SIPROTEC 5 - V7.9 - V8.0 - en
SIPROTEC 5 - V7.9 - V8.0 - en
SIPROTEC 5 - V7.9 - V8.0 - en
0
Protection, Automation and Monitoring
of Digital Substations
SIPROTEC 5 –
A flexible generation of intelligent, digital field devices with a high degree of modularity
Individually configurable devices –
Save money over the entire life cycle
Application Scenarios
Control Center SIPROTEC
Integration in DigitalTwin
SICAM Systems
Firewall SICAM Substation SICAM Human SICAM Power Quality DIGSI 5 DIGSI
Station PAS Automation SCC
Machine
PQS Analysis Online Testing
Interface
Level
Process
Level
Training Implementation
• Device handling • Planning
• Operators • Algorithm
• Customer specific • Settings
• Flexible at any place • Pre-testing
Operation Commissioning
• Device handling • FAT
• COMTRADE replay • SAT, Field test
• Fault analysis
Unrestricted © Siemens 2019
Page 7 July 2019 SI DG SA&P / Energy Automation Products
Benefits –
The customer value proposition
1 2 3 4 5
Open DIGSI 5 Export SIM file Connection to Import SIM SIPROTEC
project the Cloud DigitalTwin
Supported
by all major
Webbrowsers
• Device view
• Operating via SIPROTEC 5 operation panel
• Testing all protection algorithms
• Testing of automation logic (CFC)
• Interaction of several devices
USART-AE2FO
• New devices to be added to the protection topology
• Stepwise replacement or retrofit of SIPROTEC 4 FO5
protection devices
USART-AE2FO
7XV5662 7XV5662
• Distance protection: PUTT or POTT teleprotection
USART-AE2FO
• Transformer within protection zone
FO17
PUTT: Permissive Underreaching Transfer Trip
POTT: Permissive Overreaching Transfer Trip
7XV5461-0BG00
Benefits
• Monitoring of protection interface transfer quality individual substations
• Remote commands and signals via protection • Line differential protection of other systems remains
interface in operation
• Short switch-off time during conversion
• Use of existing communication links
Unrestricted © Siemens 2019
Page 14 July 2019 SI DG SA&P / Energy Automation Products
Interoperability of SIPROTEC 4 and SIPROTEC 5
Example 1 – stepwise retrofit of protection relays
Station 1 Station 2
Device logoff
Device logon
Station 3 Station 4
Station 1 Station 2
Device logoff
Device logon
Station 33
Station Station 4
Station 1 Station 2
Device logoff
Device logon
Station 3 Station 4
Station 1 Station 2
Device logoff
Device logon
Station 3 Station 4
Station 1 Station 2
Station 1 Station 2
Device logon
Station 3
requirementrequirementrequirement
Customer Customer Customer Distances of more then 100 km
USART-AD1FO
/ FO5
USART-AE2FO
Distances up to 60 km
USART-AD1FO
/ FO17-18
USART-AE2FO
Distances up to 100 km
USART-AD1FO
Benefits
/ FO19
USART-AE2FO
USART-AD1FO
/ FO5
USART-AE2FO
Benefits
• Flexible solutions for different
level of digitalization
• Process bus closes the gap
to a fully digitalized system
• Agile for future requirements
• Digitalization of all primary
data close to the process
• Data for optimizing grid
control and monitoring
• Remote engineering and testing
PTP
Protocol on ETH-BD-2FO MU PB Client
(1 µs acc.)
7SA86, 7SA87 P P P
7SD86, 7SD87 P P P
7SL86, 7SL87 P P P
7VK87 P P P
7UT85, 7UT86, 7UT87 P P P
7SK85 P P P
7UM85 P P P
7VE85 P P P
7SS85 P P P
7SJ85, 7SJ86 P P P
6MD85, 6MD86 P P P
6MU85 P P P
7KE85 O P P
MU: Merging Unit functionality – Sampled Measured Value server
PB Client: Process Bus Client – Sampled Measured Value client 7SJ81, 7Sx82 (non modular) O O O
PTP: Precision Time Protocol according to IEEE 1588v2/PTP with 1µs accuracy
7ST85, 6MD89 O O O
LPIT
Optical HSR* or PRP Network
current sensor’
IEC 61869
IEC 61850-9-2
* In preparation
IEC 61850-8-1
Unrestricted © Siemens 2019
Page 25 July 2019 SI DG SA&P / Energy Automation Products
Highlights V7.9 and V8.0
• SIPROTEC DigitalTwin
• Compatibility of SIPROTEC 4 and SIPROTEC 5 for 87L and 21
• IEC 61850-9-2 Process bus for digital substations (Server/Client)
• SIPROTEC 6MU85 Merging Unit
• Time synchronization with IEEE 1588 for High Precision applications
• SIPROTEC 7SS85 distributed busbar protection based on process bus
• Point-on-wave switching
• Conformal coating of SIPROTEC 5 devices as standard
• Cyber Security
• ATEX certification for 7SK85 and 7UM85
• New overcurrent and feeder protection SIPROTEC 7SJ81
• Web Browser
• Further functions
SIPROTEC 5 Merging Unit –
Perfectly tailored fit to your requirements (examples shown)
CT 4 Rogowski CT
12 PCIT Perfectly tailored fit
4 MCIT
VT 4 C devider VT 4 CIT • Adoptable to multiple
BI 111
CT, VT, LPIT inputs
BI 19
BO-STD 91 • Scalable BI and BO
BO-STD 9
BO-HS 8 • Direct “high speed” tripping
BO-HS 4 4 … 20 mA 4 of circuit breaker < 1 ms
• Collection of additional data
Aux-PS Single
(temperature, pressure,
Aux-PS Redundant*
tap changer positions, …)
CT 8 PCIT CT 8 optical*
• Redundant power supply*
VT 8 CIT
VT 4 CIT • Expendable by a 2nd row
BI 11
BI 35
BO-STD 7
TR 1200 IP
BO-STD 15 4 … 20 mA 4
BO-HS 8 RTD 12
PCIT … Protection CIT, MCIT … Measurement CIT
* in preparation
PRP 2 LAN A
PRP 2 LAN B
MU
• Ethernet communication module ETH-BD-2FO for process 7SA86, 7SA87 P
bus functionality required
7SD86, 7SD87 P
• One Sampled Measured Value (SMV) stream per
7SL86, 7SL87 P
ETH-BD-2FO Ethernet module
7VK87 P
• up to 32 analog values in any combination of CT and VT Stream #1
PRP 2 LAN A
PRP 2 LAN B
7SS85 P
• IEC 61869-9, IEC 61869-13 compliant
PRP 1 LAN A
PRP 1 LAN B
7SJ85, 7SJ86 P
• IEC 61850-8-1 GOOSE, MMS and
6MD85, 6MD86 P
Merging Unit protocol on the same Ethernet module Stream #4 Stream #2
6MU85 P
Stream #3 Stream #1
7KE85 O
• Sample synchronization via IEEE 1588v2/PTP
7SJ81, 7Sx82 (non
O
modular)
• Engineering with DIGSI 5 and IEC 61850 System Example:
Maximum configuration of four SMV streams, 7ST85, 6MD89 O
Configurator publishing to two physically separated
networks (four networks possible) Availability of Merging Unit functionality (server)
Simplify complexity
Use of more than one redundant
process bus network reduces the
6MU85 6MU85 6MU85 6MU85 6MU85
network engineering
Feeder CT values
FG VI 10 50 67 FG Circuit 50BF
3ph 1 51 21 Breaker 10 CTRL
FG Line 87L
FG Transf. 50
side 1 51
87 FG Circuit 50BF
FG Transf.
87N Breaker 1 CTRL
FG Transf. 50
6MU85
Process Bus (PRP) side 2 51
FG VI 50 FG Circuit 50BF
3ph 1 51 Breaker 2 CTRL
IEEE 1588v2
/ PTP GMC
FG VI 50 FG Circuit 50BF
Communication ETH-BA-2EL
NEW ETH-BD-2FO
Plug-In Module ETH-BB-2FO
Protocol IEEE 1588v2-2008 IEEE 1588v2-2008
Accuracy 1µs 1 ms
Clock Type Ordinary Slave Clock (OSC) Ordinary Slave Clock (OSC)
• Engineering
• Standard IEC 61850-Konfigurationstools, e.g. IEC 61850 System Configurator
• DIGSI 5
operations
• Longer service life of equipment and reduced
aging
• Increased system reliability (due to reduced voltage
fluctuaions and lower harmonic stress)
Benefits
and PoW function
Necessary Hardware: • One device for all type of loads
• 2x IO209 with high-speed outputs for • Integration into substation automation system
controlled one-phase CB-opening/ with standard protocols like IEC 61850
• 1x IO212 with 8x fast transducer inputs • Easy engineering
Unrestricted © Siemens 2019
Page 43 July 2019 SI DG SA&P / Energy Automation Products
Point-on-Wave Switching with SIPROTEC 5
• The PoW function operates the CB pole-selectively and determines the optimal switching
instance for each phase / pole individually, with an IED accuracy of ~ 50µs
→ PoW switching can only be applied on circuit breaker supporting phase-selective
switching
Switching sequence: C → B → A
Remarks:
• All transducer inputs are passive and require external 24 VDC supply
• CB control voltage must be externally transduced into 4..20 mA
Unrestricted © Siemens 2019
Page 47 July 2019 SI DG SA&P / Energy Automation Products
Point-on-Wave switching device with SIPROTEC 5
Possible Device Types
PoW switching will be a platform functionality. This allows to apply this functionality in different
device application options:
Customer Benefit:
• Highest lifetime and availability of SIPROTEC devices even under
extreme environmental conditions:
• Increased protection against harmful environmental
influences such as corrosive gases, salts, and moisture
• Additional mechanical protection against dust and abrasion
• Highest coating quality due to qualified production process
Cyber Security
Bay level
2. Install in the device the customer CA that is used
to sign the DIGSI 5 client certificates
Unrestricted © Siemens 2019
Page 54 July 2019 SI DG SA&P / Energy Automation Products
Role-based Views In DIGSI 5 (V7.90)
5
Role 1 x x • The role-based views are also
Role 2 x x
…
available for Windows user accounts
that are not centrally managed in AD
Unrestricted © Siemens 2019
Page 55 July 2019 SI DG SA&P / Energy Automation Products
Authenticated Network Access for COM-Modules using IEEE
802.1X (V8.0)
1. Install customer-issued IEEE 802.1X Client 1. Install customer-issued IEEE 802.1X CA certificate
certificates for COM modules (for network in RADIUS Server
client authentication) Customer CA und certificates
can be created and managed
with SICAM GridPass
RADIUS
Server
Bundesanstalt
potentially explosive atmospheres
• Feeder protection
• All network types, medium voltage level
Application
• Dir. & Non-Dir. OC protection with basic functionality • IEC 61850 (Edition 1 and 2)
Device functions
Recording:
• Download, Delete and Trigger of
Fault Records
Parameterization:
• Change of settings within an
active setting-group
Display all signal state:
• Indication of all information
• Centralized view on warnings,
alarms and inactive functions
.....11010110....
.
• Accurate fault location by measuring at both ends of a 2-ended line with communication link via
protection interface (Accuracy of 1%)
• Separate line sections with individual line data for non-homogeneous lines,
e.g. for overhead line/cable sections
• Section specific auto-reclosure (AR) on overhead line sections
The Positive-sequence overcurrent protection function detects short circuits in electric equipment and is
applied when the zero-sequence current or negative-sequence current should not influence the tripping, for
example, on the tertiary delta winding of an auto transformer.