2ft Ex Lights
2ft Ex Lights
2ft Ex Lights
The SafeSite LED Linear fixture’s rugged solid state design makes it highly
® resistant to shock and vibration. Its fully gasketed IP 66 rated enclosure
SafeSite LED Linear Fixture makes it suitable for dust & wet locations, its 1598A rating guarantees added
Low Profile - Class I, Div. 2 / Class II protection from salt water spray. The SafeSite LED Linear’s superior design
allows for wiring and mounting versatility and ease of installation for
many lighting applications.
Mechanical Information
Fixture Weight: 4’ - 10 lbs (4.53 kg)
2’ - 7 lbs (3.18 kg)
Shipping Weight: 4’ - 11 lbs (4.99 kg)
2’ - 8 lbs (3.63 kg)
Mounting: (4) 3/4” NPT openings
Optional swivel bracket - LPXW4
Optional low profile bracket - LPXW4LP
Electrical Specifications
Dimensions in Inches [mm]
Operating Voltage: 100 - 277V AC 50/60Hz
Certifications & Ratings
• Class I Div. 2 Groups A, B, C, D Power Consumption: See ordering information
• Class II Div. 1 Groups E, F, G
• Class II Div. 2 Groups F, G Operating Temp: -40°F to +149°F (-40°C to +65°C)
• Class III Div. 1
• Class III Div. 2 Harmonics: IEC 61000-3-2
• UL 1598/A
• UL 844 Noise Requirements/
• UL 8750 EMC: FCC Title 47, Subpart B, Section 15, class
A device. RF Immunity; 10V/m,
• CSA C22.2 No.137 80MHz-1GHz
• CSA C22.2 No.250
• IP 66 (pending) Surge Protection EN 61000-4-5
• NEMA 4X (pending) 4 kV line to line
4 kV line to ground
Features & Benefits
• 5 year full performance warranty THD: < 20%
• L70 rated for >100,000 hours @ 25°C
• DLC Listed (80 CRI CW & NW models only) Power Factor: > 0.9
• Low profile housing for limited space applications Construction
• Dual NPT entries for in / out wiring
• Thru wiring capability Body: Powder coated aluminum
• Instant on/off operation
• Resistant to water, salt, dust & vibration Lens: Polycarbonate
• Resistant up to 20 PSI of hose directed water
• Universal input (100-277V AC), 50/60Hz Photometric Information
• Mercury free
• Temperature compensation technology for longer life CRI: 75, 80
• Factory sealed
• Integrated wiring box CCT: 5000K (cool white)
4000K (neutral white)
Light Distribution IES Files: Available upon request
All values typical unless otherwise stated
All lumen values are typical (tolerance +/- 10%)
Temperature Ratings
Ambient Temperature Range Ambient Temperature Range
T4A Temperature Code T5 Temperature Code
Mounting Options
LPXW4LP Side Mount - LPXW4 Top Mount - LPXW4
2
www.dialight.com
SafeSite® LED Linear Fixture
Class I Div. 2 Ordering Information
Part Number1 Length Type4 CRI Voltage Lens6 Initial Fixture Lumens2,3 Watt Lumens Per Watt
Low Profile Models
LPD3C4M2P 4’ Low Profile 75 100 - 277V AC Clear 7,400 66 112
LPD3C4H2D 4’ Low Profile 75 100 - 277V AC Diffused 7,000 66 106
LPD3B4M2P 4' Low Profile 80 100 - 277V AC Clear 6,300 66 95
LPD3B4H2D 4' Low Profile 80 100 - 277V AC Diffused 6,000 66 91
LPD3C4D2P 2’ Low Profile 75 100 - 277V AC Clear 3,700 33 112
LPD3C4B2D 2’ Low Profile 75 100 - 277V AC Diffused 3,500 33 106
LPD3B4D2P 2' Low Profile 80 100 - 277V AC Clear 3,100 33 94
LPD3B4B2D 2' Low Profile 80 100 - 277V AC Diffused 2,900 33 88
304 2 Brackets
LTXENDCAPKIT Chain mount and secondary retention bracket
Stainless Steel Mounting hardware
2 brackets
304
LTXSAFEKIT Safety Cable Kit for secondary retention 2 53” Safety cables
Stainless Steel
Mounting hardware
www.dialight.com 3
Application
The first of its kind, Dialight’s SafeSite® LED linear fixture replaces HID and
fluorescent lighting fixtures in industrial applications and hazardous
location applications.
The SafeSite LED Linear fixture’s rugged solid state design makes it highly
resistant to shock and vibration. Its fully gasketed IP 66 rated enclosure
SafeSite® LED Linear Fixture makes it suitable for dust & wet locations, its 1598A rating guarantees added
protection from salt water spray. The SafeSite LED Linear’s superior design
Top Conduit Mount- Class I, Div. 2 / Class II allows for mounting versatility and ease of installation for many lighting
applications.
Mechanical Information
Fixture Weight: 4’ - 11 lbs (4.99 kg)
2’ - 10 lbs (4.53 kg)
Shipping Weight: 4’ -13 lbs (5.90 kg)
2’ - 12 lbs (5.44 kg)
Mounting: (3) 3/4” NPT openings
Optional swivel bracket - LTXW4
Optional low profile bracket - LTXW4LP
Temperature Ratings
Ambient Temperature Range Ambient Temperature Range
T4A Temperature Code T5 Temperature Code
Mounting Options
Conduit Top Mount Conduit Side Mount LTXW4 LTXW4LP
4 www.dialight.com
SafeSite® LED Linear Fixture
Class I Div. 2 Ordering Information
Part Number1
Length Type 5
CRI Voltage Lens6 Initial Fixture Lumens2,3,4 Watt Lumens Per Watt
Top Conduit Models
LTD3C4M2P 4’ Top Conduit 75 100 - 277V AC Clear 7,400 66 112
LTD3C4H2D 4’ Top Conduit 75 100 - 277V AC Diffused 7,000 66 106
LTD3B4M2P 4' Top Conduit 80 100 - 277V AC Clear 6,300 66 95
LTD3B4H2D 4' Top Conduit 80 100 - 277V AC Diffused 6,000 66 91
LTD3C4D2P 2’ Top Conduit 75 100 - 277V AC Clear 3,700 33 112
LTD3C4B2D 2’ Top Conduit 75 100 - 277V AC Diffused 3,500 33 106
LTD3B4D2P 2' Top Conduit 80 100 - 277V AC Clear 3,100 33 94
LTD3B4B2D 2' Top Conduit 80 100 - 277V AC Diffused 2,900 33 88
304 2 Brackets
LTXENDCAPKIT Chain mount and secondary retention bracket
Stainless Steel Mounting hardware
2 brackets
304
LTXSAFEKIT Safety Cable Kit for secondary retention 2 53” Safety cables
Stainless Steel
Mounting hardware
www.dialight.com 5
Application:
Dialight’s SafeSite® LED linear fixture replaces HID and fluorescent lighting
fixtures in industrial and hazardous applications. The SafeSite® LED Linear
fixture’s rugged solid state design makes it highly resistant to shock and
vibration. Its fully gasketed IP 66 rated enclosure makes it suitable for dusty
& wet locations. The SafeSite LED Linear’s superior design allows for
mounting versatility and ease of installation for many lighting applications.
SafeSite® LED Linear Fixture This fixture is offered in sustained and maintained configurations.
Sustained has a single AC input and battery backup mode is entered
Battery Backup - Class I, Div. 2 / Class II upon any loss of power. Fixture cannot be turned off without entering
battery backup mode. Maintained has two AC inputs. The fixture can be
turned on and off via AC-1 and Fixture only enters battery backup mode
when AC-2 is lost or low.
Mechanical Information
Fixture Weight: 18.0 lbs (8.16 kg)
Shipping Weight: 21.0 lbs (9.53 kg)
Mounting: (1) Threaded 3/4” NPT Side
(2) Threaded 3/4” NPT Ends
Electrical specifications:
Operating Voltage: 100-277V AC 50/60 Hz
Power Consumption: 85W
Dimensions in Inches [mm]
Operating Temp: -20°F to +149°F (-20°C to +65°C)
Certifications Battery:
• Class I, Division 2, Groups A, B, C, D 3.6V 10Ah NiMH
• Class II, Division 1, Groups E, F, G Expected Battery Life: 4 years
• Class II, Division 2, Groups F, G
• Class III, Division 1 Battery Duration: >3 hours
• Class III, Division 2 Harmonics: IEC 61000-3-2
• UL1598/A
• UL 844 Noise Requirements/
• UL 924 EMC: FCC Title 47, Subpart B, Section 15, class
• CSA C22.2 #250.0 A device. RF Immunity; 10V/m,
• CSA C22.2 No.137 80MHz-1GHz
• IP 66 Surge Protection EN 61000-4-5
• NEMA 4X 1 kV line to line
2 kV line to ground
-
Temperature Ratings
Ambient Temperature Range Ambient Temperature Range
T4A Temperature Code T5 Temperature Code
-20°F to +149°F (-20°C to +65°C) -20°F to +113°F (-20°C to +45°C)
Mounting Options
In-line Conduit Mount Overhead Conduit Mount LSXW4
6
www.dialight.com
SafeSite® LED Linear Fixture
Class I Div. 2 Ordering Information
Part Number1 Length Type5 Voltage Lens6 Initial Fixture Lumens2,3,4 Watt Lumens Per Watt
Battery Backup Models
LSD3C4MEP 4’ Sustained 100 - 277V AC Clear 7,000 85 85
LSD3C4MNP 4’ Maintained 100 - 277V AC Clear 7,000 85 85
2 Eyelets
316
HZXSAFEKIT Safety Cable Kit 2 53” Safety cables
Stainless Steel
Mounting hardware
www.dialight.com 7
Application
The first of its kind, the Dialight SafeSite® LED linear luminaire was
designed specifically to replace HID and fluorescent lighting fixtures in
industrial and hazardous location applications. The SafeSite LED Linear
fixture’s rugged solid state design makes it highly resistant to shock and
vibration , while it’s superior design allows for increased mounting
versatility and ease of installation.
Mechanical Information
SafeSite® LED Linear Fixture Fixture Weight: 4’ - 26.0 lbs (11.79 kg)
2’ - 17.5 lbs (7.94 kg)’
Class I, Div. 1 Shipping Weight: 4’ - 28.0 lbs (12.70 kg)
2’ - 19.5 lbs (8.85 kg)
47.46 Mounting: (1) Threaded 3/4” NPT Side
(1205,4) (2) Threaded 3/4” NPT Ends
Electrical specifications:
Operating Voltage: 100 - 277V AC 50/60Hz or
347 - 480V AC 50/60Hz
Power Consumption: See ordering information
4.25 25.56
(108) (649,1) Operating Temp: -40°F to +149°F (-40°C to +65°C)
Harmonics: IEC 61000-3-2
6.98
(177,4) Noise Requirements/
EMC: FCC Title 47, Subpart B, Section 15, class
A device. RF Immunity; 10V/m,
Dimensions in Inches [mm] 80MHz-1GHz
Surge Protection EN 61000-4-5
Certifications 4 kV line to line
• Class I, Div 1 Groups C, D 4 kV line to ground
• UL 844 THD: < 20%
• UL1598
Power Factor: > 0.9
• CSA 22.2 No.137
• UL 8750 Construction
• ABS Design Assessed: # 12-HS942957-PDA Body: Powder Coated Aluminum
• IP 66
Lens: Glass
• NEMA 4X
Photometric Information
CRI: 75
Light Distribution CCT: 5000K Cool White (100-277V AC)
5650K Cool White (347-480V AC)
IES Files: Available upon request
All values typical unless otherwise state
All lumen values are typical (tolerance +/- 10%)
Temperature Ratings
LSC3C4M3GEX (4ft) LSC3C4D3GEX (2ft)
Ambient Temperature Range Ambient Temperature Range
T4a Temperature Code T5 Temperature Code
-40°F to +149°F (-40°C to +65°C) -40°F to +149°F (-40°C to +65°C)
Mounting Options
Conduit Top Mount Conduit Side Mount LSXW5
8 www.dialight.com
SafeSite® LED Linear Fixture
Class I Div. 1 Ordering Information
1
Part Number Length Voltage Lens Initial Fixture Lumens Watt Lumens Per Watt
Class I, Div 1
LSC3C4M3GEX 4’ 100 - 277V AC Clear 7,000 66 106
LSC3C5M3GEX 4’ 347 - 480V AC Clear 7,250 78 93
LSC3C4D3GEX 2’ 100 - 277V AC Clear 3,500 33 106
LSC3C5D3GEX 2’ 347 - 480V AC Clear 3,600 39 92
Notes:
1
Part numbers listed in the above table are cool white. For neutral white models replace the 5th character with N. Ex. LSC3C4D3GEX becomes LSC3N4D3GEX
For Dialight’s complete list of DLC qualified products, please click this link: www.dialight.com/DLC
2 Eyelets
316
HZXSAFEKIT Safety Cable Kit 2 53” Safety cables
Stainless Steel
Mounting hardware
Dialight reserves the right to make changes at any time in order to supply the best product possible. The most current version of this document will always be available at:
www.dialight.com/Assets/Brochures_And_Catalogs/Illumination/MDTFSLINX001.pdf. Warranty Statement: EXCEPT FOR THE WARRANTY EXPRESSLY PROVIDED FOR
[HEREIN/ABOVE/BELOW], DIALIGHT DISCLAIMS ANY AND ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE, TITLE, AND NONINFRINGEMENT.
www.dialight.com MDTFSLINX001_L 9
SafeSite® LED Linear Fixture - UL 844
for Indoor and Outdoor Hazardous Locations