FireWorks v8.1 With Win10

To run FireWorks v8.1 on a Windows 10 system, several steps must be followed: 1. Install minimum system requirements including .NET Framework 3.5 and 4.0. 2. Change DEP settings, turn off antivirus and firewalls, and ensure policies allow for USB and updates. 3. Install FireWorks by copying files to C:\leo folder, running setup, and entering PIN code during installation process. 4. Configure compatibility settings and ports, ensure servers are running, then test the system.

Uploaded by

Ravi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views2 pages

FireWorks v8.1 With Win10

To run FireWorks v8.1 on a Windows 10 system, several steps must be followed: 1. Install minimum system requirements including .NET Framework 3.5 and 4.0. 2. Change DEP settings, turn off antivirus and firewalls, and ensure policies allow for USB and updates. 3. Install FireWorks by copying files to C:\leo folder, running setup, and entering PIN code during installation process. 4. Configure compatibility settings and ports, ensure servers are running, then test the system.

Uploaded by

Ravi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

FireWorks v8.

1 with Win10

To add a stand-alone FireWorks command and control interface to your EST3(X) life safety system, you need the
following:

• A Windows 10 2-in-1 laptop with the following applications installed.

Minimum system requirements


For FireWorks stand-alone, FireWorks nonredundant client, and remote programming applications, we recommend
using a 2-in-1 laptop with the minimum system requirements listed in Table 3 below.

• FireWorks 8.1 (required PINs: FW-CGSUL). For installation instructions, see “Installing the FireWorks 8.1 software”.

Changing the Data Execution Prevention settings


1. Right-click the Start button, and then click System.
2. On the System screen, click Advanced system settings.
3. In the System Properties dialog box, on the Advanced tab, in the Performance group, click Settings.
4. In the Performance Options dialog box, on the Data Execution Prevention tab, click Turn on DEP for essential
Windows programs and services only.

Installing the FireWorks 8.1 software


1. Go to http://www.microsoft.com, and then download and install .NET Framework 3.5 (includes .NET Framework
2.0) and .NET 4.0 Framework Client Profile.
2. Restart the computer.
3. Turn off all antivirus, all malware protection, and all firewalls.
Note: There are typically three firewalls in Windows: Domain, Private, and Public

4. If computers are subject to administrative/group policies or other types of controls, these policies/controls must be
evaluated/modified to ensure that:
• Automatic updates are turned off
Updates should be done manually. If system has redundant servers, the servers should be updated separately at
alternate dates and times.
• USB ports are 100% active
• Terminal services are not used.
Terminal services will shut off the Aladdin/Sentinel/Gemalto hasps, which will stop Edwards software.

5. Go into Window Features, and then do the following:


• Turn on .NET Framework 3.5 (includes .NET 2.0 and 3.0) and both sub options
• Make sure .NET Framework 4.6 Advanced Series and all sub options are selected
• Turn on all options & sub options for Microsoft Message Queue (MSMQ) Server Core
• Turn on all options and sub options for Simple Network Management Protocol (SNMP)
• Turn on Simple TCPIP services (i.e. echo, daytime etc.)
• Turn on Telnet Client
• Turn on TFTP Client
• Apply changes.
6. Run Windows Update and then get all of the latest updates before starting this procedure.
7. Right click on the Windows icon in the lower left of the screen
8. Click Run.
9. Enter Regedit, and then click OK
10. Navigate to: HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Policies\System.
11. In the right pane, look for EnableLUA, click on it and modify its value to 0. Close regedit.
12. Restart computer.

13. Create a folder on the C drive called leo.


14. Copy the entire FireWorks DVD to the leo folder.
15. Turn off ALL network connections (physical and wireless).
16. Right click on the Windows icon in the lower left of the screen.
17. Click Run.
18. Enter the following command to instruct the FireWorks installation routine to ignore the flag for Windows 7 Service
Pack 2: C:\leo\setup nocareaboutSP
19. Click OK.
20. FireWorks will start installation.
21. If hasp is already programmed, use the PIN code fireworks (all lower case, no spaces
22. Note – once you click OK, the computer may appear to hang up – LEAVE IT ALONE! It may take up to half an
hour to go to the next step.
23. FireWorks installation is a multi-step process. The system will have to be rebooted manually when prompted.
24. Move the FireWorks System Builder and System Control icons from the FireWorks folder on the desktop to the
actual desktop.
25. Right click on the FireWorks System Builder icon and go to Properties. Then click on Compatibility and check to
make sure that the Compatibility mode is NOT selected.
26. Right click on the FireWorks System Control icon and go to Properties. Then click on Compatibility and check to
make sure that the Compatibility mode is NOT selected.
27. Do NOT try to adjust the compatibility of the FireWorks programs. If you try that, FireWorks will not run and will
post SQL Automation errors.
28. After installation has been completed & you have verified that FireWorks is running ok, run Windows Update
again.
29. After FireWorks have completed installation and tested, change the EnableLUA value back to 1 and restart.
FireWorks will work with the value at 1, but you cannot do any FireWorks software installation.
30. If you are running FireWorks Network, ALL FireWorks computers must be at the exact same SQL revision level.
Easy way to do this is to run updates on all computers after installation.
31. Once everything is working properly, you can enable antivirus and the firewalls.
32. Run the Edwards FireWorks Ports Batch file (all programs/Edwards)
33. Once FireWorks is running, SHUT OFF Automatic Updates.
34. FireWorks servers MUST be up and running for any nodes or workstations to work. If using Redundant Servers
are used, the PRIMARY must be up and running when you start Workstations for the 1st time.
35. Test system.