Project Job Ref.

AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &


BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
PILE ANALYSIS AND DESIGN 1 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

PILE ANALYSIS
In accordance with EN 1997-1:2004 incorporating Corrigendum dated February 2009 and the UK national annex
Tedds calculation version 1.0.02

Pile details
Installation method; Drilled
Shape; 300 mm diameter
Length; L = 12000 mm
Material details
Material; Concrete
Concrete strength class; C20/25
Part. factor, concrete (EN1992-1-1 cl. 2.4.2.4(1)); C = 1.50
Coefficient cc (EN1992-1-1 cl. 3.1.6(1)); cc = 0.85
Characteristic compression cylinder strength; fck = 20 N/mm2
Design comp. strength (EN1992-1-1 cl. 3.1.6(1)); fcd = cc  fck / C = 11.3 N/mm2
Mean value of cyl. strength (EN1992-1-1 Table 3.1); fcm = fck + 8 MPa = 28.0 N/mm2
Secant mod. of elasticity (EN1992-1-1 Table 3.1); Ecm = 22000 MPa  (fcm / 10 MPa)0.3 = 30.0 kN/mm2
Modulus of elasticity; E = Ecm = 30.0 kN/mm2
Geometric properties
Pile section depth; h = 300 mm
Bearing area; Abearing =   h2 / 4 = 0.071 m2
Pile perimeter; Perimpile =   h = 0.942 m
Moment of inertia; I =   h4 / 64 = 39761 cm4
Fd
2000 mm

qsk1 = 3.35 kN/m2


3500 mm

qsk2 = 4.02 kN/m2


12000 mm

1000 mm
2000 mm

qsk4 = 6.7 kN/m2

1000 mm
5000 mm

qsk6 = 31.49 kN/m2


qbk6 = 18800 kN/m2

q ski = Characteristic value, shaft resistance, qbki = Characteristic value, base

Stratum details
Stratum Geomaterial Thickness, tstratai Characteristic value, Characteristic value,
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
PILE ANALYSIS AND DESIGN 2 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

(mm) base, qbki shaft, qski


(kN/m2) (kN/m2)
1 Cohesionless 2000 - 3.4
2 Cohesionless 3500 - 4
3 Cohesionless 1000 - 14.1
4 Cohesionless 2000 - 6.7
5 Cohesionless 1000 - 16.1
6 Cohesionless 5000 18800 31.5

Action details
Characteristic perm. unfav. action, compression; Gc,k,unfav = 74.5 kN
Characteristic perm. fav. action, compression; Gc,k,fav = 0 kN
Characteristic variable unfav. action, compression; Qc,k = 113.1 kN
Characteristic perm. unfav. action, tension; Gt,k,unfav = 0 kN
Characteristic perm. fav. action, tension; Gt,k,fav = 0 kN
Characteristic variable unfav. action, tension; Qt,k = 0 kN
Geotechnical partial and model factors:
Design approach 1:
Model factor on axial resistance; model = 1.00
Permanent unfavourable, A1 (Table A.3); G,unfav,A1 = 1.35
Permanent favourable, A1 (1); G,fav,A1 = 1.35
Variable unfavourable, A1 (Table A.3); Q,A1 = 1.50
Permanent unfavourable, A2 (Table A.3); G,unfav,A2 = 1.35
Permanent favourable, A2 (Table A.3); G,fav,A2 = 1.35
Variable unfavourable, A2 (Table A.3); Q,A2 = 1.50

Characteristic axial resistance


Characteristic axial base resistance; Rbk = Abearing  qbk = 1328.9 kN
Characteristic axial shaft resistance per stratum
Stratum 1; Rsk1 = qsk1  Perimpile  tstrata1 =6.3 kN
Stratum 2; Rsk2 = qsk2  Perimpile  tstrata2 =13.3 kN
Stratum 3; Rsk3 = qsk3  Perimpile  tstrata3 =13.3 kN
Stratum 4; Rsk4 = qsk4  Perimpile  tstrata4 =12.6 kN
Stratum 5; Rsk5 = qsk5  Perimpile  tstrata5 =15.2 kN
Stratum 6; Rsk6 = qsk6  Perimpile  (L - Dstrata6) =74.2 kN
Characteristic total axial shaft resistance; Rsk = Rsk1 + Rsk2 + Rsk3 + Rsk4 + Rsk5 + Rsk6 = 134.8 kN
Axial compressive resistance
Load combination 1: A1 + M1 + R1
Design compression action; Fc,d,C1 = G,unfav,A1  Gc,k,unfav - G,fav,A1  Gc,k,fav + Q,A1  Qc,k
Fc,d,C1 = 270.2 kN
Partial resistance factor, bearing (Table A.NA.7); b,R1 = 1.00
Partial resistance factor, shaft (Table A.NA.7); s,R1 = 1.00
Design compressive resistance; Rc,d,C1 = (Rbk / b,R1 + Rsk / s,R1) / model = 1463.7 kN
Fc,d,C1 / R c,d,C1 = 0.185
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
PILE ANALYSIS AND DESIGN 3 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

PASS - Design compressive resistance exceeds design load


Load combination 2: A2 + M1 + R4
Design compression action; Fc,d,C2 = G,unfav,A2  Gc,k,unfav - G,fav,A2  Gc,k,fav + Q,A2  Qc,k
Fc,d,C2 = 270.2 kN
Partial resistance factor, bearing (Table A.NA.7); b,R4 = 2.00
Partial resistance factor, shaft (Table A.NA.7); s,R4 = 1.60
Design compressive resistance; Rc,d,C2 = (Rbk / b,R4 + Rsk / s,R4) / model = 748.7 kN
Fc,d,C2 / R c,d,C2 = 0.361
PASS - Design compressive resistance exceeds design load
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 1 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

FOUNDATION ANALYSIS (EN1997-1:2004)


In accordance with EN1997-1:2004 incorporating Corrigendum dated February 2009 and the UK National Annex
incorporating Corrigendum No.1
TEDDS calculation version 3.2.15

Pad foundation details


Length of foundation; Lx = 5800 mm; Width of foundation; Ly = 5537 mm
Depth of foundation; h = 350 mm; Depth of soil over foundation; hsoil = 500 mm
Level of water; hwater = 300 mm; Density of water; water = 9.8 kN/m3
Density of concrete; conc = 25.0 kN/m3

21.7 kN/m2 20 kN/m2


9 11
7

8 10

6 17 23 29

5 16 22 28

4 15 21 27

3 14 20 26

2 13 19 25

y
1 12 18 24

23 kN/m2 21.3 kN/m2

Column no.1 details


Length of column; lx1 = 200 mm; Width of column; ly1 = 100 mm
position in x-axis; x1 = 920 mm; position in y-axis; y1 = 672 mm
Column no.2 details
Length of column; lx2 = 200 mm; Width of column; ly2 = 100 mm
position in x-axis; x2 = 920 mm; position in y-axis; y2 = 1979 mm
Column no.3 details
Length of column; lx3 = 200 mm; Width of column; ly3 = 100 mm
position in x-axis; x3 = 920 mm; position in y-axis; y3 = 2357 mm
Column no.4 details
Length of column; lx4 = 200 mm; Width of column; ly4 = 100 mm
position in x-axis; x4 = 920 mm; position in y-axis; y4 = 2727 mm
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 2 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column no.5 details


Length of column; lx5 = 200 mm; Width of column; ly5 = 100 mm
position in x-axis; x5 = 920 mm; position in y-axis; y5 = 3056 mm
Column no.6 details
Length of column; lx6 = 200 mm; Width of column; ly6 = 100 mm
position in x-axis; x6 = 920 mm; position in y-axis; y6 = 3428 mm
Column no.7 details
Length of column; lx7 = 200 mm; Width of column; ly7 = 100 mm
position in x-axis; x7 = 200 mm; position in y-axis; y7 = 5347 mm
Column no.8 details
Length of column; lx8 = 200 mm; Width of column; ly8 = 100 mm
position in x-axis; x8 = 1572 mm; position in y-axis; y8 = 4968 mm
Column no.9 details
Length of column; lx9 = 200 mm; Width of column; ly9 = 100 mm
position in x-axis; x9 = 1572 mm; position in y-axis; y9 = 5425 mm
Column no.10 details
Length of column; lx10 = 200 mm; Width of column; ly10 = 100 mm
position in x-axis; x10 = 2080 mm; position in y-axis; y10 = 4968 mm
Column no.11 details
Length of column; lx11 = 200 mm; Width of column; ly11 = 100 mm
position in x-axis; x11 = 2080 mm; position in y-axis; y11 = 5425 mm
Column no.12 details
Length of column; lx12 = 200 mm; Width of column; ly12 = 100 mm
position in x-axis; x12 = 2080 mm; position in y-axis; y12 = 672 mm
Column no.13 details
Length of column; lx13 = 200 mm; Width of column; ly13 = 100 mm
position in x-axis; x13 = 2080 mm; position in y-axis; y13 = 1979 mm
Column no.14 details
Length of column; lx14 = 200 mm; Width of column; ly14 = 100 mm
position in x-axis; x14 = 2080 mm; position in y-axis; y14 = 2357 mm
Column no.15 details
Length of column; lx15 = 200 mm; Width of column; ly15 = 100 mm
position in x-axis; x15 = 2080 mm; position in y-axis; y15 = 2727 mm
Column no.16 details
Length of column; lx16 = 200 mm; Width of column; ly16 = 100 mm
position in x-axis; x16 = 2080 mm; position in y-axis; y16 = 3056 mm
Column no.17 details
Length of column; lx17 = 200 mm; Width of column; ly17 = 100 mm
position in x-axis; x17 = 2080 mm; position in y-axis; y17 = 3428 mm
Column no.18 details
Length of column; lx18 = 200 mm; Width of column; ly18 = 100 mm
position in x-axis; x18 = 3721 mm; position in y-axis; y18 = 672 mm
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 3 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column no.19 details


Length of column; lx19 = 200 mm; Width of column; ly19 = 100 mm
position in x-axis; x19 = 3721 mm; position in y-axis; y19 = 1979 mm
Column no.20 details
Length of column; lx20 = 200 mm; Width of column; ly20 = 100 mm
position in x-axis; x20 = 3721 mm; position in y-axis; y20 = 2357 mm
Column no.21 details
Length of column; lx21 = 200 mm; Width of column; ly21 = 100 mm
position in x-axis; x21 = 3721 mm; position in y-axis; y21 = 2727 mm
Column no.22 details
Length of column; lx22 = 200 mm; Width of column; ly22 = 100 mm
position in x-axis; x22 = 3721 mm; position in y-axis; y22 = 3056 mm
Column no.23 details
Length of column; lx23 = 200 mm; Width of column; ly23 = 100 mm
position in x-axis; x23 = 3721 mm; position in y-axis; y23 = 3428 mm
Column no.24 details
Length of column; lx24 = 200 mm; Width of column; ly24 = 100 mm
position in x-axis; x24 = 4881 mm; position in y-axis; y24 = 672 mm
Column no.25 details
Length of column; lx25 = 200 mm; Width of column; ly25 = 100 mm
position in x-axis; x25 = 4881 mm; position in y-axis; y25 = 1979 mm
Column no.26 details
Length of column; lx26 = 200 mm; Width of column; ly26 = 100 mm
position in x-axis; x26 = 4881 mm; position in y-axis; y26 = 2357 mm
Column no.27 details
Length of column; lx27 = 200 mm; Width of column; ly27 = 100 mm
position in x-axis; x27 = 4881 mm; position in y-axis; y27 = 2727 mm
Column no.28 details
Length of column; lx28 = 200 mm; Width of column; ly28 = 100 mm
position in x-axis; x28 = 4881 mm; position in y-axis; y28 = 3056 mm
Column no.29 details
Length of column; lx29 = 200 mm; Width of column; ly29 = 100 mm
position in x-axis; x29 = 4881 mm; position in y-axis; y29 = 3428 mm
Soil properties
Density of soil; soil = 18.0 kN/m3; Net ultimate bearing pressure; nf = 30 kN/m2
Friction angle; k = 15 deg

Foundation loads
Self weight; Fswt = 5.8 kN/m2; Soil weight; Fsoil = 9.0 kN/m2
Column no.1 loads
Permanent load in z; FGz1 = 0.8 kN; Variable load in z; FQz1 = 7.2 kN
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 4 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column no.2 loads


Permanent load in z; FGz2 = 0.8 kN; Variable load in z; FQz2 = 7.2 kN
Column no.3 loads
Permanent load in z; FGz3 = 0.8 kN; Variable load in z; FQz3 = 7.2 kN
Column no.4 loads
Permanent load in z; FGz4 = 0.8 kN; Variable load in z; FQz4 = 7.2 kN
Column no.5 loads
Permanent load in z; FGz5 = 0.8 kN; Variable load in z; FQz5 = 7.2 kN
Column no.6 loads
Permanent load in z; FGz6 = 0.8 kN; Variable load in z; FQz6 = 7.2 kN
Column no.7 loads
Permanent load in z; FGz7 = 0.8 kN; Variable load in z; FQz7 = 0.3 kN
Column no.8 loads
Permanent load in z; FGz8 = 4.4 kN; Variable load in z; FQz8 = 1.1 kN
Column no.9 loads
Permanent load in z; FGz9 = 4.4 kN; Variable load in z; FQz9 = 1.1 kN
Column no.10 loads
Permanent load in z; FGz10 = 4.4 kN; Variable load in z; FQz10 = 1.1 kN
Column no.11 loads
Permanent load in z; FGz11 = 4.4 kN; Variable load in z; FQz11 = 1.1 kN
Column no.12 loads
Permanent load in z; FGz12 = 0.8 kN; Variable load in z; FQz12 = 7.2 kN
Column no.13 loads
Permanent load in z; FGz13 = 0.8 kN; Variable load in z; FQz13 = 7.2 kN
Column no.14 loads
Permanent load in z; FGz14 = 0.8 kN; Variable load in z; FQz14 = 7.2 kN
Column no.15 loads
Permanent load in z; FGz15 = 0.8 kN; Variable load in z; FQz15 = 7.2 kN
Column no.16 loads
Permanent load in z; FGz16 = 0.8 kN; Variable load in z; FQz16 = 7.2 kN
Column no.17 loads
Permanent load in z; FGz17 = 0.8 kN; Variable load in z; FQz17 = 7.2 kN
Column no.18 loads
Permanent load in z; FGz18 = 0.8 kN; Variable load in z; FQz18 = 7.2 kN
Column no.19 loads
Permanent load in z; FGz19 = 0.8 kN; Variable load in z; FQz19 = 7.2 kN
Column no.20 loads
Permanent load in z; FGz20 = 0.8 kN; Variable load in z; FQz20 = 7.2 kN
Column no.21 loads
Permanent load in z; FGz21 = 0.8 kN; Variable load in z; FQz21 = 7.2 kN
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 5 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column no.22 loads


Permanent load in z; FGz22 = 0.8 kN; Variable load in z; FQz22 = 7.2 kN
Column no.23 loads
Permanent load in z; FGz23 = 0.8 kN; Variable load in z; FQz23 = 7.2 kN
Column no.24 loads
Permanent load in z; FGz24 = 0.8 kN; Variable load in z; FQz24 = 7.2 kN
Column no.25 loads
Permanent load in z; FGz25 = 0.8 kN; Variable load in z; FQz25 = 7.2 kN
Column no.26 loads
Permanent load in z; FGz26 = 0.8 kN; Variable load in z; FQz26 = 7.2 kN
Column no.27 loads
Permanent load in z; FGz27 = 0.8 kN; Variable load in z; FQz27 = 7.2 kN
Column no.28 loads
Permanent load in z; FGz28 = 0.8 kN; Variable load in z; FQz28 = 7.2 kN
Column no.29 loads
Permanent load in z; FGz29 = 0.8 kN; Variable load in z; FQz29 = 7.2 kN
Bearing resistance (Section 6.5.2)
Forces on foundation
Force in z-axis; Fdz = 690.5 kN
Moments on foundation
Moment in x-axis; Mdx = 1976.1 kNm; Moment in y-axis; Mdy = 1891.1 kNm
Eccentricity of base reaction
Eccentricity in x-axis; ex = -38 mm; Eccentricity in y-axis; ey = -30 mm
Eccentricity of base reaction
Eccentricity in x-axis; ex = -38 mm; Eccentricity in y-axis; ey = -30 mm
Pad base pressure
q1 = 23.0 kN/m2; q2= 21.7 kN/m2; q3 = 21.3 kN/m2; q4 = 20.0 kN/m2
2
Minimum base pressure; qmin = 20.0 kN/m ; Maximum base pressure; qmax = 23.0 kN/m2
Presumed bearing capacity
Presumed bearing capacity; Pbearing = 30.0 kN/m2
PASS - Presumed bearing capacity exceeds design base pressure
Design approach 1
Partial factors on actions - Combination1
Partial factor set; A1
Permanent action; G = 1.35; Variable action; Q = 1.50

Partial factors for spread foundations - Combination1


Resistance factor set; R1
Bearing; R.v = 1.00; Sliding; R.h = 1.00

Forces on foundation
Force in z-axis; Fdz = 958.8 kN
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 6 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Moments on foundation
Moment in x-axis; Mdx = 2744.1 kNm; Moment in y-axis; Mdy = 2618.1 kNm
Eccentricity of base reaction
Eccentricity in x-axis; ex = -38 mm; Eccentricity in y-axis; ey = -38 mm
Effective area of base
Effective length; L'x = 5724 mm; Effective width; L'y = 5461 mm
Effective area; A' = 31.260 m2
Pad base pressure
Design base pressure; fdz = 30.7 kN/m2
Design approach 1
Partial factors on actions - Combination2
Partial factor set; A2
Permanent action; G = 1.00; Variable action; Q = 1.30

Partial factors for spread foundations - Combination2


Resistance factor set; R1
Bearing; R.v = 1.00; Sliding; R.h = 1.00

Forces on foundation
Force in z-axis; Fdz = 743.8 kN
Moments on foundation
Moment in x-axis; Mdx = 2128.9 kNm; Moment in y-axis; Mdy = 2021.3 kNm
Eccentricity of base reaction
Eccentricity in x-axis; ex = -38 mm; Eccentricity in y-axis; ey = -51 mm
Effective area of base
Effective length; L'x = 5725 mm; Effective width; L'y = 5435 mm
Effective area; A' = 31.116 m2
Pad base pressure
Design base pressure; fdz = 23.9 kN/m2

FOUNDATION DESIGN (EN1992-1-1:2004)


In accordance with EN1992-1-1:2004 incorporating Corrigendum dated January 2008 and the UK National Annex
incorporating National Amendment No.1
TEDDS calculation version 3.2.15

Concrete details (Table 3.1 - Strength and deformation characteristics for concrete)
Concrete strength class; C20/25; Char.comp.cylinder strength; fck = 20 N/mm2
Partial factor for concrete; C = 1.50; Maximum aggregate size; hagg = 20 mm
2
Design compressive strength; fcd = 11.3 N/mm ; Design tensile strength, plain; fctd,pl = 0.8 N/mm2
Reinforcement details
Characteristic yield strength; fyk = 410 N/mm2; Partial factor for reinforcment; S = 1.15
2
Design yield strength; fyd = 357 N/mm ; Nominal cover; cnom = 50 mm
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 7 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Shear diagram, x axis (kN)


53.8
34.4 37.6
20.5 17.3 26.1
12.2
3.1 1.2
-17.5
-30.6 -33.6
-45.2
-52

Moment diagram, x axis (kNm)


32.5

0.4 4.2 3.5


7.5 10.6
1.2

24.5 20.6
25.5 24.7
35.7

Rectangular section in flexure (Section 6.1)


Design bending moment; MEd.x.max = 32.5 kNm; K = 0.004; K' = 0.207
K' > K - No compression reinforcement is required
Tens.reinforcement required; Asx.bot.req = 2189 mm2
Tens.reinforcement provided; 28 No.12 dia.bars bottom (200 c/c); Asx.bot.prov = 3167 mm2
2
Min.area of reinforcement; As.min = 2189 mm ; Max.area of reinforcement; As.max = 62457 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm; Maximum crack width; wk = 0.025 mm
PASS - Maximum crack width is less than limiting crack width
Rectangular section in shear (Section 6.2)
Design shear force; abs(VEd.x.min) = 30.6 kN; Design shear resistance; VRd.c = 611.1 kN
PASS - Design shear resistance exceeds design shear force
Shear diagram, y axis (kN)
55.0
74.8
42.7 49.5
23.3
8.4 9.5
7.1
-4.9 3.9 -2.1 3.8
-12.3 -5.6
-24.2
-53
-61.4
-79.7
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 8 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Moment diagram, y axis (kNm)


78.7

2.6 -3.2 -1.4 -0.4


10.9 13.3 12 7.9
1 0.3
14.4

60.6 59.1
75.1 79.8 74.9

Rectangular section in flexure (Section 6.1)


Design bending moment; MEd.y.max = 78.7 kNm; K = 0.008; K' = 0.207
K' > K - No compression reinforcement is required
Tens.reinforcement required; Asy.bot.req = 2390 mm2
Tens.reinforcement provided; 29 No.12 dia.bars bottom (200 c/c); Asy.bot.prov = 3280 mm2
Min.area of reinforcement; As.min = 2390 mm2; Max.area of reinforcement; As.max = 68208 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm; Maximum crack width; wk = 0.023 mm
PASS - Maximum crack width is less than limiting crack width
Rectangular section in flexure (Section 6.1)
Design bending moment; abs(MEd.y.min) = 3.2 kNm; K = 0.000; K' = 0.207
K' > K - No compression reinforcement is required
Tens.reinforcement required; Asy.top.req = 2293 mm2
Tens.reinforcement provided; 24 No.12 dia.bars top (250 c/c);Asy.top.prov = 2658 mm2
Min.area of reinforcement; As.min = 2293 mm2; Max.area of reinforcement; As.max = 65424 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm; Maximum crack width; wk = 0.009 mm
PASS - Maximum crack width is less than limiting crack width
Rectangular section in shear (Section 6.2)
Design shear force; abs(VEd.y.min) = 61.4 kN; Design shear resistance; VRd.c = 640.1 kN
PASS - Design shear resistance exceeds design shear force
Punching shear (Section 6.4)
Maximum shear resiastance; vRd.max = 3.128 N/mm2; Punching shear resistance; vRd.c = 0.391 N/mm2
Column No.1 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.1 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 9 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.2 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.2 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.3 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.3 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.4 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.4 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.5 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.5 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 10 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column No.6 - Punching shear perimeter at column face


Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.6 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.7 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 1.3 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.011 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.8 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 7.3 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.064 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.8 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 2.7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.006 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.9 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 7.4 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.064 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.9 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 1430 mm; Area within shear perimeter; A1 = 0.313 m2
Design punching shear force; VEd.1 = 6 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.022 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.9 - Punching shear perimeter at 2d from column face
Punching shear perimeter; u2 = 2334 mm; Area within shear perimeter; A2 = 0.855 m2
Design punching shear force; VEd.2 = 1.6 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.2 = 0.003 N/mm2
PASS - Design punching shear resistance exceeds design punching shear stress
Column No.10 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 11 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Max.punching shear force; VEd.max = 7.3 kN


Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.064 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.10 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 2.7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.006 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.11 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 7.4 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.064 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.11 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 1430 mm; Area within shear perimeter; A1 = 0.313 m2
Design punching shear force; VEd.1 = 6 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.022 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.11 - Punching shear perimeter at 2d from column face
Punching shear perimeter; u2 = 2334 mm; Area within shear perimeter; A2 = 0.855 m2
Design punching shear force; VEd.2 = 1.6 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.2 = 0.003 N/mm2
PASS - Design punching shear resistance exceeds design punching shear stress
Column No.12 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.12 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.13 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.13 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 12 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column No.14 - Punching shear perimeter at column face


Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.14 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.15 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.15 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.16 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.16 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.17 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.17 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.18 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 13 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Max.punching shear force; VEd.max = 11.7 kN


Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.18 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.19 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.19 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.20 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.20 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.21 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.21 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.22 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 14 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Column No.22 - Punching shear perimeter at 1d from column face


Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.23 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.23 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.24 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.24 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.25 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.25 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.26 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.26 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 15 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

Design punching shear force; VEd.1 = 7 kN


Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.27 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.27 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.28 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.28 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.29 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 600 mm; Area within shear perimeter; A0 = 0.020 m2
Max.punching shear force; VEd.max = 11.7 kN
Punching shear stress factor;  = 1.500; Max.punching shear stress; vEd.max = 0.101 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.29 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2410 mm; Area within shear perimeter; A1 = 0.453 m2
Design punching shear force; VEd.1 = 7 kN
Punching shear stress factor;  = 1.500; Design punching shear stress; vEd.1 = 0.015 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Project Job Ref.
AIR SEPARATION NIGERIA LIMITED ENGINEERING, PROCUREMENT, INSTALLATION &
BLOCK C, ACME ROAD, BEHIND FUMMEC Section Sheet no./rev.
FILLING STATION
COMBINED FOOTING FOR AIR COMPRESSORS 16 01
OGBA INDUSTRIAL ESTATE, IKEJA
Calc. by Date Chk'd by Date App'd by Date
LAGOS STATE, NIGERIA
KG 17/08/2019 EOB 17/08/2019

9 11
7

8 10

29 No.12 dia.bars bottom (200 c/c)


6 17 23 29 24 No.12 dia.bars top (250 c/c)

5 16 22 28

4 15 21 27

3 14 20 26

2 13 19 25

1 12 18 24

28 No.12 dia.bars bottom (200 c/c)


23 No.12 dia.bars top (250 c/c)