Brochure Agbk 2010 Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

NH3 Process Room Evaporator

Ammonia Industrial Applications 1-10 Tons (For Rooms Above Freezing)

AGBK
> > U s e d f o r I n d u s t r i a l A m m o n i a P r o c e s s R o o m a pp l i c a t i o n s .
The Global Leader
In Heat Exchange Technology

With seven decades of experience and commitment to total client


satisfaction, Guntner has earned a reputation as the global leader in
heat exchange technology. Supported by the best R&D engineers in the
business, cutting-edge technology, and eight manufacturing facilities
around the world, Guntner continues to break new ground in the
demanding market of finned heat exchangers for industrial refrigeration,
HVAC, and process cooling applications. Our high standards and
dedication to society and the environment around us have earned us the
respect of the industry, and the privilege of long-term relationships with
our customers around the world.

…keep(s) your quality

…keep(s) your quality. www.guntnerus.com 09.09


The Guntner Product Calculator MPC
MPC_Label_2007.qxd 21.11.2006 14:53 Uhr Seite 1

With the Guntner product calculator “MPC,” we are able to offer you
more than just an overview of prices or the complete product range.
This thermodynamic selection program enables you to calculate your
own tailored selections based on precise and actual thermodynamics
rather than factors or multipliers. A team of experts stand by to guide
you through the selection process.

The program can be updated via the internet ensuring that you always
Guntner Product have the most exact and precise information for proper selection.
Calculator

We recommend using Guntner’s Product Calculator for exact


thermodynamic calculations. Varying conditions such as refrigerants,
humidity levels and material combinations are all taken into account by
the software to most accurately select products to fit your specific needs.

> > c a l c u l a t i o n s m a d e e a s y wi t h o u r p r e c i s e M P C s o f t w a r e

09.09 www.guntnerus.com …keep(s) your quality. 1


Standard Features of Construction

The AGBK range provides a unique air distribution


pattern that offers the ultimate in worker comfort for
any type of processing room. Extreme low noise fan
operation coupled with our superior technology sets
the benchmark for the industry. These features result
in less acoustic stress on staff, reduction in staff
absenteeism due to illness, and provide a pleasing
atmosphere which encourages work performance.

CASING: Corrosion resistant Aluminum (AIMg3),


sea-water resistant.

All casings are powder coated – color RAL 9003


(Signal White) and suitable for all stringent food
industry applications. Construction detail takes
accessibility into account and does not allow for
“tight spots.” All parts are easily accessible for
service and cleaning purposes. Fan orifices are
optimized by manufacturer to ensure maximum
efficiency, air throw and airflow. All fans are
individually compartmented within complete tube
sheets to allow for fan cycling for capacity control
and reduction of operating costs. All hangers and
fittings used for construction and assembly are
manufactured from stainless steel 304.

TRAY: Trays come with insulated (air gap) pans to


prevent condensation.

Corrosion and sea-water resistant light weight


Aluminum (AIMg3) offered for all models. Trays
are powder coated color RAL 9003 (Single White).
All trays are our unique “fold down” type and can
be either folded down or completely removed,

2 …keep(s) your quality. www.guntnerus.com 09.09


if required, for cleaning purposes. The “Sloped FANS & MOTORS: External rotor axial fans,
design” of the cooler ensures maximum and efficient designed for low noise level operation are standard
drainage during the defrost cycle. Drain outlet for the entire range.
connection PVC 1 1/4”.
All motors are aluminum die cast and of the highest
efficiency, maintenance free, guarantee a long life
TUBE: Tubing is manufactured from the highest
and have low noise levels.
quality 304 stainless steel in accordance with ASME
B31.5 1/2” (12mm) tubing. All fan motor assemblies are of the blow-through

Staggered tube arrangements- 1.969” x .98” (50 x type.

25 mm) allows for maximum heat transfer efficiency.


Fan guards are galvanized steel and PVC coated.

Tubes are mechanically expanded to ensure


Standard voltages include 230V and 460V for 60Hz
mechanical bonding coupled with the best heat
applications and 400V for 50Hz applications.
transfer efficiency ratio from fin to tube.

All coils are pressure tested to 450 psig with dry air DEFROST: Air or electric are standard options for
all units. Electric heater elements are stainless steel
under water, and shipped with a holding charge.
sheathed and fit directly into tubes within the coil
bundle to provide for enhanced heat transfer during
FINS: Aluminum fins with a corrugated pattern
the defrost cycle. Elements are held in place with
provide enhanced air turbulence, guaranteeing
clips to prevent them from moving during transport
contact with all surface areas within the coil bundle.
or operation.
100% drawn die formed finned collars are standard
and result in accurate fin spacing of 6.3 and 3.6 FPI ELECTRICAL: Each fan motor is factory wired

(4mm and 7mm). to the junction box with a single point connection.
(Factory installed jumpers can be removed for
All fins are manufactured with a continuous fin sheet individual/capacity control.)
in order to reduce the risk of frost build-up, air-side
All heater wiring is terminated within a junction box
pressure drops, dust, dirt and bacteria, and simplify
for quick and simple field connections.
any cleaning procedure.

DELIVERY & PACKING: All units are shipped


COIL CIRCUITING: Each unit is specifically
crated, and in a position to facilitate installation.
circuited to optimize coil performance and capacity
with a low-pressure drop.

09.09 www.guntnerus.com …keep(s) your quality. 3


Optional Features

CONSTRUCTION MATERIALS ELECTRICAL

• The entire casing, tube sheets and tray manufactured • No wiring.


with either 304 or 316 stainless steel.
• All motors wired to common/individual non-fused
• Epoxy coated aluminum or stainless steel (304 or disconnect.
316) fins.
• All motors wired to common fused disconnect with
• Units are supplied standard with carbon steel black thermal protection for each motor.
pipe connections but can be ordered with either
• All motors wired to fused disconnect with single starter
stainless steel pipe flanges (ANSI B16.5) or carbon
and thermal protection for each motor.
steel threaded connection (ASME B1.20).
• Various wiring options are available – please consult
• Re-heat coils – separated from the cooling coil by
with factory for an alternative to suit your specific
means of an air gap.
requirements.
• Extended pan at connection end.

• For unit operation below 35ºF room temperature –


consult sales office.

DEFROST OPTIONS:

• For electric defrost – defrost termination and fan delay


thermostat factory fitted.

• Heater limit thermostat fitted and pre-wired.

• Hot gas defrost in the coil.

4 …keep(s) your quality. www.guntnerus.com 09.09


Evaporator AGBK

AGBK 050 B/ 1 7 -A L

Product Line Voltage


X 1/230/60
W 1/230/50
J 3/400/60
L 3/460/60

Fan Diameter S 3/460/50

18” 045 U 3/230/60

20” 050

Defrost
A AIR
E ELECTRIC
H HOT GAS
Rows Deep B/

Fin Spacing
4 4mm- 6.3 FPI
No. of Fans 1 7 7mm- 3.6 FPI

Fan Motors – Electrical Specifications


Unit
Sound Power
Model Fan Diameter Guntner
Level
Fan
mm inch Voltage Phase HP rpm FLA dB (A) Spare Part No.

230 1 1/8 1010 1.05 68.0 VT0329U


045…
450 18 230 3 1/8 1020 0.49 63.0
VT0353U
460 3 1/8 1170 0.33 63.0
230 1 1/4 1100 1.4 70 VT01240U
050…
500 20 230 3 1/4 1100 1.3 72.0
VT01187U
460 3 1/4 1130 0.8 72.0

09.09 www.guntnerus.com …keep(s) your quality. 5


Performance Data: All Models

COIL CAPACITY COil


Model Fin
Wet Surface Area Tube Volume
No. Spacing
AGBK @ 3/460/60
Btu/hr/°F TD ft2 ft3 fpi
1 FAN
045.1A/14 1,505 311 0.19
045.1B/14 2,482 466 0.29 6.3
050.1B/14 2,892 560 0.34
045.1A/17 1,017 186 0.19
045.1B/17 1,737 279 0.29 3.6
050.1B/17 2,102 335 0.34

2 FAN
045.1A/24 3,011 621 0.36
045.1B/24 4,847 932 0.54 6.3
050.1B/24 6,101 1,118 0.63
045.1A/27 2,135 372 0.36
045.1B/27 3,473 557 0.54 3.6
050.1B/27 4,304 669 0.63

3 FAN
045.1B/34 7,339 1,398 0.78
6.3
050.1B/34 9,027 1,677 0.93
045.1B/37 5,212 836 0.78
3.6
050.1B/37 6,390 1,004 0.93

4 FAN

045.1B/44 9,700 1,864 1.03


6.3
050.1B/44 12,203 2,237 1.23

045.1B/47 6,953 1,116 1.03


3.6
050.1B/47 8,609 1,339 1.23

(For room temperatures above freezing)

6 …keep(s) your quality. www.guntnerus.com 09.09


Air Flow Electric Defrost
Sound
Model Air
Pressure Total Coil Amp Draws
No. Throw
Level
AGBK @ 3/460/60 @ 3/230/60 @1/230 @ 3/460 @ 3/230
cfm fpm cfm fpm ft db (A) kW W A A A
1 FAN
045.1A/14 1,972 308 1,677 262 2x26 53 1.5 1,500 6.5 1.9 3.8
045.1B/14 1,825 285 1,589 249 2x26 53 1.5 1,500 6.5 1.9 3.8
050.1B/14 2,560 333 2,501 325 2x30 55 2 2,000 8.7 2.5 5.0
045.1A/17 2,089 326 1,825 285 2x26 53 1.5 1,500 6.5 1.9 3.8
045.1B/17 2,031 317 1,766 276 2x26 53 1.5 1,500 6.5 1.9 3.8
050.1B/17 2,678 348 2,619 340 2x30 55 2 2,000 8.7 2.5 5.0

2 FAN
045.1A/24 3,943 308 3,355 262 2x36 55 3.5 3,500 15 4.4 8.8
045.1B/24 3,649 285 3,178 252 2x36 55 3.5 3,500 15 4.4 8.8
050.1B/24 5,121 333 5,003 325 2x39 57 4 4,000 17 5.0 10.0
045.1A/27 4,179 326 3,649 285 2x36 55 3.5 3,500 15 4.4 8.8
045.1B/27 4,061 317 3,531 276 2x36 55 3.5 3,500 15 4.4 8.8
050.1B/27 5,356 348 5,238 340 2x39 57 4 4,000 17 5.0 10.0

3 FAN
045.1B/34 5,474 285 8,100 246 2x46 56 4.8 4,800 21 6.0 12.0
050.1B/34 7,681 333 12,750 323 2x49 58 6.2 6,200 27 7.8 15.6
045.1B/37 6,092 317 9,000 273 2x46 56 4.8 4,800 21 6.0 12.0
050.1B/37 8,034 348 13,350 338 2x49 58 6.2 6,200 27 7.8 15.6

4 FAN

045.1B/44 7,298 285 10,800 246 2x52 57 7 7,000 30 8.8 17.6

050.1B/44 10,241 333 17,000 323 2x56 58 8 8,000 35 10.0 20.1

045.1B/47 8,122 317 12,000 273 2x52 57 7 7,000 30 8.8 17.6

050.1B/47 10,712 348 17,800 338 2x56 58 8 8,000 35 10.0 20.1

09.09 www.guntnerus.com …keep(s) your quality. 7


Dimensions: All Models

UNIT DIMENSIONS
Model
No.
AGBK L B E H1 H2 A1 C A2 F
inch inch inch inch inch inch inch inch inch
1 FAN
045.1A/14 58 5/8 43 1/8 39 1/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
045.1B/14 58 5/8 43 1/8 39 1/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
050.1B/14 66 7/16 43 1/8 47 1/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
045.1A/17 58 5/8 43 1/8 39 1/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
045.1B/17 58 5/8 43 1/8 39 1/4 28 5/8 27 1/2 14 5/8 9 3/4 12 1/4 41
050.1B/17 66 7/16 43 1/8 47 1/4 28 5/8 27 1/2 14 5/8 9 3/4 12 1/4 41

2 FAN
045.1A/24 98 43 1/8 78 3/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
045.1B/24 98 43 1/8 78 3/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
050.1B/24 113 3/4 43 1/8 94 1/2 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
045.1A/27 98 43 1/8 78 3/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
045.1B/27 98 43 1/8 78 3/4 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41
050.1B/27 113 3/4 43 1/8 94 1/2 28 5/8 27 1/2 14 5/8 9 3/4 13 7/16 41

3 FAN
045.1B/34 137 5/16 43 1/8 59 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41
050.1B/34 161 43 1/8 70 7/8 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41
045.1B/37 137 5/16 43 1/8 59 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41
050.1B/37 161 43 1/8 70 7/8 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41

4 FAN
045.1B/44 176 3/4 43 1/8 78 3/4 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41
050.1B/44 208 1/4 43 1/8 94 1/2 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41
045.1B/47 176 3/4 43 1/8 78 3/4 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41
050.1B/47 208 1/4 43 1/8 94 1/2 28 5/8 26 5/16 14 5/8 9 3/4 12 5/16 41

DRAWINGS FOR ALL MODELS

8 …keep(s) your quality. www.guntnerus.com 09.09


CONNECTIONS
Model
Refrigerant Drain Dry Weight
No.
AGBK in out
NPS NPS NPT lb
1 FAN
045.1A/14 1/2 1/2 1 1/4 187
045.1B/14 1/2 1/2 1 1/4 220
050.1B/14 1/2 1/2 1 1/4 247
045.1A/17 1/2 1/2 1 1/4 165
045.1B/17 1/2 1/2 1 1/4 205
050.1B/17 1/2 1/2 1 1/4 229

2 FAN
045.1A/24 1/2 1/2 1 1/4 324
045.1B/24 1/2 1 1 1/4 377
050.1B/24 1/2 1 1 1/4 432
045.1A/27 1/2 1/2 1 1/4 302
045.1B/27 1/2 1 1 1/4 346
050.1B/27 1/2 1 1 1/4 395

3 FAN
045.1B/34 1/2 1 1 1/4 547
050.1B/34 1/2 1 1/4 1 1/4 633
045.1B/37 1/2 1 1 1/4 494
050.1B/37 1/2 1 1 1/4 577

4 FAN
045.1B/44 1/2 1 1/4 1 1/4 696
050.1B/44 1/2 1 1/4 1 1/4 829
045.1B/47 1/2 1 1 1/4 635
050.1B/47 1/2 1 1/4 1 1/4 756

DRAWINGS FOR ALL MODELS

09.09 www.guntnerus.com …keep(s) your quality. 9


www.guntnerus.com

…keep(s) your quality.