100% found this document useful (2 votes)
821 views7 pages

Distance Protection Examples PDF

1) The settings for the three-zone mho relay are: Zone 1: 0.32+j3.2 Ω secondary Zone 2: 0.48+j4.8 Ω secondary Zone 3: 0.72+j7.2 Ω secondary or 8.04∠84.3° Ω secondary The relay will not trip during emergency loading conditions. 2) For a fault at bus 4, the apparent impedance seen by relay B12 is affected by line 2-3 current. If the line 2-3 to 1-2 current ratio is over 0.2, the relay will not see the fault. 3) The load
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
821 views7 pages

Distance Protection Examples PDF

1) The settings for the three-zone mho relay are: Zone 1: 0.32+j3.2 Ω secondary Zone 2: 0.48+j4.8 Ω secondary Zone 3: 0.72+j7.2 Ω secondary or 8.04∠84.3° Ω secondary The relay will not trip during emergency loading conditions. 2) For a fault at bus 4, the apparent impedance seen by relay B12 is affected by line 2-3 current. If the line 2-3 to 1-2 current ratio is over 0.2, the relay will not see the fault. 3) The load
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Power System Protection F2015

Distance Protection Examples

Problem:
1) Three-zone mho relays are used for transmission line protection of the power system shown in Figure 1. Positive-
sequence line impedances are given as follows:
Line Positive-Sequence Impedance, Ω
1–2 6+ j60
2–3 4+ j40
2–4 5+ j50

Rated voltage for the high-voltage buses is 500 kV. Assume a 1500:5 CT ratio and a
4500: 1 VT ratio at B12. (a) Determine the settings Zt1, Zt2, and Zt3 for the mho relay
at B12. (b) Maximum current for line 1–2 under emergency loading conditions is 1400 A
at 0.90 power factor lagging. Verify that B12 does not trip during emergency loading
conditions.

FIGURE 1
1
= = =
15

a) The settings Zt1, Zt2, and Zt3 for the mho relay at B12 are:

Zone1 Zt1=0.8*Z12=0.8*(6+j60)/15= 0.32+j3.2 Ω secondary


Zone 2 Zt2= 1.2*(6+j60)/15=0.48+j4.8 Ω secondary
Zone 3 Zt3= Z12+1.2*Z23
=(6+j60)/15+1.2*(4+j40)/15=0.72+j7.2 Ω secondary

Or =(6+j60)/15+1.2*(5+j50)/15=0.8+j8 Ω secondary =8.04∠84.3° Ω secondary


Usually the longest line is chosen

b) The secondary impedance s`een by B!@ during emergency loading is:


Zsec= Zpr*CTratio/VTratio= VLN/IL*(1/15)
-..
%&' * *
( ! ") =$ (&
)$ ) = ,
*+
√0
*.2∠4 ! 56 7.8
9 $*+) = 13.7∠025.8° Ω
Zsec at emergency loading lies outside the trip region of zone 3. So the moh-relay does not trip.
2) Line impedances for the power system shown in Figure 2 are Z12 = Z23 =3+ j40Ω, and Z24 = 6+ j80 Ω. Reach for the
zone 3 B12 impedance relays is set for 100% of line 1–2 plus 120% of line 2–4.
(a) For a bolted three-phase fault at bus 4, show that the apparent primary impedance ‘‘seen’’ by the B12 relays is
Zapparent = Z12 + Z24+(I32/I12)Z24
where(I32/I12) is the line 2–3 to line 1–2 fault current ratio.

(b) If |I32=I12| > 0.20, does the B12 relay see the fault at bus 4? Note: This problem illustrates the ‘‘infeed effect.’’ Fault
currents from line 2–3 can cause the zone 3 B12 relay to underreach. As such, remote backup of line 2–4 at B12 is
ineffective.

FIGURE 2

B* E E E EC
a) The apparent primary impedance seen by relay B12 is
*D CF C *D C
̅ =, 9= = F
̅
*C
̅
*C
̅
*C
̅
*C

EC
̅ ̅ F
= *C
̅
*C

Since V2=Z24 I24 and I24=I12+I32

̅
C2 ( *C F GC )
̅ ̅ F
= *C ̅ ̅ F C2
= *C ̅ F GC
̅ ̅ C2
*C*C


b) The apparent secondary impedance seen by relay B12 for fault at bus 4 is :
̅ 4 = ̅ = *C̅ F C2 ̅ F GC C2̅
̅
*C


̅ = H3 F I40 F (6 F I80) F
GC
(6 F I80)L
4 ̅
*C
Zone 3 of relay B12
MN O!
Zone 3 Zt3= (Z12+1.2*Z24)
%N O!
=
MN O ! MN O!
(3 F I40 F 1.2(6 F I80)) = (10.2 F I136)
%N O! %N O!
(0P
When ̅ Q 0.2
(6P
Zapp-secQ Zt3 ∴ Zapp-sec lies outside the trip reqion ofr a 3-phase fault at bus 4.
Remote backup od line 2-4 us then ineffective.
3) Consider the transmission line shown in Figure 3 with series impedance ZL, negligible shunt admittance, and a load
impedance ZR at the receiving end.
(a) Determine ZR for the given conditions of VR = 1 per unit and SR = 2+ j0.8 per unit.
(b) Construct the impedance diagram in the R-X plane for ZL = 0.1 +j0.3 per unit.
(c) Find ZS for this condition and the angle d between ZS and ZR.

( ER )C (1)C
FIGURE 3

= ∗ = 0.431 F I0.1724 UV
R EEE
S R (2 D 0.8)
The R-X diagram is given in FIGURE 4

FIGURE 4

̅ = ̅ F R̅ = (0.1 F 0.431) F I(0.3 F 0.1724) UV = 07107∠41.66°

0.1724
W = X F XR = 41.66° D Y4* = 19.66°
0.431
FIGURE 5

You might also like