Manual Secutron
Manual Secutron
P ROGRAMMING
MANUAL
Revision 1
Document #: LT-2001
Table of Contents
1.0 Operation and Programming Concepts ......................................................................... 1
1.1 Introduction ................................................................................................................... 1
1.2 General Information ...................................................................................................... 1
1.3 Networks ....................................................................................................................... 1
1.4 Addressable Devices .................................................................................................... 4
1.5 Resetting 4-Wire Detectors ........................................................................................... 7
2.0 Editing MHI Databases ..................................................................................................... 8
2.1 Introduction ................................................................................................................... 8
2.2 General Comments ....................................................................................................... 8
2.3 System Window ............................................................................................................ 9
2.4 Switches Window .......................................................................................................... 13
2.5 Groups Window ............................................................................................................. 14
2.6 Panel Window ............................................................................................................... 16
2.7 Outputs Dialog .............................................................................................................. 19
2.8 Options Dialog ............................................................................................................... 21
2.9 Circuits and Devices Windows ...................................................................................... 30
2.10 Internal Circuits Window ............................................................................................. 35
2.11 Relate Window ............................................................................................................ 36
3.0 LCD Programming ............................................................................................................ 39
3.1 Introduction ................................................................................................................... 39
3.2 General Comments ....................................................................................................... 39
3.3 Menus ........................................................................................................................... 40
4.0 Appendix A: Condition Codes and Zone Numbers ....................................................... 46
4.1 Introduction ................................................................................................................... 46
4.2 List of Codes and Zone Numbers ................................................................................. 46
5.0 Appendix B: Stand-by Battery Calculation .................................................................... 52
6.0 Appendix C: Service Terminal ........................................................................................ 53
6.1 General ......................................................................................................................... 53
6.2 Control Unit ................................................................................................................... 53
7.0 Appendix D: Table of Reporting Codes ......................................................................... 60
i
MR-2100/2200 Programming Manual
List of Figures
Figure 1: Typical Network Layout ........................................................................................ 1
Figure 2: Single Network Break .......................................................................................... 3
Figure 3: Panel Removed from Network ............................................................................. 4
Figure 4: Four Wire Device Wiring (Typical) ....................................................................... 7
Figure 5: Modul-R System Window ..................................................................................... 9
Figure 6: Switches Window ................................................................................................. 13
Figure 7: Groups Window ................................................................................................... 14
Figure 8: Panel Window ...................................................................................................... 16
Figure 11: Panel Outputs .................................................................................................... 19
Figure 12: Options Dialog ................................................................................................... 21
Figure 13: Default Key Assignments ................................................................................... 23
Figure 14: Dialer Settings .................................................................................................... 25
Figure 14: Dialer Configuration 1 ........................................................................................ 26
Figure 15: Dialer Configuration 2 ........................................................................................ 27
Figure 16: Call Directions .................................................................................................... 28
Figure 17: Zone Data .......................................................................................................... 29
Figure 18: Dialer Maintenance and Common Reporting Codes ......................................... 29
Figure 19: Circuits Window ................................................................................................. 30
Figure 20: Devices Window ................................................................................................ 30
Figure 22: Copy Window ..................................................................................................... 34
Figure 23: Internal Circuits Window .................................................................................... 35
Figure 24: Relate Window ................................................................................................... 36
Figure 25: Program Menu ................................................................................................... 39
Figure 26: Selector Screen ................................................................................................. 40
List of Tables
Table 1: Automatic Contact ID/SIA Reporting Codes ......................................................... 60
Table 2: Contact ID Zone Alarm/Restore Event Codes ...................................................... 61
Table 3: SIA Format Automatic Zone Alarm/Restore Codes .............................................. 61
iii
MR-2100/2200 Programming Manual
Downloadable Database
The panel uses a downloaded database for input circuit programming. This database includes the
addressable devices on-line, and the Zone LEDs, Bells, Functions Relays and Control Modules
activated by addressable devices. This database is created and downloaded from an IBM
compatible computer using the Modul-R Human Interface (MHI) program. Refer to the Modul-R
Human Interface User Guide for instructions on downloading the database.
Note: All communications are stopped during the database load. This causes a trouble to be recorded by those
units that are normally communicating with the panel.
1.3 Networks
General
The MR-2200 can be incorporated into a network including other MR-2900 panels and MR-2944
annunciators. Though up to 254 panels and annunciators can be supported by the network, such a
network would probably be too large to properly maintain. The network can be setup for single
building or multiple building operation.
MR-2200 MR-2900 MR-2944
ID #1 ID #2 ID #3
Com2 Com1 Com2 Com1 Com2 Com1
MR-2200 MR-2944
ID #5 ID #4
Com1 Com2 Com1 Com2
1
MR-2100/2200 Programming Manual
The basic layout of the network is a single loop (see Figure 1). Each panel and annunciator has a
unique ID. There is no requirement that the IDs be sequential or that they start with 1. The master
panel can be any fire panel in the network. The panels work in a peer-to-peer fashion. This means
that each panel is responsible for the programming of the inputs connected to it. The master panel
does not control the network, but it is the central location for network information. Information is
exchanged over the network via two basic means: a) specific frames, which are from one panel to
another, and b) broadcast frames, which are from one panel to all others.
Note: 1. For correct operation of the network, all panels and annunciators need to be loaded with the
same version of operating programs and with the same database. If changes are made to the
database, it is necessary that ALL panels and annunciators be reloaded.
2.When panels and annunciators are first installed, the panel ID must be entered into it before
loading the database.
Feature Operation
The following are the various types of frames that are sent on the network.
Commands & Restores
These specific frames are sent when a device in alarm requires operation of outputs at another
unit. These commands are for the bells, relays, control modules, device messages and LEDs.
When the device itself restores, the restore commands are sent right away so that the other panels
know that they can be reset. Anything operated stays latched until the Reset key is pressed.
Hotkey and Hotkey LED Operation
If Hotkey routing is on a panel, it will send Ack, Reset, Sig Sil and Second Stage Inhibit to the other
panels as specific frames.
If a panel’s function keys are sent to other panels, those panels will send commands to the panel
to have it turn on and off the hot key LEDs. This is so that there is indication that the key function
has become available. This will cause the LEDs to continue flashing after the key is pressed until
the frame is received to turn off the LED.
Time/Date Change
This broadcast frame is sent by a panel or annunciator if the time or date is changed. The master
panel also sends both a date and time change frame at 3:30am every day to synchronize all the
clocks in the network.
Manual Switch Operation
If the state of any of the 16 software switches is changed manually at any panel, this change is
broadcast to all other panels. The software switches are a system resource.
Network Reboot
If a Network Reboot command is initiated at a panel, it is broadcast normally and then the panel
reboots itself. Upon receiving the Network Reboot command, a panel passes the command on to
the next panel and then reboots itself. This has the affect of causing all the panels to reboot
simultaneously.
2
MR-2100/2200 Programming Manual
Network Verify
Network Verify is the process by which the master panel queries the rest of the network to
determine on-line status. Each panel will respond to the network verify request. The user can also
request a Network Verify at any time from any panel in the network.
Network Communications
Information is sent across the network in frames. In addition to the operator generated frames
described above, alarm, supervisory, and trouble frames are sent across the network
whenever a device or panel indicates a problem. There are two types of frames: specific and
broadcast. Specific frames are sent from one unit to another. Broadcast frames are sent from one
unit to all others.
Specific Frames
Specific frames deal with information generated at one panel and required at another. This type of
frame is passed from panel to panel until it reaches its destination. Each panel has a list as to
which port to send frames from to reach all other panels through the fewest number of panels.
Since networks generally have all communications links running at the same baud rate, this is
generally the shortest time as well.
If there is a break in the communications (see Figure 2), the panel that cannot pass the message
on sends it back the way it came. This causes the frame to go the long way around the network. If
there are two breaks in the network loop, the frame is again reversed at the second break. When
the originating panel receives it after the second turn around, the originating panel realizes there is
a major fault in the network and considers the frame to be orphaned and destroys it. This
generates a Network Reboot Required trouble. This is passed on to all other panels (or at least as
many as can be reached). The reason the orphan frame is destroyed is to prevent unexpected
operation when the network is finally repaired, such as a panel starts ringing its bells because of
an alarm from the previous day.
M R 2 9 4 4
M R 2 2 0 0 M R 2 9 0 0 ID # 3
ID # 1 ID # 2
C O M 2 C O M 1 C O M 2 C O M 1 C O M 2 C O M 1
M R 2 2 0 0 M R 2 9 4 4
ID # 5 ID # 4
C O M 1 C O M 2 C O M 1 C O M 2
3
MR-2100/2200 Programming Manual
Broadcast Frames
Broadcast frames deal with information that affects the entire network. When a broadcast frame is
created by a panel or annunciator, it is sent out both network communications ports. Each unit in
turn receives the broadcast in one port, act upon it and pass it on out the other port. Upon reaching
the unit that generated the broadcast frame, that unit then disposes of it. This means that under
normal circumstances, all units receive a broadcast twice and act upon it twice.
If there is break in a communications link (see Figure 2) the broadcast is disposed of by the unit
unable to pass it on. In the situation where a unit has been removed from the loop (see Figure 3),
the broadcast is passed only from com2 to com1 at the jump. In Figure 3, panel 5 passes the
broadcast to panel 3, but panel 3 will not pass the broadcast on to panel 5 since it is supposed to
be communicating to panel 4.
M R 2944
M R 2200 M R 2900 ID # 3
ID # 1 ID # 2
C O M 2 C O M 1 C O M 2 C O M 1 C O M 2 C O M 1
M R 2200 M R 2944
ID # 5 ID # 4
C O M 1 C O M 2 C O M 1 C O M 2
4
MR-2100/2200 Programming Manual
The MRI-M500S control module can be used to control a supervised output, such as a bell or
strobe circuit. The control module monitors the circuit wiring and troubles will be reported. The
module will require a separate 24 VDC supply for the controlled circuit. When programming the
database in MHI, be sure to program the control module correctly. Choose any “Control (str)” other
than “Control (relay)” for the MRI-M500S module. The MR-2400 will not operate a control module
if the supervised circuit is shorted. Also there are options in MHI that affect the MRI-M500S control
module but not the MRI-M500R relay module.
The MRI-M500R relay provides two Form C relays. Choose “Control (relay)” for the MRI-M500R
module. There are options in MHI that affect the MRI-M500R relay module that do not affect the
MRI-M500S control module.
The MRI-M500X isolator module is used to prevent wiring faults from affecting the entire circuit. It
divides the addressable circuit into sections. The isolator has separate IN and OUT wiring. A short
on one side of the isolator is not seen on or affects the other side. Isolator modules do not use
addresses. The isolator relies on a voltage threshold to determine whether it should be isolating or
not. This voltage threshold is around 6.5V. All isolators in a system are in isolated mode on system
power up. If there is an excess of current draw, the isolator will not close. When the short is
removed, the isolator module automatically closes the circuit again. The LED on the isolator
module turns on when the module is in isolated mode, otherwise it flashes periodically. System
Sensor recommends no more than 25 devices between isolator modules since the inrush current
of the devices may mimic a short condition preventing the isolator from closing.
The sensors all use bases for mounting. Besides the standard plain bases, there are also relay
bases, isolator bases and a sounder base. The available bases are:
5
MR-2100/2200 Programming Manual
The sensor LED activates the relay and sounder bases. When this LED stays on for more than 10
seconds, the base activates. This requires that the MR-2200 have the LED mode set to FLASH/
ON. This is done through the LCD Menu by choosing PROGRAM/ADDRESSABLE/LED MODE/
FLASH. The MR-2200 only turns on the LEDs of up to 5 devices per addressable circuit to prevent
excess current flow. While the panel continues to respond to further alarms from the circuit, the
panel does not turn on additional LEDs. The MRI-B501BH sounder base requires a separate 24
VDC supply for operation. If the polarity of this supply is reversed for more than 10 seconds, the
sounder base activates.
Isolator bases function the same as isolator modules. The sensor plugged into the base is
connected to the IN wiring to the base. The isolator is between the sensor and the OUT wiring.
While both sensors and modules have rotary dials that allow for addresses from 00 to 99, modules
add 100 internally to the address programmed, thus using the address range 100 to 199. Since
sensors and modules come from the factory addressed as 00, we do not allow that address to be
used for an installed device. Address 0 is used for indication of wiring faults on the addressable
circuit.
Device Faults
The following troubles (with condition code letter) can be reported by or for addressable devices:
• Missing (M): A device listed in the database is not reporting back when polled by the
panel. For a new installation, this is generally indicative of devices that have been mis-
addressed. This error can also occur if there are any wiring faults.
• Illegal (I): A device is reporting in on an address that the database shows as unused. For
a new installation, this is generally indicative of devices that have been mis-addressed.
For illegal sensors, since there is no programming available, if an alarm condition is
detected, the MR-2200 operates all its bell circuits. In a network system, only the local
panel activates its bells. The MR-2200 always ignores illegal modules.
• Wrong Type (U): This occurs if the device is not the type expected for the address. For
example, the database lists an address to have a ion smoke detector, but a photo smoke
detector has reported for the address. This error is also used if the panel cannot determine
the type of the device. If the device goes into alarm, the panel operates normally.
• Trouble (T): Sensors: The device is defective and needs to be replaced.
Modules: The extended circuit from the module has a wiring fault. Note: Control modules
that supervise their output circuits are not operated if the output circuit is shorted.
• Duplicate (D): This means that two devices are using the same address. The MR-2200
does a check every hour for duplicate devices. If either device goes into alarm, the panel
operates normally. Note: Due to the method used to detect duplicate devices, it is possible
for a single device to appear as duplicate devices. Generally, the device needs to be
replaced.
6
MR-2100/2200 Programming Manual
To Monitor Module
Input
-
AUX
+
- -
AUX
+ 4 Wire Device
COM +
RLY 4 NC
NO
COM
RLY 3 NC
NO
COM
RLY 2 NC
NO
COM
RLY 1 NC
NO
7
MR-2100/2200 Programming Manual
Note: When upgrading from a version 17 (or earlier) system, a number of items that were programmed
at the panel are now included in the database. See the file UPGRADE.TXT for a complete
description of these changes.
Follow these instructions to obtain the required information before upgrading your firmware:
1.Connect your computer to the panel and open the Terminal window
2.Select the Printer screen in the Terminal: press 14<Tab>
3.You should note that the title bar of the Terminal window displays the text "File logging in
progress...". If this does not appear, press the button Log On.
4.In the terminal window, type the following command: 99?
5.The panel's configuration settings will be listed in the Terminal window and it will also be
saved in the file: LOG_CONT.TXT, located in your program directory
6.Close the Terminal window
7.You may now view the contents of the file using any standard word processor or text editor
You must perform the above procedure for ALL panels in your system
8
MR-2100/2200 Programming Manual
9
MR-2100/2200 Programming Manual
The text in the top left corner provides information about the database. The top line gives the date
and time the database was last edited. The next line states whether the current contents have
been verified or not; and whether the database has been compressed or not.
The options Bell System, Subsequent Alarm, Resound, Evac and Waterflow all affect how the
notification appliance circuits (NAC), hereafter referred to as bells, react to alarm conditions.
Bell System
Bell System is a drop down list for selecting how the bells and strobes will operate. This sets the
base operation for the entire network. If coded bells are required, the bell codes are defined for
each input individually. The following options are available:
• Alert: A First Stage alarm activates the selected bells in Alert mode. If the Signal Silence
or Second Stage Inhibit Hot Key is not pressed before the [No Acknowledge] Second
Stage Inhibit timeout, the panel will progress to Second Stage. Second stage will activate
all bells in Evacuation mode.
• Evac: A First Stage alarm will activate selected bells in Evacuation mode. Second Stage
will activate all bells in Evacuation mode. There is no timeout from First to Second Stage.
• Alert/Evac: A First Stage alarm activates the selected bells in Evacuation mode and all
other bells on the panel in Alert mode. If the Signal Silence or Second Stage Inhibit Hot
Key is not pressed before the [No Acknowledge] Second Stage Inhibit timeout, the system
will progress to Second Stage. Second Stage will activate all bells in Evacuation mode.
• Staged: The 1st alarm will activate selected bells in Alert mode. If the Signal Silence or
Second Stage Inhibit Hot Key is not pressed before the [No Acknowledge] Second Stage
Inhibit timeout, the selected bells are switched to Evacuation mode and the next bells, i.e.
the ones with the next higher number, are activated in Alert mode. This sequence is
repeated until all bells are in Evacuation mode. When the highest numbered bell circuit
switches to Evacuation mode, all bell and strobe circuits on the panel will be turned on in
Evacuation mode. For example, if the alarm activates Bells 1 and 4, after the NAK timeout,
Bells 1 and 4 are switched to Evacuation mode and Bells 2 and 5 are set to Alert mode. A
2nd alarm will activate all bells in Evacuation mode.
Note: 1.Bells must be assigned consecutive bells circuits with no Releasers assigned in
between Bells. For example: circuits 1, 2, 3, 4 can be assigned as Bells but not
circuits 1, 2, 4, 5 with circuit 3 a Releaser.
2.Control modules cannot be programmed as bell or strobe if the Staged Bell
system is used.
Subsequent Alarm
Subsequent Alarm controls how Alert, Evac and Alert/Evac type bell systems behave when a new
alarm is received while one is still active. 1st Stage has the panel repeat the First Stage operation.
2nd Stage has the panel go immediately to Second Stage operation.
Resound
Resound controls how the panel handles the automatic resounding of silence bells when a new
alarm is received. There are two modes:
• Local: Each panel resounds only its own silenced bells when a new alarm is received.
This would be used when panels in a network are in different buildings, such as a campus.
• Global: All panels in a network resound silenced bells when a new alarm condition is
received on any panel in the network. This is used when the panels are all in the same
building, such as a large plant.
10
MR-2100/2200 Programming Manual
Evac
Evac controls whether the bell system Evacuation Mode sounds Steady (continuously) or uses a
Temporal pattern as specified in ANSI S3.41 and ISO 8201 Audible Emergency Evacuation Signal.
The pattern used ½s On, ½s Off, ½s On, ½s Off, ½s On, 1½s Off repeated.
Waterflow
Waterflow controls if bells can be silenced if they are started by a waterflow type input. If Non-
Silenceable is chosen, bell circuits activated due to a waterflow input cannot be silenced until the
waterflow device has restored.
Language
Language chooses English (default), French or Hungarian characters to be used in messages.
Disconnects
Disconnects controls which panels the Signal Disconnect, Relay Disconnect, Releaser Disconnect
and Common Disconnect hot keys affect.
• Local: The Disconnect hot keys affect only the panel they are on.
• Global: The Disconnect hot keys affect all the panels in the network. This means that if
any Disconnect key is pressed on a panel, all other panels in the system take on the state
of that Disconnect, either on or off.
System Message
The System Message is a text entry box for defining a message that is 3 lines by 20 characters
that is used to identify the system. This message is printed at the top of printouts and shown on
some service terminal screens, but it is not used in any LCD except in STATUS/IDENTIFICATION.
System Banner
The System Banner is a 20 character message that is used as a banner for the Main Menu of the
LCD. The default banner is “Modul-R by Secutron”.
Pre-Alarm Buzzer
The Pre-Alarm Buzzer, when enabled, will cause a tone to sound when a smoke detector is
verifying its alarm. The tone is a triple beep repeated every second.
11
MR-2100/2200 Programming Manual
Master ID
Master ID defines which panel in a network acts as the Master panel. Only control panels may be
chosen as the Master panel. The Master panel retains an alarm list for the entire network and
synchronizes the date and time on all panels and annunciators at 3:30am everyday. (The alarm list
functionality is programmable for several modes of operation. See below for more detail.)
Common Relays
Common Relays controls what signals affect the common alarm, common supervisory and
common trouble relays of each panel. The are two settings:
• Local: The common relays of a panel follow the events of events on that panel only.
• follow Alarm List Mode: The common relays of a panel react to both events of the panel
and any events listed in its Alarm List.
Non-Latch Mode controls if the panel will auto store. The options are as follows
• More: Everything Latched
• Trouble only: Only trouble conditions will auto restore; Note some troubles require user
intervention before the panel can determine if the condition be restored
• Supv and Trbl: Supervisory and Trouble conditions will automatically restore.
Pushbuttons
The System Window has the following push buttons on the right hand side:
• Exit: Closes the System Window and, if editing, causes the database to be saved. After
an edit session, a requester asks if the database should be Verified. A database has to
verify without errors before it can be downloaded.
• Panels: Displays the Panel Window. If no panel is currently defined, the Add Panel Box is
displayed.
• Switches: Displays the Switches Window. This window determines which devices are
attached to the switches and the timers associated to each switch. See section 2.4
Switches Window.
• Groups: Displays the Groups Window. This window is used to define groups of relates.
See section 2.5 Groups Window.
• Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
• Verify List: Displays the Verify List. If there is no Verify List, a requester will appear asking
whether you wish to perform a verification. See section 2.6.5 of the Modul-R Human
Interface User Guide for a full description of the Verify List and its uses.
• Settings: Defines the Verify warnings to disable and/or errors to reduce to warnings for
the current database. Not all warnings/errors can be disabled/reduced. The use of this is
not recommended, but provided for special circumstances.
12
MR-2100/2200 Programming Manual
The title bar of the window always lists the currently highlighted switch.
Switches Table
The Switches Table shows all 16 possible switches and highlights the current one. Select any one
to make it the current switch. List entries show the message RELATES FOUND for switches that
have related devices.
HH:MM (Timer)
The HH:MM (Timer) entries control the times that the switch changes state. An even number of
times must be entered, ie. each on must have a corresponding off. All times are entered using 24
hour notation, e.g.: one minute after midnight=0:01, noon=12:00, 3 PM=15:00, 4 AM=4:00, etc. A
time of 0:00 is considered as not used. If an action at midnight is desired set the time to 0:01, one
minute after midnight; or 23:59, a minute before midnight. MHI sorts the times into ascending order
after the Switches Window is closed.
Start Mode - On
The Start Mode - On check box determines if the first time listed should turn the switch On or Off. If
it is not checked, the first time turns the switch off. If it is checked, the first time turns the switch on.
The on and off indication beside each time entry changes to reflect what each time in the sorted
list does.
13
MR-2100/2200 Programming Manual
14
MR-2100/2200 Programming Manual
The use of Groups greatly simplifies the changes made to a database as changes are needed by
the system. For example, if new door is installed that has to be unlocked during a fire alarm, the
control module that unlocks the door is simply added to a Group. This single change is then
automatically picked up by any inputs that are related to the Group. Since this number could be
hundreds, the use of the Groups makes databases easier to maintain and decreases the likelihood
of mistakes when items are added.
Note: Though any relationship can be selected for inclusion into a group, an input that references the group must
be able to accommodate the group’s relates. It may be advantageous to separate groups in these cases.
Group List
The Group List shows all the defined groups along with their message (if any) and if there are any
relates defined for the group. The current group is highlighted. Use the <Backspace> key in order
to quickly re-position the current selection to another group.
Message Description
The Message/Description is used to enter a message for the group. This set of text-boxes allows
you to enter a message describing the Group. You are allowed space for 3 lines by 20 characters.
If desired, this message may be adopted by a circuit or device by checking the Use Grp Msg
check-box and specifying this Group ID. This is a powerful feature if you are defining a large
number of inputs that require the same message.
Pushbuttons
The following push buttons are defined:
• Exit: Close the Groups Window and return to the previous window.
• Add Group: This defines a new group ID. The new group can have any number between
1 and 250. By default, the number is the next one available. There is no need for the
groups to be sequentially numbered or to start at 1.
• Delete Group: This removes the group from the list. You are asked if you want to have
references to the group automatically removed.
• Reset Group: This removes all relates for the currently highlighted group.
• Change ID: This allows the group ID to be changed. This may need to be done if two
databases are being merged together. MHI automatically changes all references to use
the new ID. A gauge is displayed to show the progress of the change.
• Relate: Shows the Relate Window. Items marked *on* are operated by inputs related to
the group. When relating inputs to groups, be sure that all relates defined by the group are
allowable for the input.
• Copy Relates: Copies the relates and/or message from an input point to the current
group. The values of the panel, circuit and device are required. Most conventional circuits
use a device number of 0 (zero). Press Copy to copy the information.
• Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
• Verify List: Displays the Verify List. If there is no Verify List, a requester will appear asking
whether you wish to perform a verification. See section 2.6.5 of the Modul-R Human
Interface User Guide for a full description of the Verify List and its uses.
15
MR-2100/2200 Programming Manual
Note: Changing the panel type can have far reaching effects on a system. Any information that is no
longer valid with the new panel type will be lost
16
MR-2100/2200 Programming Manual
• Change ID: Displays a dialog box for changing the ID of the current panel. MHI will
automatically change all references to use the new ID. This process could take a long time
for a large database. A gauge will be displayed to show the progress of the change.
• Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
• Verify List: Displays the Verify List. If there is no Verify List, you will be given the option to
perform a verification. See section 2.6.5 of the Modul-R Human Interface User Guide.
The Panel List is located in the top left corner of the window. It lists all the panels, both Control and
Annunciator, that are defined in the system. The highlighted entry in the List is the one that is
currently being edited. Its description is also shown in the title bar of the Panel Window. If a
different panel is selected, all the controls in the window will change to reflect this. Use the
<Backspace> key in order to quickly re-position the current selection to another panel.
The Message is located below the Panel List. This is a 3 line by 20 character message that is
associated with the Panel. This message will be displayed in Alarm Lists with signals that are
generated by this panel. It will also be included in any print-outs generated by the Master Panel of
the system. This message should include enough information that it will identify the panel and its
location to fire or service personnel.
The Outputs area lists the function of the outputs of the panel. Use the Outputs Button to show the
Outputs Dialog (see the Outputs Dialog section) which allows for the programming of the Outputs
and the relays.
The Options button displays the Options Dialog (see the Options Dialog section). This allows for
the programming of the various panel options, such as Hot Keys, bell timers, etc.
The Next ID is located to the left of the push buttons at the top of the Panel Window. It is not
displayed for single panel systems. It is used to define the ID of the next panel in the network loop.
Specify the panel ID of the panel to be connected to the COM 1 terminals of the current panel. See
Links for notes on programming systems that contain single-port MR-2934 or MR-2944
Annunciators.
Links is used to enter the IDs of single port annunciators that are connected to COM 1 of the
MR-2100 panel. These annunciators do not reside in the network loop, but are branches off of it.
Port 3 sets the purpose of the Port 3 general communications port. If the operating program
loaded does not support the selected setting, a wrong port 3 program trouble will be generated by
the panel. The options are:
• none: Port 3 is not used.
• PC Connect: Sets Port 3 to use the GRID program interface.
• Voice Evac. System: Sets Port 3 to communicate with the MV-2700 voice evacuation
panel.
Local Ann. LED Cnt sets the number of LED zones available either on the front of the panel using
the MRDL modules and/or and MR-2614 annunciators connected to the panel.
17
MR-2100/2200 Programming Manual
The IDs Supervised button displays all possible IDs of the MR-
2614 and MR-2644 annunciators (see Figure 9) as well as the
MR-2801B-MR and MRDL. Check the IDs that will be connected
to the system. When the MRDL is enabled, a button will appear
next to that option called Dialer Settings (see the section on
Dialer Options for a description of the dialer options).
Hot Key Routing is a set of radio buttons for setting the other
panels or annunciators to be controlled by the current panel. To
have no other panels affected by the current panel, mark Local.
To have the current panel affect all other panels on the network,
mark Global. To choose only some panels, mark Custom. A text
entry box entitled route panel ids is then displayed. Enter the
panel IDs to be controlled separated by commas, e.g. “2, 3, 4".
Each ID listed will receive Hot Key commands from the current Figure 9: IDs Supervised
panel whenever its Hot Keys are pressed.
Annunciators have the
following unique controls
for programming (see
Figure 10).
The LCD check box is
located immediately left of
the buttons. It indicates
whether or not the
annunciator has an alpha-
numeric LCD. This setting
is used by MHI only to
determine if the Message
Receive check box should
be shown for the
annunciator in the Relate
Window. This value is not
sent to the annunciator.
LED Count is located
directly below the LCD
Figure 10: Annunciator Panel Window
check box. This defines the
number of LED zones the
annunciator will be using. A count of zero will disable the Hot LEDs and Common LED.
Hot LED is located directly below the LED Count drop down. This value defines the first of four
LED zones the annunciator will use for internal functions. Any of the zones can be chosen with the
requirement that there are four consecutive zones available. Entering a zone of 0 will disable the
hot key zones. These will reflect the current status of the annunciator and the panel(s) it sends
commands to.
18
MR-2100/2200 Programming Manual
Note: The Power On LED refers to the 24 VDC to the annunciator, not to any AC source.
Message Receive is a group of a radio buttons for setting which panels this annunciator will display
messages for. If all panels are chosen, every message in the system is displayed. If custom is selected,
then all messages from the listed panels will be displayed.
Common LED is located directly below the Hot LED setting. This is the LED zone the annunciator will use
for common alarm, supervisory and trouble indication. It is a summation of the zone LEDs of the
annunciator. Any LED zone may be used. The zone chosen will not be available for general annunciation.
Entering a zone of 0 will disable the common zone.
Ports is located below the Common LED setting. It is not displayed for MR-2914 Annunciators. This option
enables (double) or disables (single) the COM 1 network port. If both ports are enabled, the Next ID text
box will become available (see above for a description of Next ID).
19
MR-2100/2200 Programming Manual
Outputs
The Outputs section is a list box that is used to select the output to program. Once the output is
selected, it is programmable for the following output types:
• Bell: This is a standard signalling circuit. It does not sound codes.
• Strobe: This signalling circuit for use with strobes. Strobe circuits cannot be silenced until
the system is reset.
• Coded Bell: This signalling circuit sounds out the code for any input that operates it and
then silences.
• Auxiliary Power (AuxPwr): This turns on the Output continuously to supply power for
auxiliary devices, such as annunciators. If a Duration time is given for the Auxiliary Power
circuit, the circuit is powered off for that number of seconds (from 1 to 30) when the panel
Reset key is pressed with neither of its LEDs flashing. This allows for the reset of 4 wire
detectors. A duration time of 0 prevents this operation. Auxiliary Power circuits are turned
off by the panel while it is in its power up cycle.
• Follow Supervisory (follow Supv): The output sounds when there is any supervisory
condition present on the panel. Pressing Acknowledge silences the circuit.
• Follow Trouble (follow Trbl): The output sounds when there is any trouble condition
present on the panel. Pressing Acknowledge silences the circuit.
• Follow Supervisory and Trouble (follow Supv and Trbl): This output will sound when
there is a supervisory condition and/or a trouble condition on the panel. Pressing
Acknowledge will silence the circuit.
Relay Delay
Relay Delay is the times that the relay waits before activating. A delay of 0 causes instant
operation. This can be from 0 to 60 seconds.
Relay Duration
Relay Duration affects the time the relay is activated. For relays operated from inputs, it is the
minimum time the relay operates. The relay must stay on for this length of time before it can be
reset. This is for equipment that must remain off a length of time before it can be started up again.
If no input operates the relay, it is available for the reset of 4 wire devices. If the duration is not 0
(zero), then the relay activates for the duration time when the Reset hot key is pressed with neither
of its LEDs flashing. The duration can be from 0 to 300 seconds (5 minutes).
20
MR-2100/2200 Programming Manual
Buzzer Mode
Buzzer Mode sets when the panel buzzer sounds. Normal causes the buzzer to sound for new
supervisory and trouble conditions. All causes the buzzer to sound for all new conditions.
Note: Always set this option to All (default) to meet current codes.
Bypass Priv
Bypass Priv. sets the privilege level required to set circuit and device bypasses, and manual
control of relays, control modules and switches. This privilege can be set to Level 2 (default) or
Level 1.
Disconnect
Disconnect sets the privilege level required for the Disconnect and Test Mode Hot Keys. These
can be set to Level 1 (default) or Level 0. If Level 0 is chosen, the Disconnect Hot Keys can be
operated without a passcode being entered into the panel.
Banner Mode
Banner Mode dictates what the top line of the Main Menu of the LCD is. There are four modes of
operation:
• Status Ind.: This mode displays the lines SYSTEM NORMAL and SYSTEM OFF
NORMAL.
• Panel Ban.: This mode displays the 20 characters of text entered into the text box that
appears below the drop down while this mode is selected.
• System Ban.: This mode displays the text defined by the System Banner.
• Equip. Desc.: This mode allows the panel to display its own identification text.
21
MR-2100/2200 Programming Manual
Remote AC Fail
The Remote AC Fail is the delay before the panel will report that it has lost AC power to a remote
monitoring location. The panel will report AC Fail locally after 60s. The panel itself will go into AC
Fail mode to conserve power immediately upon losing AC. This delay is the length of time before
the panel generates the trouble condition. This can be set from 0 to 1800 minutes (30 hours). If a
time of 0 minutes is entered, the panel will use a 10 second delay.
Fan Delay
Fan Delay sets the number of scans between the reset of each Control Module (relay) on an
addressable circuit. This is to allow for the staggered restart of fans when the system is reset. This
option can be enabled or disabled on each addressable circuit as required. It has no affect on
Control Modules (supervising).
Bell Cutoff
Bell Cutoff is the length of time the bells sound before they are automatically silenced by the panel.
A time of 0 disables this feature. The cutoff can be set from 5 to 30 minutes.
Maintenance Margin
Maintenance Margin sets the gap between the maintenance threshold and the alarm threshold for
addressable sensors. If the sensor stays between these two values for the Maintenance Retard
time, the panel reports a Maintenance Alert trouble for the sensor. The margin can be set from 0 to
500, with 0 giving no warning and 500 giving the earliest warning.
Maintenance Retard
Maintenance Retard is the number of consecutive scans the addressable sensor has to stay
between the maintenance and alarm thresholds to generate the Maintenance Alert trouble. This
retard can be from 5 to 50 scans. Scan time can vary from 2.5 to 5 seconds with usual values from
3.5 to 4 seconds.
22
MR-2100/2200 Programming Manual
Hot Keys
Hot Keys are a set of drop down boxes that allow you to set the functions of the operator keys on
the front of the panel. There are 8 keys, each with yellow and green LED. The LEDs are used to
display function status.
SYSTEM CONTROLS
Acknowledge
Signal Silence
System Reset
User Assigned
Key Action
Acknowledge Silences the buzzer and acknowledges new troubles and alarms. If the buzzer is on,
Acknowledge will silence it. If the buzzer is not on, any flashing LEDs will become
steady. The green LED will flash when there is something to acknowledge.
Signal Silence Silences the bells. The green LED will flash when Signal Silence is available. There
may be a silence inhibit before the bells can be silenced if they are activated by an
Alarm condition. The yellow LED flashes when the bells have been silenced. The bells
will reactivate if a subsequent Alarm is received by the panel.
23
MR-2100/2200 Programming Manual
Key Action
Second Stage Prevents the automatic operation of second stage operation. This applies only to
Inhibit panels with ALERT or STAGED type bell systems. For ALERT systems, pressing the
Second Stage Inhibit will prevent the panel from going into second stage. For STAGED
systems, it will prevent the system from going to the next stage. Second Stage Inhibit
has no effect on an EVAC type bell system. The green LED will flash when Second
Stage Inhibit is available, and the yellow LED will flash when it has been activated.
Fire Drill Activates all the bell circuits, both regular and coded, in Alert mode. Press a second
time to have all bell circuits sound in Evacuation mode. Press a third time to end the
Fire Drill. The yellow LED will flash while the Fire Drill is happening. The Fire Drill
cannot be performed if the bells are already activated, or if AC power is off. The Fire
Drill is automatically ended if an alarm condition occurs.
Releaser Causes the releaser circuits to ignore any new alarms. The buzzer beeps every 2
Disconnect seconds while the releasers are disabled. This beeping is suppressed while a
privileged level is entered in the panel. Press again to restore normal operation. The
yellow LED will flash while active. If no releasers can be disconnected, Releaser
Disconnect will do nothing. This function can be set to Privilege Level 0 or 1.
Relay Causes the function relays and control modules to ignore any new alarms. Press again
Disconnect to restore normal operation. The yellow LED will flash while active. If no relays nor
control modules can be disconnected, Relay Disconnect will do nothing. This function
can be set to Privilege Level 0 or 1.
Test Mode Places panel into test mode. Press again to return to normal mode. The yellow LED
will flash while in test mode. This function can be set to Privilege Level 0 or 1. It follows
the Disconnect privilege level (set in MHI). During test mode, the remote annunciator
zone LEDs becomes non-latching for the zone(s) under test. The common indicators,
bells, relays and releasers are not activated and no commands are sent to other units
and no signal is sent out of Port 3. Test signals can be archived or not as required.
Before beginning testing, the circuits/devices to be tested must be selected. All
unselected circuits/devices will operate normally. Be sure that the panel is in test
mode. To select circuits/devices, select PROGRAM from the Main Menu on the LCD.
The arrow keys move the cursor and the <Enter> key selects the item. Then select
ADDRESSABLE, then TEST. Enter the device circuit and address for each device to
be tested. <Clear> will return to the previous menu.
When test mode is ended, all zones and devices selected for testing automatically
return to normal operation.
Note: There is no Ground Fault isolation while Test Mode is active.
Signal Disables sounding of the bells. The buzzer beeps every 2 seconds while the bells are
Disconnect disabled. This beeping is suppressed while a privileged level is entered in the panel.
Press Signal Disconnect again to re-enable the bells. The yellow LED will flash while
the bells are disabled. Signal Disconnect is not available if the bells are already
activated. This function can be set to Privilege Level 0 or 1.
Common Disables the municipal relays from functioning. Press again to enable relays. The
Disconnect yellow LED flashes while the relays are disabled. The municipal relays affected are
programmable. If no relays are selected for disabling, Common Disconnect is
unavailable. This function can be set to Privilege Level 0 or 1.
24
MR-2100/2200 Programming Manual
Key Action
General Initiates the general evacuation sequence. All bells are activated in Evacuation mode,
Alarm selected function relays are activated and selected releaser circuits are activated and
municipal alarm relay is activated. The yellow LED will flash when activated. Press
System Reset to cancel the General Alarm. Note: General Alarm is recorded in the
panel archive.
Halt Stops the operation of all releaser type outputs on the panel. The green LED flashes
when the key is available and the yellow LED flashes when it has been pressed.
Switch n On Change the state of the software switch n between Auto and On. The yellow LED will
flash while the switch is forced On. The green LED will flash whenever the switch is
on, either automatically or forced. Switches can affect relays, control modules and
LEDs. This function can be set to Privilege Level 1 or 2.
Switch n Off Change the state of the software switch n between Auto and Off. The yellow LED will
flash while the switch is forced Off. The green LED will flash whenever the switch is off,
either automatically or forced. Switches can affect relays, control modules and LEDs.
This function can be set to Privilege Level 1 or 2.
Manual This will cause the programmed control modules to reset after the system has been
Restart reset in general. This is an MEA (New York City) requirement.
Dialer Settings
The Dialer Settings dialog (see Figure 13) allows
for the programming of various communications
options.
The 1st, 2nd and 3rd Telephone Numbers can be up
to 32 digits. Special digits may be used to perform
the following functions:
• HEX (B)-simulates the [*] key
• HEX (C)-simulates the [#] key
• HEX (D)-forces the panel to search for dial
tone; must be first digit of telephone
number
• HEX (E)-forces the panel to pause for 2
seconds
• HEX (F)-end of telephone number marker
Figure 14: Dialer Settings
The first number is the primary number, the
second number is for a second monitoring station, and the third number is the backup number for
the first number.
The 1st and 2nd Account Codes identify the system to the central station when a communication is
sent. The code can be programmed for up to four digits. The first and third telephone number
transmit the first account code. The second telephone number transmits the second account code.
The 1st and 2nd # Format setting affects the type of communication that the dialer sends to the
central station. There are seven formats available including Contact ID, SIA and a pager format.
25
MR-2100/2200 Programming Manual
The Dialer Settings window has the following push buttons along the right side:
• Exit: Close the Dialer Settings window and return to the IDs window.
• Configuration 1: Display the Dialer Configuration 1 dialog.
• Configuration 2: Display the Dialer Configuration 2 dialog.
• Call Directions: Display the Call Directions dialog.
• Zone Data: Display the Zone Data dialog.
• Maintenance/Common: Display the Dialer Maintenance and Common Reporting Codes
dialog.
Dialer Configuration 1
The Dialer Configuration 1
dialog (see Figure 14)
contains the First
Communicator Options,
Second Communicator
Options and International
Options.
The Communications option
determines if the dialer will
communicate to the central
station. When Enabled is
selected, the dialer will
communicate all events as
programmed. When Figure 14: Dialer Configuration 1
Disabled is selected, the
dialer will not communicate any events.
The TLM One/Two Check options determine whether the dialer will test for telephone line faults on
line one and line two respectively.
The Third Phone # can be programmed for two different modes of operation. When Alternate
Dialing Enabled is selected, the dialer switches between the first and third telephone numbers
after each dialing attempt, until the maximum number of dialing attempts have been made to each
number. When Third Number Backup is enabled, the dialer will use the third telephone number
only if all attempts to communicate to the first telephone number fail. If all attempts to
communicate to the third number also fail, a failure to communicate trouble will be generated.
When Disabled is selected, the third telephone number is not used.
The Dialing option has three different options for pulse or DTMF dialing. If All attempts Pulse is
selected, the dialer will always use pulse (rotary) dialing. If All attempts DTMF Dialing is selected,
the dialer will always use DTMF dialing. If 4 attempts DTMF then Pulse is selected, the dialer will
use DTMF dialing for the first four attempts. If unsuccessful, the dialer will switch to pulse (rotary)
dialing for the remaining attempts.
The SIA Rep. Codes option determines whether the dialer will send the automatic reporting codes
that are in the dialer, or use the reporting codes that are programmed in the Zone Data and
Maintenance/Common reporting codes sections. See See “7.0 Appendix D: Table of Reporting
Codes” on page 60 for a list of the automatic SIA Reporting Codes.
The SIA Max Events option sets the maximum number of events the dialer will send for one SIA
transmission. When 20 per Round is selected, SIA sends a maximum of 20 events per round.
When 8 per Round is selected, SIA sends maximum of 8 events per round.
The Contact ID Rep. Codes option determines whether the dialer will send the automatic reporting
codes that are in the dialer, or use the reporting codes that are programmed in the Zone Data and
26
MR-2100/2200 Programming Manual
Maintenance/Common reporting codes sections. See See “7.0 Appendix D: Table of Reporting
Codes” on page 60 for a list of the automatic Contact ID Reporting Codes.
The Test Transmission Line option determines how the dialer chooses a telephone line to send the
automatic test transmission. If Alternate is selected, the dialer will alternate between using
Telephone Lines 1 and 2 for transmissions, regardless of telephone line troubles. If Available is
selected, the dialer will use Telephone Line 1 for transmissions. If a trouble exists on Telephone
Line 1, the dialer will switch to Line 2.
When the Force Dialing option is set to enabled, if the first attempt by the panel to call the
monitoring station fails, on every subsequent attempt the panel will dial regardless of the presence
of dial tone. When Disabled is selected, the panel will not dial the programmed telephone number
if dial tone is not present.
When the Busy Tone Detection option is enabled, if busy tone is detected, the dialer will disengage
the phone line and try to place the call again following the delay between dialing attempts. When
Disabled is selected, the dialer will use the standard dialing procedure for every attempt.
The Pulse Make/Break Ratio option is for panels in international applications. When 40/60 is
selected, the pulse dialing make/break ratio is the 40/60. When 33/67 is selected, the pulse dialing
make/break ratio is 33/67.
The Handshake option determines the handshake used for BPS transmissions. When 1600 Hz is
selected, the dialer responds to a 1600 Hz handshake. When Standard is selected, the dialer
responds to the handshake designated by the format selected (1400 or 2300 Hz).
The ID Tone can be set to 1300Hz or 2100 Hz. The panel will emit a tone at the selected frequency
for 500 ms every 2 seconds when it places a call to indicate that it is a digital equipment call, not
voice. When Disabled is selected, this feature will not be used.
Dialer Configuration 2
The Dialer Configuration
2 screen (see Figure 15)
contains the Swinger
Shutdown Variables, Test
Transmission options and
Other Options.
The Swinger Shutdown
options determine the
maximum number of
zone events and trouble
events that the dialer will
transmit in one day. The
trouble or alarm will still
be displayed on the panel
and logged in the archive,
but the dialer will not
transmit the event. There Figure 15: Dialer Configuration 2
are individual counters for
Zone Alarm and Restore, Zone Supervisory and Restore, Zone Trouble and Restore and
Maintenance Trouble and Restore. This feature will be reset at midnight. To disable the feature,
program 000.
The Test Transmission Time of Day determines when the automatic test transmission will occur.
The entry is four digits (HH:MM). To disable the feature, program the time as [9999].
27
MR-2100/2200 Programming Manual
The Test Transmission Cycle determines the number of days between test transmissions. This is
automatically set so that tests are performed daily and may not be varied.
Note: If an upgraded database has a value other than 1, choose Set Default to reset the value.
The TLM Trouble Delay controls the number of telephone line monitoring checks required before a
telephone line trouble is generated. The dialer checks the telephone connection at 10-second
intervals.
The Maximum Dialing Attempts to Each Phone Number is the number of attempts that the dialer
will make to each telephone number before generating a fail to communicate trouble.
Post Dial Wait for Handshake is the amount of time the dialer will wait for a valid initial handshake
from the receiver after dialing the programmed telephone number.
Call Directions
The Call Directions dialog (see
Figure 16) contains the options that
determine which telephone
numbers will be used to
communicate events.
There are five different types of
events that can each be sent to
telephone number one or telephone
number two. The event types are
Fire Zone Alarm/Restore,
Supervisory Zone Alarm/Restore,
Zone Trouble/Restore, Maintenance Figure 16: Call Directions
Trouble/Restore and Test
Transmissions.
Note: UL Listing requires that the Test Transmission be sent to both telephone numbers
Zone Data
The Zone Data dialog (see Figure 17) contains zone definitions and reporting codes that the dialer
will use to communicate events.
28
MR-2100/2200 Programming Manual
29
MR-2100/2200 Programming Manual
Circuit List
The Circuit List is located in the top left corner of the window. It is shown on the Circuits Window
only. This lists any defined circuits for the current panel. Each circuit shows the circuit number,
type of circuit and function if applicable. The highlighted circuit is described in the title bar of the
30
MR-2100/2200 Programming Manual
Circuits Window. Unused circuits are shown using three dashes. Use the <Backspace> key in
order to quickly re-position the current selection to another circuit. The <Up> and <Down> Arrow
keys change the current circuit. The <Right> and <Left> Arrow keys change the type of the
current circuit. The <Plus> and <Minus> keys change the function of the current circuit.
Note: Both devices listed for Dual end-of-line and Smoke Detector + N/O Contact circuits must be defined.
31
MR-2100/2200 Programming Manual
• Control (Strobe): This programs the MRI-M500S as a signalling circuit for use with
strobes. They are non-silenceable and will be turned on continuously for both Alert and
Evacuation mode operation. Strobe circuits cannot be silenced until the system is reset
(unless the strobe duration is programmed – see Strobe Duration in section 2.5.2).
• Control (C-Releaser): This programs the MRI-M500S as a continuous releaser which
remains on until an alarm is received on a zone activating the releaser. The releaser is
then turned off after the Delay until the panel is reset. The Delay can be from 0 to 180
seconds.
• Control (M-Releaser): This programs the MRI-M500S as a momentary releaser which is
inactive until an alarm is received on a zone activating the releaser. The releaser is then
not activated until after the Delay time. The releaser is turned off after the Duration time, or
the activating zone and panel are reset. Momentary releasers function normally during an
AC power fail. The Delay can be from 0 to 180 seconds and the Duration can be up to
1800 seconds. 1800 seconds is 30 minutes. A Duration of zero (0) will cause the releaser
to stay on until it is reset.
Message
The Message is located in the middle of the top of the window. This 3 line by 20 character text
message is displayed or printed for all signals originating from the current input point. Circuit types
that use devices have a default message created for them when defined. This message can be
changed.
32
MR-2100/2200 Programming Manual
33
MR-2100/2200 Programming Manual
Pushbuttons
The push buttons located on the right hand side are:
• Exit: Closes the window and returns to the previous window.
• Devices: Opens the Devices Window for the current circuit (Circuits Window only).
• Copy: Copies the circuit/device information, relates and message from another input to
the current input (see Figure 21). The current input does not have to be defined. Relates
cannot be copied between conventional and addressable input points. The Panel ID,
Circuit ID and Device ID (not always shown) list the circuit/device to be copied from.
Marking Transfer Main Definition copies the listed circuit/device type and function to the
current circuit/device. Note: Not all inputs can be copied to all other possible inputs.
Marking Transfer Relates copies the relates from the listed circuit/device relates to the
current one. This may cause some invalid relates. Marking Transfer Message causes the
message to be copied. Marking Transfer Devices (if shown) copies any device definitions
that the listed circuit contains. These devices copy messages and relates as based on
those settings above. There is no checking made at this time as to the validity of the
values copied. Unexpected results can occur if care is not taken. For each database
that is created, a warning about using copy is shown. Marking the check box in the
warning stops the box from appearing again for the database. This option can help speed
up the creation of a database. By completely defining one input, these values can be
copied to all other inputs, making any minor changes that are required after the copy.
34
MR-2100/2200 Programming Manual
35
MR-2100/2200 Programming Manual
Pushbuttons
The following push buttons are available:
• List Entries: This new feature allows the user to control the information displayed.
Relevant only lists items applicable to the current version only. All lists all possible items
so that relates made on previous versions may be removed.
• Exit: Closes the Internal Circuits Window and returns to the Panel Window.
• Reset: Clears all relates associated with the current internal circuit.
• Relate: Opens the Relate Window for the internal circuit. This allows for the programming
of outputs, LEDs, relays and control modules to be operated by the internal circuit.
• Copy Relates: Copies the relates from another input to the current internal circuit (see
Figure 21). The values of the panel and circuit are required. Press Copy to copy the
information. If the function type of the two circuits is different, a requester is presented to
confirm the copy.
• Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
• Verify List: Displays the Verify List. If there is no Verify List, a requester will appear asking
whether you wish to perform a verification. See section 2.6.5 of the Modul-R Human
Interface User Guide for a full description of the Verify List and its uses.
36
MR-2100/2200 Programming Manual
Groups
Groups is a comma separated list of all the groups that the point is to use for relates. Up to ten
groups can be listed. These groups are assigned to the point itself and does not change as the
current output panel changes. Relates that are part of the groups are not shown in the Relate
Window but can be shown on the Map Window if so desired.
Panel List
The Panel List is a list-box located in the top left corner of the window. It lists all the panels, both
Control and Annunciator, that are defined in the system along with their panel message. The high-
lighted entry in the list is the one that is being related to by the current input. When a different
panel is selected, all the controls in the window change to reflect this. Use the <Backspace> key
in order to quickly re-position the current selection to another panel.
Outputs List
The Outputs List shows the programmable outputs of the panel. It is not shown for annunciators. It
lists all outputs, along with their definition and current state. The states are *on* for selected, blank
for not selected, act if they activated by default, and n/a for not available. A blank definition is for
unused outputs. Bell and Strobe outputs can only be selected for Fire Alarm type inputs. If
Complex Releasers are enabled, releasers can have three other states: Fast which operates the
releaser immediately regardless of any delay that is programmed in; *A* or *B* which allow for
AND logic. The releaser will not operate until both an A and a B input have been activated. Use the
<space> key or double click on the entry to cycle between available selections. Use the
<Backspace> key in order to quickly reposition the current selection to another output.
Relays List
The Relays List shows the general purpose function relays of the panel. It is not shown for
annunciators. Each is listed by number and state. The states are *on* for selected, n/a for not
available, and blank for not selected. Use the <space> key or double click on the entry to cycle
between available selections. Use the <Backspace> key in order to quickly re-position the current
selection to another relay.
LEDs List
The LEDs List shows the LED zones available on the panel or annunciator. This is not shown if the
panel has no LEDs. Each is listed by number and state. The states are *on* for selected, blank for
not selected and n/a for not available. Use the <space> key or double click on the entry to cycle
between available selections. Use the <Backspace> key in order to quickly re-position the current
selection to another LED. The actual number of LED zones varies depending upon the panel or
annunciator.
Device List
The Device List shows the addressable devices that can be related to the current point. For
system inputs and groups, it is displayed only if there are any control modules defined for the
panel; for switches, it is displayed if there are any addressable detectors or control modules
defined. Each entry shows the devices’s address (panel.circuit.device), its state and its device
message. The states are *on* for selected and blank for not selected. Devices that are not
available are not shown. Use the <space> key or double click on the entry to cycle between
available selections.
Evac
THe EVAC checkbox is an option for fire alarm type inputs only. Checking this option will cause all
bells and strobes to operate in second stage (evacuation) mode.
37
MR-2100/2200 Programming Manual
Pushbuttons
The push buttons, located on the right side of the window, are:
• Exit: Closes the Relate Window and returns to the previous window.
• Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
• Verify List: Displays the Verify List. If there is no Verify List, a requester will appear asking
whether you wish to perform a verification. See the Modul-R Human Interface User Guide
for a full description of the Verify List and its uses.
• View Groups: Displays the Groups Window. This is for reviewing the defined groups. No
editing can be done to the groups. To edit the groups, return to the System Window.
38
MR-2100/2200 Programming Manual
Note: The only item that must be programmed from the LCD menu is the Panel ID. This must be
done before the database is downloaded.
There are multiple levels of program access. Privilege Level 0 is the base level of operation.
Privilege Level 1 allows access to privileged Hot Key functions and limited programming. Privilege
Level 2 allows programming of almost all system parameters. (Note that a Service Mode Trouble
occurs when logged in Level 2.) Higher Privilege Levels are reserved for Secutron's own use and
are not discussed here. Certain functions can be assigned to different privilege levels. These
functions default to the higher of the two privilege levels.
While programming through the LCD menu, the panel beeps once when a valid key is pressed and
beep three times if an invalid key is pressed. Programming is done through a series of menus and
requester screens. The menus present options to display other menus, show information, or
request information. Menus have a ">" or "<" next to the description of each item. Use the arrow
keys on the keypad to move the cursor and press <Enter> to select. In Figure 24, pressing
<Enter> brings up the Program Menu.
39
MR-2100/2200 Programming Manual
Options A S T
Selections * - * OK<
3.3 Menus
Clock Menu
This menu has the following options:
• Date: View or change the date. The date is entered in MM.DD.YY format. Each section of
the date must be separated by a dot. Press <Enter> to accept date typed. <Clear>
removes any digits typed. If no digits are displayed, <Clear> returns you to the Clock
Menu. The new date is sent to all other panels on the Network, if used. All panels assume
this date. The date change is recorded in the Archive.
• Time: Change the time. The time is entered in HH.MM.SS format. Each section of the
time must be separated by a dot. All times are in 24 hour format. Press <Enter> to accept
time typed. <Clear> removes any digits typed. If no digits are displayed, <Clear>
returns you to the Clock Menu. The new time is sent to all other panels on the Network, if
used. All panels assume this time. If <Enter> is pressed with no time entered, the current
time is sent to all panels on the network. If a change of greater than 5 minutes occurs, the
new time is recorded in the archive.
Note: 1. The Master Panel in a network synchronizes all clocks in the network at 03:30 every day,
sending both date and time.
2. Changing the time while the panel is calibrating aborts the calibration.
• Calibrate: Calibrates the clock so that it keeps correct time. Calibration takes 2 to 45
days. Waiting longer gives more accurate results. The panel functions normally while
calibrating. When sufficient time has passed, re-selecting this function asks for the correct
time. The calibration is then be reported. In a network, only the master panel needs to
calibrated.
Note: Changing the time using the Time option aborts the calibration. If a panel is currently in a
calibration, it ignores time changes sent over the network.
40
MR-2100/2200 Programming Manual
Switches Menu
This function can be set to Privilege Level 1 or 2. View or change the status of any switches.
These switches can be set to On, Off or Auto. The Auto state only applies to switches that have a
timer associated with them. The Auto state allows the switch to follow the timer settings. Any
changes made are broadcast to the network so that all panels have the same state. Settings are
retained by the panel if it is re-booted and the Master Unit broadcasts its settings to the network
upon start up. See Switches Window for information on programming what the switch affects.
The menu has the following options:
• Individual: View or change the status of an individual switch. Each switch is shown in
turn. If a switch has no timer, the Auto option is not shown.
• All Off: Force switches into the Off mode. The number displayed is the number of timers
that are switched On. This option is shown only if no switches have timers associated with
them.
• All Auto: Force all switches with timers to Auto mode. All switches with timers go into the
state dictated by the time. The number displayed is the number of switches with timers
forced On or Off. This option has no effect on switches without timers. This option is not
shown if no timers are associated with the switches.
Battery
Displays the current battery status. The display shows:
Line 1: Screen Title
Line 2: AC State (diagnostic use only)
Line 3: Current State of the Battery and Menu Option (see below)
Line 4: Menu Options (listed below)
The menu has the following options:
• OK: Return to Program Menu.
• Test: Force an immediate battery test.
• Calibrate: This function is restricted to Privilege Level 2. This calibrates the Battery
Charger. The batteries must be disconnected before beginning calibration. No keypad
control is provided during calibration. The calibration display will return when calibration is
over. Calibration only needs to be done when the configuration is erased. All Battery
Chargers come calibrated from the factory.
Addressable
The menu has the following options:
• Reset Max/Min: Clears the stored values for the maximum and minimum values returned
by the addressable devices. These values are automatically cleared when the panel
reboots.
• Duplicates Check: This causes an immediate check to see if more than one device is
using an address. The panel automatically does this check on the hour.
• LED Mode: This controls how the LEDs on the devices are used. There are three options:
-- OFF/FLASH: The device LEDs are normally off and flash when an alarm is reported.
The flashing LED is reset when System Reset is pressed.
-- FLASH/ON: The device LEDs flash each time they are polled. They latch on in Alarm.
The LEDs are reset when System Reset is pressed. Note: Due to current draw
limitations, only the first 5 detectors on a circuit latch their LEDs. This has no effect on
other panel operation.
-- OFF/ON: The LEDs are normally off and latch on in Alarm. The LEDs are reset when
System Reset is pressed. Note: Due to current draw limitations, only the first 5
detectors on a circuit latch their LEDs. This has no effect on other panel operation.
41
MR-2100/2200 Programming Manual
42
MR-2100/2200 Programming Manual
-- SELECT: Change the Auto/On/Off state of control modules. The first screen asks for a
circuit and device number. Enter the circuit and device or press <Enter> without
entering any number to view the first control module in the database. Each control
module is displayed in turn, showing the current state and allowing for it to be changed
or the next control module to be displayed. Press <Clear> to stop viewing the control
module list.
-- ALL AUTO: Change any control modules that are forced on or off back to automatic
mode.
Archive
This function is restricted to Privilege Level 2. View and change the settings for the recording of
optional entries into the history. The following items can be included or not included in the history:
• Test: View or change whether Test signals should be recorded in the history. The current
setting is shown in the upper right corner. Test signals are marked as such.
• Non-Reporting: View or change whether non-reporting signals are recorded in the history
or not. Non-reporting signals are recorded by default.
• Network: View or change the type of archive events that the panel will record in the
archive. This is only available on the network master panel. The options are:
-- LOCAL: Record only panel events in the archive.
-- GLOBAL: Record all events in the archive.
Relays
This function can be set to Privilege Level 1 or 2. If Privilege Level 1 is set and Level 2 is required,
access to the menu is denied. This function allows for the manual operation of the relays. There
are three possible states: Automatic (state determined by inputs), Forced On, or Forced Off. This
mode is retained if the panel is re-booted.
• SELECT: Change the Auto/On/Off state of relay. Each relay is shown in turn, showing the
current state and allowing for it to be changed or the next relay to be displayed. Press
<Clear> to stop viewing the relay list.
• ALL AUTO: Change any relays that are forced on or off back to automatic mode.
Ports
This menu has the following options:
• Network: Allows for the setting of parameters related to the network. If the downloaded
database indicates that there is no network, the only option is Panel ID. The Network
Menu has the following options:
-- Panel ID: This function is restricted to Privilege Level 2. Set the Network ID number.
This is between 1 and 254.
-- Reboot: Cause all panels on the network to do a Hard reboot, ie equivalent to pressing
the Hard Reboot button on the top of the main board. Each panel records in the history
the time it received the Network Reboot command.
-- Global Commands: Sends the selected key (acknowledge, signal silence, or system
reset) to all Control panels and annunciators on the Network. Each unit, including the
sending unit, responds as if that key has been pressed.
-- Retry: Set the number of times to try to resend a message before giving up. If this
number of retries are attempted without success, the other panel or annunciator is
considered to be off-line. The default value is 8.
-- Baud: Set the communications baud rate for Com Port 1. This value may need to be
changed if the default rate (4800) does not allow for communications. Since each
installation is different, this value needs to be chosen by trial and error. If the default rate
43
MR-2100/2200 Programming Manual
does not work, chose the next slower rate. Continue this process until a rate that works
is chosen. The available baud rates are: 9600, 4800, 2400, 1200, 600 and 300. The
recommended rates are: 4800, 2400, and 1200. Below is a table documenting the
maximum wire capacitance allowed on a single port connection.
9600 100 nF
4800 220 nF
2400 470 nF
1200 680 nF
• Port 3: These options are restricted to Privilege 2. The options available vary depending upon
the Port 3 setting in the database. This port can only be disabled from the database.
PC Connect (MR2-8G Program): Allows for the configuration of the communications to a
GRID package. If more than one signal needs to be sent, new alarms take precedence.
-- Baud: Set the communications baud rate. The available fixed baud rates are 9600,
4800, 2400, 1200, 600 and 300.
-- Delay: Sets the length of time the panel will wait before reporting the GRID package off-
line. This can be set from 10 to 255 seconds.
-- Disconnect: If enabled, the Common Disconnect hot key will shut down Port 3. The
GRID package will report the panel as offline.
Voice Evac.System (MR2-8E Program): Allows for setting parameters related to the
connection to the MV2700 voice evacuation panel.
-- Mode: Selects how information is sent to the MV2700. There are the following options:
DEVICE (default): Send the device address or internal circuit number without
translation.
ZONE: Send the LED number turned on for input circuits and devices and send the
internal circuit for internal circuits.
GROUP: Send the associated Group ID(s) for all conditions. Anything not associated
with a specific group sends a group number of 0.
-- Retry: Set the number of times to try to resend a message before giving up. If this
number of retries are attempted without success, the other panel is considered to be
off-line. The default value is 8. This would be increased only if the communications line
cycles between on-line and off-line. (Range: 1 to 25)
-- Disconnect: If enabled, the Common Disconnect hot key shuts down Port 3.
-- Baud: Set the communications baud rate. The available fixed baud rates are 9600,
4800, 2400, 1200, 600 and 300.
• Terminal: Select ANSI or TeleVideo protocol. Most terminals and terminal emulator
programs support ANSI protocol.
• Port 6: Allows for the setting of the baud rate to MR-2614 and MR-2644 annunciators, the
city tie modules, and the MRDL dialer. The settings are 4800 and 1200. If none of these
devices are programmed in the database, the message “nothing to program” is shown.
44
MR-2100/2200 Programming Manual
Alarm List
This menu controls the operation of the Alarm List. This function is restricted to Privilege Level 2. It
has the following options:
• Reset: Select when entries are taken out of the Alarm List. AUTO removes entries as
soon as the condition restores. MANUAL requires that Reset be pressed before they are
removed. Conditions that have restored are shown as a restored condition in the Alarm
List.
• Remote: Routes the messages for events from the panel to annunciators. The options
are:
-- ALL: All messages are sent to all annunciators.
-- SELECT: Messages are sent as directed in the database.
Passcode
Allows for the changing of passcodes. The Privilege Level 2 can change both the Level 1 and 2
passcodes, while Level 1 can only change the Level 1 passcode. Passcodes are four digit
numbers in the range 1000 to 9999. Type in the new passcode and press <Enter> to accept.
Asterisks are displayed instead of the numbers. <Clear> removes any digits typed. If no digits are
displayed, <Clear> returns to the Program or Passcode Menu.
The default Level 2 passcode is 2222. The default Level 1 passcode is 1111. These passcodes
should be changed to prevent unauthorized access.
There is a special Level 2 passcode that is variable from day to day. It can be obtained from
Secutron if the Level 2 passcode is forgotten.
Memory
This function is restricted to Privilege Level 2. This menu has the following options:
• Erase Configuration: This erases all initiating circuit, bell, relay, and privilege values
entered from the keypad and LCD menu, and replace them with default values. With MR2
programs, this has no effect on information contained in the downloaded database.
Confirmation is asked before erasure. After the Configuration has been erased, the panel
must be reset using the reset button at the top of the Main Circuit Board, if the panel does
not do this automatically. The following items are not erased: Serial Number, Clock
Calibration, Level 1 Passcode, Level 2 Passcode, Main Board Type, Input Circuit
Modules.
45
MR-2100/2200 Programming Manual
A ALARM Alarm
C com Comlink
J Switch
N nofire Non-Fire
S spv Supervisory
X warn Pre-Alert
A plus sign (+) refers to a new or on condition, a minus sign (-) refers to a restoral or off condition,
and an equal sign (=) refers to a one time event.
46
MR-2100/2200 Programming Manual
Zone Number
PPP:ZZ.SSS Format:
PPP Control Panel Number
ZZ Panel Zone
Panel Panel
Description Description
Zone Zone
70 Battery Charger
Notes:
1. These zones do not restore.
2. Privilege Level 0 generates a restore signal; all others generate a trouble signal.
3. This zone does not restore and is not repeated sequentially in the archive.
4. Programs dated before March 4, 1996 use a different numbering sequence. Panels
updated erase the archive the first time the new program runs.
47
MR-2100/2200 Programming Manual
001 - Watchdog
48
MR-2100/2200 Programming Manual
007 - Acknowledge
009 - Reset
016 - Switch 1 On
017 - Switch 2 On
018 - Switch 3 On
49
MR-2100/2200 Programming Manual
021 - Switch 6 On
022 - Switch 7 On
023 - Switch 8 On
024 - Switch 9 On
025 - Switch 10 On
026 - Switch 11 On
027 - Switch 12 On
028 - Switch 13 On
029 - Switch 14 On
030 - Switch 15 On
031 - Switch 16 On
50
MR-2100/2200 Programming Manual
Network Reboot Required Who Unit ID of panel generating the Network Reboot
(Zone 94): Required trouble
51
MR-2100/2200 Programming Manual
52
MR-2100/2200 Programming Manual
1 LCD Display and control the panel LCD. This is useful for training
sessions since more people can view the terminal screen than
can view the LCD directly. All keypad keys are mapped to the
equivalent key board key, with the keypad <Clear> being
mapped to the key board <End>. Note: The control feature does
not work over a network.
2 Misc A list of the program version, boards installed in the system and
other information not listed elsewhere.
3 Battery Displays the current battery level, and the current status of the
battery and AC power. Also shows the timer for the battery test.
Commands
<Ctrl-B> Print battery calculation
0<Ctrl-B> Execute a dynamic battery test once and end
continuous testing if on.
9900<Ctrl-B> Start continuous dynamic battery testing.
4 AC Display the current status of the AC power and the delay timer for
report AC fail.
53
MR-2100/2200 Programming Manual
5* Bells Displays the current status of the bell circuits. Also shows the
timers and settings for the cut-off. See screen 11 for acceptable
supervision values.
6 Function Relays Displays the current settings and timers for the 4 function relays.
7 Releasers Displays the current settings and timers for the releasing circuits
(if any).
8 Common Relays Displays the current status of the 3 common system relays. Also
shows which relays may be disconnected by the Common
Disconnect hot-key.
9* Alarm List Shows the current alarm list. This is the same list that is
displayed on the LCD menu. Each screen in the LCD
corresponds to one line on the terminal screen. See Appendix A
for a description of the condition codes and zone numbers.
Commands
J Page down
0 J Go to the end of the list
K Page up
0 K Go to the beginning of the list
10* Miscellaneous Display a list of all the troubles currently displayed by the
Troubles STATUS/MISC. TROUBLES selection from the LCD.
11* Output Displays the current status of each of the outputs and the aux
Supervision power outputs. An asterisk is shown for each output that is
assigned, if it is turned on (if applicable) and the current
supervision condition. The aux power outputs show a scaled
number that should be about 225. An output with a power fault
has had the 24VDC power connection to the MRNC2 board
disconnected.
12 Relay Summary Displays the installed expansion modules and which relays have
been operated. The first section shows which modules have
been installed in the panel. Module 0 is the main board itself. The
second section shows how many of each of the MRNC2 (UA228)
and MRRL4 (UA229) modules are needed and installed. The
bottom section shows all the relays in the system, which ones are
on and the function of each. Note that a common trouble relay is
turned on when the panel has no troubles; the minus sign is a
reminder of this.
13* Archive Displays the Archive History List. This is the list of the last 900
(approximate) events that happened. See Appendix A for a
description of the condition codes and zone numbers.
Commands
J Page down
0 J Go to the end of the list
K Page up
0 K Go to the beginning of the list
54
MR-2100/2200 Programming Manual
17 Port 1 Displays information about the primary network port. Includes the
status of the panels that are and should be online.
Commands
0 V Clear counters on screen
19 Port 3 Shows the current status ID, frame count and baud rate for the
central station communications link. A question mark will appear
in front of the baud rate when the port is offline.
Commands
0 V Clear counters on screen
27 Misc. Outputs Displays the status of follow trouble, follow supervisory and aux
power output types.
29 System Reset Displays a list of resettable items. These are the items that are
reset when System Reset is pressed.
38 Switches Show the current on/off status of each switch and list the timer
associated with each one.
49 Clock Shows the status of the Daylight Savings Time option & clock
calibration.
55
MR-2100/2200 Programming Manual
51* FIFO This screen is restricted to Privilege Level 1 and above. Displays
the FIFO memory usage of various system tasks. This diagnostic
screen needs to be consulted if the panel has a Memory
Overflow trouble. The first line shows the total FIFO space and
the largest amount any one task has used. For each task, the first
number is the current usage and the second is the maximum
usage. If a task uses a large amount of FIFO memory, this means
that task is having difficulty in operating.
61 Local Displays the states of the optional LED zones on the front panel.
Annunciator
68* Remote Displays the service terminal screens for another panel in the
Terminal network. This allows for the trouble shooting of a system from a
single location. This screen automatically disconnects the remote
connection if memory gets low or if no communication is received
for 15 seconds. The remote panel stops sending data after 15
minutes.
Commands
(id) N Display the service terminal for Panel id
<Esc> Disconnect remote connection
69* Network Verify Displays the current status of the network verify feature.
80* Totals Displays totals for both SLCs, including items such as assigned,
on-line, missing, etc. Also lists the total number of devices in
alarm, supervisory or trouble conditions. Also lists current wiring
supervision status for each loop.
81* Detail For a single device, shows all the programming, analog values,
status and commands sent.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
82 Type On-Line For a single circuit, shows a grid displaying all the devices that
are actually on the circuit.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
56
MR-2100/2200 Programming Manual
83 Type Assigned For a single circuit, shows a grid displaying all the devices that
are programmed to be on the circuit.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
84* Errors For a single circuit, shows a grid displaying all the incorrect,
missing and mismatched devices. This shows the differences
between what is expected to be on the circuit and what actually is
on the circuit.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
85 Alarms For a single circuit, shows a grid displaying the current Alarm,
Early Warning, Supervisory and Trouble conditions for all devices
on the circuit.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
86 Function For a single circuit, shows a grid displaying the Alarm and
Supervisory initiating devices. Control modules are neither type
and are displayed as a dash (-).
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
57
MR-2100/2200 Programming Manual
88 Control Modules For a single circuit, shows a grid displaying the current status of
all the Control modules.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
89 Bypass & Test Displays the Bypass and Test status of all devices on an
addressable circuit.
Commands
A Display next device
(address)A Display selected device at address
0M Reset Minimum/Maximum Values
0P Energize both sets of terminals
1P Energize only B terminals
2P Energize only A terminals
Command Description
58
MR-2100/2200 Programming Manual
Command Description
A Silence buzzer.
(month).(date).(year) D Enter the date and year. The year may be entered as 00
to 99 in a two-digit format, or as 1991 to 2090 in a four-
digit format.
90 ? Print archive.
99 ? Print configuration.
59
MR-2100/2200 Programming Manual
Contact
SIA Auto
Dialer ID Auto
Reporting Code Code sent when... Rep.
Direction* Rep.
Codes
Codes
Zone Supv./Rest. zone goes into supervisory/ restore (2) S/R AA See Table 4
Zone Alarms/ zone goes into alarm/ alarm condition A/R (1) 3A See Table 4
Rest. has been restored
Zone Trouble/ zone exhibits a trouble condition/ zone T/R (3) 73 See Table 4
Rest. trouble condition has been restored
60
MR-2100/2200 Programming Manual
Contact
SIA Auto
Dialer ID Auto
Reporting Code Code sent when... Rep.
Direction* Rep.
Codes
Codes
Walk Test Start/ control panel has entered/exited walk MA/R (6) A7 TS-000/
Stop test mode; no TE-000
events will be communicated
61
© 2007 Secutron, Inc.
Canada U.S.A
25 Interchange Way 4575 Witmer Industrial Estates
Vaughan, ON L4K 5W3 Niagara Falls, New York 14305
Tel: (888) SECUTRON Tel: (888) SECUTRON
(888) 732-8876 (888) 732-8876
Fax: (905) 660-4113 Fax: (905) 660-4113