2 ABB Short-circuit current limiter
S800-SCL-SR
Self-resetting current limiting module
−− MNS installation
−− Shipbuilding
−− Mining
−− Oil & Gas
−− Power generation
−− Wind Power
−− …
Compact design
− − Less cabinet space required
Reliability
− − Proven S800 high performance miniature circuit breaker technology
− − Third party testing
Safety
− − All advantages of a fuseless distribution
− − Low let through energy values
− − Limited current peak
− − Maximum personnel safety
−− Increased breaking capacity of the connected circuit breaker- or
motor starter combination
Flexibility
− − One size fits all approach regarding standards
− − Simple and compact for the DIN rail
S800S-SCL-SR S803W-SCL-SR
Rated operational current I e [A] 32, 63, 100
Pole 1, 2, 3 3
Rated operational voltage U e
(AC) according to IEC 60947-2 50/60 Hz [V] 400/690 690
(AC) according to UL 508 50/60 Hz [V] 600
Rated insulation voltage U i [V] 690
Rated impulse withstand voltage U imp [kV] 8
Rated ultimate short-circuit breaking capacity
I cu = Ics according to IEC 60947-2 *
(AC) 50/60 Hz 240/415 V [kA] 100
(AC) 50/60 Hz 254/440 V [kA] 100
(AC) 50/60 Hz 277/480 V [kA] 65
(AC) 50/60 Hz 289/500 V [kA] 65
(AC) 50/60 Hz 346/600 V [kA] 65
(AC) 50/60 Hz 400/690 V [kA] 50
Short-circuit rating according to UL 508, CSA 22.2 *
(AC) 50/60 Hz 480 V [kA] 65
(AC) 50/60 Hz 600 V [kA] 65
*) V
alid only for approved combinations
Please have a look to separate coordination tables on pages 14 and 15
100
Time in s time [s]
10
0.1
0.01
1 10 100
n x Ie
2-pole
32 S802S-SCL32-SR 2CCS802901R0539 412074 0.5 1
63 S802S-SCL63-SR 2CCS802901R0599 412098 0.5 1
100 S802S-SCL100-SR 2CCS802901R0639 412050 0.5 1
3-pole
32 S803S-SCL32-SR 2CCS803901R0539 411930 0.75 1
63 S803S-SCL63-SR 2CCS803901R0599 411947 0.75 1
100 S803S-SCL100-SR 2CCS803901R0639 411954 0.75 1
A typical application of the conventional S803S-SCL is the The conventional short-circuit limiter S803S-SCL can also
airflow alignment in wind energy plants. If a failure does not be used for group protection, though all downstream circuits
isolate all motor protection devices, the system could possibly would be de-energized in case of a short circuit exceeding the
be harmed. breaking capacity of one downstream device.
S803S-SCL
Rated operational current Ie [A] 32, 63, 125
Pole 3
Rated operational voltage Ue
(AC) 50/60 Hz [V] 400/690
Disconnector properties compliant to IEC 60947-2 yes
Standard IEC 60947-2
Ambient air temperature [°C] –25 ... +60
Storage temperature [°C] –40 ... +70
Vibration IEC 60068-2-27; IEC 60068-2
*) V
alid only for approved combinations
Please have a look to separate coordination tables on pages 14 and 15
Short-circuit current limiter Type designation Product number EAN number Weight Pack.
with cage terminal
[A] 7612271 [kg] unit
32 S803S-SCL32 2CCS800900R0291 1208912 0.74 1
63 S803S-SCL63 2CCS800900R0301 1208929 0.74 1
125 S803S-SCL125 2CCS800900R0281 1208905 0.74 1
Short-circuit current limiter Type designation Product number EAN number Weight Pack.
with ring lug
terminal
[A] 761227 [kg] unit
32 S803S-SCL32-R 2CCS800900R0332 1408916 0.74 1
63 S803S-SCL63-R 2CCS800900R0331 1208950 0.74 1
125 S803S-SCL125-R 2CCS800900R0311 1208936 0.74 1
Dimension Dimension
S800S-SCL-SR/S803S-SCL S803W-SCL-SR
79.50 79.50 76.50
53 76.50 53 46
26.50 6 46 26.50 6
35
45
95
142
35
45
95
Minimum cable length between S800-SCL-SR/S803S-SCL
and downstream devices
MS/MO325
MS/MO132
S800
S800-SCL-SR/S803S-SCL min. length X min. cross section
32 A 80 mm 6 mm2
63 A 80 mm 16 mm2
100/125 A 250 mm 35 mm2
x