design and specification of the project.
1. Economical (Cost)
The cost of the power plant is very vital since huge amount of money is going to be used as
an investment for this project. Money is important in daily lives of people and is used for transactions
in buying needs and wants. Therefore, it must be used efficiently in financing the project. This
constraint is important to the owner especially to the investors. The budget is always dependent on
the client’s ability to pay. It has high regards with its financial comparability to current or existing
power plant, specific to the following points: establishment or erection, operational, and maintenance.
The graph below shows the statistical data of the average cost of coal, oil/petroleum, and
natural gas for electricity generation in the United States from the year 2005 up to 2016. As of 2016,
the average cost of all fossil fuels for electricity generation was 2.47 US dollars per million British
thermal units (BTU).
25
Figure 3.1.1 Cost of fossil fuels as of year 2016
(Source: www.statistica.com)
1. Environmental
This factor honors the ecosystem integrity of the design. This is important to consider
because of the possible effects of the project to the environment. Air pollution is highest in this
consideration, branching up to global warming, defining the carbon emission of each design.
Effects on the bodies of water and landscape are also considered. Biodiversity within the potential
area of the project shall also be considered because it could affect the lives of the people near the
area. Hence, designing a power plant also considers this constraint for the future of the project.
Computations were done and shown below to easily identify the amount of harmful gases emitted
by the three design alternatives.
26
EXTERNAL OXYGEN (& NITROGEN)
Carbon 32 O₂
X 0.8405 C = 2.241333 O₂
12 C
Hydrogen 16 O₂
X 0.045 H₂ = 0.36 O₂
2 H₂
Oxygen
-0.06 O₂
Sulfur 32 O₂
X 0.0055 S = 0.0055 O₂
32 S
TOTAL: 2.546833 O₂
Nitrogen 0.768 N₂
2.546833333 O₂ X = 8.430897 N₂
0.232 O₂
EXHAUST GAS
27
CHECK:
GAS COMPOSITION:
CO₂ 3.081833333
X 100% = 25.8101 %
11.94042989
H₂O 0.405
X 100% = 3.39184 %
11.94042989
SO₂ 0.011
X 100% = 0.09212 %
11.94042989
N₂ 8.442596552 X = 70.706 %
100%
11.94042989
TOTAL: 100 %
28
Oil Fuel Analysis Molecular Weight
Fuel = C12H23 C = 12
Where: n = 12 H = 1
M = 23 O = 16
N₂ = 28
H: m = 2c
c = m
2
c = 11.5
O: 2a = 2b + c
a = 2b + c
2
a = 17.75
29
Cn Hm + 17.75 (O₂ + 3.76N₂) → 12 CO₂ + 11.5 H₂O + 17.75 (3.76)N₂
14.5911377 3.16167664
1 + 2 → 7 + 1.239520958 + 11.18994012
14.5911377
1 + 2 → 15.59113772
30
Gas Analysis
CO₂: 3.161676647 3.161676647
x 100% = x 100%
rgf 15.59113772
= 20.2786782 %
= 7.950163612 %
= 71.77115819 %
Total = 100%
Fuel: CnHm
n = 1
m = 4
*For Complete Combustion
CH4 + a (O2 + 3.76 N2) → bCO2 + cH2O + a3.76N2
C: b = N
b = 1
H: m = 2c
c = m
2
c = 2
O: 2a = 2b + C
a = 2b + C
2
a = 2
31
FUEL + AIR → GAS
C1 H4 + 2(O2 + 3.76N2) → 1CO2+2H2O+2(3.76) N2
Molecular Weight:
C=12 H=1 O=16 N2=28
CO2 H2O N2
16 274.56 44 36 210.56
+ = + +
16 16 16 16 16
1 + 17.16 = 2.75 + 2.25 + 13.16
1 + 17.16 = 18.16
raf = 17.16
rgf = 18.16
= 15.14317181 %
= 12.38986784 %
= 72.46696035 %
Total = 100%
32
Fuel Percent Carbon Emission
Coal 25.8101%
Oil 20.2787%
Based on the computations on combustion as shown above, coal has a higher carbon
dioxide emission compared to the two alternatives. Coal emits 25.8101% carbon dioxide while the
oil and natural gas emits 20.2787% and 15.1432% respectively. Therefore, the Coal has the most
negative effect on the environment while the natural gas or Methane is considered as the most
environmentally friendly among the three design alternatives.
2. Sustainability
The sustainability of the power plant’s fuel is important to maintain the plant in producing
reliable power. The power plant’s fuel sustainability is important to know the best fuel to be used
while considering its possible future depletion. Life-span is the main concern in term of sustainability.
The proponents collected a data from different resource on three fuels that should be used for this
design project. Sustainability is the ability of the plant to work and produce electricity in a consistent
manner. It also considers how long does the design of the project last measured in total number of
years which it will still be considered useful, functional and structurally safe.
33
The data below shows the fossil fuel reserves based on the year 2016. The graph shows
the life span on how many years the fossil fuels can last. Among the three alternatives, it can be
seen on the graph that the coal is the most sustainable type of fuel because of its long years of
reserve left.
2.2 TRADE-OFFS
3.2.1. COAL-FIRED STEAM POWER PLANT
Coal energy is a nonrenewable energy which means that this is a type of energy that
we cannot re-create. The supply of coal energy is limited and therefore if we continue to consume
too much of this, we will eventually run out of this kind of energy.
Coal energy is used for the creation of electricity to power industrial or manufacturing
plants and even to power our appliances at home. Many industrial plants or manufacturing plants
use coal energy to generate electricity because coal energy is an affordable source of energy.
Moreover, coal is very abundant even if it is non-renewable because it has the largest reserve
around the world.
ADVANTAGES
Coal is abundant
DISADVANTAGES
Coal energy produces large amount of carbon dioxide which leads to global warming and climate
change
The burning of coal is not environmental friendly because it produces harmful byproducts and gas
emissions such as sulfur dioxide, carbon dioxide and nitrogen oxide that causes pollution to the
environment including acid rain
Coal mining ruins the environment and puts the lives of people specially the coal miners in danger
Oil is one of the most important commodities in the world playing an important part in some
of the biggest industries like chemicals, transport, power, petrochemicals etc. The high energy
density and easy availability have made mankind almost completely dependent on oil for most of his
needs. Almost all of the world’s cars run on petrol /gasoline which is derived from crude oil. Despite
new evidence that burning oil leads to massive pollution and greenhouse warming nothing had been
done to prevent its usage growth
35
Figure 3.2.1.2 Diagram of Oil Fired Power Plant
ADVANTAGES
DISADVANTAGES
it is a nonrenewable resource
Natural gas power plants are a type of power plant that use natural gas as their fuel in order to generate
electricity. This process is done using a large gas turbine, where the natural gas
36
is input along with a stream of air which is combusted, and then expands through a turbine
causing a generator to spin.
ADVANTAGE
Environment friendly
DISADVANTAGE
37
1.2 DESIGNER’S RAW RANKING:
Our Trade-offs is based on the constraints stated above. There are three designs that we are
going to proposed these were considered to satisfy the constraints that are stated at Chapter 3.1. In
identifying the client satisfaction we by Otto and Antonsson (1991), scaled the criterion’s importance
from 0 to 5, 5 being the highest and 0 will be the lowest scale.
The presided ranking is depending on the final choice of the designers based on their study and analysis.
In criterion for the importance of each constraints they had research and come up with ranking it from 0-5, 0
will be the lowestrank and 5 will be the highest rank. It is not just a choice but it is all based on the research
and supporting analysis.
Before having a decision on which constraint won they had estimated on each proposal.
38
ABILITY TO SATISFY THE CRITERION (on scale from 1 to 10)
Criterion's Importance
DECISION CRITERION
(on the scales of 1 to 10)
COAL OIL NATURAL GAS
ECONOMICAL 10 10 5 8
ENVIRONMENTAL 8 6 8 10
SUSTAINABILITY 7 10 8 7
CONSTRAINTS
ECONOMICAL 2.11 $/million BTU 5.25 $/million BTU 2.87 $/million BTU
39
3.3.1 Computation of ranking for Economic Constraint
CONSTRAINTS
ECONOMICAL 2.11 $/million BTU 5.25 $/million BTU 2.87 $/million BTU
ECONOMICAL 10 10 5 8
COAL-OIL
𝑆𝑢𝑏𝑜𝑟𝑑𝑖𝑛𝑎𝑡𝑒 𝑟𝑎𝑛𝑘 = 10 − 6
40
𝑺𝒖𝒃𝒐𝒓𝒅𝒊𝒏𝒂𝒕𝒆 𝒓𝒂𝒏𝒌 = 𝟒
Figure 3.3.1.1 Ranking Scale for Percentage Difference for Coal and Oil
COAL-NATURAL GAS
𝑆𝑢𝑏𝑜𝑟𝑑𝑖𝑛𝑎𝑡𝑒 𝑟𝑎𝑛𝑘 = 10 − 3
𝑺𝒖𝒃𝒐𝒓𝒅𝒊𝒏𝒂𝒕𝒆 𝒓𝒂𝒏𝒌 = 𝟕
Figure 3.3.1.2 Ranking Scale for Percentage Difference for Detention Basin and Box Culvert
41
Table 3.3.1C Actual Trade off values for Economic Constraint
ECONOMICAL 10 10 4 7
CONSTRAINTS
42
NATURAL GAS-COAL
Figure 3.3.2.1 Ranking Scale for Percentage Difference for Detention Basin and RC Pipes
NATURAL GAS-OIL
Figure 3.3.2.2 Ranking Scale for Percentage Difference for Detention Basin and Box Culvert
43
Table 3.3.2C Actual Trade off values for Economic Constraint
ENVIRONMENTAL 8 5 7 10
CONSTRAINTS
SUSTAINABILITY 7 10 8 7
44
COAL-OIL
ℎ𝑖𝑔ℎ𝑒𝑟 𝑣𝑎𝑙𝑢𝑒 − 𝑙𝑜𝑤𝑒𝑟 𝑣𝑎𝑙𝑢𝑒
% 𝑑𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 = × 100
ℎ𝑖𝑔ℎ𝑒𝑟 𝑣𝑎𝑙𝑢𝑒
114 − 50.7
% 𝑑𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 = × 10
114
%𝑑𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 = 5.55 = 6
𝑆𝑢𝑏𝑜𝑟𝑑𝑖𝑛𝑎𝑡𝑒 𝑟𝑎𝑛𝑘 = 𝐺𝑜𝑣𝑒𝑟𝑛𝑖𝑛𝑔 𝑟𝑎𝑛𝑘 − %𝑑𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒
𝑆𝑢𝑏𝑜𝑟𝑑𝑖𝑛𝑎𝑡𝑒 𝑟𝑎𝑛𝑘 = 10 − 6
𝑺𝒖𝒃𝒐𝒓𝒅𝒊𝒏𝒂𝒕𝒆 𝒓𝒂𝒏𝒌 = 𝟒
Figure 3.3.3.1 Ranking Scale for Percentage Difference for Detention Basin and RC Pipe
COAL-NATURAL GAS
Figure 3.3.3.2 Ranking Scale for Percentage Difference for Detention Basin and Box Culvert
45
Table 3.3.3C Actual Trade off values for Sustainability Constraint
SUSTAINABILITY 7 10 4 4
ECONOMICAL 10 10 4 7
ENVIRONMENTAL 8 5 7 10
SUSTAINABILITY 7 10 4 4
46
3.4 Sensitivity Analysis
3.4.1 Case 1: Sensitivity Analysis for Economic Constraints > Environmental > Sustainability
The table below shows that the Economic constraint has been given importance as per basis for
the trade-off selection.
ECONOMICAL 10 10 4 7
ENVIRONMENTAL 8 5 7 10
SUSTAINABILITY 6 10 4 4
The Table above shows that when the Economical>Environmental>Sustainability, the Coal is the
better choice.
3.4.2 Case 2: Sensitivity Analysis for Economic Constraint > Sustainability > Environmental
The table below shows that the environmental constraint has been given importance as per basis
for the trade-off selection.
47
Table 3.4.2 Sensitivity Analysis for Case 2
ECONOMICAL 10 10 4 7
ENVIRONMENTAL 6 5 7 10
SUSTAINABILITY 8 10 4 4
The Table above shows that when the Economical>Sustainability>Environmental, the Coal is the
better choice.3.4.3 Case 3: Sensitivity Analysis for Environmental Constraint > Economical >
Sustainability
The table below shows that the environmental constraint has been given importance as per basis
for the trade-off selection.
48
ENVIRONMENTAL 10 5 7 10
SUSTAINABILITY 4 10 4 4
The Table above shows that when the Environmental>Economical>Sustainability, the Natural Gas
is the better choice.
3.4.4 Case 4: Sensitivity Analysis for Environmental Constraint > Sustainability > Economical
The table below shows that the environmental constraint has been given importance as per basis
for the trade-off selection.
ECONOMICAL 4 10 4 7
ENVIRONMENTAL 10 5 7 10
SUSTAINABILITY 6 10 4 4
49
The Table above shows that when the Environmental>Sustainability>Economical, the Natural Gas
is the better choice.
3.4.5 Case 5: Sensitivity Analysis for Sustainability Constraint > Economical > Environmental
The table below shows that the environmental constraint has been given importance as per basis
for the trade-off selection.
ECONOMICAL 8 10 4 7
ENVIRONMENTAL 6 5 7 10
SUSTAINABILITY 10 10 4 4
The Table above shows that when the Sustainability>Economical>Environmental, the Coal is the
better choice.
3.4.6 Case 6: Sensitivity Analysis for Sustainability Constraint > Environmental > Economical
The table below shows that the environmental constraint has been given importance as per basis
for the trade-off selection.
50
Table 3.4.5 Sensitivity Analysis for Case 6
ECONOMICAL 6 10 4 7
ENVIRONMENTAL 8 5 7 10
SUSTAINABILITY 10 10 4 4
The Table above shows that when the Sustainability>Environmental>Economical, the Coal is the better
choice.
51
3.5 Summary of Sensitivity Analysis
250
Coal
Oil
210 210
200 Natural Gas
200
200
174
162 162
150 158 156
150 152
150
100
50
0
Case 1 Case 2 Case 3 Case 4 Case 5 Case 6
The table shows the relation between the different alternative sources with respect to the constraint
sand trade-offs that was considered by the designers. The table shows that in any case, the Coal-Fired
Steam Power Plant dominates almost all the cases.
52
3.6 TRADE-OFF ASSESSMENT
The Trade-off Assessment discussed the results of justification in rating the criteria above of the
designers based on research and analysis shown above:
53
3.7 Design Standards
In order for the designers to have a best project proposal, the designers made sure that this
project will comply on the standards and codes of the American Society of Mechanical Engineers
(ASME).
The designers will only include the standards and codes for the equipments used and the
piping. The codes and standards for buildings and other codes is not included as the designers
pointed out in the limitations.
Many standards and codes were cinsidered in designing a steam power plant. The ASME
Performance Test Codes provide standard directions and rules for conducting and reporting tests of
specific materials such as fuels, equipment and process functions related to power plants.
3.5.1 ASME Performance Test Codes
PTC1 - 1999 - General Instructions
PTC2 - 1980 (R1985) - Code on Definitions and Values
PTC4- 1998 - Fired Steam Generators
PTC4.2 - 1969 (R1997) - Coal Pulverizes
PTC4.3 - 1968 (R1991) - Air Heaters
PTC4.4 - 1981 (R1992) - Gas Turbine Heat Recovery Steam Generators
PTC5 - 1949 - Reciprocating Steam Engines
PTC6 - 1996 - Steam Turbines
PTC6A - 2001 - Test Code for Steam Turbines - Appendix to PTC 6
PTC6-REPORT - Guidance for Evaluation of Measurement Uncertainty in Performance Tests of
Steam Turbines
PTC6-S - Procedures for Routine Performance Test of Steam Turbines
PTC7.1 - 1962 (R1969) - Displacement Pumps
PTC8.2 - 1990 - Centrifugal Pumps
PTC9 - 1970 (R1997) - Displacement Compressors, Vacuum Pumps and Blowers
PTC10 - 1997- Test Code on Compressors and Exhausters
PTC11 - 1984 (R1995) – Fans
PTC12.1 - 2000 - Closed Feedwater Heaters
PTC12.2 - 1998 - Steam Surface Condensers
54
PTC12.3 - 1997 - Deaerators PTC12.4 - 1992 (R1997) - Moisture Separator Reheaters
PTC17 - 1973 (R1997) - Reciprocating Internal-Combustion Engines
PTC18 - 1992 - Hydraulic Prime Movers
PTC18.1 - 1978 (R1984) - Pumping Mode of Pump/Turbines
PTC19.1 - 1998 - Measurement Uncertainty
PTC19.2 - 1987(R1998) - Pressure Measurement
PTC19.3 - 1974 (R1998) - Temperature Measurement
PTC19.5 - 1972 - Application, Part II of Fluid Meters: Interim Supplement on Instruments and
Apparatus
PTC19.5.1 - 1964 - Weighing Scales
PTC19.7 - 1980 (R1988) - Measurement of Shaft Power
PTC19.8 - 1970 (R1985) - Measurement of Indicated Power
PTC19.10 - 1981 - Flue and Exhaust Gas Analyses
The designers also comply with A ME’s B31 code. B31 Code for pressure piping, developed by American
Society of Mechanical Engineers - ASME, covers Power Piping, Fuel Gas Piping, Process Piping, Pipeline
Transportation Systems for Liquid Hydrocarbons and Other Liquids, Refrigeration Piping and Heat Transfer
Components and Building Services Piping. ASME B31 was earlier known as ANSI B31.
55
B31.2 - 1968 - Fuel Gas Piping
This has been withdrawn as a National Standard and replaced by ANSI/NFPA Z223.1, but B31.2 is still
available from ASME and is a good reference for the design of gas piping systems (from the meter to the
appliance)
B31.3 - 2012 - Process Piping
Design of chemical and petroleum plants and refineries processing chemicals and hydrocarbons, water and
steam. This Code contains rules for piping typically found in petroleum refineries; chemical, pharmaceutical,
textile, paper, semiconductor, and cryogenic plants; and related processing plants and terminals.
This Code prescribes requirements for materials and components, design, fabrication, assembly, erection,
examination, inspection, and testing of piping. This Code applies to piping for all fluids including: (1) raw,
intermediate, and finished chemicals; (2) petroleum products; (3) gas, steam, air and water; (4) fluidized
solids; (5) refrigerants; and (6) cryogenic fluids. Also included is piping which interconnects pieces or stages
within a packaged equipment assembly.
B31.4 - 2012 - Pipeline Transportation Systems for Liquid Hydrocarbons and Other Liquids
This Code prescribes requirements for the design, materials, construction, assembly, inspection, and testing
of piping transporting liquids such as crude oil, condensate, natural gasoline, natural gas liquids, liquefied
petroleum gas, carbon dioxide, liquid alcohol, liquid anhydrous ammonia and liquid petroleum products
between producers' lease facilities, tank farms, natural gas processing plants, refineries, stations, ammonia
plants, terminals (marine, rail and truck) and other delivery and receiving points.
Piping consists of pipe, flanges, bolting, gaskets, valves, relief devices, fittings and the pressure containing
parts of other piping components. It also includes hangers and supports, and other equipment items
56
necessary to prevent overstressing the pressure containing parts. It does not include support structures such
as frames of buildings, buildings stanchions or foundations
Requirements for offshore pipelines are found in Chapter IX. Also included within the scope of this Code are:
(A) Primary and associated auxiliary liquid petroleum and liquid anhydrous ammonia piping at pipeline
terminals (marine, rail and truck), tank farms, pump stations, pressure reducing stations and metering
stations, including scraper traps, strainers, and prover loop;
(B) Storage and working tanks including pipe-type storage fabricated from pipe and fittings, and piping
interconnecting these facilities;
(C) Liquid petroleum and liquid anhydrous ammonia piping located on property which has been set aside for
such piping within petroleum refinery, natural gasoline, gas processing, ammonia, and bulk plants;
(D) Those aspects of operation and maintenance of liquid pipeline systems relating to the safety and
protection of the general public, operating company personnel, environment, property and the piping
systems.
B31.5 - 2013 - Refrigeration Piping and Heat Transfer Components
This Code prescribes requirements for the materials, design, fabrication, assembly, erection, test, and
inspection of refrigerant, heat transfer components, and secondary coolant piping for temperatures as low as
57
-320 deg F (-196 deg C), whether erected on the premises or factory assembled, except as specifically
excluded in the following paragraphs.
Users are advised that other piping Code Sections may provide requirements for refrigeration piping in their
respective jurisdictions.
This Code shall not apply to:
(a) any self- contained or unit systems subject to the requirements of Underwriters Laboratories or other
nationally recognized testing laboratory:
(b) water piping;
(c) piping designed for external or internal gage pressure not exceeding 15 psi (105 kPa) regardless of size;
or
(d) pressure vessels, compressors, or pumps,
but does include all connecting refrigerant and secondary coolant piping starting at the first joint adjacent to
such apparatus.
B31.8 - 2012 - Gas Transmission and Distribution Piping Systems
This Code covers the design, fabrication, installation, inspection, and testing of pipeline facilities used for
the transportation of gas. This Code also covers safety aspects of the operation and maintenance of those
facilities.
B31.8S - 2012 - Managing System Integrity of Gas Pipelines
This Standard applies to on-shore pipeline systems constructed with ferrous materials and that transport
gas.
Pipeline system means all parts of physical facilities through which gas is transported, including pipe, valves,
appurtenances attached to pipe, compressor units, metering stations, regulator stations, delivery stations,
holders and fabricated assemblies.
The principles and processes embodied in integrity management are applicable to all pipeline systems. This
Standard is specifically designed to provide the operator (as defined in section 13) with the information
58
necessary to develop and implement an effective integrity management program utilizing proven industry
practices and processes.
The processes and approaches within this Standard are applicable to the entire pipeline system.
B31.12 - 2011 - Hydrogen Piping and Pipelines
Gaseous and liquid hydrogen service and to pipelines in gaseous hydrogen service.
B31G - 2009 - Manual for Determining Remaining Strength of Corroded Pipelines
A supplement To B31 Code-Pressure Piping
59
mechanical and electrical equipment requirements are extremely important for all modern buildings,
particularly factories.
2.2 Requirements for number, size, location and height of rise for elevators with particular attention to
penthouse dimensions and equipment loads.
General requirements for plumbing with particular attention to the location of soil stacks, standpipes,
main pumps, water storage tanks and sprinkler systems.
If steam is to be produced within the buildings, requirements of the boiler room and accessories,
such as fuel storage, the probable location of steam mains and ducts and their approximate sizes in
order to avoid interference with a structure member of other utilities.
Typical lighting demands with particular attention to ceiling outlets as their proper locations may
influence the framing of the building and the necessary space required for the electric conduits often
affect the floor design.
For industrial buildings, all specific demands of the manufacturing processes such as special
mechanical and electrical equipment of interior clearances should be identified.
60
The success depends to a great extent upon the care with which material is selected, mixed and
poured.
1.1 Installation and Operating Permits Application for permits to install and operate steam generators
for power or heat, unfired pressure vessels for steam, air or gases shall be secured from the place or locality
of installation. For municipalities, permits shall be secured from the office of the Municipal/City Engineer or
Building Official, if available, or from the Regional Office of the Department of Labor and Employment. A
similar permit to install and operate pollution sources equipment shall also be secured from the offices of the
Department of Environment and Natural Resources. Application forms shall be accompanied by plans and
specifications in quadruplicate showing:
General Layout giving a plan view longitudinal view and at least a front view showing location of
boiler with respect to building, location, size, height of smoke stack, location of steam generator
auxiliaries and location and size of fuel supply. Building permit and location plan of the same,
Electrical Permit, Fire Department permit and other permits necessary should also be stipulated on
the plan.
Detailed assembly plan of boiler should show all appendages indicating instruments, panels if any
for controls and all safety devices. Details should show actual joints, riveting, welding, thickness of
plates, tubes, fusible plugs etc. Steam conditions like temperature, pressure, degrees superheat
should be indicated. Piping drawing, preferably in isometric drawing showing elevation headers,
leads to headers preferably from the bottom, branches from headers, preferably from the top,
expansion joints, pipes covering sizes, fittings and valves and method support.
All plan and specification should be prepared under supervision of a Professional Mechanical
Engineer and should have his signature and seal on every page, regardless of boiler horsepower.
In detached buildings of fire resistant construction used for no other purpose and situated not less
than 3 m distances from the buildings not forming part of the factory, or in structures of fire resisting
61
materials, preferably stone or concrete walls connected to or in close proximity to other factory
buildings.
No part of the steam boiler should be closer than one meter from any wall.
In case of fire tube boilers, sufficient room for tube removal either thru the front or rear should be
provided.
Although not to be used for passage, boiler rooms should be provided with two doors preferably on
opposite ends or sides which if locked may be opened without key from the inside.
As the room air is usually the source of combustion air, sufficient ventilation from outside should be
provided.
Steam boilers should be mounted over a suitable foundation or concrete pad of not less than 305
mm thick and with sufficient area t base to be supported by the bearing capacity of the soil with a
safety factor of not less than four (4).
1.4 Where brickwork is necessary, the surface facing the hot gases should be fired brick and the outside may
be red brick or other suitable material,
Brickwork should be provided with sufficient expansion joints both vertically and horizontally to take
care of expansion at operating temperature.
Insulating cables is used for medium pressure boiler.
1.5 No structural stress other than its own weight should be imposed on any brick and on and any brickwork
and in no case should the full weight or part weight of the steam boiler or its appurtenances be supported on
brickwork.
1.6 No steam boiler should be enclosed or walled-in without authorization and inspection by authorized
government representative and who will conduct a hydrostatic test of 130% of stipulated working pressure.
62
When boilers are replaced, new boilers are installed in either existing or new buildings, a minimum
height of at least 2,130 mm should be provided between the top of the boiler proper and the ceiling
except in single installation of self-contained boilers where a minimum height requirement of at least
915 mm shall be provided between the highest point of any valve stem or fitting and the ceiling.
All boiler and unfired pressure vessels shall be so located that adequate space will be provided for
the proper operation of the boiler and its appurtenances, for the inspection of all surfaces, tubes,
water walls, valves, and other equipment and for their necessary maintenance and repair.
Smokestacks should be of sufficient capacity to handle flue gases, self-supporting or guyed to
withstand a wind load 160 kph and rise at least 5,000 mm above the eaves of any building within a
radius of 50 meters. However, in lieu of the said height requirement, a system should be so designed
and constructed to eliminate smoke nuisances to the neighboring structures.
No smokestack should be closer than 305 mm from any exposed woodwork or framing.
Where two or more steam boilers will be connected in parallel, each steam outlet should be provided
with a non-return valve and a shut off valve.
Only stem pressure sufficient for requirements should be allowed. No high pressure will be generated
just to be reduced on the line to suit requirements.
All construction features of boiler should be in conformity with the ASME Boiler Construction Code
when available or its equivalent. (JIS, ASTM, ISO Standards). All boiler installations, including
reinstalled boilers, shall be installed in accordance with the requirements of the latest revision of the
A.S.M.E. Boiler Construction Code and/or Rules and Regulations provided herein.
Ladders and Catwalks. A steel catwalk or platform at least 455 mm wide and provided with standard
handrails and toe-board on either side shall be installed across the tops of adjacent boilers or at
some other convenient level for the purpose of affording safe access to the boilers. All catwalks shall
be remotely located from the other, and connected to a permanent stairway or inclined ladder leading
the floor level.
63
3.5.4 Chapter 10 PSME Code – Pumps
Section 1.0 General Requirements
1.1 Scope. This standard deals with the selection and installation of pumps supplying water for domestic,
industrials, for private and/or public fire protection. Items include water supplies, suction, discharge and
auxiliary equipment, power supplies, electric drive control: internal combustion engine drive and control,
acceptance test, operations and maintenance.
1.2 Purpose. The purpose of this standard is to provide a reasonable degree technical knowhow, and safety,
through installation requirements for pumps based on sound engineering principles, test data and field
experience. Guidelines are established for the design, installation and maintenance for pumps, drivers and
associated equipment. This standard endeavors to continue the excellent record that has been established
by pumps installation and to meet the needs of changing technology.
1.3 Other Pumps. Pumps other than those specified in this standards and having different design features
may be installed when such pumps are listed by a testing laboratory. Pumps shall be selected based on the
64
conditions under which they are to be installed and used. The pump manufacturer shall be given complete
information concerning the water, or liquid and power supply characteristics.
1.4 Unit Performance. The unit consisting of pumps, driver and controller, shall perform is compliance with
this standard as an entire unit when installed. Certified shop test curves, showing head capacity and brake
horsepower of the pump shall be furnished by the manufacturer to the purchaser Engineer.
1.5 Installation of pumping equipment to supply buildings, from existing water supply should only be allowed
if there is always water in the mains to prevent contamination of water systems when air gains entrance due
to negative pressure created by pumping.
1.6 A shut off valve followed by a check valve shall be placed between the suction of pump and water mains
to prevent any return of water to mains when pump is stopped.
1.7 Overhead Tank Supply. A water tank may be installed above the roof of the building or by separate tower
for the purpose. Water from the water mains is pumped to the tank and the building draws its supply from
overhead tank.
o Suitable float switch or other devices should be installed with the tank to stop or start
operation of pump depending on water level in the tank.
o A check valve should be installed between the pump and tank.
o Water tank should be provided with an overflow pipe, leading to storm drain and a vent
properly protected from insects.
o Water tank should be fully covered to keep out flying debris and to prevent growth or moss
o For multi-storey buildings, suitable pressure reducing valves should be supplied to regulate
water pressure for each floor.
Material Piped Pipe Color Pipe Identification Acetylene Orange Acetylene Acid Yellow Acid Air-High Pressure
Yellow H.P. Air Air-Low Pressure Green L.P. Air Ammonia Yellow Ammonia Argon-Low Pressure Green L.P.
65
Argon Blast Furnace Gas Orange B.F. Gas Carbon Dioxide Red Carbon Dioxide Gasoline Orange Gasoline
Grease Orange Grease Helium-Low Pressure Green L.P. Helium Hydrogen Orange Hydrogen Nitrogen-Low
Pressure Green L.P. Nitrogen Oxygen Orange Oxygen Oil Orange Oil Steam-High Pressure Yellow H.P.
Steam Tar Orange Tar Producer Gas Orange Producer Gas Liquid Petroleum Gas Orange Producer Gas
66
CHAPTER 4
METHODOLOGY
4.1 Design of Methodology
The designers designed an 18 MW Steam Power Plant and determine which the best fuel among
the three classifications such as: Coal, Oil and Natural Gas. Undergoing trade off analysis, the designers
were able to determine the best fuel and will be presented as the final design.
67
Figure 4 – 1 is the design methodology for Steam Power Plant. The designers arrived on the step
by step process from the first thing to do up to the last, to solve a problem and satisfy the needs of certain
client. The designers are also considered multiple constraints and trade – offs that will set as a limitation
of the design project. Only 1 trade – off will be chosen to represent the design based on the 3 constraints
mentioned in Chapter 3 and the final details of the governing trade – off will be shown in chapter 5 of this
design.
START
DATA GATHERING
IDENTIFY THE DESIRED POWER CAPACITY NAME THE THREE ALTERNATIVE FUELS
68
END
MULTIPLYING FACTOR
END
69
Figure 4 - 3: Design Flow Chart of Coal – Fired Power Plant
How it Works: Traditional coal plants burn coal to make steam. The steam is used as fuel in a type
of engine, called a “turbine”. This turbine runs a generator to make electricity. When coal is burned, CO2
is released by the plant. In Option 1, this CO2 escapes into the air because no equipment is added to
capture the CO2.
70
Computation for kW – h for Coal
38 MW = 38 000 kW
Ng = Generator Efficiency
Ng = 96.0169
Btu
3412
kW of Electricity
Ng =
Btu
Heat Rate
kWh
Btu
3412
kWh
Heat Rate =
Ng
Btu
3412
kWh
Heat rate =
0.960196
Btu
Heat Rate = 3 553.441172 kWh
Btu
3 553.441172
kWh
Coal used per kWh =
19 146 000 Btu
1 short ton
Short ton
Coal used per kWh = 0.185970528 x 10 – 3
kWh
Computation for the fuel cost per kwh for Coal
71
kWh 1 Short ton $1
18 MW = 18 000 kW
P 0.3886039627
Over all fuel cost = x 157 680 000 kW - h
kW - h
Coal
Computation for Carbon dioxide emission (Referring to US Energy Information Administration we have
gathered some data to compute for the CO2 emission)
lbs CO2
Fuel Multiplying Factor
million Btu
Coal 214.3
Oil 161.3
Natural Gas 117.0
72
IDENTIFY OIL - BASED POWER
Start
PLANT LIFE SPAN
MULTIPLYING FACTOR
END
73
Oil – Based Power Plant Design Result
According to National Renewable Energy Laboratory (NREL)
Plant Lifetime
Plant lifetimes are shown in Table 11, and in Figure 5. It can be difficult to draw conclusions when
comparing lifetimes. For example, some data sets, such as AEO and EPA do not use plant lifetimes. The
models supported by these two data sets – NEMS and IPM, respectively – allow plants to run for as long
as they are economic, with no pre-determined retirement age. In some data sets, lifetimes represent the
maximum service life, whereas in other models, the reported lifetime is the value used to compute
economic results, such as the levelized cost of energy (LCOE) or for retirement calculations.
DATA SET
NREL – Standard Coefficient
Technology AEQ GPRA MiniCAM EPA MERGE 21
SEAC Deviation of Variation
Coal x --- 60 45 x 30 15.0 33 %
IGCC x --- 60 45 x 30 15.0 33 %
Combustion
x --- 30 45 x --- 10.6 28 %
Turbine
Combined
x --- 30 45 x 30 8.7 25 %
Cycle
Nuclear x --- 6 60 x 30 17.3 35 %
Biomass x --- 45 30 x 30 8.7 22 %
Geothermal
x + 20 20 x --- 7.1 28 %
(hydrothermal)
Wind
x 20 20 30 x 30 5.8 23 %
(onshore)
Wind
x 20 20 --- x --- 0.0 0%
(offshore)
Solar Thermal x 30 30 30 x 30 0.0 0%
PV x 30 30 30 x 30 0.0 0%
74
--- Technology not included in data set
Renewable technologies – geothermal, wind, and solar – have lifetimes in the range of 20 to 30
years.
Nuclear plants in most data sets have a lifetime of 60 years (30-40 year initial license plus one 20-
In the MERGE data set, all plants are assumed to have an economic life of 30 years. These 30-
year plant lifetime values are for economic calculations, and are not intended to reflect service
lifetimes.
75
Computation for kW – h for Oil
38 MW = 38 000 kW
Ng = Generator Efficiency
Ng = 96.0169
Btu
3412
kW of Electricity
Ng =
Btu
Heat Rate
kWh
Btu
3412
kWh
Heat Rate =
Ng
Btu
3412
kWh
Heat rate =
0.960196
Btu
Heat Rate = 3 553.441172
kWh
Btu
3 553.441172
kWh
Diesel used per kWh =
137 452 Btu
1 Gallon
Gallon
Diesel used per kWh = 0.0258522253
kWh
76
Gallon $ 3.070 P 52.24
Cost per kwh = 0.0258522253 x x
kWh 1 Gallon $1
38 MW = 38 000 kW
P 4.116331216
Over all fuel cost = x 332 880 000 kW - h
kW - h
Computation for Carbon dioxide emission (Referring to US Energy Information Administration we have
gathered some data to compute for the CO2 emission)
lbs CO2
Fuel Multiplying Factor
million Btu
Coal 214.3
Oil 161.3
Natural Gas 117.0
77
IDENTIFY NATURAL GAS
Start
POWER PLANT LIFE SPAN
MULTIPLYING FACTOR
END
78
Natural Gas Power Plant Design Result
Natural Gas
How it works: Most of the natural gas in western PA is used to heat homes. But, it can also be used in
power plants to make electricity. In the plant, natural gas is burned. Its heat is used as fuel in a type of
engine, called a “turbine”. This turbine then runs a generator to make electricity. The left-over hot gas is
used to make steam. The steam also fuels a turbine, which runs a second generator to make more
79
Middle East. A portion of U.S. government funds is used to make sure we
can get gas and oil from the Middle East.
Reliability Natural gas, when available, can provide steady and dependable electricity.
The cost of natural gas may increase in the future. Since U.S. supplies are running
low, we may also become more dependent on foreign (Middle East) natural gas.
Limits of use
For these reasons, it is risky to make all the electricity needed for PA with natural
gas.
Noise These plants are about as loud as average street traffic.
These plants do not use much land. But, pipelines sometimes must be built under
Land use and private land. The landowner and pipeline company will have to agree about how
ecology to maintain the land around the pipeline. Drilling for natural gas can disturb local
land, plants and animals. This is especially true in unpopulated areas, like Alaska.
These plants are quite safe for operators. It is rare for natural gas to leak from a
Safety pipeline. If it does occur, unlike CO2, the gas can burn or explode. Like CO2,
people can suffocate from the gas.
The lifetime of any plant is uncertain. But, a new natural gas plant built today
Lifespan
would likely make electricity for at least 30 years.
Current use There are more than 350 of these plants working in the U.S. today.
80
Computation for kW – h for Natural Gas
38 MW = 38 000 kW
Ng = Generator Efficiency
Ng = 96.0169
Btu
3412
kW of Electricity
Ng =
Btu
Heat Rate
kWh
Btu
3412
kWh
Heat Rate =
Ng
Btu
3412
kWh
Heat rate =
0.960196
Btu
Heat Rate = 3 553.441172
kWh
Btu
3 553.441172
kWh
Natural Gas per kWh =
1 037Btu
ft 3
ft3
Natural Gas per kWh = 3.426654939
kWh
81
Computation for the fuel cost per kwh for Natural Gas
38 MW = 18 000 kW
P 0.5136201897
Over all fuel cost = x 322 880 000 kW - h
kW - h
Computation for Carbon dioxide emission (Referring to US Energy Information Administration we have
gathered some data to compute for the CO2 emission)
lbs CO2
Fuel Multiplying Factor
million Btu
Coal 214.3
Oil 161.3
Natural Gas 117.0
117 lbs CO2 1 037 Btu 1062 359 267 128 894 987.5 lbs
x x =
106 1 ft3 ft3 CO2
82
4.5 Final Estimate Trade off Values
Table 4 - 7: Final Estimate Trade off Values
Environmental 115 294 291.5 lbs CO2 754 121 643.2 lbs CO2 128 894 987.5 lbs CO2
Php
Php
Php Php Php Php P
Economic 165 837
152 525 502.9 1 630 601 513 203 460 269.4 61 275 072.84 1370244335.
686.9
1
Environment 239.5902241 180.3355257 130.7707552 115 294 291.5 86 780 071 62 946
al lbs CO2 lbs CO2 lbs CO2 lbs CO2 lbs CO2 lbs CO2
83
4.6.1 Computation of Ranking for Economic Constraint
Table 4 - 9: Estimated Values for Economic Constraint
Economic 50 100 9 76
Coal Vs Diesel
% difference = 95.52 = 96
Subordinate rank = 4
84
Coal Vs Natural Gas
% difference = 63.05 = 64
Subordinate rank = 36
85
4.6.2 Computation of Ranking for Environmental Constraint
Table 4 - 10: Estimated Values for Environmental Constraint
Environmental 115 294 291.5 lbs CO2 86 780 071 lbs CO2 62 946 486 lbs CO2
Environmental 30 55 73 100
% difference = 45.4 = 45
Subordinate rank = 55
86
Natural Gas Vs Diesel
% difference = 27.46 = 27
Subordinate rank = 73
87
4.6.3 Computation of Ranking for Sustainability Constraint
Table 4 - 11: Estimated Values for Sustainability Constraint
Sustainably 20 83 100 25
Diesel Vs Coal
higher value – lower value
% difference = X 100
higher value
60 – 50
% difference = X 100
60
% difference = 16.6 = 17
Subordinate rank = 83
88
Diesel Vs Natural Gas
60 – 30
% difference = X 100
60
% difference = 50
Subordinate rank = 50
89
4.7 Final Designer’s Raw Ranking
Economical 50 % 100 9 76
Environmental 30 % 55 73 100
Sustainability 20 % 83 100 25
Total 100 %
Overall Rank 83 46 73
90
4.8 Trade off assessment
The comprehensive discussions using data are presented below and covers the designers
of ten(10) since the estimated cost for this design is P 61 275 072.84 since this design is the most
economical and the cost of installation is cheaper than the two trade-offs.
4.8.2 Environmental
Among the three trade – offs coal fired fuel got the lowest Carbon Dioxide (CO2 ) Produced Using coal as
a fuel the power plant will extract a 115 294 291.5 lbs of CO2. While having diesel as a fuel will produce
86 780 071 lbs of CO2. For the last option the natural gas will extract 62 946 lbs of CO2.
4.8.3 Sustainability
In terms of sustainability, Coal Fired Fuel Power plant, Oil-Based Power Plant, and Natural Gas Power
Plant has the service life of 50 years , 60 years and 30 years respectively. Oil-Based Power Plant has the
longest service life having 10 years advantage from the picked fuel of the designer.
trusted design. The designers assured that every single detail that they have included in the design
The tradeoff is significant by solving the problem regarding the expenses concern and considering the
91
4.9.1 Economic Alternatives
92
4.9.2 Environmental Alternatives
93
4.9.3 Sustainability Alternatives
criterion’s importance may varies dependent on the client’s perspectives. By interchanging the value for
criterion’s importance the designers came up on every different perspective that the client can decide by
94
Case 1: Economical and Environmental
On the table below, the designers considered the Economical and Environmental to be
interchanged and set the Environmental as the most important constraint, where in they will choose the
Economical 30 % 100 9 76
Environmental 50 % 55 73 100
Sustainability 20 % 83 100 25
Total 100 %
Overall Rank 74 59 78
95
Case 2: Economical and Sustainability
For this case the designers chose the sustainability constraint over economical constraint as the
more important. The lifespan of the Power Plant over the fuel cost.
Economical 20 % 100 9 76
Environmental 30 % 55 73 100
Sustainability 50 % 83 100 25
Total 100 %
Overall Rank 78 75 58
96
Case 3: Environmental and Sustainability
For the last case the designers considered the Environmental constraint and the Sustainability
taking more consideration for the plant lifespan and neglecting some environmental issues.
Economical 50 % 100 9 76
Environmental 20 % 55 73 100
Sustainability 30 % 83 100 25
Total 100 %
Overall Rank 86 49 66
97
Figure 4 - 12: Sensitivity Analysis of Steam Power Plant
Having the analysis above, the designers made a summary of every case and concluded that a slight
difference happened when interchanging the criterions importance factor. Also a slight affect result of the
final raw ranking. However, the leading trade – off that validated by designers still wins the ranking after
interchanging the importance factor has been interchanged. Lastly, the designers must understand these
98
CHAPTER 5
FINAL DESIGN
Conclusion
After trade-offs the designers came up with the best alternative design to meet the power demands in
MAJAYJAY LAGUNA specifically in the franchise areas of Therma South Inc. Coal Power Plant. Coal Fired
Power Plant is the best alternative design among other alternative designs (Oil based Power Plant and
Natural Gas Power Plant). Based on the following constraints and its corresponding trade – offs the Coal
Fired Power Plant fit to the designer ideals and achieved the following aspects:
Economical
Environmental
Sustainability
The Coal Fired Power Plant is best suitable when it comes to the manufacturing and sustainability. This
shows how almost insignificant their differences are. But Oil based Power Plant comes to last due to its
reliability of energy sources, meaning arising scarcity in the amount of its fuel.
Recommendation
To the future designer, the group suggests to look for more accurate equipment specifications that
will suit the design capacity. They also suggest justifying the power demand computations as well as the
equipment to be used. Lastly, the designers would like to recommend a precise constraints and trade-off in
choosing the alternative that will suit best in the design.
99
DESIGN OF AN 38 MW STEAM POWER PLANT
(COAL FIRED POWER PLANT)
100
FIRST CHECKING
Assumptions:
P₂ 9 MPa T₂ 430 °C
P₃ 6.5 MPa
P₅ 4.5 MPa
P₆ 2.5 MPa
P₇ 0.5 MPa
P₈ 0.01 MPa
ww
12 11 10
SOLUTION
@ P1 = P2 = 9 MPa
= 92.37601776 kg / cm 2
101
@ 3 stages of extraction,
202.32758
T12 = oC
Temperature Difference:
t9
@ P8
=
@ P8 = 0.01 MPa
t9 = 45.81 oC
202.32758 –
t₁₂ - t₉
40.29
Δt = =
No. of
3
Stages
Δt = 52.17334299oC
Temperature @ Point 10
102
t₉ = 45.81°C
t₁₀ = t₉ + Δt
40.29 +
t₁₀ =
52.17334299
t₁₀ = 97.98 °C
Temperature @ Point 11
t₁₁ = t₁₀ + Δt
t₁₁ = 150.15 °C
Temperature @ Point 12
t₁₂ = t₁₁ + Δt
t₁₂ = 202.33°C
Illustration:
2 4
3 5 6 7 8
103
Figure 5 - 2: Schematic diagram of Quality of Steam (First Checking)
P3 = P 4
2 4 P5
T 5’ P6
3’ 6’
3 5 P7
6 7’
7 P8
8 8’
@ Point 2
P2 = 9 MPa
t2= 430 ⁰C
h2 = 3202.7 kJ/kg
s2 = 6.4087 kJ/kg-K
@ Point 3
S3 = S2 = 6.4087 kJ / kg - K
104
from Steam Tables, Table 3 by Interpolation;
h₃ 6.4087
h₂ - h₃'
ηs =
h₂ - h₃
3202.7 - h₃'
0.8 =
3202.7 - 3111.367
h3 = 3115.934 kJ / kg
105
from Steam Tables, Table 3 by Interpolation;
3115.933999 s₃'
@ Point 4
P4 = 6.5 MPa
t4= 430 ⁰C
h4 = 3244.6 KJ/kg
s4 = 6.5708827 KJ/kg-k
@ Point 5
S5 = S4 = 6.5708827 kJ / kg - K
h₅ 6.5708827
106
3131.2 6.593 h5 = 3116.502 kJ / kg
107
Actual Enthalpy @ Point by Stage Efficiency,
h4 – h5'
ηs =
h4 – h5
3224.6 – h5'
0.8 =
3224.6 – 3116.502
H5` = 3122.907 kJ / kg
3122.907129 s₅'
@ Point 6
S6 = S5’ = 6.580923 kJ / kg - K
108
h₆ 6.5809233
h5’ – h6'
ηs =
h5’ – h6
3122.907 – h6'
0.8 =
3122.907- 2972.845
H6` = 2980.348 kJ / kg
2980.348259 s₆'
@ Point 7
S7 = S6’ = 6.59432152kJ / kg - K
by Interpolation;
from Steam Tables, Table 3
109
h ( kJ / kg) s ( kJ / kg – K ) (6.3963 – 6.3938159)( 2913.9 – 2899.9 )
h7 = 2913.9 -
2899.9 6.3703 (6.3963 – 6.3938159 )
h7 6.3938159
h 6’ – h 7'
ηs =
h 5’ – h 7
2980.348 – h6'
0.8 =
2980.348 – 2651.951
H7` = 2668.37 kJ / kg
2668.370497 s₇'
@ Point 8
110
P8 = 0.01 MPa
h ( kJ / kg ) S ( kJ/kg-K )
F 168.79 0.5764
Fg 2406.01 7.6751
S8 = sf +sfg ( x8 ) h8 = hf +hfg ( x8 )
h 7’ – h 8'
ηs =
h 7’ – h 8
2668.37– h8'
0.8 =
2668.37 – 2100.627
h 8’ = 2129.014 kJ / kg
111
Actual Quality of Steam @ Point 8,
112
SECOND CHECKING
Po₁ 19000 kW
Po₂ 19000 kW
Po 38000 kW
ww 0.01 ws
ηt 94 %
Solution:
Generator Efficiencies:
Generator 1:
0.055
ηg1 = 0.98 - ( RatingLoad )
³√(Rated kW1 /1000)
0.055
ηg1 = 0.98 - (0.75 )
³√([19000)1000]
0.055
ηg1 = 0.98 - ( RatingLoad )
³√(Rated kW1 /1000)
0.055
ηg1 = 0.98 - (0.75 )
³√([19000)1000]
113
Turbine Output
Turbine 1:
Po₁
Pt1=
(ηg₁)(ηt)
9000
Pt1=
(0.964541308) (0.80)
Pt1= 20955.832 kW
Turbine 2:
Po2
Pt2=
(ηg2)(ηt)
9000
Pt2=
(0.960169) (0.80)
Pt2= 20955.832 kW
Total:
Pt = Pt₁ + Pt₂
Pt = 20955.832+ 20955.832
Pt = 41911.665 kW
114
Heat Balance on Turbine Output
2 4
3 5 6 7 8
Pt = [ws (h₂-h₃') + ws (h₄-h₅') +(ws-x₅) (h₅' - h₆') + (ws – x₅ - x₆) (h₆ ' - h₇') + (ws - x₅ - x₆ -
x₇)(h₇' - h₈')]
h₂ = 3202.7 kJ/kg
h₃' = 3115.934 kJ/kg
h₄ = 3244.6 kJ/kg
h₅' = 3122.9071 kJ/kg
h₆' = 2980.3483 kJ/kg
h₇' = 2668.3705 kJ/kg
h₈' = 2129.0143 kJ/kg
115
41911.66474 =(1202.351698)ws -(993.8928266x₅ -(311.9777618 x₆ - (0x₇) - EQUATION1
ww
12 11 10
h₉ = 191.8122952 kJ/kg
Substituting:
116
2668.370497 x₇ +191.8122952(ws-x₅-x₆-x₇) =640.1853354x₇ +410.5824894(ws-x₅-x₆x₇)
12 11 10
117
h₁₂ = 862.8975531 kJ/kg
Substituting:
2000.764137 x₅ +-232.2797551ws = 0
Determined Values:
118
From Steam Tables:
hw = hf at t = 100 °C
hw = 419.099155 kJ/kg
Substituting:
119
Elimination:(Matrix)
A ws x₅ x₆ x₇ b
1 1202.3517) -(993.892827 -(851.334 -(539.356194 41911.665
2 -218.77019 218.7701942 218.77019 2246.955356 0
3 -232.27976 2000.764137 0 0 0
4` -224.47329 711.5605034 2569.7658 229.6028459 0
A⁻ ¹ ws x₅ x₆ x₇ b
1 0.0009977 0.000207527 0.0003617 0.000312875 41911.665
2 0.0001158 2.40929E-05 0.0005418 3.63234E-05 0
3 4.782E-05 -3.01655E-05 -0.000118 0.000407552 0
4` 8.121E-05 0.000465843 -6.06E-06 -1.27546E-05 0
x
ws 41.817214
x₅ 4.8547913
x₆ 2.0044202
x₇ 3.4036141
Where,
x = A⁻ ¹ × b
ws = 41.81721406 kg/s
x₅ = 4.854791258 kg/s
x₆ = 2.004420241 kg/s
x₇ = 3.403614136 kg/s
Percent Extraction:
%x = (x₅+x₆+x₇)/ws
120
4.8547913 + 2.0044202 + 3.40361414
%x =
41.817214
%x = 24.542108%
121
THIRD CHECKING
Assumptions:
Fuel Number = 5
Boiler Efficiency = 50 %
Air Enthalpy (Entry) = 57.069 kJ/kg
tdb₁ = 30 °C
twb₁ = 20 °C
Air Enthalpy (Exit) = 67.324 kJ/kg
tdb₂ = 40 °C
tw = 10 °C
Cg = 1.04645 kJ/kg-K
122
Table 5 - 1: Ultimate analysis
COMBUSTION ANALYSIS
C 0.84 C + O₂ → CO₂
H₂ 0.0452 H₂ + ½ O₂ → H₂O
O₂ 0.0603
N₂ 0.0117
S 0.0055 S + O₂ → SO₂
Ash 0.0373
Total: 1
Oxygen = -0.0603 O₂
32 O₂
Sulfur = X 0.0055 S = 0.0055 O₂
32 S
TOTAL: 2.5468 O₂
0.768 N₂
Nitrogen = 2.546833333 O₂ X = 8.430786 N₂
0.232 O₂
Air - Fuel Ratio, raf = 10.97759 AIR
EXHAUST GAS
44 CO₂
Carbon Dioxide = X 0.8405 C = 3.08 CO₂
12 C
18 H₂O
Water Vapour = X 0.045 H₂ = 0.4068 H₂O
2 H₂
64 SO₂
Sulfur Dioxide = X 0.0055 S = 0.011 SO₂
32 S
123
CHECK:
GAS COMPOSITION:
3.08
CO₂ X 100% = 25.795 %
11.94028621
0.4068
H₂O X 100% = 3.40695 %
11.94028621
0.011
SO₂ X 100% = 0.09213 %
11.94028621
8.442486207
N₂ X 100% = 70.7059 %
11.94028621
TOTAL: 100 %
Solve:
Qh = 34356 kJ/kg
124
Fuel:
Heat of Fuel:
Qf = wf (Qh)
Qf = (4.622299853) (34356)
Qf = 158803.7338 kJ/s
Where, Where,
ws = 41.81721 kg/s
ww = 0.01 ws
h₁₂ = 862.8976 kJ/kg
h₁ = hg at P₁ ; P₁ = P₂ = 9
h₁ = 2742.882 kJ/kg
Substituting,
wf = 4.6223 kg/s
Heat of Fuel:
Qf = wf (Qh)
Qf = (4.6223) (34356)
125
Qf = 87158.01 kJ/s
Air
wair
raf =
wf
wair = raf × wf
Heat of Air:
Qa = wair (hair)
Qa = (57.069) (57.069)
Qa = 2895.778kJ/s
Make-up Water:
ww = wm = 0.01 ws
wm = 0.01 (41.8172)
wm = 0.418172 kg/s
hw = hf at tw ;tw = 20 °C
hw = 83.9199 kJ/kg
Qw = (0.41817) (83.9199)
126
Qw = 35.09296 kJ/s
Qin = Qf + Qa +Qw
Qin = 158803.7+2895.778+35.09296
Energy Out: (Power Output, Condenser, Blowdown, Refuse, Flue Gas, Losses)
x₇ = 3.403614136 kg/s
Condenser:
Heat of Condenser
Qc = (31.55438843) (1937.202008)
Qc = 61127.22 kJ/s
127
Blowdown:
Qbd = wm (h₁)
Refuse:
Ash
wref = (wf)
0.8
0.0373
wref = (4.6223)
0.8
wg
rgf =
wf
wg = rgf ( wf )
wg = (11.9404)(4.6223)
wg = 55.19158kg/s
tga = 1050 °C
128
Through Superheater:
Qs = ws(h₂ - h₁)
Qs = 19228.31 kJ/s
Qg = Qs
Qs = 19228.31
Qg = wg (cg)(tga - tgb)
19228.31
tgb = 1050 -
(55.1916) (1.04645)
tgb = 717.072 ⁰C
Through Economizer:
Qw = ww(hw₂ - hw₁)
Qw = 140.1626 kJ/s
Qg = Qw
Qg = wg (cg)(tgb - tgc)
129
Qw = = 140.1626 Kj/s
140.1626
tgc = 717.072 -
(55.1916) (1.04645)
tcg = 714.646 ⁰C
h₁ = 57.069 kJ/kg
h₂ = 67.324kJ/kg
Qg = Qair
Qg = wg (cg)(tgc - tgd)
Qair = = 520.3561
520.3561
tgd = 714.646 -
(55.1916)(1.04645)
130
Total for Blowdown, Refuse and Flue Gas:
131
STEAM BOILER
A boiler is a closed vessel in which water or other fluid is heated but the fluid does not necessarily boil.
In North America, the term "furnace" is normally used if the purpose is not to boil the fluid. The heated or
vaporized fluid exits the boiler for use in various processes or heating applications, including water
heating, central heating, boiler-based power generation, cooking, and sanitation. The two types of boiler is
The pressure vessel of a boiler is usually made of steel (or alloy steel), or historically of wrought
iron. Stainless steel, especially of the austenitic types, is not used in wetted parts of boilers due to corrosion
and stress corrosion cracking. However, ferritic stainless steel is often used in superheated sections that will
not be exposed to boiling water, and electrically heated stainless steel shell boilers are allowed under the
European "Pressure Equipment Directive" for production of steam for sterilizers and disinfectors. In live
steam models, copper or brass is often used because it is more easily fabricated in smaller size boilers.
Historically, copper was often used for fireboxes (particularly for steam locomotives), because of its better
formability and higher thermal conductivity; however, in more recent times, the high price of copper often
makes this an uneconomic choice and cheaper substitutes (such as steel) are used instead.
For much of the Victorian "age of steam", the only material used for boiler making was the highest
grade of wrought iron, with assembly by rivet rolled and its suitability for high-reliability use in critical
applications, such as high-pressure boilers. This iron was often obtained from specialist ironworks, such as
at Cleator Moor (UK), noted for the high quality of their In the 20th century, design practice instead moved
towards the use of steel, which is stronger and cheaper, with welded construction, which is quicker and
requires less labor. It should be noted, however, that wrought iron boilers corrode far slower than their
modern-day steel counterparts, and are less susceptible to localized pitting and stress-corrosion. This makes
the longevity of older wrought-iron boilers far superior to those of welded steel boilers. Cast iron may be used
132
for the heating vessel of domestic water heaters. Although such heaters are usually termed "boilers" in some
countries, their purpose is usually to produce hot water, not steam, and so they run at low pressure and try
to avoid boiling. The brittleness of cast iron makes it impractical for high-pressure steam boilers.
In this design, the designers used Water-tube Boiler because this type generally gives higher steam
production rates and is generally preferred in high-pressure applications since the high-pressure water/steam
is contained within small diameter pipes which can withstand the pressure with a thinner wall.
(Source: http://www.nonwoventools.com/wp-content/uploads/2013/01/BoilerSeries_300_ca-01-src.jpg)
133
DESIGN OF STEAM BOILER
Data:
P1 = 10 MPa
T1 = 450˚C
P2 = 9 MPa
T2 = 202.328 ˚C
Ws = 41.81721 kg/s
Assumed Values:
Boiler Efficiency, Nb = 53 %
h1 = hs @ P1 = 10 MPa
h1 = 3240.9 kJ/kg
h2 = hf @ P2 = 9 MPa
At table 1 by Interpolation:
202 861.47
202.3275772 h2
203 863.99
134
(202-202.3275772)(861.47-
h2 = 861.47 – 863.99)
(202-203)
kJ
h2 = 862.9506489
kg
(Ws )(h1-h2)
DBH =
35322
(41.81721) (3240.9-1363.26)
DBH = ( 3600 )
35322
DBH = 8002.481 HP
DBH
RBH =
BR
8002.48076
RBH =
1.5
135
RBH = 5334.987171 HP
H.S = k (RBH)
H.S = π × D × Lt × Nt
H.S
Nt =
π (D) (Lt)
4854.83833
Nt =
π (0.05) (6)
Nt = 5151.14345 tubes
Nt = 5152 tubes
136
Solve for Weight of Fuel Supplied, Wf
(41.817214)(3240.9-1363.26)
Wf =
(0.53)(34356)
kg
Wf = 4.312101
s
Wair = raf(Wf)
kg
Wair= 47.3364807
s
Wg = rgf(wf)
Wg = (11.94029)(4.312101)
kg
Wg= 51.4877407
s
137
FURNACE
A furnace is a device used for high-temperature heating. The name derives from Greek word fornax,
which means oven. The heat energy to fuel a furnace may be supplied directly by fuel combustion, by
electricity such as the electric arc furnace, or through induction heating in induction furnaces. In American
English and Canadian English usage, the term furnace refers to the household heating systems based upon
a central furnace, otherwise known either as a boiler, or a heater in British English. Furnace may also be a
synonym for kiln, a device used in the production of ceramics. In British English, a furnace is
an industrial furnace used for many things, such as the extraction of metal from ore (smelting) or in oil
refineries and other chemical plants, for example as the heat source for fractional distillation columns. The
term furnace can also refer to a direct fired heater, used in boiler applications in chemical industries or for
providing heat to chemical reactions for processes like cracking, and is part of the standard English names
The first categories of furnaces are natural draft, atmospheric burner furnaces. These furnaces
consisted of cast-iron or riveted-steel heat exchangers built within an outer shell of brick, masonry, or steel.
The heat exchangers were vented through brick or masonry chimneys. Air circulation depended on large,
upwardly pitched pipes constructed of wood or metal. The pipes would channel the warm air into floor or wall
vents inside the home. This method of heating worked because warm air rises.
The system was simple, had few controls, a single automatic gas valve, and no blower. These
furnaces could be made to work with any fuel simply by adapting the burner area. They have been operated
with wood, coke, coal, trash, paper, natural gas, and fuel oil. Furnaces that used solid fuels required daily
maintenance to remove ash and "clinkers" that accumulated in the bottom of the burner area. In later years,
these furnaces were adapted with electric blowers to aid air distribution and speed moving heat into the
home. Gas and oil-fired systems were usually controlled by a thermostat inside the home, while most wood
138
and coal-fired furnaces had no electrical connection and were controlled by the amount of fuel in the burner
(Source: http://en.wikipedia.org/wiki/Furnace)
139
DESIGN OF FURNACE
(Source: http://en.wikipedia.org/wiki/Furnace)
Data:
Assumed values:
kcal
Use : HRR (Area)= 1 350 000
hr-m2
140
Refer to page 314 of Power Plant Engineering by FT Morse
kcal
HRR (Volume)= (178,000 – 267,000)
hr-m3
HRR kcal
Use : 267 000
(Volume)= hr-m2
Qt = Qf +Qair
2895.777798 + 158803.73
Qt =
3600
kcal
Qt = 139029912
hr
Qt
Af =
HRR (A)
139029912
Af =
1 350 000
Af = 102.9851 m2
141
Solve for Volume of the Furnace, 𝑽𝒇
Qt
Vf =
HRR (v)
139029912
Vf =
267 000
Vf = 520.7113 m3
Vf
Hf=
Af
520.71128 m3
Hf=
102.98512 m2
Hf= 5.05618 m
𝐐𝐭
𝑉𝑓𝑏 =
𝐇𝐑𝐑𝐕
𝟏𝟑𝟗𝟎𝟐𝟗𝟗𝟏𝟐
𝑉𝑓𝑏 = 𝟐𝟔𝟕𝟎𝟎𝟎𝟎
𝑉𝑓𝑏 520.7113 m3
142
Solve for Weight of Fuel Bed, 𝑾𝒇𝒃
T= 50.13013595 min
𝐿𝑓 = 𝑉𝑐𝑔 (T)
mm (43.204450 1m
𝐿𝑓 = 300
min min) ( 1 000 mm
)
𝐿𝑓 = 15.03904078 m
Af
Wf =
Lf
102.98512 m
Wf =
15.03904078 m
Wf = 6.847852 m
143
STEAM REHEATER
Steam Re-heater is a Steam Boiler component in which heat is added to intermediate-pressure
steam, which has given up some of its energy in expansion through the High-Pressure Turbine. The steam
after reheating is used to rotate the second steam turbine where the heat is converted to mechanical
energy. This mechanical energy is used to run the alternator, which is coupled to turbine, there by
Power plant furnaces may have a Steam Re-heater section containing tubes heated by hot flue
gases outside the tubes. Exhaust steam from the high pressure turbine is passed through these heated
tubes to collect more energy before driving the intermediate and then low pressure turbines.
(Source: http://en.wikipedia.org/wiki/Steamreheater)
144
DESIGN OF STEAM REHEATER
𝑘𝑔 𝑎𝑖𝑟
Raf = 11.977586𝑘𝑔 𝑓𝑢𝑒𝑙
𝑘𝑔
Ws = 41.817214
𝑠
𝑘𝑔
Wf = 4.361531 𝑠
𝑘𝑔
Wair = 3184536.445 𝑠
𝑘𝑗
hair = 57.06 𝑘𝑔
𝑘𝑗
h3ˈ = 3115.934 𝑘𝑔
𝑘𝑗
h4 = 3244.5 𝑘𝑔
LF = 15.03904078 m
145
Assumptions:
Tube Diameter, do = 0. 05 m
𝑘𝑔
𝑄𝑠𝑟 = (41.8172141 ) (3244.6 − 3115.9)
𝑠
𝑘𝑗
𝑄𝑠𝑟 = 5380.45369
𝑠
𝑄𝑠𝑟
𝛺=
𝑄𝑡
𝑘𝑗
5380.45369 𝑠
𝛺=
𝑘𝑗
2895.7778 + 158804 𝑠
𝛺 = 0.0332744
Solve for Mass of Cool Per Equivalent Radiant Surface Per HR, Cr
1
𝛺=
𝑟𝑎𝑓√𝐶𝑟
1+ 60
1
0.0332744 =
10.97759√𝐶𝑟
1+ 60
𝑘𝑔. 𝑚2
𝐶𝑟 = 25,215.9219
ℎ𝑟
146
Solve for Equivalent Radiant Heating Surface, Ar
𝑊𝑓
𝐴𝑟 =
𝐶𝑟
𝑘𝑔
2.53690791 𝑠
𝐴𝑟 =
7.004423 ÷ 3600
𝐴𝑟 = 0.6599116035284 𝑚2
𝐴𝑟
𝐴𝑃 =
(𝑆)(𝛿)
0.6599``6035284
𝐴𝑃 = 𝜋
(0.9) ( )
2
𝐴𝑃 = 0.46679197 𝑚²
Lf = Lt
𝐴𝑃 = 𝜋(𝐷𝑜)(𝐿𝑡)(𝑁𝑡)
𝐴𝑃
𝑁𝑡 =
𝜋(𝐷𝑜)(𝐿𝑡)
0.46679197
𝑁𝑡 =
𝜋(0.05)(15.03904 m )
𝑁𝑡 = .197598372960118
Nt = 1 tube
147
CONDENSER
Steam after rotating steam turbine comes to condenser. Condenser refers here to the shell
and tube heat exchanger (or surface condenser) installed at the outlet of every steam turbine in
Thermal Power Stations of utility companies generally. These condensers are heat exchangers which
convert steam from its gaseous to its liquid state, also known as phase transition. In doing so, the
The purpose is to condense the outlet (or exhaust) steam from steam turbine to obtain
maximum efficiency and also to get the condensed steam in the form of pure water, otherwise known
(Source: http://en.wikipedia.org/wiki/Condenser)
148
DESIGN OF CONDENSER
(Source: http://en.wikipedia.org/wiki/Condenser)
149
Data and Assumptions:
𝜃1 = 3 ˚C
Terminal Differences:
𝜃2 = 5.6 ˚C
𝜃1 Assume Range:
𝜃1 – (3 – 5.6 ˚C)
kcal
kt = 39.7 m – hr -
˚C
Solution:
hₓ₋₁ = hf at Pc
hf at Pc = 29.3 kJ/kg
Qs = 66255.2007 kJ/s
MKS:
150
kJ 3600s 1 kCal
Qs = Qs = 66255.2007 x x 56966496.9kcal / hr
s 1 hour 4.187 kJ
ts' = tsat at Pc
tsat at Pc = 45.81 ºC
twb' = ts' - θ₁
twb' = 45.81 - 3
twb' = 42.81 ºC
twa' = twb' - θ₂
twa' = 37.21 ºC
θmax = 8.6 ⁰C
θmin = 3.0 ⁰C
θmax – θmin
LMTD=
ln (θmax/ θmin)
8.6 – 3.0
LMTD=
ln 8.6
151
3.0
LMTD = 5.317382 ⁰C
tm = 40.00754821 ⁰C
by Interpolation:
1 1
Fluidity, J = =
CP 0.67993
J= 1.47073665
J⁰·²⁴
b= 1379.7
Dw⁰·²⁷
b = 1379.7 1.4707⁰·²⁴
152
0.02292⁰·²⁷
b = 4195.030264
Uw = (4195.030264) 2.4⁰·⁷³
Uw = 7948.575518 kcal/ m² - hr - ⁰C
Dv - Dw 25.4 – 22.92
t= =
2 2
t= 1.24 mm
t= 0.00124 m
kt 39.7
𝑈𝑡 = =
t
𝑈𝑡 = 32016.12903 kcal/ m² - hr - ⁰C
111910
Uv = = Av⁰ ·¹⁸
(Qs / Av)⁰·¹⁸⁸ 3897.74 ⁸
153
Heat: Q= 56966497kCal/hr
LMTD: θ = 5.317382 ⁰C
2 Dv 2 (25.4)
= = 0.00003283733965002410
Ut (Dw+Dv) 32016.129 (22.92 + 25.4)
Dv 25.4
= = 0.00005674359668617390
Us Dw (19530) (22.92)
Dv 25.4
= = 0.00013551105189437700
Uw Dw (7948.58) (22.92)
; Simplification
56966497 1
5.317382 = [ + 0.0002 ]
Av 3897.74 Av0.188
154
14615.28 13075.54
5.317382 = +
Av1.188 Av
Av = 2303.124375 m²
66255.2007
Ww=
4.187 (42.80755 – 37.21)
Ww = 2825.719092 kg/s
Ww = Aw × Vw × Nt
π Dw²
Ww = x Vw x Nt x pw
4
π (0.02292m)2
Ww = x 2.4 m/s x Nt x 1000 kg/m3
4
Nt = 2853.636402
Nt = 2854 Tubes
155
Lt = 10.11299596 m
156
COOLING TOWER
A cooling tower is a heat rejection device that rejects waste heat to the atmosphere through the
cooling of a water stream to a lower temperature. Cooling towers may either use the evaporation of water to
remove process heat and cool the working fluid to near the wet-bulb air temperature or, in the case of closed
circuit dry cooling towers, rely solely on air to cool the working fluid to near the dry-bulb air temperature.
Common applications include cooling the circulating water used in oil refineries, petrochemical and
other chemical plants, thermal power stations and HVAC systems for cooling buildings. The classification is
based on the type of air induction into the tower: the main types of cooling towers are natural draft and induced
draft cooling towers. Cooling towers vary in size from small roof-top units to very large hyperboloid
structures (as in the adjacent image) that can be up to 200 meters (660 ft) tall and 100 meters (330 ft) in
diameter, or rectangular structures that can be over 40 meters (130 ft) tall and 80 meters (260 ft) long. The
hyperboloid cooling towers are often associated with nuclear power plants, although they are also used in
some coal-fired plants and to some extent in some large chemical and other industrial plants. Although these
large towers are very prominent, the vast majority of cooling towers are much smaller, including many units
157
Figure 5 - 18: Cooling Tower
(Source: http://en.wikipedia.org/wiki/Coolingtower)
Industrial cooling towers can be used to remove heat from various sources such as machinery or
heated process material. The primary use of large, industrial cooling towers is to remove the heat
absorbed in the circulating cooling water systems used in power plants, petroleum refineries,
petrochemical plants, natural gas processing plants, food processing plants, semi-conductor plants, and
for other industrial facilities such as in condensers of distillation columns, for cooling liquid in
crystallization, etc. The circulation rate of cooling water in a typical 700 MW coal-fired power plant with
a cooling tower amounts to about 71,600 cubic meters an hour (315,000 US gallons per minute)] and the
158
circulating water requires a supply water make-up rate of perhaps 5 percent (i.e., 3,600 cubic meters an
hour).
If that same plant had no cooling tower and used once-through cooling water, it would require
about 100,000 cubic meters an hour. A large cooling water intake typically kills millions of fish and larvae
annually, as the organisms are impinged on the intake screens. A large amount of water would have to be
continuously returned to the ocean, lake or river from which it was obtained and continuously re-supplied
to the plant. Furthermore, discharging large amounts of hot water may raise the temperature of the
receiving river or lake to an unacceptable level for the local ecosystem. Elevated water temperatures can
kill fish and other aquatic organisms (see thermal pollution), or can also cause an increase in undesirable
organisms such as invasive species of zebra mussels or algae. A cooling tower serves to dissipate the heat
into the atmosphere instead and wind and air diffusion spreads the heat over a much larger area than hot
water can distribute heat in a body of water. Evaporative cooling water cannot be used for subsequent
purposes (other than rain somewhere), whereas surface-only cooling water can be re-used. Some coal-
fired and nuclear power plants located in coastal areas do make use of once-through ocean water. But
even there, the offshore discharge water outlet requires very careful design to avoid environmental
problems. Petroleum refineries also have very large cooling tower systems. A typical large refinery
processing 40,000 metric tonnes of crude oil per day (300,000 barrels (48,000 m3) per day) circulates
about 80,000 cubic meters of water per hour through its cooling tower system.
159
DESIGN OF COOLING TOWER
Data:
Qs = 61127.225 kJ/s
ts = 45.81 ⁰C
td1 = 30 ⁰C
tw1 = 20 ⁰C
RH2 = 80 %
twc = 20 ⁰C
Θ1= 5.6
Terminal Differences:
Θ2 = 7.5
Θ Assume Range:
Θ1 – (3 – 5.6 ⁰C)
160
Solve:
Temperatures of Water:
Condenser - HE Loop:
twc = 20 ⁰C
Ƞct = 66.613128 %
Temperature of Approach:
tapp = 24.1075 - 20
tapp = 75.393587 - 68
tapp = 7.39358677 ⁰F
161
Types of Approach:
Large Approach: 15 - 20 ⁰F
Moderate Approach: 10 - 15 ⁰F
Small Approach: 04 - 08 ⁰F
tapp, ⁰F H, feet
10 - 25
11 - 26
12 - 27
13 - 28
14 - 29
15 - 30
tapp = 7.39358677 ⁰F
H = 39.2419835 feet
Air Properties:
162
Determining Partial Pressure of Water Vapor by Carrier's Equation:
Pv
ω₁ = (0.622)
P - Pv
0.001693065
ω₁ = (0.622)
0.101325 – 0.001693065
h₁ ≈ cpa(td₁) + ω₁(2500+1.88(td₁))
163
kJ
h₁ ≈ 57.170549
kgda
𝑚3
v1 = 0.872823
𝑘𝑔
Ps = 0.005091784 MPa
Pv₂ = RH₂ × Ps
Pv
ω₂ = (0.622)
P - Pv
164
0.004073427
ω₂ = (0.622)
0.101325 – 0.004073427
kgv
ω₂ = 0.02605276
kgda
165
SUPERHEATER
A Superheater is a device used to convert saturated steam or wet steam into dry steam.
Superheaters are used in steam engines or in processes, such as steam reforming. The function of a
Superheater is to increase the temperature of the steam above saturation by utilizing the heat from the
flue gas.
The main advantage of using Superheater is reducing fuel and water consumption. Although using
Superheater will result in increased maintenance costs, benefits outweighed the costs. This is the reason
why Superheaters are widely used.
(Source: http://en.wikipedia.org/wiki/Superheater)
166
DESIGN OF SUPERHEATER
Data:
t s₂ = 430 ⁰ C
tga = 1050 ⁰ C
D₁ = 0.04 m REFERENCES:
167
Specific Enthalpies:
Qs = 19228.31 kJ/s
tgb = 693.123 ⁰ C
θmax = 620 ⁰ C
θmin = 382.063 ⁰ C
θmax − θmin
LMTD =
ln ( θmax / θmin)
620−382.062804
LMTD =
ln ( 570 062804)
LMTD = 491.4692 oC
168
Solve for Overall Coefficient of Heat Transfer, Ut
wg′ 0.981684872
Gg = =
s₁ (h) (0.2)(1.75)
Gg = 2.804814 kg/m²- s
µ₂ = 38 x (10¯⁷ ) µ₁ = 26 x (10¯⁷ )
h₁ = 1125.087 kCal/hr-m²-⁰ C
h₂ = 3924405 kCal/hr-m²-⁰ C
Ut = k / t = 2k / (D₂-D₁)
Ut = 7940 kCal/hr-m²-⁰ C
1 1 1 1
= + +
𝑈 h₁ 𝑈𝑡 h₂
1 1 1 1
= + +
𝑈 1193.787122 7940 39.244046
Ut = 37.84469036 kCal/hr-m²- oC
169
Solve for Number of Tubes of Superheater, Nt
Qs = U(At)(LMTD)
At = 745.6129 m²
Ae = At/Ne = 745.6129 / 51
Ae = 8.669918 m²
Le = Ae / πD₂
Le = 55.19441 m
Nts = Le / h
Nts = 31.53966
Nts = = 32 tubes
W = 86(0.05) + 87(0.2)
Width = 21.7 m
= 32 (0.05) + 343(0.4)
Length = 14.8 m
170
ECONOMIZER
Economizers are mechanical devices intended to reduce energy consumption, or to perform useful
function such as preheating a fluid. In simple terms, an Economizer is a heat exchanger. It recovers more heat
A common application of Economizers in steam power plants is to capture the waste heat
from boiler stack gases (flue gas) and transfer it to the boiler feedwater. This raises the temperature of the
boiler feedwater, lowering the needed energy input, in turn reducing the firing rates needed for the rated
boiler output.
(Source: http://en.wikipedia.org/wiki/Economizer)
171
DESIGN OF ECONOMIZER
t w₁ 20 ⁰C
t w₂ 100 ⁰C
tgb 693.1228039 - ⁰C
dₒ 0.03 m REFERENCES:
cg - Page 280
P.P.E., F. MORSE
Specific Enthalpies:
172
h₂ = hf = 419.04 kJ/kg (from Table 1 at tw₂)
Qw = ww (h₂ - h₁)
Qw = 140.1211 kJ/s
tgc = 690.52 ⁰ C
θmax = 593.12 oC
θmin = 670.52 oC
θmax − θmin
LMTD =
ln ( θmax / θmin)
670.52 − 593.123
LMTD = 670.522
ln593.123
LMTD = 631.0315591 oC
G = 5198.75 kg/hr-m²
Ut= A + B(G)
173
Ut = 1.22 + 0.00075 (5198.75)
Ut = 5.119064 kCal/hr-m²-oC
Ut = 0.005953756 kW/m²-oC
Qw = U(At)(LMTD)
CD - x(dₒ (D)) = Wg / G
x = 10C - 1
D = 3C
EQUATIONS 1, 2, AND 3:
2A
C = 4.0990671 m width
D = 4.099071 (3)
D = 12.29721 m length
x = 4.099071(10) -1
174
x = 39.099071
x = 40 tubes
H = 9.4 m height
HS = x (π)(dₒ) (D)
HS = 43.3594 m²
y = At / HS = 37.29593 / 46.3594
y = 0.804496rows = 1 row
175
AIR-PREHEATER
An Air Pre-Heater is a general term used to describe any device designed to heat air before another
process (for example, combustion in a boiler) with the primary objective of increasing the thermal efficiency
of the process.
The purpose of the Air Pre-Heater is to recover the heat from the boiler flue gas which increases
the thermal efficiency of the boiler by reducing the useful heat lost in the flue gas. As a consequence, the
flue gases are also conveyed to the flue gas stack (or chimney) at a lower temperature, allowing simplified
design of the conveyance system and the flue gas stack. It also allows control over the temperature of
(Source: http://en.wikipedia.org/wiki/Airpreheater)
176
AIR-PREHEATER
t db₁ 30 ⁰C
t wb₁ 20 ⁰C
t db₂ 40 ⁰C
Saturation Pressures:
177
Determining Partial Pressure of Water Vapor by Carrier's Equation, Pv
Pv = 0.001676197 MPa
ω₁ = ω₂ = (0.622) Pv / P - Pv
ω₁ = 0.010462688 kgv
h₁ = cpa(tdb₁) + ω₁(2500+1.88(tdb₁))
h₂ = cpa(tdb₂) + ω₂(2500+1.88(tdb₂))
h₁ = 57.069 kJ/kg
h₂ = 67.324 kJ/kg
178
Solve for Heat Loss from Gas (Final Temperature), tgd
tgd = 681.512 ⁰ C
TgC
gas
TgD θMIN
Ta2 θMAX
air
Ta1
θmax = 650.52 oC
θmin = 651.51 oC
θmax − θmin
LMTD =
ln ( θmax / θmin)
651.512− 650.522
LMTD = 651.512
ln650.522
LMTD = 651.0172 oC
G = 4982.768 kg/hr-m²
179
U = A + B(G)
U = 4.192246 kcal/hr-m²-⁰ C
U = 0.00488 kW/m²-oC
Qw = U(At)(LMTD)
At = 152.9298 m²
HS = π (dₒ) (Lt)
HS = π (0.05) (3)
HS = 0.471239 m²
Nt = At / HS
Nt = 152.9298 m² / 0.471239
Nt = 324.52702
Nt = 325 Tubes
Ntx = 17 tubes
Nty = 23 tubes
L = 4.45 m
180
w = Nty(dₒ) + (Nty +1) (S₂)
w = 5.95m
181
STACK
A Stack is a vertical pipe, channel or similar structure through which combustion product gases
called flue gases are exhausted to the outside air. Flue gases are produced when coal, oil, natural gas, wood
or any other fuel is combusted in an industrial furnace, a power plant's steam-generating boiler, or other large
combustion device.
The flue gas stacks are often quite tall, up to 400 metres (1300 feet) or more, so as to disperse the
exhaust pollutants over a greater area and thereby reduce the concentration of the pollutants to the levels
(Source: http://en.wikipedia.org/wiki/Stack)
182
Design of Stack
183
Given and Assumptions:
Wg 52.00260165 kg/s
Ds 2 cmw
ta 30 °C
tg 705.6358972 - °C
Wg = 52.00260165 kg/s
Wg = 55.19158318 kg/s
tg = tgd = 685.071553 - °C
Ds = 2cmw
dg = 0.384482141 kg/m³
Dm = 0.004 (V²)(0.384482141)cmw
Dm = 0.001537929(V²) cmw
184
Available Draft per 30m of Stack/Chimney Equation:
; Qg = Wg /(dg)
; Qg =(52.00260165) / (0.384482141)
Qg =135.2536205 m3/s
da = 1.152 kg/m³
= 135.2536205
= 135.2536205
DS + DM
H = (30)
D30
2 + 0.001537929(V²)
H = (30)
1.842042861 -0.002913606√ (V⁵ ) - equation 3
185
Table 5 - 4: SUMMARY TABLE
Vg D₁ H D₁ x H
6.1 5.3209353 33.92861 180.531962
7.014 4.9621514 34.41459 170.770414
7.928 4.6673576 34.98899 163.306116
8.842 4.4195458 35.65818 157.59294
9.756 4.207431 36.42946 153.274426
10.67 4.0231913 37.31127 150.110393
11.584 3.8612117 38.31346 147.936368
12.498 3.717343 39.44752 146.639972
13.412 3.5884436 40.72705 146.146707
14.326 3.4720856 42.16811 146.4113
15.24 3.3663589 43.78991 147.412535
Graph:
200
180
160
140
120
H × D₁
100
80
60
40
20
0
6.1 7.014 7.928 8.842 9.756 10.67 11.584 12.498 13.412 14.326 15.24
Vg, m/s
186
SOLVE FOR MECHANICAL DRAFT (DM):
DT = DS + DM
DT = 2 + 0.2655622234 𝐻2 𝑂
DT = 2.2655622234 cm 𝐻2 𝑂
(Using EQUATION 2)
D30 = 1.471101598 cm 𝐻2 𝑂
(Using Equation 4)
187
SOLVE FOR HEIGHT OF STACK, H
(Using Equation 3)
2 + 0.2655622234 (Vg)2
H = (30)
1.842042861 -0.002913606√ (V⁵ )
2 + 0.2655622234 (13.142)2
H = (30)
1.842042861 -0.002913606√ (⁵ )
2 + 0.2655622234 (13.142)2
H = (30) 1.842042861 -0.002913606√
(13.142⁵ )/135.422
H= 40. 7270463m
X = H (tan ( α ) )
X = 2.134414053 m
D2 = D1 + 2(X)
D2 = 2.709578473 m + 2(2.134414053 m)
D2 = 6.978406579 m
188
189
LOW PRESSURE HEATERS
Low pressure (LP) feedwater heaters are basically simple straightforward 'tube and shell' heat
exchangers, with the condensate passing through the tubes and the bled-steam being admitted to the shell.
This type of heater, arranged vertically, has been used for many decades, but two advances worthy of note
have been made in recent years and are now treated as modern practice. With the turbine exhaust being
connected to its underslung condenser by a large, deep, transition piece, a significant volume of unused
space exists between the exhausts of a double-flow cylinder and above the condenser tubenests. This space
can be effectively utilized by inserting one or two Low Pressure feedwater heaters in a horizontal attitude.
190
DESIGN OF LOW PRESSURE HEATERS
X7 = 9.2506729
k = 39.7 kCal/hr-m²-⁰C
T7' = 120.562535 °C
T10 = 105.633156 °C
T7a at P7 = 99.63°C
T9 =60.06°C
Vw = 2.4 m/s
thickness = 0.005 m
D0 = 0.05m
Di = 0.04m
h' t'
2572.7 50
2590 t7'
2583.2 55
by: Interpolation ;
c-a
191
Solve for Log Mean Temperature Difference (LMTD);
Qmax = 14.929379 °C
Qmin = 39.57 °C
θmax − θmin
LMTD = ln ( θmax / θmin)
14.929379 − 39.57
LMTD = ln ( 14.929379 ÷ 39.57)
LMTD = 25.27916671 ℃
𝑈𝑠𝑒: 𝐷𝑜 = 0.05 𝑚
𝐷𝑖 = 0.045 m
𝐷𝑜 −𝐷𝑖
t= 2
.05−.045
t= 2
t = .0025 m
192
Solve for Thermal Conductivity of Tube, (𝑼𝒕 )
𝑈𝑡 =Centipoise
39.7
k = 39.7
ℎ𝑟− 𝑚2 −℃
𝑘
𝑈𝑡 =
𝑡
39.7
=
.0025
39.7 kcal
𝑈𝑡 = 15880
ℎ𝑟− 𝑚2 −℃
105.633156 ℃−60.06 ℃
t= 2
t = 82.846578℃
J = 4.347826087
193
Solve for Value of b:
Dw = 𝐷𝑖 =0.05m
𝐽0.24
b = 1379.7 x 𝐷𝑤.27
4.347826087.24
b = 1379.7 x .05.27
b = 4408.06594
𝑈𝑤 = (4408.06594) (2.40.72 )
𝑘𝑐𝑎𝑙
𝑈𝑤 =8352.226994
𝐻𝑅−𝑚2 −℃
𝑘𝑐𝑎𝑙
𝑈𝑠 = 19530 𝐻𝑅−𝑚2 −℃
1 1 1 1
= 19530+ 7940 + 8352.226994
𝑈
𝑘𝑐𝑎𝑙
U = 3368.405076 𝐻𝑅−𝑚2 −℃
194
Solve for Heat at High Pressure Heater, (Q)
Q = 𝑥5 (ℎ5 ′ − ℎ5𝑎 )
Q = U(A)(LMTD)
𝑄
A=
𝑈(𝐿𝑀𝑇𝐷)
𝐾𝐽 3600 𝑠
17280672.34 ( )
A= 𝑘𝑐𝑎𝑙
𝑠 4.18
3368.405076 (25.27916671 ℃)
𝐻𝑅−𝑚2 −℃
A = 202.9427628 𝑚2
20098.38917
Ww = 4.187(105.633156−60.06)
Ww = 105.3292592 kg/s
195
Solve for Area of Shell, (𝑨𝒔 )
𝜋 𝐷𝑜 2 𝑁𝑡
𝐴𝑡 = 4 ( )
4
𝐴𝑡 = .090320789 𝑚2
𝐴𝑠 = .361283155 𝑚2
𝜋 𝐷𝑠 2
𝐴𝑠 =
4
4 (𝐴𝑠 )
𝐷𝑠 =√ 𝜋
4 (.090320789 𝑚2 )
𝐷𝑠 =√ 𝜋
𝐷𝑠 = 0.339116499 m
Using Tables of Design of Machine Elements (4th Edition) by VM Faires, page 576
Use:
AISI No. 8760
Sy = 250,000 psi
As prescribed by Philippine Mechanical Code
FS = 3
𝑆𝑦
Sd = 𝐹𝑆
250,000 𝑝𝑠𝑖
Sd = 5
Sd = 57.44047619 MPA
196
Solve for Thickness of Shell, (t)
𝑃5 (𝐷𝑠 )
t=
2 𝑆𝑑
14.7 𝑝𝑠𝑖
(4.5 𝑚𝑝𝑎 𝑥 )(.339116499 𝑥 3.28 𝑥 12)
.101325 𝑚𝑝𝑎
t=
2 (57.44047619 𝑀𝑃𝐴)
t = 0.00590379 in
t = 0.2324267 m
197
HIGH PRESSURE HEATER
Current High Pressure heaters and associated systems use welded joints wherever practicable, as
bolted joints have proved difficult to maintain leak-free when subjected to thermal cycling. It is now
accepted that to maintain heater internals, the heater shell has to be cut off and likewise any defective
valves, etc., have to be cut from the pipework. The subsequent re-welding of the heater shell has proved
to be less difficult than the reassembly of complicated bolted joints, which require special techniques to
ensure precise bolt tensioning and thereafter periodic checking and possible tensioning to allow for gasket
relaxation. As the high-pressure feedwater heaters are on the discharge side of the feed pumps, the
feedwater within the water headers and the tubes is at boiler pressure plus the pressure rise between the
heater and the boiler. To contain this high pressure, various designs of water header have been used in
the past, but virtually all current 660 MW units employ hemispherical-headed heaters with a flat
tubeplate. The tubes are welded onto the back of the tubeplate by the 'Foster Wheeler fusion welding
process' illustrated. This method of tube attachment has been used for many years and, once initial
difficulties with the quality of welds were overcome, it has proved a cost-effective method of tube
attachment.
198
DESIGN OF HIGH PRESSURE HEATER
𝑋5 = 4.8547913 𝑘𝑔/𝑠
ℎ5 ′ = 3122.9071 KJ/kg
𝑡5 ’ = 663.36791 ℃
𝑡5𝑎 = 257.48 ℃
𝑡11 = 150.15 ℃
𝑡12 = 202.33 ℃
𝑡5 ’ = 663.36791 ℃
𝑡5𝑎 = 257.48 ℃
𝑡11 = 150.15 ℃
𝑡12 = 202.33 ℃
θ max = 𝑡5 ’- 𝑡12
θ max = 461.003791 ℃
θmin= 107.33 ℃
199
θmax − θmin
LMTD = ln ( θmax / θmin)
461.003791 − 107.33
LMTD = ln ( 461.003791 ÷ 107.33)
LMTD = 242.6692419 ℃
𝑈𝑠𝑒: 𝐷𝑜 = 0.05 𝑚
𝐷𝑖 = 0.045 m
𝐷𝑜 −𝐷𝑖
t= 2
.05−.045
t= 2
t = .0025 m
𝑈𝑡 =Centipoise
𝑘
𝑈𝑡 = 𝑡
39.7
= .0025
39.7 kcal
𝑈𝑡 = 15880 ℎ𝑟− 𝑚2 −℃
200
Solve for Mean Water Temperature:
𝑇11+ 𝑇12
t= 2
202.33 ℃−150.15 ℃
t= 2
t = 176.24 ℃
J = 2.804289956w
Dw = 𝐷𝑖 = .05 m
𝐽0.24
b = 1379.7 x 𝐷𝑤.27
2.804289956.24
b = 1379.7 x .05.27
b = 3967.713116
𝑈𝑤 = (3967.713116) (2.40.72 )
𝑘𝑐𝑎𝑙
𝑈𝑤 = 7517.846079
𝐻𝑅−𝑚2 −℃
201
Solve for Conductivity of Scale on Water, (𝑼𝒔 )
𝑘𝑐𝑎𝑙
𝑈𝑠 = 19530 𝐻𝑅−𝑚2 −℃
1 1 1 1
= 19530+ 7940 + 7518
𝑈
𝑘𝑐𝑎𝑙
U = 3224.096996 𝐻𝑅−𝑚2 −℃
Q = 𝑥5 (ℎ5 ′ − ℎ5𝑎 )
Q = U(A)(LMTD)
𝑄
A = 𝑈(𝐿𝑀𝑇𝐷)
𝐾𝐽 3600 𝑠
8351525.953
( )
A= 𝑘𝑐𝑎𝑙
𝑠 4.18
3229.096996 (24.6692419)
𝐻𝑅−𝑚2 −℃
A = 10.67439228𝑚2
20098.38917
Ww = 4.187(105.633156−60.06)
Ww = 105.3292592 kg/s
202
Solve for Number of Tubes, (𝑵𝒕 )
A = 𝜋𝐷𝑜 x 𝐿𝑡 x 𝑁𝑡
4𝑊𝑤
𝑁𝑡 =
𝜋𝐷𝑜 (Uw)(pw)
𝑁𝑡 = 9.434486856
𝑁𝑡 = 10 𝑇𝑢𝑏𝑒𝑠
𝐴𝑡 = .039269903 𝑚2
𝐴𝑠 = .157079633 in
𝜋 𝐷𝑠 2
𝐴𝑠 =
4
4 (𝐴𝑠 )
𝐷𝑠 =√ 𝜋
4 (.039269903 𝑚2 )
𝐷𝑠 =√ 𝜋
𝐷𝑠 = 0.447213595 m
203
Solve for Design Stress, (Sd)
Using Tables of Design of Machine Elements (4th Edition) by VM Faires, page 576
Use:
AISI No. 8760
Sy = 200,000 psi
As prescribed by Philippine Mechanical Code
FS = 3
𝑆𝑦
Sd = 𝐹𝑆
250,000 𝑝𝑠𝑖
Sd = 3
Sd = 57.4404762 MPA
𝑃5 (𝐷𝑠 )
t=
2 𝑆𝑑
14.7 𝑝𝑠𝑖
(2 𝑚𝑝𝑎 𝑥 )(.4472136 𝑥 3.28 𝑥 12)
.101325 𝑚𝑝𝑎
t=
2 (57.4404762 𝑀𝑃𝐴)
t = 0.007785687 m
t = 0.306523129 in
204
PIPING
Within industry, piping is a system of pipes used to convey fluids (liquids and gases) from one
location to another. The engineering discipline of piping design studies the efficient transport of fluid. Industrial
from wood, fiberglass, glass, steel, aluminum, plastic, copper, and concrete. The in-line components, known
as fittings,[3] valves, and other devices, typically sense and control the pressure, flow rate and temperature of
the transmitted fluid, and usually are included in the field of piping design (or piping engineering). Piping
systems are documented in piping and instrumentation diagrams (P&IDs). If necessary, pipes can be cleaned
Piping sometimes refers to piping design, the detailed specification of the physical piping layout
within a process plant or commercial building. In earlier days, this was sometimes called drafting, technical
drawing, engineering drawing, and design, but is today commonly performed by designers that have learned
Plumbing is a piping system with which most people are familiar, as it constitutes the form of fluid
transportation that is used to provide potable water and fuels to their homes and businesses. Plumbing pipes
also remove waste in the form of sewage, and allow venting of sewage gases to the outdoors. Fire
sprinkler systems also use piping, and may transport non-potable or potable water, or other fire-suppression
fluids.
205
Piping also has many other industrial applications, which are crucial for moving raw and semi-processed
fluids for refining into more useful products. Some of the more exotic materials used in pipe construction
206
DESIGN OF PIPING
Mass flow
Ws = 41.81721 kg/s
V= 1219 m/min
Np = 1 v = 32.11x10-3m3/kg
Q = ws (v)
Q = 41.81721 x 32.11x10-3
Q = 80.56503679 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(80.56503679)(60)
D=√ 𝜋(1829)
D = 0.2368217093 m = 236.8217093 mm
207
From, page 598, PPE by Morse (Table 14.15)
Di = 254 mm Ts = 32 mm
Mass flow
Ws = 41.81721 kg/s
V= 4000 m/min
Np = 1 v = 32.11x10-3 m3/kg
Q = ws (v)
Q = 41.81721 x 32.11x10-3 x 60
Q = 80.56503679 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(80.56503679)(60)
D=√ 𝜋(4000)
D = 0.16010394633 m = 160.1394633 mm
208
From, page 665, PPE by Morse
Di = 203.2 mm Ts = 32 mm
Mass flow
Ws = 2509.0326 kg/min
V= 4200 m/min
Np = 1
By interpolation;
H V
3114.5 42.44
3115.934 V3
3167.7 43.38
Solve;
3114.5 − 3115.934 42.44 − 𝑋
= 42.44 − 43.48 V3 = 0.0424653375
3114.5 − 3167.7
209
Solve for Volume Flowrate (Q);
Q = ws (v)
Q = 2509.0326 x 0.0424653375
Q = 106.5469162 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(106.5469162)(60)
D=√ 𝜋(4200)
D = 0.17972184 m = 179.72184 mm
Di = 203.2 mm Ts = 32 mm
Mas flow
Ws = 25.037278 kg/s
210
Assuming the flow velocity for = high-pressure saturated steam
V= 4000 m/min
Np = 1 v = 46.10x10-3 m3/kg
Q = ws (v)
Q = 2509.0326 x 46.10x10-3
Q = 115.6664029 m3/min
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(115.6664029)(60)
D=√ 𝜋(4000)
D = 0.1918795444 m = 191.8795444 mm
Di = 203.2 mm Ts = 32 mm
X5 =4.8547913 kg/s x 60
X5 = 291.287478 kg/min
V= 3800 m/min
Np = 1
By interpolation;
H V
3061.1 59.71
3122.9071 V3
3113.1 60.99
Solve;
3061.1 − 3122.9071 59.71 − 𝑋
= 59.71 − 60.99 V3 = 0.06056709514 m3/kg
3061.1 − 3113.1
Q = ws (v)
Q = 291.287478 x 0.06056709514
Q = 17.64243639 m3/s
212
(𝐷𝑝)2
Q =𝜋 4
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(17.64243639)(60)
D=√ 𝜋(3800)
D = 0.0681377018 m, 68.13770189 mm
Di = 76.2 mm Ts = 26 mm
Mass flow
X6 = 2.0044202 kg/s x 60
X6 = 120.0463212 kg/min
V= 3500 m/min
Np = 1
By interpolation;
213
H V
2959.3 94.32
2980.3483 V6
2984.3 96.63
Solve;
2959.3 − 2980.3483 94.32 − 𝑋
= 94.32 − 96.63 V6 = 96.26486292x10-3 m3/kg
2959.3 − 2984.3
Q = ws (v)
Q = 2.0044202 x 96.26486292x10-3 x 60
Q = 11.55624265 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(11.55624265)(60)
D=√ 𝜋(3500)
D = 0.0648379631 m, 64.8379631 mm
214
Di = 76.2 mm Ts = 26 mm
Mass flow
X7 = 3.4036141 kg/s
V= 4572 m/min
Np = 1
By interpolation;
H V
2658.9 333.1
2668.37 V7
2671.7 339.1
Solve;
2658.9 − 2668.37 333.1 − 𝑋
= 333.1− 339.1 V7 = 0.3375390625 m3/kg
2658.9 − 2671.7
Q = ws (v)
Q = 3.4036141 x 0.3375390625 x 60
Q = 68.93116275 m3/s
215
Solve for Diameter of Pipe (D);
(𝐷𝑝)2
Q =𝜋 4
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(68.9311625)(60)
D=√ 𝜋(4572)
D = 0.1696896603 m = 169.6896603 mm
Di = 203.2 mm Ts = 32 mm
Mass flow
Ws – X7 – X6 – X5 = 31.5543884 kg/s
V= 7315 m/min
Np = 1 v = 0.0010102 m3/kg
Q = ws (v)
216
Q = 31.5543884 x 0.0010102
Q = 1.91257459 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(1.91257459)(60)
D=√ 𝜋(7315)
D = 0.0182455552 m = 18.2455552 mm
Di = 19.1 mm Ts = 22 mm
Mass flow
Ws – X7 – X6 – X5 = 31.5543884 kg/s
V= 152 m/min
Q = ws (v)
Q = 31.5543884 x 0.0010102
Q = 1.91257459 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(1.91257459)(60)
D=√ 𝜋(152)
D = 0.1266782974 m = 126.6782974 mm
Di = 127 mm Ts = 29 mm
Mass flow
Ws – X7 – X6 – X5 = 31.5543884 kg/s
Np = 1 v = 0.0010102 m3/kg
Q = ws (v)
Q = 31.5543884 x 0.0010102
Q = 1.91257459 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(1.91257459)(60)
D=√ 𝜋(183)
D = 0.1153556061 m = 115.3556061 mm
Di = 127 mm Ts = 29 mm
Mass flow
219
Ws – X7 – X6 – X5 = 31.5543884 kg/s
V= 183 m/min
Np = 1
By interpolation;
T V
96.71 1.0410
97.98 V10
98.20 1.0421
Solve;
96.71 − 97.98 1.0410 − 𝑋
= 1.0410− 1.0421 V10 = 0.001041937511 m3/kg
96.71 − 98.20
Q = ws (v)
Q = 31.5543884 x 0.001041937511 x 60
Q = 1.972662055 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(1.972662055)(60)
D=√ 𝜋(183)
D = 0.1171536597 m, 117.1539597 mm
220
From, page 665, PPE by Morse
Di = 127 mm Ts = 29 mm
Mass flow
Ws + Wm = 42.6535542 kg/s
V= 183 m/min
Np = 1
By interpolation;
T V
149.54 1.0900
150.15 V11
150.32 1.0917
Solve;
149.54 − 150.15 1.0900 − 𝑋
= 1.0900− 1.0917 V11 = 0.001091329261 m3/kg
149.54 − 150.32
221
Q = ws (v)
Q = 42.6535542 x 0.001091329261 x 60
Q = 2.7929452 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(2.7929452)(60)
D=√ 𝜋(183)
D = 0.1393993413 m, 139.3993413 mm
Di = 153.4 mm Ts = 29 mm
Mass flow
Ws + Wm = 42.6535542 kg/s
V= 183 m/min
222
Np = no. of pipes v = vf at [email protected]°C
Np = 1
By interpolation;
T V
201.33 1.1587
202.33 V12
202.89 1.1610
Solve;
201.33 − 202.33 1.1587 − 𝑋
= 1.1587− 1.1610 V12 = 0.00160129193 m3/kg
201.33 − 202.89
Q = ws (v)
Q = 42.6535545 x 0.00160129193 x 60
Q = 0.06830076573 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(0.06830076573)(60)
D=√ 𝜋(183)
D = 0.0217992875 m, 21.79928758 mm
223
Di = inside diameter Wp = Weight of pipe Tw = Wall thickness
Di = 25.4 mm Ts = 22 mm
Mass flow
Ww = 0.418172 kg/s
V= 100 m/min
Np = 1 v = 0.0010018 m3/kg
Q = ws (v)
Q = 0.418172 x 0.0010018
Q = 0.02513548258 m3/s
(𝐷𝑝)2
Q=𝜋 4
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(0.02513548258)(60)
D=√ 𝜋(100)
224
D = 0.0178895193 m = 17.8895193 mm
Di = 19.1 mm Ts = 22 mm
Mass flow
Ww = 2825.719092 kg/s
V= 152 m/min
Np = 1
By interpolation;
Twa’ Vg
36.16 1.0064
37.21 Vg
37.63 1.0069
225
Solve;
36.16 − 37.21 1.0064 − 𝑋
= 1.0064− 1.0069 V14 = 0.001006787143 m3/kg
36.16 − 37.63
Q = Ww (v)
Q = 2825.719092 x 0.00100657143 x 60
Q = 170.6887728 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(170.6887728)(60)
D=√ 𝜋(152)
D = 1.195737208 m, 1195.737208 mm
Dpa = 597.8686038 mm
Di = 609.6 mm Ts = 38 mm
226
Pipe 15 Condenser to Heat exchanger
Mass flow
Ww = 2825.719092 kg/s
V= 152 m/min
Np = 1
By interpolation;
Twb’ V
42.67 1.0089
42.81 V15
43.76 1.0094
Solve;
42.67 − 42.81 1.0089 − 𝑋
= 1.0089− 1.0094 V15 = 0.001008826316 m3/kg
42.67 − 43.76
Q = ws (v)
Q = 2825.719096 x 0.001008826316 x 60
Q = 171.0395869 m3/s
227
(𝐷𝑝)2
Q=𝜋 4
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(171.0395869)(60)
D=√ 𝜋(152)
D = 1.1969367 m, = 1196.965367 mm
Dpa = 598.4823836 mm
Di = 609.6 mm Ts = 38 mm
Mass flow
Ww = 2109.870236 kg/s
V= 152 m/min
228
Np = no. of pipes v = vf at [email protected]°C
Np = 1
By interpolation;
T Vf
30.62 1.0045
31.30 V11
31.40 1.0048
Solve;
30.62 − 31.30 1.0045 − 𝑋
= 1.0045− 1.0048 V16 = 0.001004761538 m3/kg
30.62 − 31.40
Q = Ww (v)
Q = 2109.870236 x 0.001004761538 x 60
Q = 127.194878 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(127.1949878)(60)
D=√ 𝜋(100)
D = 1.272594548 m, 1272.594548 mm
Dpa = 636.297274 mm
229
From, page 665, PPE by Morse
Di = 609.6 mm Ts = 38 mm
Mass flow
Ww = 2109.870256 kg/s
V= 100 m/min
Np = 1
By interpolation;
T Vf
23.52 1.0026
23.80 V12
24.08 1.0027
Solve;
230
23.52 − 23.80 1.0026 − 𝑋
= V12 = 0.00100265 m3/kg
23.52 − 24.08 1.0026− 1.0027
Q = Ww (v)
Q = 2109.870236 x 0.00100265 x 60
Q = 126.9276835 m3/s
4(𝑄)(60)
D=√ 𝜋(𝑉)
4(126.9276835)(60)
D=√ 𝜋(100)
D = 1.271256644 m, 1271.256644 mm
Dpa = 635.628322 mm
Di = 609.6 mm Ts = 38 mm
231
REFERENCES
232