Series: CFW-11
Language: English
Document: 10000063093 / 02
Models: 6...105 A / 200...240 V
3,6...88 A / 380...480 V
02/2008
Summary of Revisions
2
Index
CHAPTER 1
Safety Instructions
CHAPTER 2
General Instructions
CHAPTER 3
Installation and Connection
CHAPTER 4
KEYPAD AND DISPLAY
CHAPTER 5
First Time Power-Up and Start-Up
CHAPTER 6
Troubleshooting and Maintenance
CHAPTER 7
Option Kits and Accessories
CHAPTER 8
Technical Specifications
SAFETY INSTRUCTIONS
DANGER!
Failure to follow the recommended procedures listed in this warning may result in death, serious
injury, and equipment damage.
ATTENTION!
Failure to follow the recommended procedures listed in this warning may result in equipment
damage.
NOTE!
This warning provides important information for the proper understanding and operation of the
equipment.
The following symbols are attached to the product and require special attention:
1-1
Safety Instructions
DANGER!
Only trained personnel, with proper qualifications, and familiar with the CFW-11 and associated
machinery shall plan and implent the installation, starting, operation, and maintenance of this
equipment.
1 The personnel shall follow all the safety instructions described in this manual and/or defined by the
local regulations.
Failure to comply with the safety instructions may result in death, serious injury, and equipment
damage.
NOTE!
For the purpose of this manual, qualified personnel are those trained and able to:
1. Install, ground, power-up, and operate the CFW-11 according to this manual and to the current
legal safety procedures;
2. Use the protection equipment according to the established regulations;
3. Provide first aid.
DANGER!
Always disconnect the main power supply before touching any electrical device associated with the
inverter.
Several components may remain charged with high voltage and/or in movement (fans), even after
the AC power supply has been disconnected or turned off.
Wait at least 10 minutes to guarantee the fully discharge of capacitors.
Always connect the equipment frame to the ground protection (PE).
ATTENTION!
The electronic boards contain components sensitive to electrostatic discharges. Do not touch the
components and terminals directly. If needed, touch first the grounded metal frame or wear an
adequate ground strap.
NOTE!
Frequency inverters may cause interference in other electronic devices. Follow the recommendations
listed in Chapter 3 – Installation and Connection, to minimize these effects.
NOTE!
Fully read this manual before installing or operating the inverter.
1-2
General Instructions
GENERAL INSTRUCTIONS
It is also possible to operate the CFW-11 in the following control modes: V V W, Sensorless Vector and Vector with
Encoder. For further details on the inverter operation with other control modes, refer to the Software Manual.
2
For information on other functions, accessories, and communication, please refer to the following manuals:
Software Manual, with a detailed description of the parameters and advanced functions of the CFW-11.
Incremental Encoder Interface Module Manual.
I/O Expansion Module Manual.
RS-232/RS-485 Serial Communication Manual.
CANopen Slave Communication Manual.
Anybus-CC Communication Manual.
These manuals are included on the CD supplied with the inverter or can be downloaded from the WEG website
at - www.weg.net.
Normal Duty Cycle (ND): Inverter duty cycle that defines the maximum continuous operation current (IRAT-ND) and
the overload current (110 % for 1 minute). The ND cycle is selected by setting P0298 (Application) = 0 (Normal
Duty (ND)). This duty cycle shall be used for the operation of motors that are not subjected to high torque loads
(with respect to the motor rated torque) during its operation, starting, acceleration, or deceleration.
IRAT-ND: Inverter rated current for use with the normal duty (ND) cycle.
Overload: 1.1 x IRAT-ND/ 1 minute.
Heavy Duty Cycle (HD): Inverter duty cycle that defines the maximum continuous operation current (IRAT-HD)
and the overload current (150 % for 1 minute). The HD cycle is selected by setting P0298 (Application) = 1
(Heavy Duty (HD)). This duty cycle shall be used for the operation of motors that are subjected to high torque
(with respect to the motor rated torque) during its operation, starting, acceleration, or deceleration.
IRAT-HD: Inverter rated current for use with the heavy duty (HD) cycle.
Overload: 1.5 x IRAT-HD / 1 minute.
Rectifier: Input circuit of inverters that transforms the AC input voltage in DC voltage. It is composed of power
diodes.
Pre-charge Circuit: Charges the DC bus capacitors with limited current, which avoids higher peak currents
at the inverter power-up.
2-1
General Instructions
DC Bus: Inverter intermediate circuit; DC voltage obtained from the rectification of the AC input voltage or
from an external power supply; feeds the output inverter bridge with IGBTs.
Power modules U, V, and W: Set of two IGBTs of the inverter output phases U, V, and W.
IGBT: Insulated Gate Bipolar Transistor; basic component of the output inverter bridge. The IGBT works as an
electronic switch in the saturated (closed switch) and cut-off (open switch) modes.
Braking IGBT: Works as a switch to activate the braking resistors. It is controlled by the DC bus voltage
level.
2 PTC: Resistor which resistance value in ohms increases proportionally to the temperature increase; used as a
temperature sensor in electrical motors.
NTC: Resistor which resistance value in ohms decreases proportionally to the temperature increase; used as a
temperature sensor in power modules.
Keypad: Device that allows controlling the motor, and viewing/editing inverter parameters. It is composed of
motor control keys, navigation keys, and a graphic LCD display.
FLASH memory: Non-volatile memory that can be electronically written and erased.
USB: Universal Serial Bus; is a serial bus standard that allows devices to be connected using the ”Plug and
Play” concept.
RFI Filter: Radio-Frequency Interference Filter for interference reduction in the Radio-Frequency range.
PWM: Pulse Width Modulation; pulsed voltage that feeds the motor.
Switching frequency: Frequency of the IGBTs switching in the inverter bridge, normally expressed in kHz.
General enable: When activated, this function accelerates the motor via acceleration ramp set in the inverter.
When deactivated, this function immediately blocks the PWM pulses. The general enable function may be
controlled through a digital input set to this function or via serial communication.
Start/Stop: When enabled in the inverter (start), this function accelerates the motor via acceleration ramp up
to the speed reference. When disabled (stop), this function decelerates the motor via deceleration ramp up to
the complete motor stop; at this point, the PWM pulses are blocked. The start/stop function may be controlled
through a digital input set for this function or via serial communication. The operator keys and of the
keypad work in a similar way:
=Start, =Stop.
Heatsink: Metal device designed to dissipate the heat generated by the power semiconductors.
2-2
General Instructions
Amp, A: Ampères.
hp: Horse Power = 746 Watts (unit of power, used to indicate the mechanical power of electrical motors).
2
Hz: hertz.
min: minute.
s: second.
V: volts.
Ω: ohms.
2-3
General Instructions
The CFW-11 frequency inverter is a high performance product designed for speed and torque control of three-
phase induction motors. The main characteristic of this product is the “Vectrue” technology, which has the
following advantages:
2-4
General Instructions
= DC bus connection
= Braking resistor connection
Pre-
charge
Mains Power Motor
Supply
Capacitor Inverter
Rectifier Bank with IGBT
PE RFI Filter transistors 2
PE
DC BUS
Feedback:
- voltage
- current
POWER
CONTROL
PC
Accessories
I/O Expansion
(Slot 1 - white)
Keypad (remote)
Keypad
Encoder Interface
Digital (Slot 2 - yellow)
Inputs CC11
(DI1 to DI6) COMM 1
Control
(Slot 3 - green)
Board with
Analog a 32 bits
Inputs "RISC" COMM 2
(AI1 and AI2) CPU (anybus) (Slot 4 )
Analog
FLASH Outputs
Memory (AO1 and AO2)
Module
Digital Outputs
DO1 (RL1) to
DO3 (RL3)
2-5
General Instructions
A – Mounting supports
(for through the wall mounting)
B – Heatsink
C – Top cover
D – Fan with mounting support
E – COMM 2 module (anybus)
F – Option board / accessory module
G – FLASH memory module
H – Front cover
I – Keypad
1 USB Connector
2 USB LED
Off: No USB connection
On/Flashing: USB communication is active
3 STATUS LED
Green: Normal operation with no fault or alarm
Yellow: Alarm condition
Flashing red: Fault condition
2-6
General Instructions
There are two nameplates on the CFW-11: one complete nameplate is affixed to the side of the inverter and
a simplified one is located under the keypad. The nameplate under the keypad allows the identification of the
most important characteristics of the inverter even if they are mounted side-by-side.
1
1 Nameplate affixed to the
side of the heatsink
2-7
2
HOW TO CODIFY THE CFW-11 MODEL (SMART CODE)
2-8
INVERTER MODEL AVAILABLE OPTION KITS (CAN BE INSTALLED IN THE PRODUCT FROM THE FACTORY)
General Instructions
Field Market WEG CFW-11 Rated output Number of Power supply Option kit Enclosure Keypad Braking RFI filter Safety stop 24 Vdc external Special Special Character
description identification frequency current for power phases voltage type power supply for hardware software that
(defines inverter series use with the control identifies
the manual Normal Duty the code
language and (ND) cycle end
the factory
settings)
Available 2 characters S=single-phase 2=200...240 V S=standard Blank= Blank= Blank= Blank= Blank=standard Blank=standard Blank= Blank=
options power supply 4=380...480 V product standard standard standard standard (safety stop function is (not available) standard standard
T=three-phase O=product N1=Nema1 IC=no keypad FA=class 3 not available) W=24 Vdc H1=special S1=special
power supply with option 21=IP21 (blind cover) internal RFI Y=safety stop external power hardware #1 software #1
B=single or kit filter according to supply for control
three-phase EN-954-1 category 3
power supply
The CFW-11 is packaged and shipped in a cardboard box for models of frames A, B, and C. The bigger frame
models are packaged and shipped in a wood crate.
The same nameplate affixed to the CFW-11 inverter is affixed to the outside of the shipping container.
Follow the instructions below to remove the CFW-11 models above frame C from the package:
1- Put the shipping container over a flat and stable area with the assistance of another two people;
2- Open the wood crate;
3- Remove all the packing material (the cardboard or styrofoam protection) before removing the inverter.
2
Check the following items once the inverter is delivered:
Verify that the CFW-11 nameplate corresponds to the model number on your purchase order;
Inspect the CFW-11 for external damage during transportation.
Report any damage immediately to the carrier that delivered your CFW-11 inverter.
If CFW-11 is to be stored for some time before use, be sure that it is stored in a clean and dry location that
conforms to the storage temperature specification (between -25 °C and 60 °C (-13 °F and 140 °F)). Cover the
inverter to prevent dust accumulation inside it.
ATTENTION!
Capacitor reforming is required if drives are stored for long periods of time without power. Refer to
the procedures in item 6.5 - table 6.3.
2-9
General Instructions
2-10
Installation and Connection
Mount the inverter in the upright position on a flat and vertical surface.
External dimensions and fixing holes position according to the figure 3.1. Refer to the section 8.3 for more
details.
First mark the mounting points and drill the mouting holes. Then, position the inverter and firmly tighten the screws
in all four corners to secure the inverter.
Minimum mounting clearances requirements for proper cooling air circulation are specified in figures 3.2 and 3.3.
Inverters of frames A, B, and C can be arranged side-by-side with no clearance required between them. In this
case, the top cover must be removed as shown in figure 3.3 (b).
ATTENTION!
When arranging two or more inverters vertically, respect the minimum clearance A + B (figure 3.2) and
provide an air deflecting plate so that the heat rising up from the bottom inverter does not affect the
top inverter.
3-1
Installation and Connection
ATTENTION!
Provide conduit for physical separation of the signal, control, and power conductors (refer to item
3.2 - Electrical Installation).
A1 B1 C1 D1 E1 a2 b2 c2 a3 b3 c3 d3 e3 Torque (*)
Model mm mm mm mm mm mm mm mm mm mm mm N.m
M M
(in) (in) (in) (in) (in) (in) (in) (in) (in) (in) (in) (lbf.in)
145 247 227 70 270 115 250 130 240 135 225 5.0
Frame A M5 M5
(5.71) (9.73) (8.94) (2.75) (10.61) (4.53) (9.85) (5.12) (9.45) (5.32) (8.86) (44.2)
190 293 227 71 316 150 300 175 285 179 271 5.0
Frame B M5 M5
(7.46) (11.53) (8.94) (2.78) (12.43) (5.91) (11.82) (6.89) (11.23) (7.05) (10.65) (44.2)
220 378 293 136 405 150 375 195 365 205 345 8.5
Frame C M6 M6
(8.67) (14.88) (11.52) (5.36) (15.95) (5.91) (14.77) (7.68) (14.38) (8.08) (13.59) (75.2)
300 504 305 135 550 200 525 275 517 285 485 20.0
Frame D M8 M8
(11.81) (19.84) (12.00) (5.32) (21.63) (7.88) (20.67) (10.83) (20.36) (11.23) (19.10) (177.0)
Tolerances for dimensions d3 and e3: +1.0 mm (+0.039 in)
Tolerances for remaining dimensions: ±1.0 mm (±0.039 in)
(*) Recommended torque for the inverter mounting (valid for c2 and c3)
3-2
Installation and Connection
A B C
Model mm mm mm
(in) (in) (in)
25 25 10
Frame A
(0.98) (0.98) (0.39)
40 45 10
Frame B
(1.57) (1.77) (0.39)
110 130 10
Frame C
(4.33) (5.12) (0.39)
110 130 10
Frame D
(4.33) (5.12) (0.39)
Figure 3.2 - Minimum top, bottom, and front clearance requirements for air circulation
* Dimensions in mm [in]
(b) Frames A, B, and C: side-by-side mounting - No clearance required between inverters if top cover is removed
3-3
Installation and Connection
There are two possibilities for mounting the inverter: through the wall mounting or flange mounting (the heatsink
is mounted outside the cabinet and the cooling air of the power module is kept outside the enclosure). The
following information shall be considered in these cases:
Flange mounting:
The losses specified in table 8.1 "Dissipated power in Watts - Flange mounting" will be dissipated inside the
cabinet. The remaining losses (power module) will be dissipated through the vents.
3 The mounting supports shall be removed and repositioned as illustrated in figure 3.4.
The portion of the inverter that is located outside the cabinet is rated IP54. Provide an adequate gasket for
the cabinet opening to ensure that the enclosure rating is maintained. Example: silicone gasket.
Mounting surface opening dimensions and position/diameter of the mounting holes, as shown in figure
3.1.
3-4
Installation and Connection
1 2 3
4 5 6
At frame sizes A, B and C, it is necessary to remove the HMI and the front cover in order to get access to the
control and power terminal strips.
1 2 3
3-5
Installation and Connection
At the frame size D inverters, it is necessary to remove the HMI and the control rack cover in order to get access
to the control terminal strip (see figure 3.6). In order to get access to the power terminal strip, remove the
bottom front cover (see figure 3.7).
1 2 3
3
Figure 3.6 - HMI and control rack cover removal
1 2
3-6
Installation and Connection
DANGER!
The following information is merely a guide for proper installation. Comply with applicable local
regulations for electrical installations.
DANGER!
Make sure the AC power supply is disconnected before starting the installation.
NOTE!
Models CFW110006B2 and CFW110007B2 may operate with two phases only (single-phase power
supply) without rated output current derating. In this case, the single-phase power supply may be
connected to two of any input terminals.
Models CFW110006S2OFA, CFW110007S2OFA, and CFW110010S2 only operate with single-
3
phase power supply. In this case, the single-phase power supply shall be connected to terminals
R/L1 and S/L2.
(b) Frame D
Figure 3.8 - Power terminals
3-7
Installation and Connection
Grounding
Grounding
ATTENTION!
Provide adequate terminals when flexible cables are used for the power and grounding
connections.
ATTENTION!
Sensitive equipment such as PLCs, temperature controllers, and thermal couples shall be kept at a
minimum distance of 0.25 m (0.82 ft) from the frequency inverter and from the cables that connect
the inverter to the motor.
DANGER!
Improper cable connection:
The inverter will be damaged in case the input power supply is connected to the output terminals
(U/T1, V/T2, or W/T3).
Check all the connections before powering up the inverter.
In case of replacing an existing inverter by a CFW-11, check if the installation and wiring is according
to the instructions listed in this manual.
ATTENTION!
Residual Current Device (RCD):
- When installing an RCD to guard against electrical shock, only devices with a trip current of 300 mA
should be used on the supply side of the inverter.
- Depending on the installation (motor cable length, cable type, multimotor configuration, etc.), the
RCD protection may be activated. Contact the RCD manufacturer for selecting the most appropriate
device to be used with inverters.
3-8
Installation and Connection
Table 3.2 - Recommended Wire size/ Fuses - use only copper wire (75 ºC (167 °F))
Frame
Model Recommended Fuse [A] [A] IEC [A²s] @
Screw thread /
Terminals torque mm2 AWG Terminals (**) 25 ºC
screw head type
N.m (lbf.in)
3-9
Installation and Connection
Table 3.2 (cont.) - Recommended Wire size/ Fuses - use only copper wire (75 ºC (167 °F))
Power terminal Wire size
Fuse Fuse I2t
Frame
Model Recommended Fuse [A] [A] IEC [A²s] @
Screw thread /
Terminals torque mm 2
AWG Terminals (**) 25 ºC
screw head type
N.m (lbf.in)
3-10
Installation and Connection
Table 3.2 (cont.) - Recommended Wire size/ Fuses - use only copper wire (75 ºC (167 °F))
Power terminal Wire size
Fuse Fuse I2t
Frame
Model Recommended Fuse [A] [A] IEC [A²s] @
Screw thread /
Terminals torque mm 2
AWG Terminals (**) 25 ºC
screw head type
N.m (lbf.in)
NOTE!
The wire gauge values listed in table 3.2 are merely a guide. Installation conditions and the maximum
permitted voltage drop shall be considered for the proper wiring sizing.
Input fuses
Use High Speed Fuses at the input for the protection of the inverter rectifier and wiring. Refer to table 3.2
for selecting the appropriate fuse rating (I2t shall be equal to or less than indicated in table 3.2, consider
the cold (and not the fusion) current extinction value).
Optionally, slow blow fuses can be used at the input. They shall be sized for 1.2 x the rated input current of
the inverter. In this case, the installation is protected against short-circuit, but not the inverter input rectifier.
This may result in major damage to the inverter in the event of an internal component failure.
3-11
Installation and Connection
PE W V U
PE R S T U V W PE
PE
Shielding
R
S
T
Power Disconnect Fuses
Supply Switch
Figure 3.10 - Power and grounding connections
3 DANGER!
Provide a disconnect device for the input power supply of the inverter.
This device shall disconnect the input power supply for the inverter when needed (for instance, during
servicing).
ATTENTION!
The power supply that feeds the inverter shall have a grounded neutral. In case of IT networks, follow
the instructions described in item 3.2.3.1.1.
NOTE!
The input power supply voltage shall be compatible with the inverter rated voltage.
NOTE!
Power factor correction capacitors are not needed at the inverter input (R, S, T) and shall not be
installed at the output of the inverter (U, V, W).
3.2.3.1.1 IT Networks
ATTENTION!
Do not use inverters with internal RFI filters in IT networks (neutral is not grounded or grounding
provided by a high ohm value resistor) or in grounded delta networks (“delta corner earth”), because
these type of networks damage the inverter filter capacitors.
3-12
Installation and Connection
The CFW-11 inverter series, except the models with internal RFI filters – CFW11XXXXXXOFA, can be normally
used in IT networks. If the available model is equipped with an internal filter, remove the two grounding screws
from the filter capacitors as presented in figure 3.11. Remove the keypad and the front cover to have access to
these screws in frames A, B, and C. For frame D, the bottom front cover shall be removed as well.
Consider the following items for the use of protection devices on the supply side of the inverter such as residual
current devices or isolation monitors:
- The detection of a phase-to-ground short-circuit or an insulation fault shall be processed by the user, i.e., the
user shall decide whether to indicate the fault and/or block the inverter operation.
- Contact the RCD manufacturer for selecting the most appropriate device to be used with inverters in order to
avoid nuisance tripping due to the high frequency leakage currents that flow through the leakage capacitances
of the inverter, cable, and motor system to the ground.
Figure 3.11 - Grounding screws of the filter capacitors - valid for models with internal RFI filters
3-13
Installation and Connection
The braking torque that can be obtained from the frequency inverter without braking resistors varies from 10 %
to 35 % of the motor rated torque.
Braking resistors shall be used to obtain higher braking torques. In this case, the energy regenerated in excess
is dissipated in a resistor mounted externally to the inverter.
This type of braking is used in cases where short deceleration times are desired or when high inertia loads are
driven.
The “Optimal Braking” feature may be used with the vector control mode, which eliminates in most cases the
need of an external braking resistor.
NOTE!
Set P0151 and P0185 to their maximum values (400 V or 800 V) when using dynamic braking.
3
The following application data shall be considered for the adequate sizing of the braking resistor:
- Desired deceleration time;
- Load inertia;
- Braking duty cycle.
In any case, the effective current value and the maximum braking current value presented in table 3.3 shall
be respected.
The maximum braking current defines the minimum braking resistor value in ohms.
The DC bus voltage level for the activation of the dynamic braking function is defined by parameter P0153
(dynamic braking level).
The power of the braking resistor is a function of the deceleration time, the load inertia, and the load torque.
For most applications, a braking resistor with the value in ohms indicated in table 3.3 and the power of 20 %
of the rated driven motor power. Use WIRE type resistors in a ceramic support with adequate insulation voltage
and capable of withstanding high instantaneous power with respect to rated power. For critical applications with
very short deceleration times and high inertia loads (ex.: centrifuges) or short duration cycles, consult WEG for
the adequate sizing of the braking resistor.
3-14
Installation and Connection
Maximum Dissipated
Maximum Effective
braking power (mean Power wire size
braking braking Recommen-
power (peak value) in (terminals DC+ and
Inverter model current current ded resistor
value) the braking BR) (3)
(Imax) (Ieffective) (1) [Ω]
(Pmax) (2) resistor (PR) (2) [mm2 (AWG)]
[A] [A]
[kW] [kW]
CFW11 0006 B 2 5.3 2.1 5.20 2.03 75 1.5 (16)
CFW11 0006 S 2 O FA 5.3 2.1 5.20 2.03 75 1.5 (16)
CFW11 0007 B 2 7.1 2.9 6.96 2.71 56 1.5 (16)
CFW11 0007 S 2 O FA 7.1 2.9 6.96 2.71 56 1.5 (16)
CFW11 0007 T 2 5.3 2.1 5.20 2.03 75 1.5 (16)
CFW11 0010 S 2 11.1 4.4 10.83 4.22 36 2.5 (14)
CFW11 0010 T 2 7.1 2.9 6.96 2.71 56 1.5 (16)
CFW11 0013 T 2 11.1 4.4 8.54 2.62 36 2.5 (14)
CFW11 0016 T 2 14.8 5.9 14.44 5.63 27 4 (12)
CFW11 0024 T 2 26.7 10.7 19.15 5.50 15 6 (10)
CFW11 0028 T 2 26.7 10.7 18.21 4.97 15 6 (10)
CFW11 0033 T 2 26.7 10.7 16.71 4.19 15 6 (10)
CFW11 0045 T 2 44.0 17.6 33.29 10.1 9.1 10 (8)
CFW11 0054 T 2 48.8 19.5 32.17 8.49 8.2 10 (8) 3
CFW11 0070 T 2 48.8 19.5 26.13 5.60 8.2 6 (8)
CFW11 0086 T 2 93.0 37.2 90.67 35.3 4.3 35 (2)
CFW11 0105 T 2 111.1 44.4 90.87 29.7 3.6 35 (2)
CFW11 0003 T 4 3.6 2.9 3.54 2.76 220 1.5 (16)
CFW11 0005 T 4 5.3 4.3 5.20 4.05 150 1.5 (16)
CFW11 0007 T 4 5.3 4.3 5.20 4.05 150 1.5 (16)
CFW11 0010 T 4 8.8 7.0 8.57 6.68 91 2.5 (14)
CFW11 0013 T 4 10.7 8.5 10.40 8.11 75 2.5 (14)
CFW11 0017 T 4 12.9 10.3 12.58 9.81 62 2.5 (12)
CFW11 0024 T 4 17.0 13.6 16.59 12.9 47 4 (10)
CFW11 0031 T 4 26.7 21.3 20.49 12.6 30 6 (10)
CFW11 0038 T 4 36.4 29.1 26.06 14.9 22 6 (8)
CFW11 0045 T 4 47.1 37.6 40.00 27.2 17 10 (8)
CFW11 0058 T 4 53.3 42.7 31.71 15.1 15 10 (8)
CFW11 0070 T 4 66.7 53.3 42.87 22.1 12 10 (6)
CFW11 0088 T 4 87.9 70.3 63.08 36.2 9.1 25 (4)
Notes:
(1) The effective braking current presented is just an indicative value, because it depends on the braking duty
cycle. The effective braking current can be obtained from the equation below, where tbr is given in minutes
and corresponds to the sum of all braking times during the most severe cycle of 5 (five) minutes.
tbr
Ieffective = Imax x
5
(2) The Pmax and PR values (maximum and mean power of the braking resistor respectively) presented are valid
for the recommended resistors and for the effective braking currents presented in table 3.3. The resistor
power shall be changed according to the braking duty cycle.
(3) For specifications on the recommended terminal type (screw and tightening torque) for the connection of
the braking resistor (terminals DC+ and BR), refer to the DC+ terminal specification at the table 3.2. There
are plastic covers in front of the DC-, DC+ and BR terminals at the frame size C. It is necessary to break
off those covers in order to get access to these terminals.
3-15
Installation and Connection
Install the braking resistor between the power terminals DC+ and BR.
Use twisted cable for the connection. Separate these cables from the signal and control cables. Size the cables
according to the application, respecting the maximum and effective currents.
If the braking resistor is installed inside the inverter cabinet, consider its additional dissipated energy when sizing
the cabinet ventilation.
Set parameter P0154 with the resistor value in ohms and parameter P0155 with the maximum resistor power
in kW.
DANGER!
The inverter has an adjustable thermal protection for the braking resistor. The braking resistor and
the braking transistor may damage if parameters P0153, P0154, and P0155 are not properly set or
if the input voltage surpasses the maximum permitted value.
The thermal protection offered by the inverter, when properly set, allows the protection of the resistor in case of
overload; however, this protection is not guaranteed in case of braking circuitry failure. In order to avoid any
3 damage to the resistor or risk of fire, install a thermal relay in series with the resistor and/or a thermostat in contact
with the resistor body to disconnect the input power supply of the inverter, as presented in figure 3.12.
CFW-11
Contactor
R
Power S
supply
T
BR DC+
Thermal
Control power relay
supply
Thermostat
Braking
resistor
NOTE!
DC current flows through the thermal relay bimetal strip during braking.
3-16
Installation and Connection
ATTENTION!
The inverter has an electronic motor overload protection that shall be adjusted according to the
driven motor. When several motors are connected to the same inverter, install individual overload
relays for each motor.
ATTENTION!
If a disconnect switch or a contactor is installed between the inverter and the motor, never operate
them with a spinning motor or with voltage at the inverter output.
The characteristics of the cable used for the inverter and motor interconnection, as well as the physical location
are extremely important to avoid electromagnetic interference in other equipment and to not affect the life cycle
of motor windings and motor bearings controlled by inverters.
Note:
The magnetic field created by the current circulation in these cables may induce current in close metal
pieces, heat them, and cause additional electrical losses. Therefore, keep the 3 (three) cables (U, V, W)
always together.
Shielded Cables:
Are mandatory when the electromagnetic compatibility directive (89/336/EEC) shall be met, as defined by
the standard EN 61800-3 “Adjustable Speed Electrical Power Drive Systems”, unless the RFI filters be used
as presented in the table 3.9 and section 3.3.1. These cables act mainly by reducing the irradiated emission
in the radio-frequency range.
Are mandatory when RFI filters, internally or externally mounted, are installed at the inverter input, unless
the RFI filters be used as presented in the table 3.9 and section 3.3.1.
In reference to the type and details of installation, follow the recommendations of IEC 60034-25 “Guide
for Design and Performance of Cage Induction Motors Specifically Designed for Converter Supply” – refer
to a summary in figure 3.13. Refer to the standard for further details and eventual modifications related to
new revisions.
Keep motor cables away from other cables (signal cables, sensor cables, control cables, etc.), according to
table 3.4.
The grounding system shall be well interconnected among the several installation locations such as the
grounding points of the motor and the inverter. Voltage difference or impedance between the several points
may cause the circulation of leakage currents among the equipment connected to the ground, resulting in
electromagnetic interference problems.
Table 3.4 - Minimum separation distance between motor cables and all other cables
Cable length Minimum separation distance
≤ 30 m (100 ft) ≥ 10 cm (3.94 in)
> 30 m (100 ft) ≥ 25 cm (9.84 in) 3-17
Installation and Connection
PE oooooooo
oo
oo
ooooooooo
U U
oooooooooo
PE
W V W V
oo
oo
ooo ooooo
PE
SCu PEs AFe
(a) Symmetrical shielded cables: three concentric conductors with or without a ground conductor,
symmetrically manufactured, with an external shield of copper or aluminum.
W V
U PE
SCu
(b) Alternatives for conductors up to 10 mm2
Notes:
(1) SCu = copper or aluminum external shielding
3 (2) AFe = steel or galvanized iron
(3) PE = ground conductor
(4) Cable shielding shall be grounded at both ends (inverter and motor). Use 360º connections for a low impedance to high-frequencies. Refer
to figure 3.14.
(5) For using the shield as a protective ground, it shall have at least 50 % of the power cables conductivity. Otherwise, add an external ground
conductor and use the shield as an EMC protection.
(6) Shielding conductivity at high-frequencies shall be at least 10 % of the power cables conductivity.
Figure 3.13 - Motor connection cables recommended by IEC 60034-25
There is an option accessory for frames A, B, and C named “Kit for power cables shielding – PCSx-01” (refer
to item 7.2) that can be adapted in the bottom of the enclosure of these frames. See an example of the cable
connection with the accessory PCSx-01 in figure 3.14. The kit for power cables shielding is provided for the
inverters with internal RFI filters (CFW11XXXXXXOFA).
When the “Conduit Kit” (refer to item 7.2) is used for frames A, B, and C, motor cable shield shall be grounded
similarly as in figure 3.14.
For frame D, there is a provision for motor cable shield grounding in the standard inverter enclosure.
Figure 3.14 - Detail of the motor cable shield connection with the accessory PCSx-01 installed
3-18
Installation and Connection
DANGER!
Do not share the grounding wiring with other equipment that operate with high currents (ex.: high
power motors, soldering machines, etc.). When installing several inverters, follow the procedures
presented in figure 3.15 for the grounding connection.
ATTENTION!
The neutral conductor of the network shall be solidly grounded; however, this conductor shall not
be used to ground the inverter.
DANGER!
The inverter shall be connected to a Protective Ground (PE).
Observe the following:
- Minimum wire gauge for grounding connection is provided in table 3.2. Conform to local regulations
and/or electrical codes in case a different wire gauge is required.
3
- Connect the inverter grounding connections to a ground bus bar, to a single ground point, or to
a common grounding point (impedance ≤ 10 Ω).
- To comply with IEC 61800-5-1 standard, connect the inverter to the ground by using a single
conductor copper cable with a minimum wire gauge of 10 mm2 or a two-conductor cable with the
same wire gauge of the grounding cable specified in table 3.2, since the leakage current is greater
than 3.5 mA AC.
3-19
Installation and Connection
3.2.5 Control Connections
The control connections (analog inputs/outputs, digital inputs/outputs), shall be performed in connector XC1
of the CC11 control board.
Functions and typical connections are presented in figures 3.16 a) and b).
3 Reference (0 V) for the analog Connected to the ground (frame) through impedance: 940 Ω resistor in
AGND
8 outputs parallel with a 22 nF capacitor.
(24 V)
Analog output #2: Galvanic Isolation
amp Motor current Resolution: 11 bits
9 AO2 Signal: 0 to 10 V (RL ≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (RL ≤ 500 Ω)
Protected against short-circuit.
AGND Reference (0 V) for the analog Connected to the ground (frame) through impedance: 940 Ω resistor in
10 outputs parallel with a 22 nF capacitor.
(24 V)
Reference (0 V) for the 24 Vdc Connected to the ground (frame) through impedance: 940 Ω resistor in
11 DGND* power supply parallel with a 22 nF capacitor.
Common point of the digital
12 COM inputs
24 Vdc power supply 24 Vdc power supply, ±8 %.
Capacity: 500 mA.
Note: In the models with the 24 Vdc external control power supply
13 24 Vdc (CFW11XXXXXXOW) the terminal 13 of XC1 becomes an input, i.e., the
user must connect a 24 V power supply for the inverter (refer to the section
7.1.3 for more details). In all the other models this terminal is an output,
i.e., the user has a 24 V power supply available there.
Common point of the digital
14 COM inputs
Digital input #1: 6 isolated digital inputs
15 DI1 Start / Stop High level ≥ 18 V
Digital input #2: Low level ≤ 3 V
16 DI2 Direction of rotation (remote) Maximum input voltage = 30 V
Digital input #3: Input current: 11mA @ 24 Vdc
17 DI3 No function
Digital input #4:
18 DI4 No function
Digital input #5:
19 DI5 Jog (remote)
Digital input #6:
20 DI6 2nf ramp
21 NC1 Digital output #1 DO1 (RL1): Contact rating:
22 C1 No fault Maximum voltage: 240 Vac
23 NO1 Maximum current: 1 A
NC - Normally closed contact;
24 NC2 Digital output #2 DO2 (RL2):
C - Common;
25 C2 N > NX - Speed > P0288
NO - Normally open contact.
26 NO2
27 NC3 Digital output #3 DO3 (RL3):
28 C3 N* > NX - Speed reference >
29 NO3 P0288
Figure 3.16 a) - Signals at connector XC1 - Digital inputs working as 'Active High'
3-20
Installation and Connection
Reference (0 V) for the analog Connected to the ground (frame) through impedance: 940 Ω resistor in
AGND outputs parallel with a 22 nF capacitor.
8
(24 V)
NOTE!
Remove the jumper between XC1:11 and 12 and install it between XC1:12 and 13 to use the digital
inputs as 'Active Low'.
Slot 5
Slot 1 (white)
Slot 2 (yellow)
3
Slot 3 (green)
Slot 4
Figure 3.17 - Connector XC1 and DIP-switches for selecting the signal type of the analog inputs and outputs
The analog inputs and outputs are factory set to operate in the range from 0 to 10 V; this setting may be
changed by using DIP-switch S1.
Table 3.5 - DIP-switches configuration for the selection of the signal type for the analog inputs and outputs
Parameters related to the analog inputs and outputs (AI1, AI2, AO1, and AO2) shall be programmed according
to the DIP-switches settings and desired values.
Follow instructions below for the proper installation of the control wiring:
1) Wire gauge: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG);
2) Maximum tightening torque: 0.50 N.m (4.50 lbf.in);
3) Use shielded cables for the connections in XC1 and run the cables separated from the remaining circuits
(power, 110 V / 220 Vac control, etc.), as presented in table 3.6. If control wiring must cross other cables
(power cables for instance), make it cross perpendicular to the wiring and provide a minimum separation
of 5 cm (1.9 in) at the crossing point.
3-22
Installation and Connection
The adequate connection of the cable shield is shown in figure 3.18. Figure 3.19 shows how to connect the
cable shield to the ground.
Isolate with tape
Inverter
side
3
Do not ground
4) Relays, contactors, solenoids or coils of electromechanical brakes installed close to the inverter may eventually
create interferences in the control circuitry. To eliminate this effect, RC suppressors (with AC power supply)
or free-wheel diodes (with DC power supply) shall be connected in parallel to the coils of these devices.
3-23
Installation and Connection
Control connection #1 - Start/Stop function controlled from the keypad (Local Mode).
With this control connection it is possible to run the inverter in local mode with the factory default settings. This
operation mode is recommended for first-time users, since no additional control connections are required.
For the start-up in this operation mode, please follow instructions listed in chapter 5.
This wiring example is valid only for the default factory settings and if the inverter is set to remote mode.
With the factory default settings, the selection of the operation mode (local/remote) is performed through the
operator key (local mode is default). Set P0220=3 to change the default setting of operator key to
remote mode.
3 Connector XC1
H
1 + REF
≥5 kΩ 2 AI1+
3 AI1-
4 - REF
AH
5 AI2+
6 AI2-
7 AO1
8 AGND (24 V)
9 AO2
10 AGND (24 V)
11 DGND*
12 COM
13 24 Vdc
14 COM
Start/Stop
15 DI1
16 DI2
Direction of Rotation
17 DI3
18 DI4
Jog
19 DI5
20 DI6
21 NC1
DO1
22 C1
(RL1)
23 NO1
24 NC2
DO2
25 C2
(RL2)
26 NO2
27 NC3
DO3
28 C3
(RL3)
29 NO3
3-24
Installation and Connection
Start S1 17 DI3
18 DI4
Stop S2 19 DI5
20 DI6
21 NC1
DO1
22 C1
(RL1)
23 NO1
24 NC2
DO2
25 C2
(RL2)
26 NO2
27 NC3
DO3
28 C3
(RL3)
29 NO3
3-25
Installation and Connection
When the Forward/Reverse function is set, it will be active either in Local or Remote mode. At the same time,
the operator keys and will remain always inactive (even if P0224=0 or P0227=0).
3
Connector XC1
1 + REF
2 AI1+
3 AI1-
4 - REF
5 AI2+
6 AI2-
7 AO1
8 AGND (24 V)
9 AO2
10 AGND (24 V)
11 DGND*
12 COM
13 24 Vdc
14 COM
15 DI1
16 DI2
Stop/Forward S1
17 DI3
18 DI4
Stop/Reverse S2
19 DI5
20 DI6
21 NC1
DO1
22 C1
(RL1)
23 NO1
24 NC2
DO2
25 C2
(RL2)
26 NO2
27 NC3
DO3
28 C3
(RL3)
29 NO3
3-26
Installation and Connection
The inverters with the option FA (CFW11XXXXXXOFA) are equipped with an internal RFI filter to reduce
the electromagnetic interference. These inverters, when properly installed, meet the requirements of the
electromagnetic compatibility directive - “EMC Directive 89/336/EEC” – with the complement 93/68/EEC.
The CFW-11 inverter series has been designed only for industrial applications. Therefore, the emission limits of
harmonic currents defined by the standards EN 61000-3-2 and EN 61000-3-2/A 14 are not applicable.
ATTENTION!
Do not use inverters with internal RFI filters in IT networks (neutral is not grounded or grounding
provided by a high ohm value resistor) or in grounded delta networks (“delta corner earth”), because
these type of networks damage the filter capacitors of the inverter.
1. Inverters with internal RFI filters option CFW11XXXXXXOFA (with grounding screws of the internal RFI filter
capacitors).
2. a) Shielded output cables (motor cables) and connect the shield at both ends (motor and inverter) with a
low impedance connection for high frequency. Use the PCSx-01 kit supplied with the frame size A, B and
C inverters. For the frame sizes D models, use the clamps supplied with the product. Make sure there is
a good contact between the cable shield and the clamps. Refer to the figure 3.14 as an example. The
required cable separation is presented in table 3.4. For further information, please refer to item 3.2.3.
Maximum motor cable length and conduced and radiated emission levels according to the table 3.8.
If a lower emission level and/or a longer motor cable were wished, then an external RFI filter must be
used at the inverter input. For more information (RFI filter commercial reference, motor cable length and
emission levels) refer to the table 3.8.
b) As a second option only for the V/f and VVW control modes when using a sinusoidal output filter:
Output cables (motor cables) that are not shielded can be used, provided that RFI filters are installed at
the inverter input and output, as presented in the table 3.9. In that table the maximum cable length and
the emission levels for each configuration are also presented. Keep the separation from the other cables
according to the table 3.4. Refer to the section 3.2.3 for more information.
3. Shielded control cables, keeping them separate from the other cables as described in item 3.2.5.
3-27
Installation and Connection
- Environment:
First Environment: includes domestic premises. It also includes establishments directly connected without
intermediate transformer to a low-voltage power supply network which supplies buildings used for domestic
purposes.
Example: houses, apartments, commercial installations, or offices located in residential buildings.
Second Environment: includes all establishments other than those directly connected to a low-voltage power
supply network which supplies buildings used for domestic purposes.
Example: industrial area, technical area of any building supplied by a dedicated transformer.
- Categories:
Category C1: inverters with a voltage rating less than 1000 V and intended for use in the First Environment.
3
Category C2: inverters with a voltage rating less than 1000 V, intended for use in the First Environment,
not provided with a plug connector or a movable installations, and installed and commissioned by a
professional.
Note: a professional is a person or organization familiar with the installation and/or commissioning of inverters,
including the EMC aspects.
Category C3: inverters with a voltage rating less than 1000 V and intended for use in the Second Environment
only (not designed for use in the First Environment).
Category C4: inverters with a voltage rating equal to or greater than 1000 V, or with a current rating equal to
or greater than 400 Amps, or intended for use in complex systems in the Second Environment.
EN 55011: “Threshold values and measuring methods for radio interference from industrial,
scientific and medical (ISM) high-frequency equipment”
Class B: equipment intended for use in the low-voltage power supply network (residential, commercial, and
light-industrial environments).
Class A1: equipment intended for use in the low-voltage power supply network. Restricted distribution.
Note: must be installed and commissioned by a professional when applied in the low-voltage power supply
network.
3-28
Installation and Connection
3-29
Installation and Connection
Table 3.8 - Conducted and radiated emission levels and further information - installations with shield motor cable
Table 3.9 - Required RFI filters for unshielded motor cable installations and
further information on conducted and radiated levels
Conducted emission
External RFI filters part number
- maximum motor Radiated emission - category
(manufacturer: EPCOS) (1)
Inverter model (with cable length
built-in RFI filter) Without
Inside a metallic
Inverter input Inverter output (2) Category C1 metallic
cabinet
cabinet
CFW11 0006 S 2 O FA B84142-A16-R122 B84143-V11-R127 250 m C3 C3
CFW11 0007 T 2 O FA B84143-A8-R105 B84143-V11-R127 250 m C2 C2
CFW11 0007 S 2 O FA B84142-A16-R122 B84143-V11-R127 250 m C3 C3
CFW11 0010 S 2 O FA B84142-A30-R122 B84143-V16-R127 250 m C3 C3
CFW11 0010 T 2 O FA B84143-A16-R105 B84143-V16-R127 250 m C2 C2
CFW11 0013 T 2 O FA B84143-A16-R105 B84143-V16-R127 250 m C2 C2
CFW11 0016 T 2 O FA B84143-A25-R105 B84143-V33-R127 250 m C2 C2
CFW11 0024 T 2 O FA B84143-A36-R105 B84143-V33-R127 250 m C3 C2
CFW11 0028 T 2 O FA B84143-A36-R105 B84143-V66-R127 250 m C3 C2
CFW11 0033 T 2 O FA B84143-A50-R105 B84143-V66-R127 250 m C3 C2
CFW11 0045 T 2 O FA B84143-D50-R127 B84143-V66-R127 250 m C3 C2
CFW11 0054 T 2 O FA B84143-D75-R127 B84143-V66-R127 250 m C3 C2 3
CFW11 0070 T 2 O FA B84143-D75-R127 B84143-V95-R127 250 m C3 C2
CFW11 0086 T 2 O FA B84143-A120-R105 B84143-V180-R127 250 m C3 C2
CFW11 0105 T 2 O FA B84143-A120-R105 B84143-V180-R127 250 m C3 C2
CFW11 0003 T 4 O FA B84143-A8-R105 B84143-V11-R127 250 m C2 C2
CFW11 0005 T 4 O FA B84143-A8-R105 B84143-V11-R127 250 m C2 C2
CFW11 0007 T 4 O FA B84143-A8-R105 B84143-V11-R127 250 m C2 C2
CFW11 0010 T 4 O FA B84143-A16-R105 B84143-V16-R127 250 m C2 C2
CFW11 0013 T 4 O FA B84143-A16-R105 B84143-V16-R127 250 m C2 C2
CFW11 0017 T 4 O FA B84143-A25-R105 B84143-V33-R127 250 m C3 C2
CFW11 0024 T 4 O FA B84143-A36-R105 B84143-V33-R127 250 m C3 C2
CFW11 0031 T 4 O FA B84143-A36-R105 B84143-V66-R127 250 m C3 C2
CFW11 0038 T 4 O FA B84143-D50-R127 B84143-V66-R127 250 m C3 C2
CFW11 0045 T 4 O FA B84143-D50-R127 B84143-V66-R127 250 m C3 C2
CFW11 0058 T 4 O FA B84143-D75-R127 B84143-V95-R127 250 m C3 C2
CFW11 0070 T 4 O FA B84143-A90-R105 B84143-V95-R127 250 m C3 C2
CFW11 0088 T 4 O FA B84143-A120-R105 B84143-V180-R127 250 m C3 C2
Note:
(1) The external RFI filters shown in table above were selected considering inverter rated input/output current specified for ND application
(normal duty cycle) and surrounding air temperature of 50 °C (122 °F). In order to optimize, take into account inverter input/output cur-
rent and surrounding air temperature in the application to define the rated current of external RFI filter to be used. For further information
contact EPCOS.
(2) The output filter is of the sinusoidal type, i.e., the motor voltage waveform is approximately sinusoidal, not pulsed as in the aplications
without this filter.
3-31
Installation and Connection
3-32
Keypad and Display
The integral keypad can be used to operate and program (view / edit all parameters) of the CFW-11 inverter.
The inverter keypad navigation is similar to the one used in cell phones and the parameters can be accessed
in numerical order or through groups (Menu).
4-1
Keypad and Display
Battery:
The keypad battery is used to keep the clock operating in the event of power interruption.
The expected battery life is up to 10 years. To remove the battery, rotate and pull the cover located at the rear
part of the keypad. Whenever needed, replace the battery by another of the same type (CR2032).
NOTE!
The battery is only required for the clock-related functions. If the battery is completely discharge or if
it not installed in the keypad, the displayed clock time will be invalid and an alarm condition A181
- Invalid clock time will be indicated whenever the AC power is applied to the inverter.
Installation:
The keypad can be installed or removed from the inverter with or without AC power applied to the
inverter.
The HMI supplied with the product can also be used for remote command of the inverter. In this case, use a
cable with male and female D-Sub9 (DB-9) connectors wired pin to pin (mouse extension type) or a market
standard Null‑Modem cable. It is recommended the use of the M3 x 5.8 standoffs supplied with the product.
Recommended torque: 0.5 Nm (4.5 lbf in).
4-2
Keypad and Display
When power is applied to the inverter, the display automatically enters the monitoring mode. Figure 4.3 (a)
presents the monitoring screen displayed for the factory default settings. By properly setting specific inverter
parameters, other variables can be displayed in the monitoring mode or the value of a parameter can be
displayed using bar graphs or with larger characters as presented in figures 4.3 (b) and (c).
Indication of the
control mode:
- LOC: local mode; Indication of the motor
Indication of the direction - REM: remote mode. speed in rpm.
of rotation of the motor.
Monitoring parameters:
Inverter status: - Motor speed in rpm;
- Run Run LOC 1800rpm - Motor current in Amps;
1800 rpm - Output frequency in Hz (default).
- Ready
- Config 1.0 A
P0205, P0206, and P0207: selection of parame-
60.0 Hz
- Self-tuning ters that will be displayed in the monitoring mode.
12:35 Menu
- Last fault: FXXX
P0208 to P0212: engineering unit for the speed
- Last alarm: AXXX
indication.
- etc.
Clock.
Settings via:
P0197, P0198, and P0199.
Monitoring parameters:
- Motor speed in rpm;
Run LOC 1800rpm - Motor current in Amps;
rpm 100% - Output frequency in Hz (default).
A 10%
P0205, P0206, and P0207: selection of parameters
Hz 100%
that will be displayed in the monitoring mode.
12:35 Menu
1800
Value of one of the parameters defined in P0205,
P0206, or P0207 displayed with a larger font size.
rpm Set parameters P0205, P0206 or P0207 to 0 if it is not
12:35 Menu desirable to display them.
(c) Example of a monitoring screen displaying a parameter with a larger font size
4-3
Keypad and Display
When the right soft key ("MENU") is pressed in the monitoring mode, the display shows the first 4 groups of
parameters. An example of how the groups of parameters are organized is presented in table 4.1. The number
and name of the groups may change depending on the firmware version used. For further details on the existent
groups for the firmware version used, please refer to the Software Manual.
Table 4.1 - Groups of parameters
Level 0 Level 1 Level 2 Level 3
Monitoring 00 ALL PARAMETERS
01 PARAMETER GROUPS 20 Ramps
21 Speed References
22 Speed Limits
23 V/f Control
24 Adjust. V/f Curve
25 V V W Co n t r o l
26 V/f Current Limit.
27 V/f DC Volt.Limit.
28 Dynamic Braking
29 Vector Control 90 Speed Regulator
91 Current Regulator
92 Flux Regulator
93 I/F Control
94 Self-Tuning
95 Torque Curr.Limit.
96 DC Link Regulator
30 HMI
31 Local Command
32 Remote Command
4 33 3-Wire Command
34 FWD/REV Run Comm.
35 Zero Speed Logic
36 Multispeed
37 Electr. Potentiom.
38 Analog Inputs
39 Analog Outputs
40 Digital Inputs
41 Digital Outputs
42 Inverter Data
43 Motor Data
44 FlyStart/RideThru
45 Protections
46 PID Regulator
47 DC Braking
48 Skip Speed
49 Communication 110 Local/Rem Config.
111 Status/Commands
112 CANopen/DeviceNet
113 Serial RS232/485
114 Anybus
115 Profibus DP
50 SoftPLC
51 PLC
52 Trace Function
02 ORIENTED START-UP
03 CHANGED PARAMETERS
04 BASIC APPLICATION
05 SELF-TUNING
06 BACKUP PARAMETERS
07 I/O CONFIGURATION 38 Analog Inputs
39 Analog Outputs
40 Digital Inputs
41 Digital Outputs
08 FAULT HISTORY
09 READ ONLY PARAMS.
4-4
First Time Power-Up and Start-Up
NOTE!
For a detailed description of the V V W or Vector control modes and for other available functions,
please refer to the CFW-11 Software Manual.
The inverter shall have been already installed according to the recommendations listed in Chapter 3 – Installation
and Connection. The following recommendations are applicable even if the application design is different from
the suggested control connections.
DANGER!
Always disconnect the main power supply before performing any inverter connection.
1) Check if power, grounding, and control connections are correct and firmly secured.
5
2) Remove from the inside of the inverter all installation material left behind.
3) Verify the motor connections and if the motor voltage and current is within the rated value of the inverter.
6) Measure the power supply voltage and verify if it is within the range listed in chapter 8.
5-1
First Time Power-Up and Start-Up
5.2 START-UP
The start-up procedure for the V/f is described in three simple steps by using the Oriented Start-up routine
and the Basic Application group.
Steps:
(1) Set the password for parameter modification.
(2) Execute the Oriented Start-up routine.
(3) Set the parameters of the Basic Application group.
4
press the Up Arrow P0000
Access to Parameters
until number 5 is
0
displayed in the keypad.
Return 15:45 Save
5
- When number 5 is
displayed in the keypad,
P0000
Access to Parameters
press “Save”. 5
Return 15:45 Save
5-2
First Time Power-Up and Start-Up
There is a group of parameters named ”Oriented Start-up” that makes the inverter settings easier. Inside this
group, there is a parameter – P0317 – that shall be set to enter into the Oriented Start-up routine.
The Oriented Start-up routine allows you to quickly set up the inverter for operation with the line and motor
used. This routine prompts you for the most commonly used parameters in a logic sequence.
In order to enter into the Oriented Start-up routine, follow the steps presented in figure 5.2, first modifying
parameter P0317 to 1 and then, setting all remaining parameters as they are prompted in the display.
The use of the Oriented Start-up routine for setting the inverter parameters may lead to the automatic modification
of other internal parameters and/or variables of the inverter.
During the Oriented Start-up routine, the message “Config” will be displayed at the left top corner of the
keypad.
6
“P0317 = [000] No”
is displayed.
P0317 V/f, V V W, or Vector
Reset 13:48 Select
5-3
First Time Power-Up and Start-Up
affect P0156, P0157, Config LOC 0rpm P0402. Reset 13:48 Select
5-4
First Time Power-Up and Start-Up
After running the Oriented Start-up routine and properly setting the parameters, the inverter is ready to operate
in the V/f mode.
The inverter has a number of other parameters that allow its adaptation to the most different applications.
This manual presents some basic parameters that shall be set in most cases. There is a group named “Basic
Application” to make this task easier. A summary of the parameters inside this group is listed in table 5.1. There
is also a group of read only parameters that shows the value of the most important inverter variables such as
voltage, current, etc. The main parameters comprised in this group are listed in table 5.2. For further details,
please refer to the CFW-11 Software Manual.
Follow steps outlined in figure 5.3 to set the parameters of the Basic Application group.
The procedure for start-up in the V/f operation mode is finished after setting these parameters.
5-5
First Time Power-Up and Start-Up
0 Alx Signal
0................................. 10 V
0................................20 mA
4 mA.............................20 mA
10 V...................................0
20 mA................................0
20 mA.............................4 mA
P0135 Max. Output - Avoids motor stall under torque overload condition during the 0.2 x Irat-HD to 1.5 x Irat-HD
Current acceleration or deceleration. 2 x Irat-HD
- The factory default setting is for “Ramp Hold”: if the motor current
exceeds the value set at P0135 during the acceleration or decele-
ration, the motor speed will not be increased (acceleration) or de-
creased (deceleration) anymore. When the motor current reaches a
value below the programmed in P0135, the motor speed is again
increased or decreased.
- Other options for the current limitation are available. Refer to the
CFW-11 Software Manual.
Motor current Motor current
P0135 P0135
5
Time Time
Speed
Speed
Ramp
Ramp deceleration
acceleration (P0101)
(P0100)
During Time During Time
acceleration deceleration
P0136 Manual Torque - Operates in low speeds, modifying the output voltage x frequency 0 to 9 1
Boost curve to keep the torque constant.
- Compensates the voltage drop at the motor stator resistance. This
function operates in low speeds increasing the inverter output voltage to
keep the torque constant in the V/f mode.
- The optimal setting is the smallest value of P0136 that allows the
motor to start satisfactorily. An excessive value will considerably increase
the motor current in low speeds, and may result in a fault (F048, F051,
F071, F072, F078 or F183) or alarm (A046, A047, A050 or A110)
condition.
Output voltage
Rated
P0136=9
0.5x Rated
P0136=0
0 Speed
Nrat/2 Nrat
5-6
First Time Power-Up and Start-Up
5-7
First Time Power-Up and Start-Up
Ready LOC 0rpm
27 V/F DC Volt. Limit.
- A new list of groups is Ready LOC 0rpm - Press “Return”. 28 Dynamic Braking
8 29 Vector Control
displayed and group “20 20 Ramps 30 HMI
Ramps” is selected. 21 Speed References
4 22 Speed Limits Return 18:11 Select
23 V/F Control
- Press until you
Return 16:10 Select
reach group "30 HMI". Ready LOC 0rpm
00 ALL PARAMETERS
- Press “Return”. 01 PARAMETER GROUPS
9 02 ORIENTED START-UP
Ready LOC 0rpm 03 CHANGED PARAMETERS
To prevent unauthorized or unintended parameters modification, parameter P0000 should be set to a value
different from 5. Follow the same procedures described in item 5.2.1.
5-8
First Time Power-Up and Start-Up
Notes!
- Always use a standard host/device shielded USB cable. Unshielded cables may lead to communication
errors.
- Recommended cables: Samtec:
USBC-AM-MB-B-B-S-1 (1 meter);
USBC-AM-MB-B-B-S-2 (2 meters);
USBC-AM-MB-B-B-S-3 (3 meters).
- The USB connection is galvanically isolated from the mains power supply and from other high
voltages internal to the inverter. However, the USB connection is not isolated from the Protective
Ground (PE). Use an isolated notebook for the USB connection or a desktop connected to the same
Protective Ground (PE) of the inverter.
Install the SuperDrive G2 software to control motor speed, view, or edit inverter parameters through a personal
computer (PC).
Features:
- Store a copy of the inverter parameters;
- Transfer parameters stored in the FLASH memory to the inverter;
- Transfer firmware stored in the FLASH memory to the inverter;
- Store programs created by the SoftPLC.
Whenever the inverter is powered up, this program is transferred to the RAM memory located in the inverter
control board and executed.
Refer to the CFW-11 Software Manual and to SoftPLC Manual for further details.
ATTENTION!
Before installing or removing the FLASH memory module, disconnect the inverter power supply and
wait for the complete discharge of the capacitors.
5-9
First Time Power-Up and Start-Up
5-10
Troubleshooting and Maintenance
This chapter:
- Lists all faults and alarms that may occur.
- Indicates the possible causes of each fault and alarm.
- Lists most frequent problems and corrective actions.
- Presents instructions for periodic inspections and preventive
maintenance in the equipment.
Reset the inverter to return the drive to a “READY” condition in the event of a “FAULT”. The following reset
options are available:
Removing the power supply and reapplying it (power-on reset);
Pressing the operator key (manual reset);
Through the "Reset" soft key;
Automatically by setting P0206 (auto-reset);
Through a digital input: DIx=20 (P0263 to P0270).
6-1
Troubleshooting and Maintenance
A010: A high temperature alarm was detected by the NTC Surrounding air temperature is too high (>50 °C (122 °F))
Rectifier High temperature sensors located in the rectifier modules. and output current is too high.
Temperature Note: Blocked or defective fan.
- This is valid only for the following models: Inverter heatsink is completely covered with dust.
CFW110086T2, CFW110105T2, CFW110045T4,
CFW110058T4, CFW110070T4 and
CFW110088T4.
- It may be disabled by setting P0353=2 or 3.
F021: DC bus undervoltage condition occurred. The input voltage is too low and the DC bus voltage dro-
DC Bus Undervoltage pped below the minimum permitted value (monitor the value
at Parameter P0004):
Ud < 223 V - For a 200-240 V three-phase input voltage
Ud < 170 V - For a 200-240 V single-phase input voltage
(models CFW11XXXXS2 or CFW11XXXXB2) (P0296=0);
Ud < 385 V - For a 380 V input voltage (P0296=1);
Ud < 405 V - For a 400-415 V input voltage (P0296=2);
Ud < 446 V - For a 440-460 V input voltage (P0296=3);
Ud < 487 V - For a 480 V input voltage (P0296=4).
Phase loss in the input power supply.
Pre-charge circuit failure.
Parameter P0296 was set to a value above of the power
supply rated voltage.
F022: DC bus overvoltage condition occurred. The input voltage is too high and the DC bus voltage sur-
DC Bus Overvoltage passed the maximum permitted value:
Ud > 400 V - For 220-230 V input models (P0296=0);
Ud > 800 V - For 380-480 V input models (P0296=1, 2,
6 3, or 4).
Inertia of the driven-load is too high or deceleration time is
too short.
Wrong settings for parameters P0151, or P0153, or P0185.
F030: Desaturation of IGBT occured in Power Module U. Short-circuit between motor phases U and V or U and W.
Power Module U Fault Note:
This protection is available only for frame D models.
F034: Desaturation of IGBT occured in Power Module V. Short-circuit between motor phases V and U or V and W.
Power Module V Fault Note:
This protection is available only for frame D models.
F038: Desaturation of IGBT occured in Power Module W. Short-circuit between motor phases W and U or W and V.
Power Module W Note:
Fault This protection is available only for frame D models.
F042: Desaturation of Dynamic Braking IGBT occured. Short-circuit between the connection cables of the dynamic
DB IGBT Fault Note: braking resistor.
This protection is available only for frame D models.
6-2
Troubleshooting and Maintenance
F076: Fault of motor current imbalance. Loose connection or broken wiring between the motor and
Motor Current Note: inverter connection.
Imbalance It may be disabled by setting P0342=0. Vector control with wrong orientation.
Vector control with encoder, encoder wiring or encoder
6
motor connection inverted.
F077: The dynamic braking resistor overload protection Excessive load inertia or desacceleration time too short.
DB Resistor Overload operated. Motor shaft load is excessive.
Wrong setttings for parameters P0154 and P0155.
F078: Fault related to the PTC temperature sensor installed Excessive load at the motor shaft.
Motor in the motor. Excessive duty cycle (too many starts / stops per minute).
Overtemperature Note: Surrounding air temperature too high.
- It may be disabled by setting P0351=0 or 3. Loose connection or short-circuit (resistance < 100 Ω) in the
- It is required to set the analog input / output to the wiring connected to the motor termistor.
PTC function. Motor termistor is not installed.
Blocked motor shaft.
F079: Lack of encoder signals. Broken wiring between motor encoder and option kit for
Encoder Signal Fault encoder interface.
Defective encoder.
6-3
Troubleshooting and Maintenance
6-4
Troubleshooting and Maintenance
F179: This fault indicates a problem with the heatsink fan. Dust on fan blades and bearings.
Heatsink Fan Speed Note: Defective fan.
Fault This function may be disabled by setting P0354=0.
A181: Invalid clock value alarm. It is necessary to set date and time at parameters P0194 to
Invalid Clock Value P0199.
Keypad battery is discharged, defective, or not installed.
F182: Indicates a fault on the output pulses feedback. Defect in the inverter internal circuitry.
Pulse Feedback Fault
F183: Overtemperature related to the IGBTs overload Surrounding air temperature too high.
IGBT overload + protection. Operation with frequencies < 10 Hz under overload.
Temperature
Note:
(1) Long motor cables (with more than 100 meters) will have a high leakage capacitance to the ground. The
circulation of leakage currents through these capacitances may activate the ground fault protection after
the inverter is enabled, and consequently, the occurrence of fault F074.
POSSIBLE SOLUTIONS:
- Decrease the carrier frequency (P0297).
- Install an output reactor between the inverter and the motor.
6-5
Troubleshooting and Maintenance
Point to be
Problem Corrective Action
Verified
Motor does not start Incorrect wiring connection 1. Check all power and control connections. For instance, the digital inputs
set to start/stop, general enable, or no external error shall be connected to
the 24 Vdc or to DGND* terminals (refer to figure 3.16).
Analog reference 1. Check if the external signal is properly connected.
(if used) 2. Check the status of the control potentiometer (if used).
Incorrect settings 1. Check if parameters are properly set for the application.
Motor speed Loose connection 1. Stop the inverter, turn off the power supply, and check and tighten
fluctuates (oscillates) all power connections.
2. Check all internal connections of the inverter.
Motor speed Incorrect settings 1. Check if the values of P0133 (minimum speed) and P0134
too high or too low (reference limits) (maximum speed) are properly set for the motor and application used.
Control signal from 1. Check the level of the reference control signal.
the analog reference 2. Check the settings (gain and offset) of parameters P0232 to P0249.
(if used)
Motor nameplate 1. Check if the motor has been properly sized for the application.
Motor does not reach Settings 1. Decrease P0180.
the rated speed, 2. Check P0410.
or motor speed starts
6 oscillating around
the rated speed
(Vector Control)
Power supply voltage 1. Rated values shall be within the limits specified below:
200-230 V power supply: - Minimum: 187 V
- Maximum: 253 V
380-480 V power supply: - Minimum: 323 V
- Maximum: 528 V
Blown fuses 1. Replace fuses.
6-6
Troubleshooting and Maintenance
Point to be
Problem Corrective Action
Verified
Low motor speed Encoder signals are 1. Check signals A – A, B – B, refer to the incremental encoder interface
and P0009 = P0169 inverted or power manual. If signals are properly installed, exchange two of the output
or P0170 (motor operating connection is inverted phases. For instance U and V.
with torque limitation),
for P0202 = 4 -
vector with encoder
NOTE!
For technical support and servicing, it is important to have the following information in hand:
Inverter model;
Serial number, manufacturing date, and hardware revision that are listed in the product nameplate
(refer to item 2.4);
Installed software version (check parameter P0023);
Application data and inverter settings.
DANGER!
Always turn off the mains power supply before touching any electrical component associated to
the inverter.
High voltage may still be present even after disconnecting the power supply.
To prevent electric shock, wait at least 10 minutes after turning off the input power for the complete
discharge of the power capacitors.
Always connect the equipment frame to the protective ground (PE). Use the adequate connection
6
terminal in the inverter.
ATTENTION!
The electronic boards have electrostatic discharge sensitive components.
Do not touch the components or connectors directly. If needed, first touch the grounded mettalic
frame or wear a ground strap.
6-7
Troubleshooting and Maintenance
The inverters require low maintenance when properly installed and operated . Table 6.3 presents main procedures
and time intervals for preventive maintenance. Table 6.4 provides recommended periodic inspections to be
performed every 6 months after inverter start-up.
Note:
(1) The inverters are factory set for automatic fan control (P0352=2), which means that they will be turned on
only when the heatsink temperature exceeds a reference value. Therefore, the operating hours of the fan will
depend on the inverter usage conditions (motor current, output frequency, cooling air temperature, etc.).
The inverter stores the number of operating hours of the fan in parameter P0045. When this parameter
reaches 50.000 operating hours, the keypad display will show alarm A177.
6-8
Troubleshooting and Maintenance
Ventilation system:
Disconnect the inverter power supply and wait at least 10 minutes.
Remove the dust from the cooling air inlet by using a soft brush or a flannel.
Remove the dust from the heatsink fins and from the fan blades by using compressed air.
Electronic boards:
Disconnect the inverter power supply and wait at least 10 minutes.
Remove the dust from the electronic board by using an anti-static brush or an ion air gun (Charges Burtes
Ion Gun - reference A6030-6DESCO).
If needed, remove the boards from the inverter.
Always wear a ground strap.
6-9
Troubleshooting and Maintenance
1 2
Fan removal
Releasing the latches of the fan cover
Cable disconnection
1 2
6-10
Option Kits and Accessories
Details for the installation, operation, and programming of the accessories are described in their own manuals
and were not included in this chapter.
Some models cannot incorporate all available option kits. Refer to table 8.1 for a detailed description of the
option kits that are available for each inverter model.
Inverters with the following codification: CFW11XXXXXXOFA. Refer to table 8.1 for information on availability
of this option kit for each inverter model.
ATTENTION!
Do not use inverters with internal RFI filters in IT networks (ungrounded neutral or grounding provided
by a high ohm value resistor) or in grounded delta networks (“delta corner earth”). These type of
installations will damage the inverter filter capacitors.
The RFI filter reduces the conducted noise of the inverter to the electrical supply system in the high frequency
range (>150 kHz).
The RFI filter is required for the compliance with conducted emissions limits established by the Electromagnetic
Compatibility standards such as EN 61800-3 and EN 55011.
For the proper operation of the RFI filter, please follow the instructions listed in item 3.3 for the installation of 7
the inverter, motor, cables, etc. This chapter also provides information on the compliance of these standards,
such as the maximum motor cable length.
The inverters with this option are equipped with an additional board (SRB) that contains 2 safety relays and an
interconnection cable with the power circuit.
7-1
Option Kits and Accessories
Figure 7.1 shows the location of the SRB board and the location of the connector XC25 (used for the connection
of the SRB board signals) in the inverter.
The relay coils are available through the connector XC25, as presented in figure 7.1.
DANGER!
The activation of the Safety Stop, i.e., disconnection of the 24 Vdc power supply from the safety relay
coil (XC25: 1(+) and 2(-); XC25:3(+) and 4(-)) does not guarantee the electrical safety of the motor
terminals (they are not isolated from the power supply in this condition).
Operation:
1. The Safety Stop function is activated by disconnecting the 24 Vdc voltage from the safety relay coil (XC25:
1(+) and 2(-); XC25:3(+) and 4(-)).
2. Upon activation of the Safety Stop, the PWM pulses at the inverter output will be blocked and the motor will
coast to stop.
The inverter will not start the motor or generate a rotating magnetic field even in the event of an internal
failure (pending certification).
The keypad will display a message informing that the Safety Stop is active.
3. Apply 24 Vdc voltage to the safety relay coil (XC25: 1(+) and 2(-); XC25:3(+) and 4(-)) to get back to
normal operation after activation of the Safety Stop.
XC25
7-2
Option Kits and Accessories
The use of this option kit is recommended with communication networks (Profibus, DeviceNet, etc.), since the
control circuit and the network communication interface are kept active (with power supply and responding to
the network communication commands) even in the event of main power supply interruption.
Inverters with this option have a built-in DC/DC converter with a 24 Vdc input that provides an adequate output
for the control circuit. In such manner the power supply of the control circuit will be redundant, i.e., it can be
provided by a 24 Vdc external power supply (connection as shown in figure 7.2) or by the standard internal
switched-mode power supply of the inverter.
Observe that the inverters with the external 24 Vdc power supply option use terminals XC1:11 and 13 as the
input for the external power supply and no longer as an output as in the standard inverter (figure 7.2).
In case of interruption of the external 24 Vdc power source, the digital inputs/outputs and analog outputs will
have no power supply, even if the mains power is on. Therefore, it is recommended to keep the 24 Vdc power
source always connected to terminals XC1:11 and 13.
The keypad displays warnings indicating the inverter status: if the 24 Vdc power source is connected, if the
mains power source is connected, etc.
7-3
Option Kits and Accessories
Connector XC1
1 + REF
2 AI1+
3 AI1-
4 - REF
5 AI2+
6 AI2-
7 AO1
8 AGND (24 V)
9 AO2
10 AGND (24 V)
11 DGND*
24 Vdc
±10 % 12 COM
@1.5 A 13 24 Vdc
14 COM
15 DI1
16 DI2
17 DI3
18 DI4
19 DI5
20 DI6
21 NC1
DO1
22 C1
(RL1)
23 NO1
24 NC2
DO2
25 C2
(RL2)
26 NO2
27 NC3
DO3
28 C3
(RL3)
29 NO3
Figure 7.2 - Connection terminals and 24 Vdc external power supply rating
7.2 AcCESSORIES
The accessories are installed to the inverter easily and quickly using the "Plug and Play" concept. Once the
accessory is connected to the slot, the control circuitry identifies the model and displays the installed accessory
code in P0027 or P0028. The accessory shall be installed with the inverter power supply off.
The code and model of each availabe accessory is presented in the following tables. The accessories can be
7 ordered separately and will be shippe in an individual package containing the components and the manual
with detailed instructions for the product installation, operation, and programming.
ATTENTION!
Only one module can be fitted at once in each slot (1, 2, 3, 4, or 5).
7-4
Option Kits and Accessories
417107425 IOB-01 IOB Module: 2 isolated analog inputs (voltage/current); 2 digital inputs; 1 FA-- ----
2 isolated analog outputs (voltage/current) (the programming of the
outputs is identical as in the standard CFW-11); 2 open-collector digital
outputs.
417107430 ENC-01 5 to 12 Vdc Incremental Encoder Module, 100 kHz, with an encoder 2 --C2 ----
signal repeater.
417107418 ENC-02 5 to 12 Vdc Incremental Encoder Module, 100 kHz. 2 --C2 ----
417107432 RS485-01 RS-485 Serial Communication Module (Modbus). 3 ---- CE--
417107433 RS232-01 RS-232C Serial Communication Module (Modbus). 3 ---- CC--
417107434 RS232-02 RS-232C Serial Communication Module with DIP-switches for program- 3 ---- CC--
ming the microcontroller FLASH memory.
417107435 CAN/RS485-01 CAN and RS-485 Interface Module (CANopen / DeviceNet / Modbus). 3 ---- CA--
417107436 CAN-01 CAN Interface Module (CANopen / DeviceNet). 3 ---- CD--
417107431 PLC11-01 PLC Module. 1, 2, and 3 ---- --xx(1)(3)
Stand-alone keypad, blank cover, and frame for remote mounted keypad:
WEG Part
Name Description Slot
Number
417107422 HMI-01 Stand-alone keypad.(4) HMI
417107423 RHMIF-01 Remote Keypad Frame Kit (IP56). -
417107444 HMID-01 Blank cover for the keypad slot. HMI
Miscellaneous:
WEG Part
Name Description Slot
Number
417107406 KN1A-01 Conduit kit for frame A (standard for option N1).(5)
-
417107409 KN1B-01 Conduit kit for frame B (standard for option N1).(5) -
417107412 KN1C-01 Conduit kit for frame C (standard for option N1).(5) -
417107448 KIP21D-01 IP21 kit for frame D (standard for option 21). -
417107445 PCSA-01 Kit for power cables shielding - frame A (standard for option FA). -
417107446 PCSB-01 Kit for power cables shielding - frame B (standard for option FA). -
7
417107447 PCSC-01 Kit for power cables shielding - frame C (standard for option FA). -
417107449 PCSD-01 Kit for power cables shielding - frame D (included in the standard product). -
417107441 CCS-01 Kit for control cables shielding (included in the standard product). -
Notes:
(1) Refer to the PLC Module Manual.
(2) Refer to the Anybus-CC Communication Manual.
(3) Refer to the Software Manual.
(4) Use DB-9 pin, male-to-female, straight-through cable (serial mouse extension type) for connecting the keypad to the inverter or Null-Modem
standard cable. Maximum cable length: 10 m (33 ft).
Examples:
- Mouse extension cable - 1.80 m (6 ft); Manufacturer: Clone.
- Belkin pro series DB9 serial extension cable 5 m (17 ft); Manufacturer: Belkin.
- Cables Unlimited PCM195006 cable, 6 ft DB9 m/f; Manufacturer: Cables Unlimited.
(5) Refer to the section 8.4 for more details.
7-5
Option Kits and Accessories
7-6
Technical Specifications
TECHNICAL SPECIFICATIONS
Power Supply:
Voltage tolerance: -15 % to +10 %.
Frequency: 50/60 Hz (48 Hz to 62 Hz).
Phase imbalance: ≤3 % of the rated phase-to-phase input voltage.
Overvoltage according to Category III (EN 61010/UL 508C).
Transient voltage according to Category III.
Maximum of 60 connections per hour.
Typical efficiency: ≥ 97 %.
Typical input power factor:
- 0.94 for three-phase input (CFW11XXXXTX) at rated condition.
- 0.70 for single-phase input at rated condition.
8-1
8
8-2
Availability of option kits
Use with Normal Duty (ND) cycle Use with Heavy Duty (HD) cycle that can be incorporated into the product
(refer to the intelligent code in chapter 2) (8)
Overload current Dissipated Overload current
Model Rated Dissipated power [W]
Rated output (2) [Arms] Rated carrier Maximum Rated input power [W] (2) [Arms] Rated carrier Maximum
Frame
phases
output Rated input
current (1) frequency (3) motor (4) current Surface Flange current (1) frequency (3) motor (4) Surface Flange
current [Arms]
Weight (kg/lb)
Surrounding air
temperature (1)
Cabinet
[Arms] [kHz] [HP/kW] [Arms] [kHz] [HP/kW] RFI filter
Dynamic braking
1 min 3s mounting mounting 1 min 3 s mounting mounting
Number of power
enclosure
[Arms]
nal control
Safety stop
power supply
24 Vdc exter-
CFW11 0006 B 2 1φ / 3φ 6.0 6.60 9.00 5 1.5/1.1 12.3/6.0 (5) 130 25 5.0 7.50 10.0 5 1.5/1.1 10.3/5.0 (5) 120 25 5.7/12.6 Yes (*)
CFW11 0006 S 2 O FA 1φ 6.0 6.60 9.00 5 1.5/1.1 12.3 130 25 5.0 7.50 10.0 5 1.5/1.1 10.3 120 25 5.7/12.6 Built-in
Technical Specifications
CFW11 0007 T 2 3φ 7.0 7.70 10.5 5 2/1.5 7.0 140 25 5.5 8.25 11.0 5 1.5/1.1 5.5 120 25 5.7/12.6
Yes (*)
CFW11 0007 B 2 1φ / 3φ 7.0 7.70 10.5 5 2/1.5 14.4/7.0 (5) 140 25 7.0 10.5 14.0 5 2/1.5 14.4/7.0 (5) 140 25 6.1/13.4
Nema 1
CFW11 0007 S 2 O FA A 1φ 7.0 7.70 10.5 5 2/1.5 14.4 140 25 7.0 10.5 14.0 5 2/1.5 14.4 140 25 6.1/13.4 (conduit kit for frame Built-in
A - 417107406)
CFW11 0010 T 2 3φ 10 11.0 15.0 5 3/2.2 10.0 170 30 8.0 12.0 16.0 5 2/1.5 8.0 170 30 5.7/12.6
CFW11 0010 S 2 1φ 10 11.0 15.0 5 3/2.2 20.5 180 30 10 15.0 20.0 5 3/2.2 20.5 140 25 6.1/13.4
CFW11 0013 T 2 3φ 13 14.3 19.5 5 4/3.0 13.0 200 30 11 16.5 22.0 5 3/2.2 11.0 170 30 6.1/13.4
CFW11 0016 T 2 3φ 16 17.6 24.0 5 5/3.7 16.0 230 30 13 19.5 26.0 5 4/3.0 13.0 190 30 Built-in 6.3/13.9 Yes Yes Yes
-10 ... 50 ºC
CFW11 0024 T 2 3φ 24 26.4 36.0 5 7.5/5.5 24.0 310 50 20 30.0 40.0 5 6/4.5 20.0 250 40 9.1/20
Nema 1
CFW11 0028 T 2 B 3φ 28 30.8 42.0 5 10/7.5 28.0 370 60 24 36.0 48.0 5 7.5/5.5 24.0 290 40 9.1/20 (conduit kit for frame
B - 417107409)
CFW11 0033 T 2 3φ 33.5 36.9 50.3 5 12.5/9.2 33.5 430 60 28 42.0 56.0 5 10/7.5 28.0 350 50 9.1/20
CFW11 0086 T 2 3φ 86 94.6 129 5 30/22 86.0 970 150 70 105 140 5 25/18.5 70.0 740 110 29.5/65.1 IP21
D (IP21 kit for frame D -
CFW11 0105 T 2 3φ 105 116 158 5 40/30 105.0 1200 180 86 129 172 5 30/22 86.0 920 140 31.4/69.2 417107448)
CFW11 0003 T 4 3φ 3.6 3.96 5.40 5 2/1.5 3.6 130 25 3.6 5.40 7.20 5 2/1.5 3.6 110 25 5.7/12.6
CFW11 0005 T 4 3φ 5.0 5.50 7.50 5 3/2.2 5.0 140 25 5.0 7.50 10.0 5 3/2.2 5.0 140 25 5.9/13
Nema 1
CFW11 0007 T 4 A 3φ 7.0 7.7 10.5 5 4/3 7.0 180 30 5.5 8.25 11.0 5 3/2.2 5.5 140 25 5.9/13 (conduit kit for frame
A - 417107406)
CFW11 0010 T 4 3φ 10 11.0 15.0 5 6/4.5 10.0 220 30 10 15.0 20.0 5 6/4.5 10.0 200 30 6.1/13.4
Table 8.1 - Technical specification for the CFW-11 series
CFW11 0013 T 4 3φ 13.5 14.9 20.3 5 7.5/5.5 13.5 280 40 11 16.5 22.0 5 6/4.5 11.0 220 30 6.3/13.9
CFW11 0017 T 4 3φ 17 18.7 25.5 5 10/7.5 17.0 360 50 13.5 20.3 27.0 5 7.5/5.5 13.5 270 40 9.1/20
Nema 1
CFW11 0024 T 4 B 3φ 24 26.4 36.0 5 15/11 24.0 490 70 19 28.5 38.0 5 10/7.5 19.0 360 50 Built-in 9.7/21.4 (conduit kit for frame Yes Yes Yes
B - 417107409)
-10 ... 50 ºC
CFW11 0031 T 4 3φ 31 34.1 46.5 5 20/15 31.0 560 80 25 37.5 50.0 5 15/11 25.0 430 60 10.4/22.9
CFW11 0038 T 4 3φ 38 41.8 57.0 5 25/18.5 38.0 710 110 33 49.5 66.0 5 20/15 33.0 590 90 16.4/36.2
Nema 1
CFW11 0045 T 4 C 3φ 45 49.5 67.5 5 30/22 45.0 810 120 38 57.0 76.0 5 25/18.5 38.0 650 100 19.6/43.2 (conduit kit for frame
CFW11 0070 T 4 3φ 70.5 77.6 106 5 50/37 70.5 1280 190 61 91.5 122 5 40/30 61.0 1050 160 31.1/68.6 IP21
D (IP21 kit for frame D -
CFW11 0088 T 4 3φ 88 96.8 132 5 60/45 88.0 1480 220 73 110 146 5 50/37 73.0 1170 180 32.6/71.8 417107448)
Note:
(1) Steady-state rated current in the following conditions:
- Indicated carrier frequencies. For operation with a 10 kHz carrier frequency it is necessary to derate the
output current according to table 8.2.
- Surrounding air temperature: -10 °C to 50 °C (14 °F to 122 °F). The inverter is capable of operating with an maximum
surrounding air temperature of 60 °C (140 °F) if an output current derating of 2 % is applied for each ºC above
50 °C (122 °F).
- Relative air humidity: 5 % to 90 % non-condensing.
- Altitude: 1000 m (3,300 ft). Above 1000 m (3,300 ft) up to 4000 m (13,200 ft) the output current shall be
derated by 1 % for each 100 m (330 ft) above 1000 m (3,300 ft).
- Ambient with pollution degree 2 (according to EN50178 and UL508C).
(2) Table 8.1 presents only two points of the overload curve (activation time of 1 min and 3 s). The complete
information about the IGBTs overload for Normal and Heavy Duty Cycles is presented below.
Io
IRAT ND
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9 ∆ t (s)
0 10 20 30 40 50 60 70 80 90 100 110 120
(a) IGBTs overload curve for the Normal Duty (ND) cycle
Io
IRAT HD
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1 8
1.0 ∆ t (s)
0 10 20 30 40 50 60 70 80 90 100 110 120
(b) IGBTs overload curve for the Heavy Duty (HD) cycle
8-3
Technical Specifications
Depending on the inverter usage conditions (surrounding air temperature, output frequency, possibility or not
of reducing the carrier frequency, etc.), the maximum time for operation of the inverter with overload may be
reduced.
(3) The carrier frequency may be automatically reduced to 2.5 kHz depending on the operating conditions
(surrounding air temperature, output current, etc.) - if P0350=0, 1, or 4.
(4) The motor ratings are merely a guide for 220 V or 440 V, IV pole WEG motors. The adequate inverter sizing
shall be based on the rated current of the motor used.
(5) Models that can operate from single-phase or three-phase power supply have their input current stated in
both cases. The single-phase input current is provided first.
(6) The information provided about the inverter losses is valid for the rated operating condition, i.e., for rated
output current and rated carrier frequency.
(7) The dissipated power provided for flange mounting corresponds to the total inverter losses disregarding the
power module (IGBT and rectifier) losses.
(8) If the inverter is to be provided with this option, it should be specified in the intelligent identification code of the
inverter. Exception: the RFI filter is already incorporated in models CFW110006S2OFA and CFW110007S2OFA.
For further details, please refer to chapter 2.
8-4
Carrier frequency of 10 kHz and surrounding air temperature = 50 °C (122 °F) Carrier frequency of 10 kHz and surrounding air temperature = 40 °C (104 °F)
Use with Normal Duty (ND) cycle Use with Heavy Duty (HD) cycle Use with Normal Duty (ND) cycle Use with Heavy Duty (HD) cycle
Overload Overload Overload Overload
Rated current (2) Dissipated power [W] Rated current (2) Dissipated power [W] current (2) Dissipated power [W] current (2) Dissipated power [W]
Rated Rated
Model output [Arms] output [Arms] [Arms] [Arms]
output output
current current
Frame
phases
kW]
kW]
kW]
kW]
Flange Flange current (9) Surface Flange current (9) Flange
(1) Surface (1) Surface Surface
Maximum
Maximum
Maximum
Maximum
1 min 3 s mounting mounting [Arms] 1 min 3 s mounting mounting [Arms] 1 min 3 s mounting
Rated input
Rated input
Rated input
Rated input
[Arms] mounting (6) [Arms] 1 min 3 s mounting (6) mounting (6)
current [Arms]
current [Arms]
current [Arms]
current [Arms]
Number of power
motor (4) [HP/
motor (4) [HP/
motor (4) [HP/
motor (4) [HP/
(7) (7) (6) (7) (7)
CFW11 0006 B 2 1φ / 3φ 5.5 6.05 8.25 1.5/1.1 11.3/5.5 140 25 4.6 6.90 9.20 1.5/1.1 9.4/4.6 130 25 6.00 6.60 9.00 2/1.5 12.3/6.0 150 25 5.00 7.50 10.0 1.5/1.1 10.3/5.0 130 25
CFW11 0006 S 2 O FA 1φ 5.5 6.05 8.25 1.5/1.1 11.3 140 25 4.6 6.90 9.20 1.5/1.1 9.4 130 25 6.00 6.60 9.00 2/1.5 12.3 150 25 5.00 7.50 10.0 1.5/1.1 10.3 130 25
CFW11 0007 T 2 3φ 6.2 6.82 9.30 2/1.5 6.2 140 25 4.9 7.35 9.8 1.5/1.1 4.9 120 25 7.00 7.70 10.5 2/1.5 7.0 150 25 5.50 8.3 11.0 1.5/1.1 5.5 130 25
CFW11 0007 B 2 1φ / 3φ 6.6 7.26 9.90 2/1.5 13.5/6.6 140 25 6.6 9.90 13.2 2/1.5 13.5/6.6 140 25 7.00 7.70 10.5 2/1.5 14.4/7.0 150 25 6.90 10.4 13.8 2/1.5 14.1/6.9 150 25
CFW11 0007 S 2 O FA A 1φ 7.0 7.26 9.90 2/1.5 14.35 140 25 6.6 9.90 13.2 2/1.5 13.53 140 25 7.00 7.70 10.5 2/1.5 14.35 150 25 6.90 10.4 13.8 2/1.5 14.15 150 25
CFW11 0010 S 2 1φ 8.0 8.80 12.00 2/1.5 16.4 160 25 8.0 12.00 16.0 2/1.5 16.4 160 25 9.40 10.34 14.1 3/2.2 19.3 180 30 9.40 14.1 18.8 3/2.2 19.3 180 30
CFW11 0010 T 2 3φ 8.4 9.24 12.6 2/1.5 8.4 160 25 6.7 10.1 13.4 2/1.5 6.7 140 25 10.0 11 15.0 3/2.2 10.0 180 30 8.00 12.0 16.0 2/1.5 8.0 160 25
CFW11 0013 T 2 3φ 9.8 10.8 14.7 3/2.2 9.8 180 30 8.3 12.5 16.6 2/1.5 8.3 160 25 10.7 11.8 16.1 3/2.2 10.7 190 30 9.00 13.5 18.0 3/2.2 9.0 170 30
CFW11 0016 T 2 3φ 12.8 14.1 19.2 4/3.0 12.8 210 30 10.4 15.6 20.8 3/2.2 10.4 180 30 14.6 16.1 21.9 5/3.7 14.6 240 40 12.0 18.0 24.0 4/3 12.0 200 30
CFW11 0024 T 2 3φ 23.0 25.3 34.5 7.5/5.5 23.0 320 50 19.2 28.8 38.4 6/4.5 19.2 280 40 23.8 26.2 35.7 7.5/5.5 23.8 330 50 19.9 29.9 39.8 7.5/5.5 19.9 280 40
CFW11 0028 T 2 B 3φ 23.0 25.3 34.5 7.5/5.5 23.0 330 50 19.7 29.6 39.4 6/4.5 19.7 290 40 23.8 26.2 35.7 7.5/5.5 23.8 340 50 20.4 30.6 40.8 7.5/5.5 20.4 300 50
CFW11 0033 T 2 3φ 25.2 27.7 37.8 7.5/5.5 25.2 360 50 21.0 31.5 42.0 7.5/5.5 21.0 310 50 27.5 30.3 41.3 10/7.5 27.5 390 60 23.0 34.5 46.0 7.5/5.5 23.0 330 50
CFW11 0054 T 2 C 3φ 43.2 47.5 64.8 15/11 43.2 600 90 36.0 54.0 72.0 12.5/9.2 36.0 510 80 47.0 51.7 70.5 15/11 47.0 660 100 39.3 59.0 78.6 15/11 39.3 550 80
CFW11 0070 T 2 3φ 38.5 42.4 57.8 12.5/9.2 38.5 560 80 30.8 46.2 61.6 10/7.5 30.8 460 70 42.0 46.2 63.0 15/11 42.0 610 90 33.6 50.4 67.2 12.5/9.2 33.6 500 80
CFW11 0086 T 2 3φ 68.8 75.7 103 25/18.5 68.8 770 120 56.0 84.0 112 20/15 56.0 640 100 75.7 83.3 114 30/22 75.7 850 130 61.6 92.4 123 20/15 61.6 700 110
D
CFW11 0105 T 2 3φ 84.0 92.4 126 30/22 84.0 930 140 68.8 103 138 25/18.5 68.8 770 120 96.4 106 145 30/22 96.4 1070 160 79.0 119 158 30/22 79.0 870 130
CFW11 0003 T 4 3φ 3.6 3.96 5.40 2/1.5 3.6 140 25 3.6 5.40 7.20 2/1.5 3.6 140 25 3.60 3.96 5.40 2/1.5 3.6 140 25 3.60 5.40 7.20 2/1.5 3.6 140 25
CFW11 0005 T 4 3φ 4.0 4.40 6.00 2/1.5 4.0 140 25 4.0 6.00 8.00 2/1.5 4.0 140 25 4.50 4.95 6.75 3/2.2 4.5 160 25 4.50 6.75 9.00 2/1.5 4.5 160 25
CFW11 0007 T 4 A 3φ 5.2 5.72 7.80 3/2.2 5.2 170 30 4.1 6.15 8.20 2/1.5 4.1 150 25 5.80 6.38 8.70 3/2.2 5.8 180 30 4.60 6.90 9.20 2/1.5 4.6 160 25
CFW11 0010 T 4 3φ 9.2 10.1 13.8 5/3.7 9.2 250 40 9.2 13.8 18.4 5/3.7 9.2 250 40 10.0 11.0 15.0 6/4.5 10.0 260 40 10.0 15.0 20.0 6/4.5 10.0 260 40
CFW11 0013 T 4 3φ 11.5 12.7 17.3 7.5/5.5 11.5 290 40 9.5 14.3 19.0 6/4.5 9.5 250 40 12.7 14.0 19.1 7.5/5.5 12.7 320 50 10.4 15.6 20.8 6/4.5 10.4 270 40
CFW11 0017 T 4 3φ 11.9 13.1 17.9 7.5/5.5 11.9 320 50 9.5 14.3 19.0 6/4.5 9.5 270 40 13.1 14.4 19.7 7.5/5.5 13.1 350 50 10.4 15.6 20.8 6/4.5 10.4 290 40
CFW11 0024 T 4 B 3φ 14.4 15.8 21.6 7.5/5.5 14.4 390 60 11.5 17.3 23.0 7.5/5.5 11.5 330 50 15.8 17.4 23.7 10/7.5 15.8 420 60 12.5 18.8 25.0 7.5/5.5 12.5 350 50
CFW11 0031 T 4 3φ 23.6 26.0 35.4 15/11 23.6 560 80 19.0 28.5 38.0 10/7.5 19.0 470 70 28.3 31.1 42.5 15/11 28.3 650 100 24.0 36.0 48.0 15/11 24.0 560 80
CFW11 0038 T 4 3φ 23.6 26.0 35.4 15/11 23.6 620 90 20.5 30.8 41.0 12.5/9.2 20.5 560 80 28.5 31.4 42.8 15/11 28.5 710 110 24.8 37.2 49.6 15/11 24.8 640 100
CFW11 0045 T 4 C 3φ 30.6 33.7 45.9 20/15 30.6 730 110 25.9 38.9 51.8 15/11 25.9 650 100 33.8 37.2 50.7 20/15 33.8 790 120 28.5 42.8 57.0 15/11 28.5 700 110
CFW11 0070 T 4 3φ 38.8 42.7 58.2 25/18.5 38.8 910 140 33.6 50.4 67.2 20/15 33.6 810 120 42.3 46.5 63.5 25/18.5 42.3 970 150 36.6 54.9 73.2 20/15 36.6 870 130
D
CFW11 0088 T 4 3φ 48.4 53.2 72.6 30/22 48.4 1080 160 40.2 60.3 80.4 25/18.5 40.2 940 140 52.6 57.9 78.9 30/22 52.6 1160 170 43.7 65.6 87.4 30/22 43.7 1000 150
Notes:
Table 8.2 - Specification for the CFW-11 series with a carrier frequency of 10 kHz
(9)
- Surrounding air temperature: -10 to 40 ºC (14 to 104 °F);
- Relative air humidity: 5 % to 90 % non-condensing;
- Altitude: 1000 m (3,300 ft). Above 1000 m (3,300 ft) up to 4000 m (13,200 ft) the output current shall be derated by 1 % for each 100 m (330 ft)
above 1000 m (3,300 ft).
- Ambient with pollution degree 2 (according to EN 50178 and UL 508C).
8-5
Technical Specifications
8
Technical Specifications
8-6
Technical Specifications
8-7
Technical Specifications
* Dimensions in mm [in]
Figure 8.2 - Inverter dimensions - frame A
8-8
Technical Specifications
Frame B
* Dimensions in mm [in]
Figure 8.3 - Inverter dimensions - frame B
8-9
Technical Specifications
Frame C
* Dimensions in mm [in]
Figure 8.4 - Inverter dimensions - frame C
8-10
Technical Specifications
Frame D
* Dimensions in mm [in]
Figure 8.5 - Inverter dimensions - frame D
8-11
Technical Specifications