PILE ANALYSIS
In accordance with EN 1997-1:2004 incorporating Corrigendum dated February 2009 and the UK national annex
Tedds calculation version 1.0.02
Pile details
Installation method; Drilled
Shape; 300 mm diameter
Length; L = 12000 mm
Material details
Material; Concrete
Concrete strength class; C20/25
Part. factor, concrete (EN1992-1-1 cl. 2.4.2.4(1)); C = 1.50
Coefficient cc (EN1992-1-1 cl. 3.1.6(1)); cc = 0.85
Characteristic compression cylinder strength; fck = 20 N/mm2
Design comp. strength (EN1992-1-1 cl. 3.1.6(1)); fcd = cc fck / C = 11.3 N/mm2
Mean value of cyl. strength (EN1992-1-1 Table 3.1); fcm = fck + 8 MPa = 28.0 N/mm2
Secant mod. of elasticity (EN1992-1-1 Table 3.1); Ecm = 22000 MPa (fcm / 10 MPa)0.3 = 30.0 kN/mm2
Modulus of elasticity; E = Ecm = 30.0 kN/mm2
Geometric properties
Pile section depth; h = 300 mm
Bearing area; Abearing = h2 / 4 = 0.071 m2
Pile perimeter; Perimpile = h = 0.942 m
Moment of inertia; I = h4 / 64 = 39761 cm4
Fd
2000 mm
1000 mm
2000 mm
1000 mm
5000 mm
Stratum details
Stratum Geomaterial Thickness, tstratai Characteristic value, Characteristic value,
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
PILE ANALYSIS AND DESIGN 2 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019
Action details
Characteristic perm. unfav. action, compression; Gc,k,unfav = 74.5 kN
Characteristic perm. fav. action, compression; Gc,k,fav = 0 kN
Characteristic variable unfav. action, compression; Qc,k = 113.1 kN
Characteristic perm. unfav. action, tension; Gt,k,unfav = 0 kN
Characteristic perm. fav. action, tension; Gt,k,fav = 0 kN
Characteristic variable unfav. action, tension; Qt,k = 0 kN
Geotechnical partial and model factors:
Design approach 1:
Model factor on axial resistance; model = 1.00
Permanent unfavourable, A1 (Table A.3); G,unfav,A1 = 1.35
Permanent favourable, A1 (1); G,fav,A1 = 1.35
Variable unfavourable, A1 (Table A.3); Q,A1 = 1.50
Permanent unfavourable, A2 (Table A.3); G,unfav,A2 = 1.35
Permanent favourable, A2 (Table A.3); G,fav,A2 = 1.35
Variable unfavourable, A2 (Table A.3); Q,A2 = 1.50
8 10
6 17 23 29
5 16 22 28
4 15 21 27
3 14 20 26
2 13 19 25
y
1 12 18 24
Foundation loads
Self weight; Fswt = 5.8 kN/m2; Soil weight; Fsoil = 9.0 kN/m2
Column no.1 loads
Permanent load in z; FGz1 = 0.8 kN; Variable load in z; FQz1 = 7.2 kN
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 4 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019
Forces on foundation
Force in z-axis; Fdz = 958.8 kN
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 6 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019
Moments on foundation
Moment in x-axis; Mdx = 2744.1 kNm; Moment in y-axis; Mdy = 2618.1 kNm
Eccentricity of base reaction
Eccentricity in x-axis; ex = -38 mm; Eccentricity in y-axis; ey = -38 mm
Effective area of base
Effective length; L'x = 5724 mm; Effective width; L'y = 5461 mm
Effective area; A' = 31.260 m2
Pad base pressure
Design base pressure; fdz = 30.7 kN/m2
Design approach 1
Partial factors on actions - Combination2
Partial factor set; A2
Permanent action; G = 1.00; Variable action; Q = 1.30
Forces on foundation
Force in z-axis; Fdz = 743.8 kN
Moments on foundation
Moment in x-axis; Mdx = 2128.9 kNm; Moment in y-axis; Mdy = 2021.3 kNm
Eccentricity of base reaction
Eccentricity in x-axis; ex = -38 mm; Eccentricity in y-axis; ey = -51 mm
Effective area of base
Effective length; L'x = 5725 mm; Effective width; L'y = 5435 mm
Effective area; A' = 31.116 m2
Pad base pressure
Design base pressure; fdz = 23.9 kN/m2
Concrete details (Table 3.1 - Strength and deformation characteristics for concrete)
Concrete strength class; C20/25; Char.comp.cylinder strength; fck = 20 N/mm2
Partial factor for concrete; C = 1.50; Maximum aggregate size; hagg = 20 mm
2
Design compressive strength; fcd = 11.3 N/mm ; Design tensile strength, plain; fctd,pl = 0.8 N/mm2
Reinforcement details
Characteristic yield strength; fyk = 410 N/mm2; Partial factor for reinforcment; S = 1.15
2
Design yield strength; fyd = 357 N/mm ; Nominal cover; cnom = 50 mm
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 7 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019
24.5 20.6
25.5 24.7
35.7
60.6 59.1
75.1 79.8 74.9
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.2 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor; = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.2 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor; = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.3 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor; = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.3 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor; = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.4 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor; = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.4 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor; = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.5 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor; = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.5 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor; = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 10 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019
9 11
7
8 10
5 16 22 28
4 15 21 27
3 14 20 26
2 13 19 25
1 12 18 24