Worked Example of Cable Calculation
Worked Example of Cable Calculation
Worked Example of Cable Calculation
Fig. G66: Partial results of calculation carried out with Ecodial 3.4 software (Schneider Electric)
The same calculation using the simplified method recommended in this guide
Dimensioning circuit C1
The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of:
per phase
Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to
method F.
Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm².
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are:
(cable resistance: 22.5 mΩ.mm2/m)
Dimensioning circuit C3
Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is:
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to
method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm2.
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are:
Dimensioning circuit C7
Circuit C7 supplies one 150kW load with cos φ = 0.85, so the total load current is:
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm2.
The resistance and the inductive reactance for a length of 20 metres is:
Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67)
When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in Figure
This gives:
A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the requirements for indirect contact protection (i.e. that
its impedance is sufficiently low).
Generally, for circuits with phase conductor c.s.a. Sph ≥ 50 mm2, the PE conductor minimum c.s.a. will be Sph / 2. Then, for circuit C3, the PE
conductor will be 95mm2, and for circuit C7, the PE conductor will be 50mm2.
(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-
breaker operates).
The length of 20 metres is therefore fully protected by “instantaneous” over-current devices.
Voltage drop
The voltage drop is calculated using the data given in Figure G28, for balanced three-phase circuits, motor power normal service (cos φ = 0.8).
The results are summarized on figure G68:
C1 C3 C7
c.s.a. 2 x 240mm² 2 x 95mm² 1 x 95mm²
∆U per conductor 0.21 0.42 0.42
(V/A/km) see Fig. G28
Load current (A) 866 509 255
Length (m) 5 20 5
Voltage drop (V) 0.45 2.1 0.53
Voltage drop (%) 0.11 0.53 0.13