11. How will you calculating effective length, effective height and effective thickness?
The height of a wall to be column to be considered slenderness ratio. The length of a wall
to be column to be considered slenderness ratio. The thickness of a wall or column to be
considered for calculating slenderness ratio.
Step-3
Area reduction factor=300x600
=180000mm2=0.18m2 (from page no 16)
Ka=0.7+1.5A
=0.7+1.5(0.18)
=0.97
Step-4
Shape modification factor (from page no 16)
Height to width ratio=200/200=1 (from table 10)
Shape modification factor=1.1
Step-5
Load factor
For axial load=1
For eccentric load=1.2
KL=1 (for axial column)
Step-6
Stress reduction factor (from page no 16 table 9 (IS: 1905-1987)
Slenderness ratio=effective height/least lateral dimension
=5.1/0.3=17
Stress reduction factor=0.7
Step-7
Fca=fbx Kax Kpx KLX Ksf
=0.81x0.97x1.1x1x0.7
=0.604N/mm2
Axial load
Fca=P/A
P= FcaXA
=0.604X(300X600)
=108.72kN
Step-3
Area reduction factor
=300x550=165000mm2=0.165m2 (from page no 16)
Ka=0.7+1.5A
=0.7+1.5(0.165)
=0.94
Step-4
Shape modification factor (from page no 16)
Height to width ratio=200/200=1 (from table 10)
Shape modification factor=1.1
Step-5
Load factor
For axial load=1
For eccentric load=1.2
KL=1.25 (for eccentrically loaded column)
Step-6
Stress reduction factor (from page no 16 table 9 (IS: 1905-1987)
Slenderness ratio=effective height/least lateral dimension
=4.5/0.3=15
Stress reduction factor=0.66
Step-7
Fca=fbx Kax Kpx KLX Ksf
=0.81x0.94x1.1x1x0.66
=0.552N/mm2
3. Design an interior cross wall of two story building to carry 100m thick R.C.C. slab with
3m ceiling height the wall is stiff and it support 2.65m wide salb.the live load on roof and
floor is 1.5kN/m2 and 2 kN/m2 weight of floor finish and lime terrace is 0.2 kN/m2 and
2 kN/m2 adopt crushing strength 10Mpa mortar M1. (AUC May/Jun 2013)
(AUC Nov/Dec 2012)
Data:
No of story=2
Slab thick=100mm
Live load on floor=2 kN/m2
Weight of floor finish=1.5 kN/m2
Weight of lime terrace=2 kN/m2
Crushing strength=10Mpa.
4. Design exterior wall of a building to carry 100mm thick R.C. slab 3m ceiling height
support condition is fixed, live load on roof is 2 kN/m2, adopt crushing strength of brick
units as 10 N/mm2, use M1 mortar. (AUC May/Jun 2013)
Data:
Height=3m
Live load on roof=2 kN/m2
Strength=10 N/mm2
100mm thick R.C. wall
M1 mortar
Step-1
Basic compressive stress=0.96 N/mm2