The document discusses test switches for feeder protection without an open starpoint, with an open starpoint, for 3-winding transformer differential protection, for two CT cores or separate earth fault CT, with a 4th CT and VT input, with additional contacts, and with independent switchable trip and CT circuits.

The connection diagrams are showing how to connect the 7XV75 test switches to feeder protections or measurements in different configurations based on the type of test switch and application.

7XV75 Test Switch

Application Mode of operation

The test switch serves in the test- The 7XV75 test switch serves for
ing of protection devices using testing protection devices includ-
secondary injection test sets, for ing C.T. circuits and command
example 7VP15 (Omicron CMC contacts. With the help of the
56). switches located on the front
The following versions are in a side, the current and voltage
flush mounting case available: inputs as well as the circuits of
the protection device to be tested
• For feeder protection without an are interrupted and applied to the
open starpoint. plug-in connector located on the
• For feeder protection without an front side. Via this plug-in con-
open starpoint and with addi- nector currents and voltages can
tional contacts. be fed by an injection test set
• For feeder protection without an and the different commands and
open starpoint for two CT cores indications can be tested.
or separate earth fault CT.
• For feeder protection with an
open starpoint.
• For feeder protection with an
open starpoint and independent
switchable trip and c.t. circuits.
• For a 3-winding transformer
differential protection.
• For feeder protection without an
7XV75 test switch
th
open starpoint, with 4 CT and
th
4 VT input (three-stage test
switch)

The test device can be used with


auxiliary supplies ranging from
24 V to 250 V DC. This makes
selection between varying power
supply models unnecessary.

Selection and ordering data

Test switch Rated operating voltage Vn 400 V AC


Rated operating current In 6A
Test current capacity for 1 s 150 A
for 10 s 60 A

Construction Metal case 7XP20


Dimension 1/6 of 19”wide
Weight approx. 3,4 kg

1 Siemens AG November 2007


7XV75 Test Switch

Connection diagram for 7XV7500-0CA00 test switch

2 Siemens AG November 2007


7XV75 Test Switch

Connection diagram for 7XV7501-0CA00 test switch


Typically not for distance protection or if used please consider the switch order of S1 and S2
(Operation->Test: S2 (I) – S1 (V); Test->Operation: S1 (V) – S2 (I)).

3 Siemens AG November 2007


7XV75 Test Switch

Connection diagram for 7XV7502-0CA00 test switch

4 Siemens AG November 2007


7XV75 Test Switch

IL1
IL2
IL3
IN
Feeder protection
or measurement

Reclose command
e.g. Annunciation
e.g. “Testing”
Annunciation

voltage prot.

Reserve
Trip L1

Trip L3
Trip L2
IL1

IL2
IL3
IN

7XV75
7XV7503-0CA00

VL1

VL2
VL3
VN
IL1

IL2
IL3
IN

Feeder protection
or measurement

VL1
VL2
VL3
VN
IL1
IL2
IL3
IN

Connection diagram for 7XV7503-0CA00 test switch


Typically not for distance protection or if used please consider the switch order of S1 and S2
(Operation->Test: S2 (I) – S1 (V); Test->Operation: S1 (V) – S2 (I)).

5 Siemens AG November 2007


7XV75 Test Switch

Connection diagram for 7XV7506-0CA00 three-stage test switch

6 Siemens AG November 2007


7XV75 Test Switch

Connection diagram for 7XV7507-0CA00 test switch

7 Siemens AG November 2007


7XV75 Test Switch

Connection diagram for 7XV7508-0CA00 test switch

8 Siemens AG November 2007


7XV75 Test Switch

Dimension drawings in mm / inch

Front view Side view Rear view Rear view Panel cutout
(except 7XV7506) of 7XV7506

9 Siemens AG November 2007


7XV75 Test Switch

Selection and ordering data

Item Order No.:

Test switch 7XV75 0 - C A 0 0


Application

Without open starpoint for feeder protection 0


With open starpoint for feeder protection 1
For 3-winding transformer differential protection 2
Without open starpoint for two CT cores or 3
separate earth fault CT
th th
Without open starpoint for feeder protection, with 4 CT and 4 6
VT input (three-stage test switch)
Without open starpoint for feeder protection and 7
with additional contacts
With open starpoint and independent switchable trip and 8
C.T. circuits for feeder protection

Front Test Plug connection


With 16 pole Harting socket 0
With 16 banana plugs (not available for 7XV7506) 1

Accessories:
7XV6201-5 Connecting cable with 16 pole Harting plug and 17 isolated banana connectors 4mm with cable marks
7XV6201-6 Connecting cable with 16 pole Harting plug and 17 cable end sleeves with cable marks
Cable length: 2m

Conditions of Sale and Delivery

Subject to the
General Conditions of Supply The technical data, dimensions The illustrations are for reference
and Delivery Electronic Industry and to any and weights are subject to only. We reserve the right to
for Products and Services other conditions agreed upon change unless otherwise stated adjust the prices and shall
of the Electrical and with the recipients of catalogs. on the individual pages of this charge the price applying on the
catalog. date of delivery.

Export Regulations Trademarks Siemens online

In accordance with present Export and re-export are there- All product designations used The section Power Transmission
German and US export regula- fore permissible without the are trademarks or product and Distribution
tions, export licences not re- approval of the relevant authori- names of Siemens AG or of Energy Automation can be found
quired for the products listed in ties exept where current Ger- other suppliers. under the following link:
this catalog. man export regulations contain
country-specific restrictions. http://www.siprotec.com
Relevant are the criteria stated in
the delivery note and in the
invoice. An export licence may
be required due to country-
specific application of the prod-
Embargo data uct.
AL: N, ECCN: N Subject to change without notice.

Responsible for Postal Address:


Technical contents: Siemens AG
Dipl.-Ing. Thomas Klotz, Power Transmission and Distribution
Siemens AG Energy Automation Division
PTD EA 13, Nuremberg Humboldtstr. 59
D-90459 Nuremberg

10 Siemens AG November 2007