Topics
1. Overview
2. Xe-145M Manhattan Controller
3. Xe Field Service Tools (FST)
4. Modbus Communication
5. Remote Web Access
Topic 1
Overview
Xe Series Controllers
-145F - 90M - 145M
Topic 2
Xe-M Controller
(B) Alert
° Illuminates when an
Warning (flashes) or
Trip (constant on) is
sensed. Can be in a
Ready (Warning) or
Not Ready (Trip)
state
Page Content
Dashboard
Cursor
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
1. Ensure Cursor is
on the Folder Bar
2. Use Left or Right
navigation button to
move between different
folders
Temperature Symbol
• Indicates that the related value is a temperature reading
Cancel icon
• This icon is used on graphical screens when numeric values are entered or
changed. Pressing this button cancels any changes that may have been
made to a value
Topic 3
Xe-M Fixed Speed
HINT
Pressure and temperature units in this page is
dependent on the configuration in the General
Settings folder
HINT
(E) Date and Time
All information on this page is ° Indicates the present date and time
read only of the controller
° Editable from the General Settings
Folder
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
HINT
The number of I/Os are fixed in the program. If the option are not
enabled/purchased and the related instruments are not installed, the
I/O will display a X. Units shown can be configured in the General
Settings Folder
!
Integrated Dryer not available to Asia Pacific. As such,
Aftercooler Discharge Pressure will not be displayed. Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
1AVPT 0-15 psi Inlet Vacuum P5 – 1, 2, 3 2CTT 0-246 degF Injected Coolant Temperature P6 – 1, 2
3APT 0-225 psi Wet Sump Pressure P5 – 4, 5, 6 2ATT 0-246 degF Airend Discharge Temperature P6 – 3, 4
Aftercooler Discharge
4APT 0-225 psi Package Discharge Pressure P5 – 7, 8, 9 4ATT 0-246 degF P6 – 5, 6
Temperature
Oil Cooler Out Temperature
5CPT 0-225 psi Oil filter in P5 – 10, 11, 12 3CTT 0-246 degF P6 – 7, 8
(only on VSD Water Cool units)
6CPT 0-225 psi Oil filter out P5 – 13, 14, 15 5DTT 0-4095 Evaporator (only on dryer unit) P6 – 11, 12
Remote Pressure (Optional and
10APT 0-225 psi P5 – 16, 17, 18 6DTT 0-4095 Condenser (only on dryer unit) P6 – 13, 14
only for non-dryer unit )
Interstage Pressure (only for 2-
2APT 0-225 psi P5 – 19, 20, 21 Spare P6 – 15, 16
Stage unit)
Package Aftercooler Press Package Inlet Temperature
7APT 0-225 psi P5 – 22, 23, 24 1ATT 0-246 degF P6 – 17, 18
(only on dryer units) (only on VSD units)
1 Spare Spare P3 – 1, 2
2 Spare Spare P3 – 3, 4
2 Warning P2 – 4, 5, 6
!
With Progressive Adaptive Control (PAC), if the HINT
controller measures too much pressure differential With PAC Enabled and High Sump pressure,
between the package discharge pressure and the sump New Online Pressure Setpoint = Original Online
pressure, it will reduce online and offline pressures by Setpoint – (Sump Pressure – (Rated Pressure + 25))
the amount the sump pressure is above the rated New Offline Pressure Setpoint = Original Offline
Setpoint – (Sump Pressure – (Rated Pressure + 25))
pressure plus 25 psi. Refer to Enable PAC in Factory
Ingersoll Rand Service Education Team
Settings folder
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
!
To have PORO function, the PORO Option F
Kit CCN 23749021 must be installed
!
Please note that if a sensor is currently reading a value that is
+/- 10% of its range from zero, the sensor will not be able to be
calibrated. Please make sure the sensor is being exposed to
atmosphere before attempting calibration Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
(B) Graphical Display Hours left < 75%, 60%, 45%, 30%
stipulated
B
1st Green Box from the Right < 75%
A
Hours left < 15%
2nd Green Box from the Right < 60%
3rd Green Box from the Right < 45%
4th Green Box from the Right < 30% HINT
5th Yellow Box from the Right < 15% Service Required Icon will be illuminated when
remaining hours is lower than 30% for Yellow and 15%
6th Red Box from the Right < 0% for Red.
B
(B) Pressure
° For all Pressure C
variables
psi, kpa, bar or
kg/cm2
HINT
Some of the units may not be used as it depends on
compressor type and purchased options
Pressure
# Compressors (ISC_compressors)
PL
° What is this for? Tolerance Band
PL -TO
° This is the total number of compressors being sequenced. This set point must
be set to the same number on all compressors being sequenced. Example: if
there are three compressors being sequenced, all three units must have their
Total Compressors setting at 3. If there were four compressors, the setting
would be 4 on each compressor
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
HINT
The number of inputs with values displayed will depends on
type of machines and enabled/installed options
package F
Page 5
Topic 3
Xe-M Variable Speed
HINT
Pressure and temperature units in this page is
dependent on the configuration in the General
Settings folder
HINT
The number of I/Os are fixed in the program. If the option are not
enabled/purchased and the related instruments are not installed, the
I/O will display a X. Units shown can be configured in the General
Settings Folder
!
Integrated Dryer not available to Asia Pacific. As such,
Aftercooler Discharge Pressure will not be displayed. Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
1AVPT 0-15 psi Inlet Vacuum P5 – 1, 2, 3 2CTT 0-246 degF Injected Coolant Temperature P6 – 1, 2
3APT 0-225 psi Wet Sump Pressure P5 – 4, 5, 6 2ATT 0-246 degF Airend Discharge Temperature P6 – 3, 4
Aftercooler Discharge
4APT 0-225 psi Package Discharge Pressure P5 – 7, 8, 9 4ATT 0-246 degF P6 – 5, 6
Temperature
Oil Cooler Out Temperature
5CPT 0-225 psi Oil filter in P5 – 10, 11, 12 3CTT 0-246 degF P6 – 7, 8
(only on VSD Water Cool units)
6CPT 0-225 psi Oil filter out P5 – 13, 14, 15 5DTT 0-4095 Evaporator (only on dryer unit) P6 – 11, 12
Remote Pressure (Optional and
10APT 0-225 psi P5 – 16, 17, 18 6DTT 0-4095 Condenser (only on dryer unit) P6 – 13, 14
only for non-dryer unit )
Interstage Pressure (only for 2-
2APT 0-225 psi P5 – 19, 20, 21 Spare P6 – 15, 16
Stage unit)
Package Aftercooler Press Package Inlet Temperature
7APT 0-225 psi P5 – 22, 23, 24 1ATT 0-246 degF P6 – 17, 18
(only on dryer units) (only on VSD units)
1 Spare Spare P3 – 1, 2
2 Spare Spare P3 – 3, 4
2 Warning P2 – 4, 5, 6
!
To have PORO function, the PORO Option
Kit CCN 23749021 must be installed
!
Please note that in order to disable Scheduled
Start/Stop, the Scheduled Start and Stop days,
hours, and minutes must match exactly
!
Please note that if a sensor is currently reading a value that is
+/- 10% of its range from zero, the sensor will not be able to be
calibrated. Please make sure the sensor is being exposed to
atmosphere before attempting calibration Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
(B) Graphical Display Hours left < 75%, 60%, 45%, 30%
stipulated
B
1st Green Box from the Right < 75%
A
Hours left < 15%
2nd Green Box from the Right < 60%
3rd Green Box from the Right < 45%
4th Green Box from the Right < 30% HINT
5th Yellow Box from the Right < 15% Service Required Icon will be illuminated when
remaining hours is lower than 30% for Yellow and 15%
6th Red Box from the Right < 0% for Red. No logging in Event Log
B
(B) Pressure
° For all Pressure C
variables
psi, kpa, bar or
kg/cm2
HINT
Some of the units may not be used as it depends on
compressor type and purchased options
Pressure
# Compressors (ISC_compressors)
PL
° What is this for? Tolerance Band
PL -TO
° This is the total number of compressors being sequenced. This set point must
be set to the same number on all compressors being sequenced. Example: if
there are three compressors being sequenced, all three units must have their
Total Compressors setting at 3. If there were four compressors, the setting
would be 4 on each compressor
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
HINT
The number of inputs with values displayed will depends on
type of machines and enabled/installed options
Page 5
Topic 4
Xe Field Service Tools
Xe FST Installation
• To install the Field Service Tools, click on the
installer shortcut located in the
directory of the installation folder
Xe FST Installation
Shows the
progress of
Display the location the
the tools will be installation
installed
Xe Software Update
• Automatically download new versions of the
software from server to the technician’s computer
° Once connected to the internet when the FST starts, it will
compare the version of FST to that on the update server
Xe Licensing
• The FST application includes a license file which
contains the encrypted information about the license
expiry date
° When License has expired, a message will be prompted
!
Do not misuse the license period by
changing system clock date & time, a
“License has expired” error message
box will come to the user. The
application will be forced to close
!
Click NEXT once the Ensure power is applied to
desired option is selected the Xe-145F
Expand Ports
(COM & LPT…
TOOL Bar
- Quick launch of plug-ins within the program
STATUS Bar
- Display communication status and language in used
• FILE
° Provides options to work with load service tool settings,
save service tool settings and print setup
Load Settings
– User can load a previously saved FST Window size
Save Settings
– User can save a particular size of the FST window
Print Setup
– No Functions currently
Exit
– To exit field service tools
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
• EDIT
° Used to select the controller communication port
automatically
Configure Communications
– Use USB
» When checked, automatic connection will be enabled and the user need
not create new connection manually. When the user presses the “Connect”
button, FST detects the connection with controller automatically
» When unchecked, the user will have to specify the connection manually
• SERVICE
° Provides options to work with date and time settings and
file access feature
Date Time
– To synchronize the Xe-145F date and time to PC time
» Click Connect to establish communication between controller and FST.
Once connected, click Update Controller to synchronize
File Access
– Allows downloading of files from the controller
• TOOLS
° Provides options to work with Chart and Monitor features
Chart
– Display plotted data points of variables selected for charting
– Able to launch up to 3 session of Chart Plug-In
Monitor
– Editing/viewing of variable setpoints.
– Viewing of variable present values
– Log data of selected variable to a HTML file
– Able to launch up to 3 session of Monitor Plug-In
• Language Utility
° Allows user to select the desired language to work with
Controller Programming Wizard
– English
– French
– Chinese
– German
– Italian
– Spanish
– Korean
• WIZARDS
° Provides options to work with Controller Programming
Wizard, Data Log Wizard and Report Wizard
Controller Programming Wizard
– Allows programming of Application and Firmware into the Xe-145F
hardware
Data Log Wizard
– To download Analysis (Trip) Log and Event Log from the FMM
– Analysis Log captures all Analog Input/Output data before and after a
Trip event for up to 3 instances
– Event Log captures all Events (up to 252) that are registered in the
FMM Event Log such as Trip, Alarm, Start, Stop, Setpoint change
and etc
Report Wizard
– Allows user to saved settings from the controller to the hard drive or
to download previously saved settings to the controller
– Know previously in CMC Service Tools as Load and Save Report
• WINDOW
° Provides options to work with
tiling/cascading the windows and
arrange icons
Tile
– Active sub-programs window do not
overlap each other
Cascade
– Active sub-programs window are align
over each other
• HELP
° Provides options to work with the
HTML Help file.
Contents
– Display the table of contents of the
HTML Help file
Index
– Display the index of the HTML Help
file
Search
– look for topics containing specific text
in the HTML Help file
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
About
– Display the version, loaded plug-ins and existing plug-ins of the
service tool, license expiry date and remaining days
Establishing Communications
• Programs within the Field Service Tools requires
establishment of communication to the Controller
° For Monitor, Chart, Date & Time and File Access, locate
and click on the Connect Icon
Subsequent usage of these tools may not need to click on the
connect button. Program automatically connects to the controller
° For Controller Programming Wizard, Datalog Wizard
and Report Wizard, click on Select Connection
to select the correct connection to the controller
!
Ensure Use USB is checked
under Menu – Edit>Configure
Communications
Establishing Communications
° For programs that requires user to
select the correct connection
– Select Centac Compressor on the Named
Connections window and click Select
button to proceed
Variables Selection
Allows user to select variables for monitoring, charting and
reporting as well as saving a group of variables into a Variable
Group file for use later
• Only Monitor, Chart and
Report Wizard plug-in
have the ability to allow
user to perform such
functions
Variables Selection
Go to Variable>Select Variables in Depending on the plug-in, to open the
their respective plug-in Variable Selection window are different.
Click on Select
Variables
Click on this
shortcut icon in
their respective
plug-in
Variables Selection
After a change in firmware or application of the controller, when the user click
on Select Variables button for the first time, it will start the process of reading
the available variables from the controller. The process of reading the variables
form controller will take few minutes
Controller
Details
display the
firmware and Selected Variables
application Available Variables provide provide a list of variables
file version a list of variables that are that are being selected
available for selection. It will by the user. Only
be populated once the variables in this window
variables had been read will be used in Monitor,
from the controller Chart or Report
HINT
Once a variable had been selected, it will no longer appear in Ingersoll Rand Service Education Team
the Available Variables window Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
Variables Selection
Click Remove to moved a Click Add to moved a selected
selected variable from the variable from the Available
Selected Variables window to the Variables window to the Selected
Available Variables window Variables window
Double click on Click Remove All to Click Add All to moved all
the variable will moved all variables variables from the Available
moved it from from the Selected Variables window to the
Available Variables window to Selected Variables window
Variables the Available
window to Variables window
Selected
Variables
window
Variables Selection
Click on the Scroll bar to move
updown the list
Double click on
the variable will
moved it from
Selected
Variables
window to
Available
Click OK once the Variables
desired variables had window
To find a variable, input the
name of the variable in the been selected
Find text box
Variables Selection
Selected Variables will be displayed on the
main window of the plug-in (i.e Monitor,
Chart or Report…
Variables Selection
Go to File>Save Variables Variables that are selected can be saved into a Variable
Group in their respective Group (*VGP… for future use without the need to re-select
plug-in again when you use Monitor, Chart or Report plug-in.
Click on Save
Variable Group
Click on this
shortcut icon
in their
respective
plug-in
Variables Selection
Select a location
to save the
Variable Group
Variables Selection
Go to File>Load Once there are a saved Variable Group
Variables Group in (*.VGP…, user can load the group back to the
their respective plug-in Monitor, Chart or Report plug-in
Click on Load
Variable Group
Variables Selection
Select a location
of the previously
saved Variable
Group
Select the VGP file to
load
Variables Selection
Variables that are selected can be remove from the plug-in
(i.e Monitor, Chart or Report….
Monitor Plug-In
Helps the user to monitor the performance and set values to some
of the allowed variables of the controller
• To launch the program, go
to Tools>Monitor or click
on the shortcut
Monitor Plug-In
Click Connect Icon to Click Disconnect Icon to
establish communication remove communication
with the controller. with the controller.
Monitor Plug-In
Establish communication
with the controller (Refer to
Establishing
Communication section
Disconnect
communication with the
controller
Removed a selected
variable from the
Monitor Plug-In (refer
to Variables Selection
section…
Monitor Plug-In
Places check mark on
Monitor Check Box for
all variables assigned to
the Monitor Plug-In
Monitor Plug-In
Selects how the data from FMM are displayed
on the Monitor Plug-In Readings field Number,
Percent, Raw Format or Scientific and number
of decimal
Display a sample of
the readings using
selected options
Select the Format
Type for the
variables
Set the decimal
places required in
Click OK to implement the Readings
the change to the Field
Readings field
Monitor Plug-In
StartStop Recording of all selected variables
values to a HTML file according to the specified
sampling rate (C:\Program Files\Ingersoll
Rand\Xe Field Service Tool\Data…
Monitor Plug-In
Plot the data of the presently selected variable
in the Chart Page (for multiple variable plotting,
you will need to select the variable and click
Chart icon each time…
Monitor Plug-In
Monitor - A check mark on the Check Box Readings - Display the
means the data are being monitored (Raw data present value of the
or set point will be displayed in Readings field… variable
Monitor Plug-In
Right click on the Context Menu Place a check
selected variable of the selected mark on the
to bring up the variable Monitor
Context Menu Check Box to
monitor the
selected
variable
Insert a
Remove the check blank line
mark on the Monitor above the
Check Box to stop selected
monitoring the selected variable
variable
This window display the type
Duplicate the of units. For variables with
variable to Undefined, user can select
another row from the list by clicking on the
arrow
Chart Plug-In
Helps the user to view the data in a graphical format. The user
can plot up to eight variable charts in one chart window
• To launch the program, go
to Tools>Chart or click on
the shortcut
Chart Plug-In
Click Connect Icon to Click Disconnect Icon to
establish communication remove communication
with the controller. with the controller.
Chart Plug-In
Establish communication
with the controller (refer to
Establishing
Communication section…
Disconnect
communication with the
controller
Loads a previously
saved historical data in
SQL Compact edition
database file *.SDF
from a location in the
PC for reviewing
Chart Plug-In
Load a group of
variables previously
saved by the user from
a *.VGP file (refer to
Variables Selection
section…
Chart Plug-In
Opens a window for user to
select variables that are
available for monitoring (refer
to Variables Selection section…
Chart Plug-In
StartStop Recording of all selected
variables values to a HTML file
according to the specified sampling
rate (C:\Program Files\Ingersoll
Rand\Xe Field Service Tool\Data…
Chart Plug-In
Saved the present chart as a
*.PNG file which can be inserted
into any Microsoft programs or
view directly with Picture Manager
or others
Chart Plug-In
Input the desired Timespan
for all charts in this box and
press Enter
Chart Plug-In
Stop the updating of data into the chart window for
analyzing purpose. However, new data would continue to
be gathered and the same can be retrieved on unfreeze
Chart Plug-In
Click the updown arrow
to bring upclose the
Display the name of the
Variable Specific
selected variable and the
Options window
units of measurement
Chart Plug-In
Points only
Allows user to select how the
data are displayed on the
Line Only chart Line and Points,
Points Only or Line Only
Chart Plug-In
Click on this link to switch from Real Time
View to Historical View of the selected Newest data on
variable (Hint : When Historical View link is the chart are
shown, the chart is presently in Real Time plotted on the
View. When Real Time View link is shown, the right side of the
chart is presently in Historical View chart within the
selected
Timespan and
will scroll to the
left of the chart
Chart Plug-In
In Historical View, this area is known
as the Viewer. It displays the data
points of the presently selected range
in the Navigator. The first time user
switches to the Historical View, both
Viewer and Navigator will be the
same
Chart Plug-In
Chart Plug-In
This is the maximum
value within the Viewer. If Hovering the mouse over any data point will
the value is obscured by display a text block in the Navigator showing
the data, moved mouse the exact time and values of the
over it corresponding point, also the point will be
highlighted red in Viewer
Click on + or to
resize the
Viewer. Similar
This is the minimum value to adjusting the
within the Viewer. If the resize handles
value is obscured by the
data, moved mouse over it
Chart Plug-In
Both the Viewer and the Navigator will plot the data in a candlestick
format when there is more data points then available screen space.
For example, if the historical view contains 10,000 data points and the
window size is 500 pixels. The chart requires at least 1 pixel between
each data point and therefore create 250 candle sticks, each
representing 40 data points
!
Ensure the PC are
connected to the USB port
of the Controller before
proceeding Click NEXT to
proceed
!
Do not disconnect or power off the Click NEXT once the
controller while downloading is being download has been
performed. Always plug-in your completed
notebook to a power source! Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
Report Wizard
Read and generate a group of variable values from the FMM &
store it in the PC in HTML and CSV format. The stored variable
values in the CSV file can be loaded back into the FMM
• To launch the program, go
to Report Wizard or click
on the shortcut
Report Wizard
This is the welcome screen of the Report Wizard which describes the
functionality of the wizard. Before proceeding to establish communication with
the controller, ensure the PC is connected to the USB port on the FMM
controller
!
Ensure the PC are
connected to the USB port
of the Controller before
proceeding Click NEXT to
proceed
Report Wizard
Select Connection
allows user to select
the correct connection
This window display (refer to section on
the name of the last Establishing
used connection. Communication…
Click Next to
proceed. For first
time user, this
window will be empty
Report Wizard
The Select Operation
screen allows user to
select the action to be
performed
Select Read from
Device to download
selected variables
value to a report in
HTML and CSV file
or Write to Device
to send variables
value from a
previously saved Click NEXT once the
CSV file back to the desired option is
controller selected
Destination window
display the location of
the file to be saved.
Load Variable
This window display a
Group allows user
list of variables
to load a group of
selected
variables previously
saved in a VGP file
HINT
Recommend to save all Click NEXT once
variables value instead of desired variables are
selecting certain variables to selected
save Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
This window
display summary
of the operation,
number of
variables selected
and information
that had been
input by user
Click NEXT to
proceed to download
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
Placing a check
mark on this box
will allow the
program to launch
a browser to view Click FINISH to end
the HTML file the wizard once the
after the Finish progress indicates
button is clicked Finished
!
Do not disconnect or power off the controller while downloading is being
performed. Always plug-in your notebook to a power source!
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
!
Emergency Stop (E-Stop) must be engaged prior to sending the variables value to
the controller or Digital Input DI-7 must be in the enable state. Failure to do so
may result in unexpected starting of the machine
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
!
Ensure the E-Stop button is engaged
or Digital Input #7 on the FMM is
activated before proceeding
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
!
Ensure the PC are
connected to the USB
port of the Controller
Click NEXT to
proceed
Selecting this
option allows
downloading of
new firmware or
configuration files Click NEXT once the
to the controller desired option is
selected
Select Delete
Select the desired Machine ID file.
file to download to Delete Machine ID
the controller. file will reset all
Typically both are parameters to
required Factory Default
values.
Recommended to
enable this option
whenever
programming is
Click NEXT once the needed
desired file and option is
selected
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
This window
display summary
of the operation,
options selected
and files that will
be downloaded to
the controller
!
Do not disconnect or
power off the controller
This page indicates while the downloading is
the progress of the being performed and the
updates. update is being carried out
HINT
!
It will take some time (about 10 to 15
DCU will display Diagnostic Mode (Blue Screen). Initially it will
show Security level set to 1, then followed by Distributing Files minutes) for the update to complete.
and Installing New Files. Once complete, the controller will reboot Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
File Access
Allows access to the controller files and to transfer the files from
controller to PC
• To launch the program, go
to Service>File Access or
click on the shortcut
File Access
Click on ConnectDisconnect shortcut to
This window display the
establishremove communication with the controller
location of the files to
be saved in the PC
Filename Get Delete
Analysis Log X X
Analysis Log Config X
Comm Config X
DCU Debug X X
Event Log X X
Feature List X
FMM Debug X X Click Browse to select the
IO Config
Licensed
X
X location on the PC to save
Machine ID X the files
Machine Install X
Overrides X
Private Data Map X
Protocol Data Maps
Public Data Map
X
X
This window display the
Text Translations X files that are being
saved to the PC
Value Limits X
Topic 5
Modbus Communication
Machine#1 01
Click OK once
everything had
been configured
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
Display the
Display the data that is read from the DCU. In
Absolute Address
this example, System pressure is 121.9871,
of the variable
Oil pressure is 19.7756 and Oil Temperature is
115.7436
HINT
Wired the converter at
the cable point that are
suppose to wired to
customer DCS. This will
ensure all cables and
termination are checked
PC NA 192.168.65.4 255.255.255.0 NA
Configure IP Address of PC
• Go to Control Panel>Network Connections
Configure IP Address of PC
• Select “Internet Protocol
(TCP/IP) and click
“Properties”
• Click on “Alternate
Configuration” and
select “User Configured”
Configure IP Address of PC
• Enter 192.168.65.4 for
“IP address” and
255.255.255.0 for
“Subnet mask”
° Only for direct
connection to PC
° Leave all other fields
empty
Configure IP Address of PC
• Perform a Ping Test to
determine connectivity
° Go to Start>All
Programs>Accessories>C
ommand Prompt
° Type ping 192.168.65.1
(IP address of the slave
device) and hit enter
If test is successful, you
will see reply
If test failed, you will see
Request Time Out
Set the IP
address to the
slave device IP
address
Select this to
determine the
protocol
Click OK once
everything had
been configured
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
HINT
Wired the PC at the
cable point that are
suppose to wired to
customer DCS. This will
ensure all cables and
termination are checked
Topic 6
Xe-145F Remote Web Access
IP Address 192.168.65.3
Subnet 255.255.255.0
AC-1
Ethernet Switch
AC-2
IP Address 192.168.65.2
Subnet 255.255.255.0
HINT
An Ethernet Switch is required when
distance exceeds 100 meters or more than
one Xe-145F connecting to Remote PC
Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
IP Address 11.18.65.24
Subnet 255.255.252.0
• Click on “Alternate
Configuration” and
select “User Configured”
• To access a particular
machine, input the
configured IP address on
the DCU of the Xe-145F HINT
into the IP address The compressor is accessed either by name or by
IP. Accessing by name requires that a router be in
window of the browser the network. The default name is mcb2403. The
name may be changed at Compressor Information
program folder in the Remote Web Access
D
(C) Language
° Select the desired language
Same language availability on the
DCU (30 languages) !
Only 5 users can concurrently login to the Web
(D) Login Access at a time. If another user attempts to
° Clicking this will authenticate login, an error message will be displayed
and proceed to next page Ingersoll Rand Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
Home
• Default page after logged in. Display information about the compressor
operating parameters, running hours, loaded hours, number of starts etc
Event Log
• Display the event log from the controller
Performance Log(Xe 145 only)
• Shows the performance details and system data for the compressor
including hour meters, amp meters, no. of alarms & trips
Graphing (Xe 145 Only)
• View the data in a graphical format for the selected analog input variable
and time duration
Maintenance
• Contains the contact address & number to call for parts or service and
maintenance counters with the appropriate title and service schedule hours
Inspection Log (Xe 145 Only)
• Record machine data over a fixed period of time and at a fixed rate
Compressor Information
• Indicates the compressor model, S/N, rated capacity, power requirement
and other machine information
Account
• Shows the login user name and access level. User can change the login
password through this screen
!
Only users with Admin or
User access rights can change
pressure set point and
hourmeters
Ingersoll Rand remotely
Service Education Team
Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training
HINT
Ingersoll Rand Service Education Team
The latest event is listed at the top of the page Ingersoll Rand Proprietary Information. Rev A – Jul 2011
357 Xe-M Onboard Controller Technical Training