GA-02.063-EN-26-09-2018 RS232 to Uniwire.

doc

gAVC 1200 EVCD


Accessories
Uniwire to RS232 converter
Product number : 94072

Former item no: 0618653-002

Manual
M/94072/01
Rev. 26.09.2018
GA-02.052-EN-26.09.2018

Please look at our homepage www.gavilar.nl for the latest version of the document.
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

CONTENT

1.0 Functionality ................................................................................................................ 3

2.0 Mounting ....................................................................................................................... 3


2.1 Installation type 1, Uniwire to RS232 converter for EX installation: ...................................................... 3
2.2 Installation type 2, RS232 to Uniwire converter installation: ................................................................. 4
2.3 Installation type 3, RS232 to optical isolated port at communication controller installation: ................ 4
2.4 Installation type 4, RS232 to optical isolated port at communication controller EX installation: ........... 4

3.0 Ex description .............................................................................................................. 6


3.1 General.................................................................................................................................................. 6
3.2 ATEX and intrinsic safety (Installation type 1 and 4 only): .................................................................... 6
3.3 Installation, inspection and maintenance in hazardous environment ................................................... 6

4.0 Technical data .............................................................................................................. 7


4.1 Dimensions............................................................................................................................................ 7
4.2 Common specifications ......................................................................................................................... 7
4.3 Markings ................................................................................................................................................ 7

GA-02.063-EN-26.09.2018

Page 2 of 8
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

1.0 Functionality
The Uniwire to RS232 converter is used between RS232 data signal and either Uniwire or opto isolated
port on communication interface for gAVC 1100 or gAVC 1200.

Reference to “gAVC 1100 Installation Manual” for general information.


Reference to “gAVC 1200 Installation Manual” for general information.

Definitions
Technicians are qualified persons educated or trained to mount, operate, and also troubleshoot technically
correct and in accordance with safety regulations.

Limitations
This manual only applies to the following Product numbers:

94072 Uniwire to RS232 converter

and only for mounting in non-hazardous area.

Repair of the unit and replacement of components must be done by gAvilar only.

2.0 Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who
are able to follow these should connect the module.
Should there be any doubt as to the correct handling of the module, please contact your local distributor or,
alternatively,
gAvilar b.v. - Kamerlingh Onnesweg 63 – Dordrecht – The Netherlands
Tel. +31 85489 7130 - E-mail: [email protected]

Mounting and connection of the module should comply with national legislation for mounting of electric
materials, i.a. wire cross-section, protective fuse, and location. Descriptions of input / output and supply
connections will follow in this paper.

When mounting the option board please also observe the guidelines in the paper "ESD correct handling".

2.1 Installation type 1, Uniwire to RS232 converter for EX installation:


To be connected between an RS232 port and Uniwire (going into hazardous area) with a serial data
communication isolator (type MTL5051) in between. See chapter 3 for additional EX limitations.

safe area hazard area


(Blue terminals)

RS232 2 RX Uniwire B 10 6 RX 6 1 Uniwire B


Isolated 94072
DB9 3 TX Uniwire A 12 5 TX 4 3 Uniwire A
5 GND 11 Barrier 2 12V 5 Uniwire to
MTL5051
1 GND 2 RS232
+V 24VDC 14 converter
-V 13

Setting switches at MTL5051. 1a = off. 1b = on. 2a = off. 2b = on.


Setting jumper inside 94072. Jumper must be short circuit.
The MTL5051 need additional power supply 24VDC.

GA-02.063-EN-26.09.2018

Page 3 of 8
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

2.2 Installation type 2, RS232 to Uniwire converter installation:


As above but with no serial data communication isolator.

2 RX 6 94072 1 Uniwire B
RS232 3 TX 4 Uniwire to RS232 3 Uniwire A
DB9 4 DTR # 5 converter
5 GND # 2

Setting jumper inside 94072. Jumper must be short circuit.

2.3 Installation type 3, RS232 to optical isolated port at communication controller installation:
To connect a RS232 port to the optical isolated port at communication controller for gAVC 1100 & 1200.

061864x-yyy
RS232 2 RX 6 94072 1 1T
3 TX 4 3 2R Communication-
DB9 Uniwire to RS232 controller
4 DTR # 5
5 GND # 2 converter 2 3C terminals
x-yyy is wildcard

Setting jumper inside 94072. Jumper must be open circuit.

2.4 Installation type 4, RS232 to optical isolated port at communication controller EX installation:
To connect a RS232 port to the optical isolated port at a communication controller for gAVC 1100 & 1200
(placed in hazardous area), with a serial data communication isolator (type MTL5051) and zener barrier in
between.

Only receiving data: safe area hazard area


(Blue terminals)
Zener barrier 94072
2 RX 10 Isolated 6 RX 8 PEPPERL & 1 6 Uniwire to 1 1T
5 GND 11 FUCHS RS232 3 2R
3 TX 12
Barrier 2 5V 5 4 5 2 3C
+V 24V 14 MTL5051 1 GND 7 Z961 7 2 converter
-V 0V 13

Setting switches at MTL5051. 1a = off. 1b = off. 2a = off. 2b = on.

Two way communication: safe area hazard area


(Blue terminals)
94072 Zener barrier
2 RX 10 Isolated 6 RX 6 1 RX 8 1 1T
5 GND 11 5 TX 4 Uniwire to 3 TX 5 PEPPERL & 4 2R
3 TX 12
Barrier 2 12V 5 2 GND 7 2 3C
RS232 FUCHS
+V 24V 14 MTL5051 1 GND 2
converter
-V 0V 13 Z961

Setting switches at MTL5051. 1a = off. 1b = on. 2a = off. 2b = on.

Zener barrier: The intrinsic safety does not depend on the earth connections on the Zener barrier.
Therefore it’s not needed to connect the earth terminals on the Zener barrier.
See in chapter 3 for additional EX limitations.

GA-02.063-EN-26.09.2018

Page 4 of 8
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

Setting jumper inside 94072. Jumper must be open circuit.


The MTL5051 need additional power supply 24VDC.

Notes:
# Instead of supply from RS232 terminal 4 DTR it is possible to use external supply. Then connect: 0V at
terminal 2 and +7 - 12VDC at terminal 5 on 94072 RS232 to Uniwire converter.

GA-02.063-EN-26.09.2018

Page 5 of 8
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

3.0 Ex description
3.1 General
The Uniwire to RS232 converter cannot be placed in hazardous environment, but it can be connected to
gAVC 1200 in hazardous area via Uniwire or the communication controller.

3.2 ATEX and intrinsic safety (Installation type 1 and 4 only):


The 94072 product is a “simple apparatus”
Only to be connected in the intrinsic safe circuit between communication isolator MTL5051 manufactured by
Measurement technology LTD and gAvilar intrinsic safe Uniwire circuit.
The MTL5051 isolators don’t need protective ground.

Or by using MTL5051 and zener barrier PEPPERL & FUCHS Z961 to reduce EX data signals from MTL5051
to fit opto output at communication controller.
Zener barrier: The intrinsic safety does not depend on the earth connections on the Zener barrier. Therefore
it’s not needed to connect the earth terminals on the Zener barrier.
Keep the intrinsic safe terminals at MTL5010, 94072 converter and Uniwire terminals away from other not
safe signals. A creepage distance of 50mm is adequate.

Placement in safe area only!

3.3 Installation, inspection and maintenance in hazardous environment


Repair of the unit and replacement of components must be done by gAvilar only.
For Installation, inspection and maintenance it’s recommended to follow the standards:
• EN 60079-14 Electrical apparatus for explosive gas atmospheres
Part 14. Electrical installations in hazardous area (other than mines).
• EN 60079-17 Electrical apparatus for explosive gas atmospheres
Part 17. Inspection and maintenance of electrical installations in hazardous
area (other than mines).

GA-02.063-EN-26.09.2018

Page 6 of 8
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

4.0 Technical data


4.1 Dimensions

4.2 Common specifications


Operating temperature: -30°C – 60°C

4.3 Markings
The Analogue Input board has the following markings

Description Marking Explanation Example


Product name Uniwire to RS232 converter
Product number gAvilar stock no.: 94072
Terminal description Terminals:
1: Data in (Uniwire B)
2: COM
3: Data out (Uniwire A)
4: RS232 input
5: V+ power (5-12VDC)
6: RS232 output
ATEX information ATEX and intrinsic safety: See chapter 3.
This product is a “simple
apparatus”.
Refering to installation manual for
safe use.
Placement in safe area only!
gAvilar logo
CE marking
WEEE marking

GA-02.063-EN-26.09.2018

Page 7 of 8
GA-02.063-EN-26-09-2018 RS232 to Uniwire.doc

Revision history
Rev. Init Comment
18.01.2008 TF Document created
14.11.2008 TF Two way communication added for Installation type 4
26-09-2018 JvdG Updated to gAvilar

gAvilar b.v. - Kamerlingh Onnesweg 63 – Dordrecht – The Netherlands


Tel. +31 85489 7130 - E-mail: [email protected]

GA-02.063-EN-26.09.2018

Page 8 of 8