Smartcon 4000
Smartcon 4000
Smartcon 4000
and
Operating Manual
Pyrotech Electronics Pvt. Ltd. F-16A, Road No. 3, M.I.A., Madri, Udaipur, 313 003, India.
Phone - 0091-294-2492121, 2492123, 2492124, 2492125 Fax - 0091-294-2492126
Email - [email protected], [email protected]
Web - www.peplelectronics.com
Pyrotech
Doc. No. : W/R&D/28/03/13 Date : 07/01/2008 Rev : 01
CONTENTS
1) Features . . . . . . . . . . . . . . . . . . . . . . . 2
2) Specifications . . . . . . . . . . . . . . . . . . 3
3) Wiring details . . . . . . . . . . . . . . . . . . . 5
4) Installation instructions . . . . . . . . . . 6
5) Operating Procedure . . . . . . . . . . . . 7
6) Summary of Keyboard. . . . . . . . . . . . 18
Dual set point, one set of potential free contact output for
each.
96 x 96 x 141 mm size.
Input Range :
J type - -120 to 920°C.
K type - -180 to 1350°C.
R type - 0 to 1760°C.
S type - 0 to 1760°C.
T type - 0 to 400°C.
N type - 0 to 1300°C.
E type - -120 to 700°C.
Pt-100 - -150 to 840°C.
4-20 mA - -1999 to +9999 field scalable and decimal point adjustable.
0-1 V - -1999 to +9999 field scalable and decimal point adjustable.
1-5 V - -1999 to +9999 field scalable and decimal point adjustable.
0-5 V - -1999 to +9999 field scalable and decimal point adjustable.
0-10 V - -1999 to +9999 field scalable and decimal point adjustable.
Outputs :
Two potential free contacts - Contact Rating : 250VAC, 6 A.
Retransmission O/P 4-20mA .
24Volt Auxilliary supply ( Optional ).
Display :
5 digit, 0.56", seven segment red display. (Others on request)
Two Red colour led to indicate alarms.
Keyboard :
3 control keys up, down and mode for operation, programming and calibration.
Calibration :
Through front panel.
Physical :
Case - 96 x 96 x 141 mm ABS plastic module.
Panel Cutout - 92 x 92 mm
Terminals - Screw terminals suitable for wire size up to 2.5 mm2.
Mounting - Panel Mounted.
Weight - 1 Kg. Approx.
In case of RTD input, use 3- core shielded wire between RTD sensor and input terminals of
the instrument. The shield of the wire should be earthed nearer to the instrument only.
For T/C type input, ensure that the compensating cable is not broken, is free of joints and is
of proper type.
For T/C type input, for stability of reading, use shielded compensating cable with shield
earthed nearer to the instrument only.
RF/ EMI / Vibrations generating sources should not be near to the instrument.
4. will be displayed.
5. Previously selected input will be Displayed
- K type thermocouple.
- J type thermocouple.
- R type thermocouple.
- S type thermocouple.
- T type thermocouple.
- N type thermocouple.
- E type thermocouple.
- 4 - 20 mA
- Pt 100 RTD.
- 0-1 Volt
- 0-5 Volt
- 0-10 Volt
- 1-5 Volt
(B2) Configuring parameters for 4-20 mA / 1-5 V & 0-1 V / 0-5 V / 0-10 V input :
1. Previously selected decimal point is displayed.
2. Select decimal point as per the chart
1. is displayed.
2. will be displayed.
3. If mode & down keys are pressed simultaneously, then calibration will be
18. Press mode & down keys simultaneously to save the value. will be
displayed for some time, then the instrument will return to the run mode (Step D).
1. is displayed.
2. will be displayed.
3. If mode & down keys are pressed simultaneously, then calibration will be
18. Press mode & down keys simultaneously to save the value. will be
displayed for some time, then the instrument will return to the run mode (Step D).
1. is displayed.
2. will be displayed.
3. If mode & down keys are pressed simultaneously, then calibration will be
7. is displayed.
8. Feed ohms of Zero at A(12), B(13) & b(14) terminals and press down key.
14. Press mode & down keys simultaneously to save the value. will be
displayed for some time, then the instrument will return to the run mode (Step D).
15. is displayed.
16. will be displayed.
17. If mode & down keys are pressed simultaneously, then calibration will be
28. Press mode & down keys simultaneously to save the value. will be
displayed for some time, then the instrument will return to the run mode (Step D).
1. is displayed.
2. will be displayed.
3. If mode & down keys are pressed simultaneously, then calibration will be
7. is displayed.
8. Feed 0.0 Volt at V+(15) & V-(14) and press down key.
9. Some reading will be displayed.
10. Press mode key to save the value.
11. will be displayed.
12. Feed 1.0 Volt at V+(15) & V-(14) and press down key.
or
If input selected is 0-5 V, then feed 5 Volt at V+(15) & V-(14) and press down key.
or
If input selected is 0-10 V, then feed 10 Volt at V+(15) & V-(14) and press down
key.
13. Some reading will be displayed.
14. Press mode & down keys simultaneously to save the value. will be
displayed for some time, then the instrument will return to the run mode (Step D).
In case of 0-1V, 0-5V & 0-10V inputs, when i/p is fed as 0, in open sensor condition,
Zero range will be displayed.
1. will be displayed in case the input fed is above the specified limit.
2. will be displayed in case the input fed is below the specified limit.
1.
4. is displayed.
5. Release down key.
6. will be displayed.
7. Recalibrate the instrument.
+ +
+ +
+
NOTE : While configuring parameters, one can come out of keyboard at any
time by pressing mode & down keys simultaneously. Once calibration
option ‘yes’ is selected, then one can come out of keyboard only after
calibration by pressing mode & down key.
Notes :
F:\neena\smartcon\96*96UIC.doc