0% found this document useful (0 votes)
154 views3 pages

RFQ - Acdb-Ajb&scb R1

This document is an RFQ for solar combiner boxes (AJB/SCB) with the following key details: - Technical specifications as per IS and IEC standards for 1500VDC systems. - Delivery location is in Bhagabangola, West Bengal. - Quantity required is 69 boxes for a 10kW system and 17 boxes for a 20kW system. - Delivery timeline is 50% in December 2019 and 50% in January 2020.

Uploaded by

jyoti khaitan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
154 views3 pages

RFQ - Acdb-Ajb&scb R1

This document is an RFQ for solar combiner boxes (AJB/SCB) with the following key details: - Technical specifications as per IS and IEC standards for 1500VDC systems. - Delivery location is in Bhagabangola, West Bengal. - Quantity required is 69 boxes for a 10kW system and 17 boxes for a 20kW system. - Delivery timeline is 50% in December 2019 and 50% in January 2020.

Uploaded by

jyoti khaitan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

RFQ FOR SOLAR AJB/SCB

SPECIFICATION:
As mentioned below
DELIVERY:
Bhagabangola, Murshidabad, West Bengal
Technical Specification for AJB/SCB
AS PER IS-13703-P1.IEC-60269/13704-P4.VDE 0636
BOM
Option-1 Description( In 2 Out )
IP65 Polycarbonate Enclosure
Power SPD for 1500 VDC system for 40KA Surge – Type (2)
Fuse with Fuse Holder for 18 Amps on both Input
MC4 Connectors for positive and negative Input
Copper Bus Bar (19 X 3 Sqmm) 102Amps.
Busbar Insulators (6X30)
M16 Polyamide Cable Gland with Lock Nut
35/10Sq mm Hybrid Terminals Block (HTB)
10sqmm Earthing Terminal
Bakelite sheet (270x370 Sq. mm)
Other Panel Accessories (Wire, Lugs, Din rail, Cable Duct etc.)

Option-2 Description(6 In 1 Out)


Maximum DC Input 1500V
No. of DC Inputs 4 Positive & 4 Negative
No. of DC Outputs 1
Number of Terminal Blocks 2 to 34
Reverse Blocking Diode N/A
Maximum Input Fuse Rating- Type 15/20A - Semiconductor
Maximum DC Current (A) 200
Maximum Continuous Current (A) 160
Isolator/MCB 16/32/40/63/125
Maximum Voltage, VDC 600/1000
+Ve Input wire size, 1C x sqmm 2.5 to 25
-Ve Input wire size, 1C x sqmm 2.5 to 25
Surge Protection Device (SPD) 600/1000V, Class II
Operating Temperature -10° to 55°
Enclosure Type PS/PC
Protection Type/Protection Class IP 65
Cable glands clamping range 12 to 32
Wall Mounting Yes/Structure Mounted
Bus Bar Yes
Operating Condition -10°C to 55°C
Type of Protection (As per requirement) Short – Circuit, Surge
Design Life 25 Years

Major component make


DC Disconnector Telergon/Socomac/Schneider
Fuse TB Elmex/Mersen/Bussman/Little Fuse
Enclosure Trinity touch /Fibox/Reputed
PV Connector Elmex/Multi Contact/Phoenix/Reputed
Surge Protection Device Phoenix Contact/Citel/Dehn
Gland Oratec/Comet/Dowells/Hummel/Reputed
Cable Polycab/KEI/Lapp/Reputed
Terminals Elmex/Phoenix/Connectwell/Reputed
Panel Accessories Reputed
QUANTITY:
For 10kw- 69 nos (6 In 1out-Specification & BOM are changed according to Inverter tec Spec)
For 20kw- 17nos (4 In 1out-Specification & BOM are changed according to Inverter tec Spec)

Note- Please provide Quotation 10 kW & 20 kW system Separately with BOM option 1 & 2 .
Along with GA, BOM, SLD, Drawing with Make details.

Delivery Terms: FOR at Site

Delivery Time: 50% quantity in December, 2019 and balance in January 2020.