This document provides specifications for contact wires and overhead line equipment (OHE) on electric trains. It outlines normal and minimum heights for contact wires at different locations, diameters of contact wires, allowable wire positions and gaps. It also lists requirements for jumpers, droppers, insulators and masts, including lengths, distances, clearances and tensions. Maximum spans and slopes are specified.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
75%(4)75% found this document useful (4 votes)
21K views2 pages
Parameter of Ohe
This document provides specifications for contact wires and overhead line equipment (OHE) on electric trains. It outlines normal and minimum heights for contact wires at different locations, diameters of contact wires, allowable wire positions and gaps. It also lists requirements for jumpers, droppers, insulators and masts, including lengths, distances, clearances and tensions. Maximum spans and slopes are specified.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2
Normal height of contact wire at support point :- 5.60 m ( presag of 100 mm ).
Minimum height of contact wire at level crossing : - 5.50 m
Minimum Height of contact wire at overline structure:- 4.92 m
Dia of contact wire :- 12.24 mm
Condemned dia of contact wire on main line:- 8.25 mm
Condemned dia of contact wire at loop lines/yard:- 8.00 mm
Stagger of contact wire on tangent track :- +- 200 mm Stagger of contact wire on curved track :- +- 300 mm Stagger of catenary on tangent track at support for single cantilever :- 0 Gap between two parallel running contact wires at uninsulated overlap :- 200 mm Gap between parallel running contact wires:- 500 mm Height of contact wire of turnout OHE above contact wire of the main line:- 5 cm Track separationa at turnout and cross overat the location of obligatory structure:-150-700mm. Minnimum implantion at obligatory structure/mast supporting more than one OHE:-3. Normal implantation(standard):-2.50m. +, -0.03 Minimum implantation (critical) withCEE approval. :- 2.36m. Minimum implation on platform : 4.75 m. Normal encumbrance :-1.4 m.for72m. span Maximum permisible slope of contact wire on main line:-3mm./mtr. Maximum permissible slope of contact wire in yards.:-5mm./mtr. Short time min.vertical electricl clearance:- 270mm. Short time min. Hozrizontal electrical clearance :- 220mm Long time min. horizontal eletrical clearance.:- 320mm. Stagger of contract wire at PTFE neutralsection at support:-0. Earthing resistance of FOB/ROB/Girders/Bridge/Platform shed & other overlinestructures:-10 Cross section area and length of C jumper wire:-50mm 1.7m. Cross section and length of F jumper wire :-50mm, 1.6m
Cross section area and length of G jumper wire:-105mm, 3.5m,4.2m
Distance of G jumper from obligatory mast towards overlap side-5.6m. Fixed length of the dropper wire:- 105mm.
The distance of the first dropperfrom support:-2.25m.
Swept zone clearance of section insulator at trailing side:-1.726m
Swept zone clearance of section insulator at facing side:-1.60m
For the section insulator, thedistance between contact wire and runner
oneitherside shouldnot be less than:-220mm
Maximum tension length for regulated OHE:-1500 Normal sag of regulated OHE:-100mm. Maximum span length on tangent track for regulated OHE:-2000m. ZY valueof winch type ATD at half tension length(750m) at35 c in mm.:-Z =1250, Y =2500 XY value of 3 pulley type ATD at half tension length (750 m.) at 35 c in mm. :- X=750, Y= 2500 The difference in length of adjacent spans on mian line should not bemore than:- 18m Minimum length of dropper in the span:- 150mm. In case of overlap type turnout, the turnoutspan should be less than or equal to :- 54m. With crossed type equipment with actual crossings of OHEs at facing turnouts, the anchor span should be restricted to :- 54 m. Leaning of mast should be attended if leaning at tope exceeds:- 15 cm.