Wika Ac1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Electronic

Pressure Measurement

 efrigeration and Air Conditioning Pressure Transmitter


R
Model AC-1
WIKA Datasheet
WIKA Datasheet R-1 AC-1

Applications

n Refrigeration and air conditioning applications


- Heat pumps, central air conditioners
- Compressors
- Chillers

Special Features
n Brass, CR70 (polychloroprene) and ceramic wetted parts
n Compatible with most refrigerants
n Condensation proof

Left: AC-1 with M 12x1


Center: AC-1 with Metri Pack 150
Right: AC-1 with cable

Description

Refrigeration and HVAC applications


The new AC-1 pressure transmitter uses an integrated
thick film ceramic pressure sensor to meet the price and Economical price with high performance
performance requirements of commercial and OEM HVAC Assembly on highly flexible manufacturing lines provides a
and refrigeration applications. cost effective transmitter for both small and large quantity
production runs.
The wetted parts include ceramic, brass, and a
polychloroprene (Neoprene®) sealing ring. These materials
are compatible with most common refrigerants.

Performance and reliability


The AC-1 provides a linear, amplified voltage or milliamp
signal output with short circuit, reverse polarity, and
overvoltage protection. The ceramic thick film sensor
provides a non-linearity of less than 1.0% B.F.S.L. and
has no measurable hysteresis error. The AC-1 was
tested using strict protocols designed specifically for the
refrigeration and HVAC industry. It meets or exceeds all
Neoprene® is a registered trademark of E.I. du Pont de Nemours
test requirements including resistance to high pressure
and Company
steam jets, condensation, dust tightness, and icing.

WIKA Datasheet AC-1 ∙ 02/2010 Page 1 of 4


Specifications
Pressure ranges psi1 100 150 200 300 850
Over pressure safety psi 300 300 600 600 1500
Burst pressure psi 370 370 730 730 1800
Pressure ranges bar1 7 10 16 25 60
Over pressure safety bar 20 20 40 40 100
Burst pressure bar 25 25 50 50 120
1. All pressure ranges available starting from 30INHG Vacuum (-1 bar)
{Vacuum and Compound ranges available upon request}
Materials
nWetted parts Brass, Al2 03 ceramic 96% 0-ring: CR 70 (polychloroprene)
Media compatibility Compatible with R12, R22, R134a, R404a, R407c, R410a, R502, R507 refrigerants
nCase Brass
nElectrical connection Chemical resistant fiberglass- reinforced plastic (PBT GF 30)
Signal output Power supply UB Maximum load RA
4 ... 20 mA, 2-wire 7 ... 30 VDC RA ≤ (UB – 7 V) / 0.02 A
0 ... 10 V, 3-wire 14 ... 30 VDC RA > 10 kOhm
0.5 ... 4.5 V, ratiometric 5 ± 0.5 VDC RA > 4.5 kOhm
Response time (10 ... 90 %) ms ≤5
Isolation voltage VDC 500
Accuracy % of span ≤ 1.0 (B.F.S.L.) (≤ 2.0 per IEC 61298-2 *))
*) Including non-linearity, hysteresis, zero point and full scale error
1-year stability % of span ≤ 0.3 (at reference conditions)
Permissible temperature of
nMedium -40 ... +176 °F -40 ... +80 °C
nAmbient -13 ... +176 °F -25 ... +80 °C
nStorage -13 ... +176 °F -25 ... +80 °C
Rated temperature range -13 ... +176 °F -25 ... +80 °C
Temperature coefficients within
rated temperature range
nMean TC of zero % of span typ. ≤ 0.5 / 10 K
■nMean TC of range % of span ≤ 0.3 / 10 K
CE-conformity
nEMC directive 2004/108/EEC, EN 61 326 Emission (Group 1, Class B) and
Immunity (industrial locations)
Wiring protection
nShort-circuit protection Sig+ to 0V
nReverse polarity protection UB+ to 0V
nOvervoltage protection VDC 36
Weight oz Approx. 2.8

{ }Items in curved brackets are options available for additional cost

Page 2 of 4 WIKA Datasheet AC-1 ∙ 02/2010


Dimensions in inches (mm)
Ingress Protection IP per IEC 60529. The ingress protection ratings specified only apply while the pressure transmitter is
connected with mating connectors that provide the corresponding ingress protection.

Example
Electrical connection
Cable with free ends

1.55" 40 mm)
approx. 2.4" 61 mm)
Ø 0.87" (22 mm)

0.95" (24 mm)

0.59" (15 mm)


Pressure connection
7/16-20 UNF-2A
90° Cone

7/16"-20UNF-2A

Electrical connections
Circular connector Connector Cable with free ends
M 12x1 Metri Pack Series 150 IP69K
IP67 IP67
1.52" (38.5 mm)

1.55" (40 mm)


1.25" (31.7 mm)

Ø 0.87" Ø 0.87" Ø 0.87"


(22 mm) (22 mm) (22 mm)

Pressure connections

0.95" (24 mm) 0.95" (24 mm)


0.63" (16 mm)

0.75" (19 mm)


(10 mm)

(13 mm)
0.39"

0.51"

1/8" NPT
1/4" NPT

WIKA Datasheet AC-1 ∙ 02/2010 Page 3 of 4


Pressure connections

7/16-20 UNF-2A
90° cone 7/16-20 UNF-2B
Order code: U5 Schrader internal thread
0.95" (24 mm) with deflator pin
0.95" (24 mm) Order code: U6
0.83" (21 mm)

0.63" (16 mm)


(15 mm)
0.59"

(8.4 mm)

(6.5 mm)
0.33"
7/16"-20UNF-2B

0.26"
7/16"-20UNF-2A

For installation and safety instructions refer to the operating instructions.

Electrical connections 2-wire 3-wire


Circular connector
M 12x1
4-pin

Connector
Metri Pack Series 150 connector
3-pin

Cable with free ends


brown brown

white

green
green

Legend:

Specifications and dimensions given in this data sheet represent the state of engineering at the time of printing.
Modifications may take place and materials specified may be replaced by others without prior notice.

Page 4 of 4 WIKA Datasheet AC-1 ∙ 02/2010

WIKA Instrument Corporation


1000 Wiegand Boulevard
Lawrenceville, GA 30043
Tel (770) 513-8200 Toll-free 1-888-WIKA-USA
Fax (770) 338-5118
E-Mail info@wika.com
www.wika.com

You might also like