Power System Protection
Power System Protection
of Power System 1
1
¾ Relay operating voltage, (pick up voltage); VROmin 1 2
1
¾ Relay returning current, () ; IRRmax
¾ Relay returning voltage, () ; VRRmax
I RR VRR
BDU, institute off Technology Schoo
¾ Instantaneous current counter, ICC, relay with no intentional time delay and limited zone,
Tad-2009
6/22/2010 1
Protective Relays
Protective schemes for fault currents b/n pphases and over loading
g at higher
g
voltage side.
gineering
and Electrical Eng
fig.1
ol of Computing a
6/22/2010 2
BDU, institute off Technology Schoo
ol of Computing a
and Electrical Eng
gineering
© Copyright, TassT
Tad-2009
6/22/2010
Protective Relays
systems
The fault clearance chain at redundant protection systems.
3
Protective Relays
Winding
g connections of instrumental voltage
g transformers and relays:
y (p
(p. 43, RUS fig.1a-d
g )
a) Single phase VT is connected with either of any two phases, while, if only one line
voltage is enough/required, say, VBC . (fig.1.)
gineering
and Electrical Eng
b) Two single phase VTs connection with open delta* primary is connected with any
of two line phases. Secondary's are connected with relay coils. This gives getting
an access to connect relays with all b/n phases.(VR1-VR3) and single phase
voltage with respect to the artificially neutralized system to line voltages.
voltages And also
also,
ol of Computing a
relays with the same coil resistance (VR4-VR6) can be connected in star. But can
not be implemented if phase to ground voltage is required. (fig.2.)
BDU, institute off Technology Schoo
Tad-2009
© Copyright, TassT
6/22/2010 5
Protective Relays
Winding
Wi di connections
ti off instrumental
i t t l currentt transformers
t f andd relays:
l (p.
( 159,160,162
159 160 162 RUS )
b) half
h lf star
t connection
ti (fi 6 )
(fig.6.)
ol of Computing a
BDU, institute off Technology Schoo
Tad-2009
© Copyright, TassT
6/22/2010 6
Protective Relays
c) delta star connection (fig.7.)
(fig 7 )
gineering
and Electrical Eng
d) difference
diff off two
t phase
h currents.
t (fi 8 )
(fig.8.)
ol of Computing a
BDU, institute off Technology Schoo
Tad-2009
© Copyright, TassT
6/22/2010 7
Protective Relays
Comparison of a non-conventional
non conventional
current transformer (left in the
picture) with a conventional
outdoor transformer with paper
paper-oil
oil
insulation.
ol of Computing a
BDU, institute off Technology Schoo gineering
and Electrical Eng
Tad-2009
© Copyright, TassT
6/22/2010 8
Protective Relays
Outdoor design of a combined non-conventional
CT current/voltage transformer in passive optical technology
ol of Computing a
BDU, institute off Technology Schoo gineering
and Electrical Eng
Tad-2009
© Copyright, TassT
6/22/2010 9
BDU, institute off Technology Schoo
ol of Computing a
and Electrical Eng
gineering
© Copyright, TassT
Tad-2009
6/22/2010
Protective Relays
10
BDU, institute off Technology Schoo
ol of Computing a
and Electrical Eng
gineering
© Copyright, TassT
Tad-2009
6/22/2010
Protective Relays
11
BDU, institute off Technology Schoo
ol of Computing a
and Electrical Eng
gineering
© Copyright, TassT
Tad-2009
6/22/2010
Protective Relays
12
BDU, institute off Technology Schoo
ol of Computing a
and Electrical Eng
gineering
© Copyright, TassT
Tad-2009
6/22/2010
Protective Relays
13
BDU, institute off Technology Schoo
ol of Computing a
and Electrical Eng
gineering
© Copyright, TassT
Tad-2009
6/22/2010
Protective Relays
14
Protective Relays
Selection
S l ti off Current
C t Transformers
T f is
i carried
i d outt :
current transformers
f ffor the
h ddesired
i d iinstallation
ll i (see
( table.1.).
bl 1 ) And
A d the
h
nominal coefficient of transformation will be known ;
I1N .
KTr
T .nom. = ;
ol of Computing a
I2N
By considering the type of current relay for the given protection (see table.2.)
and will be determined the min. operating current of the circuit.
BDU, institute off Technology Schoo
6/22/2010 15
Protective Relays
Where:
I Re lay Operating .min( MCP ) - operating relay current, calculated, A;
I load
l d max.- maximum load current at the section to be protected,
protected A;
K reliablity in ajustment .
and Electrical Eng
I ROmin VROmin
I Re lay current .
K schematic.relay connection =
;
I phse current
Tad-2009
Taken:
6/22/2010 16
Protective Relays
Where:
I Re lay Operating .min( MCP ) - operating relay current, calculated, A;
I load
l d max.- maximum load current at the section to be protected,
protected A;
K reliablity in ajustment .
and Electrical Eng
I ROmin VROmin
I Re lay current .
K schematic.relay connection =
;
I phse current
Tad-2009
Taken:
6/22/2010 17
Protective Relays
Where:
I Re lay Operating .min( MCP ) - operating relay current, calculated, A;
I load
l d max.- maximum load current at the section to be protected,
protected A;
K reliablity in ajustment .
and Electrical Eng
I ROmin VROmin
I Re lay current .
K schematic.relay connection =
;
I phse current
Tad-2009
Taken:
6/22/2010 18
Protective Relays
Where:
I Re lay Operating .min( MCP ) - operating relay current, calculated, A;
I load
l d max.- maximum load current at the section to be protected,
protected A;
K reliablity in ajustment .
and Electrical Eng
I ROmin VROmin
I Re lay current .
K schematic.relay connection =
;
I phse current
Tad-2009
Taken:
6/22/2010 19
Protective Relays
Where:
I Re lay Operating .min( MCP ) - operating relay current, calculated, A;
I load
l d max.- maximum load current at the section to be protected,
protected A;
K reliablity in ajustment .
and Electrical Eng
I ROmin VROmin
I Re lay current .
K schematic.relay connection =
;
I phse current
Tad-2009
Taken:
6/22/2010 20
Protective Relays
Where:
I Re lay Operating .min( MCP ) - operating relay current, calculated, A;
I load max.- maximum load current at the section to be protected, A;
gineering
K schematic.relay connection
BDU, institute off Technology Schoo
I pphse current
© Copyright, TassT
6/22/2010 21
Protective Relays
According to the type of sections to be protected,
protected the following max.
max current can be
Taken ( I load max. ):
Where,I nom. , I S ta rtin g ., and I fault .max, - nominal line current, starting current of the
electric motor and max. fault current on the
li
line.
ol of Computing a
Depending of the type of connection of the secondary winding of the CT and the
yp of faults,, K schematic
type will have the followingg values:
BDU, institute off Technology Schoo
h i .relay
l connection
i
half star.
K schematic.relay connection = 1.73
1 73 - in
i all
ll condition,
diti under
d 3 phase
h short
h t circuit.
i it
© Copyright, TassT
The remaining coefficients of the schematic can be assumed from the no.of
no of
working experiences:
= 1 - under the absence of the electric motors in the line.
gineering
K starting .current of EM
and Electrical Eng
= 0.8…….0.85
From the calculated value of the operating current, the catalogue value will be selected
I Re lay Operating .cata log ue ≥ I Re lay Operating .calculated
BDU, institute off Technology Schoo
B observing
By b i the
h condition:
di i
Vworking min.
© Copyright, TassT
Voperating =
K reliablity in ajustment . ⋅ K returning / revering ⋅ KVT
6/22/2010 23
Protective Relays
where,
V1
KVT = ; V2 = 100 V .
V2
ol of Computing a
((without blocking
g off under voltage)
g )
© Copyright, TassT
V fault .max.residual .at the protection sec tion ,kV = 0.6 Vnom
gineering
and Electrical Eng
N.B. Under having instantaneous current counter - relay with no intentional time
delay and limited zone
K reliablity in ajustment ⋅ K schematic.relay connection
I operating .current counter = ⋅ I fault .max.at the protected end of the line, A ;
ol of Computing a
K Current Transformation of CT
BDU, institute off Technology Schoo
Tad-2009
© Copyright, TassT
6/22/2010 25
Protective Relays
Structural designation
g of the current transformers.
1 - 2 - 3
L b li with
Labeling ith few
f letter:
l tt Cl
Class off accuracy and
d nos. off windings
i di
0.5/D - for two sec. windings : one has 0.5 accuracy
CT - Current Transformer.
and the second is assigned for differential P.
gineering
XX - Wound primary.
--
XX - Bar primary.y
--
and Electrical Eng
XX - Fast saturated.
--
XX - modified
Range of Voltages in number, kV.
XX - low voltage ratings
XX - enclosed with CB
XX - coil for differential p.
p
ol of Computing a
--
-- 1.5-10-15-20-30-40-50-75-100-150-200-250-300-400-500-600-
-- 750-800-1000-1200-1500-2000-3000-4000-5000-6000-8000-
Tad-2009
-- 10000-12000-14000-16000-18000-20000-25000-28000-32000-
-- 35500 40000
35500-40000
© Copyright, TassT
--
6/22/2010 26
Protective Relays
Table. 1. Current Transformers with their primary current and type of application/features.
XXX-10 10-400
XXX-10 10-1500
XXX-10 50-3000
ol of Computing a
XXX-10 20-1500
XXX-10 2000-5000
XXX 20
XXX-20 400 1500
400-1500
BDU, institute off Technology Schoo
XXX-35 400-1500
Tad-2009
N.B. For all transformers I2.Nom = 5 A * see the above structural disignation
© Copyright, TassT
6/22/2010 27
Protective Relays
Table.2. Current Relays , type and relay operating currents.
Type I1.Nom , A Type I1.Nom , A
1 2 1 2
CRM 20 60
CRM-20-60 20;40;60 CREx III CREx-VI
CREx-III, CREx VI 20;25;30;35
ol of Computing a
6/22/2010 29
Protective Relays
Example:
E l
Given data:
Distribution line with ffactoryy transformer
f havingg
a power CB with spring drive at the higher side
(as shown in the diagram here, fig.2.).
gineering
Type of Transformer,
I (f 1) = 1.8 kA
3
and Electrical Eng
I f , kA
Protection against
g short circuit b/n pphases.
ol of Computing a
Tasks to be done:
• to draw schematics diagram to protective relay-PR;
• to calculate and choose the elements of PR from
short circuit currents and over loadings;
g
BDU, institute off Technology Schoo
• Since the power CB has a drive with spring mechanism, with this, type CRM
and CREx. – relay with spontaneous operation are required;
• for protection against short circuit among phases, the connection diagram of the
CT and secondary load (relay) are required – from the current difference of two
gineering
phases;
and Electrical Eng
• since the system at higher side hasn't system neutral (neutral isolated), so,
a single phase to ground fault (or an insulation failure) can be controlled by
insulation control mechanism with alarm - signal under faults;
ol of Computing a
• at low voltage side with surge protection neural , 4-wire system, so that,
an automatic breaker CBF will provide all types of protections;
BDU, institute off Technology Schoo
STr . 250
ITr .nom. = = = 14.5 A.
3Vnom. 3 ⋅10
6/22/2010 31
Protective Relays
• Since no electric motors are connected at the distribution line, a need of
adjusting starting rush current is not required.\
For the given system will be selected the CT XXX-10 sec; I1.Nom =50 A;
I2.Nom = 5 A and quantity =2 (use Table.1)
I1N . 50
• Coefficient of transformation, KTr .nom. = = = 10;
I2N 5
gineering
K Current Transformation of CT
1.8 ⋅1.73
I operating .current counter = ⋅ 0.3 ⋅103 = 93.4 A;
10
ol of Computing a
And we determine the Ksesitivness and Kreliability under the lower fault current
© Copyright, TassT
(If 2Ф) at sending end of the DS: I fault .min.at the protected end of the line , A
K sensitiveness =
I operating . protection , A ⋅
6/22/2010 32
Protective Relays
I (2)
f .11 0.87 ⋅1800
K sensitiveness = = = 1.57;
1 57
I operating . protection , A 10 ⋅100
I (2)
f .min = I (2)
f. = 0
0.87
87 I (3)
f. ;
1 ⋅1.25 ⋅ 3
I Re lay Operating .min( MCP ) ≥ ⋅14.5 = 3.9 A;
0.8 ⋅10
Tad-2009
R lay
l Operating
O ti
K transformation of CT
I f .mini 87 ⋅ 300
0.87
0
K sensitiveness(MCP) = = = 5.2.
I operating . protection , A 5 ⋅10
gineering
fig.3. 6/22/2010 34
Protective Relays – Variants
Relay Protection I (f 3 ) , k A
Variant CB
Relay Conn. Ish.c starti Ish.c end
1 2 3 4 5 6
Assignments:
1 SDr 2 Half star 0.2 0.04 1. Sketching..
2 EMDr 1 Half star 6 1.2 2. Choosing of CT,RC.
3. Proofing of KSensitiv.
3 SDr 2 diff,.of 2ФI 12.5 2.4
gineering
4 EMDr 2 , 2ФI
diff,.of 12.5 2.4
and Electrical Eng
7 SD
SDr 2 diff f 2ФI
diff,.of 4 08
0.8
ol of Computing a
6/22/2010 35