C60N Marine PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Protection Marine C60N circuit breakers

Circuit protection
(curve C, D)

IEC/EN 60947-2
DB123102

DNV Marine approvals


LRS
BV GL
RMRoS b Schneider Electric is committing to have all products Marine type approved by
ABS
RINA
KRS IACS (International Association of Classification Societies):
v ABS, BV, DNV, GL, KRS, LRS, RINA, RMRoS and meet international standards
requirements that are compulsory for the worldwide merchant marine market,
v other classification bodies: please consult us.

b C60N circuit breakers are circuit breakers which combine the following functions:
PB100224_SE-30

PB100226_SE-30

v circuit protection against short-circuit currents,


v circuit protection against overload currents,
v breaking and industrial disconnection as per standards IEC/EN 60947-2.
b The presence of the green strip guarantees physical opening of the contacts and
allows operations to be performed on the downstream circuit in complete safety.

b Increased product service life thanks:


v overvoltage resistance,
C60N 1P C60N 2P v high performance limitation,
v to fast closing independent of the speed of actuation of the toggle.
PB100232_SE-30

PB100233_SE-30

b Upstream or downstream connection.

Positive contact indication


b Suitability for isolation in accordance with the IEC/EN 60947-2 standard.

Alternating current (AC) 50/60 Hz


C60N 3P C60N 4P
Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Service
Voltage (Ue) breaking
Ph/Ph (2P, 3P, 4P) 240 V 415 V - 440 V capacity
(Ics)
Ph/N (1P) - 240 V 415 V -
Rating (In) 1 to 63 A 20 kA 10 kA 3 kA 6 kA 75 % of Icu
iIT 1.2 x 12 In

Catalogue numbers
Marine C60N circuit breaker
Type 1P 2P 3P 4P
1 1 3 1 3 5 1 3 5 7

2 2 4 2 4 6 2 4 6 8

Rating (In) Curve Curve Curve Curve


C D C D C D C D
1A MGN60862 MGN60506 MGN60875 MGN60518 MGN60888 MGN60530 MGN60901 MGN60543
2A MGN60863 MGN60507 MGN60876 MGN60519 MGN60889 MGN60531 MGN60902 MGN60544
3A MGN60864 MGN60508 MGN60877 MGN60520 MGN60890 MGN60532 MGN60903 MGN60545
4A MGN60865 MGN60589 MGN60878 MGN60590 MGN60891 MGN60533 MGN60904 MGN60546
6A MGN60866 MGN60509 MGN60879 MGN60521 MGN60892 MGN60534 MGN60905 MGN60547
10 A MGN60867 MGN60510 MGN60880 MGN60522 MGN60893 MGN60535 MGN60906 MGN60548
16 A MGN60868 MGN60511 MGN60881 MGN60523 MGN60894 MGN60536 MGN60907 MGN60549
20 A MGN60869 MGN60512 MGN60882 MGN60524 MGN60895 MGN60537 MGN60908 MGN60550
25 A MGN60870 MGN60513 MGN60883 MGN60525 MGN60896 MGN60538 MGN60909 MGN60551
32 A MGN60871 MGN60514 MGN60884 MGN60526 MGN60897 MGN60539 MGN60910 MGN60552
40 A MGN60872 MGN60515 MGN60885 MGN60527 MGN60898 MGN60540 MGN60911 MGN60553
50 A MGN60873 - MGN60886 - MGN60899 - MGN60912 -
63 A MGN60874 - MGN60887 - MGN60900 - MGN60913 -
Width in 9-mm modules 2 4 6 8

 version: 1.2 CM901011E.indd


Protection Marine C60N circuit breakers
Circuit protection
(curve C, D) (cont.)

Connection
Rating Tightening Copper cables

DB123103
torque Rigid Flexible or
14 mm with ferrule
5.5 mm

DB122946
DB122945
PZ2

1 to 25 A 2 N.m 1 to 25 mm2 1 to 25 mm2


32 to 63 A 3.5 N.m 1.5 to 35 mm2 1.5 to 35 mm2

Technical data
According to IEC/EN 60947-2
Insulation voltage (Ui) 500 V AC
DB118767

Pollution degree 3
Rated impulse withstand voltage (Uimp) 6 kV
Thermal tripping Nominal temperature 50 °C
for operation
According to ambiant See module 92515
temperature
Magnetic tripping (Ii) C curve 8.5 In ± 20 %
D curve 12 In ± 20 %
Clip on DIN rail 35 mm.
According to current 50/60 Hz
frequency
Utilization category A
DB118772

Compliance with IACS part E10


Other characteristics
Degree of protection Device in modular IP40
enclosure
Endurance (O-F) Electrical 10,000 cycles
Mechanical 20,000 cycles
Service temperature -30°C to +70°C
Storage temperature -40°C to +80°C
Power loss See module 92517
Indifferent position of installation.
Connection Upstream or downstream

Weight (g)
Circuit-breaker
Type C60N
1P 120
2P 240
3P 360
4P 480

Dimensions (mm)
DB122577

CM901011E.indd version: 1.2 