Fire Water Tank Foundation - Design
Fire Water Tank Foundation - Design
(English Units)
Project No. 1952.000
Rev. No.
1 Service : CRUDE OIL Storage Equipment No. : T-400 & T-405
2 Location : Unit : Kirwin Design Engineer :
3 Manufacturer : Model : Mfr Ref. No. : No. Req'd : Two
4 P&ID No. PID115-EPF-01-112A1 Plot Plan No. : Other Ref. Dwg No. :
5
6
7
8
9 M
A P G
10
11
12
13 18.00 Ft
14 48" X 48"
H
15 15.00 Ft FLUSH
E CLEANOU E
16 T K
17
L F D
18
19 N N
J I
20 1 2
21
22
23
24 Shell Diameter : 18.00 Feet Shell Height : 15.00 Feet Nominal Volume : 680 Barrels
25 Roof Type : Cone Bottom Floor Type: Sloped
26 OPERATING/DESIGN DATA NOZZLES/CONNECTIONS
27 Fluid Stored : CRUDE OIL Sp. Gr. : 0.7900 Mark Service Qty Size Rating Face
28 This Tank Service is considered: Cyclic A Roof Manway 2 24" 150# F. F.
29 Vapor Pressure @ Max. Operating Temperature 5.5 psia E Shell Manway 2 24" 125# R. F.
30 Flash Point (Closed Cup) : ºF Operating Design F Flush Cleanout MW 1 48"x48" 125# R. F.
31 Negative Pressure oz/in.2 0.00 0.50 G Stilling Vent 1 6" 125# F. F.
32 Positive Pressure psig 1.00 2.00 H Temperature Indicator 1 1" 150# L. J.
33 (Hydro)test Pressure expressed in Psig ---- I Outlet Nozzle 1 8" 150# API
34 Minimum Fluid Temperature ºF -25 J Fill Nozzle 1 10" 150# L. J.
35 Maximum Fluid Temperature ºF 200 K Mixer Manway 1 30" 150# F. F.
36 Emergency Vacuum Design ? Yes Set @ 0.0.3 oz/in.2 L Water Draw Nozzle 1 4" 150# R. F.
37 METALLURGY M Top Center Vent 1 8" 150# API
38 Component Material CA, in. Remarks N1 Sample Tap 1 3/4" 150# R. F.
39 Shell & Bottom 57370 0.1250 Normalized N2 Sample Tap 1 3/4" 150# F. F.
40 Roof 516 Grade 55 0.1250 Normalized P Roof Nozzle 1 4" 150# L. J.
41 Lining/Coating D Spare 1 2" 150# API
42 150# API
43 Stress Relieve ? Yes for: 150# API
44 CONSTRUCTION/FABRICATION
45 Code (as appl.): API 650 LATEST EDITION Internals (attach separate sheet, as req'd): Others:
46 Design Specifications: Sump
47 Tank Insulation ? No Thickness : in. Seismic Zone 2 Design Wind Velocity 100 mph
48 Insulation Type: Hot Radiograph 85 % Inspection Req'd ? Yes
49 Fireproofing ? Yes Paint Spec. EmptyTank Weight lb Full of Water lb
50 Remarks
51 1. Items marked with an asterisk (*) to be completed by Vendor/Fabricator.
52 2. Fixed cone roof with internal floating roof.
Approvals
Rev Date Description By Chk. Appr. Rev Date Description By Chk. Appr.
0 For Inquiry
March 12, 2002
Art Montemayor API 650 Storage Tank
Rev: 0
API 650 Design Calculations
FileName: 451153242.xls
Page 2 of 7
WorkSheet: Steel Design
March 12, 2002
Art Montemayor API 650 Storage Tank
Rev: 0
FileName: 451153242.xls
Page 3 of 7
WorkSheet: Steel Design
March 12, 2002
Art Montemayor API 650 Storage Tank
Rev: 0
FOUNDATION DESIGN:
DATA GIVEN:
Seismic Zone; 2
Zone Coefficient Z= 0.15
Importance Factor I = 1.0
Response Modification Factor R= 8.0
Numerical Coefficient C= 2.8
Diameter of Tank D= 18 ft
Height of Liquid Content (Design) H= 12.5 ft
Shell Height Hs = 15 ft
Design Specific Gravity G= 0.79
Thickness of Bottom PL Under Shell tb = 0.3750 in
Yeild Strength of Bottom PL Fby = 36,000 PSI
Weight of Shell Ws = 18 Kips
Weight of Roof + Live Load = 2.5 + 7.63 Wy = 10.13 Kips
Weight of Product PI()/4(18)2 (12.5)(.79)(62.4) Wt = 157 Kips
FOUNDATION DESIGN:
Seismic Loads:
Overturning moment:
Ms = (Z)(I) { (C)(Ws)(Xs)+(C)(Wr)(Ht)+(C)(Wt)(Xt)}
Reistance to Overturning:
Mr = 0.5D(Wt+Ws+Wr+Wf) 2,141 Ft-Kips
FileName: 451153242.xls
Page 4 of 7
WorkSheet: Foundation Design - 1
March 12, 2002
Art Montemayor API 650 Storage Tank
Rev: 0
FOUNDATION DESIGN:
RINGWALL DESIGN:
Use Following Weight Values for Materials
F=Kah(g*p*H+1/2 soh)+270
0.3*5.0[(50*12.5+0.5*120*5.0)]+270 1,658 lb
Hoop Tension:
(2)(282)/50(15)-2(5.0)(150-120) 1.25
Use 15" Thick Concrete Wall
12"
Top of Ground Elevation
15"
60"
15"
FileName: 451153242.xls
Page 5 of 7
WorkSheet: Foundation Design - 2
March 12, 2002
Art Montemayor API 650 Storage Tank
Rev: 0
Case 1
Case 2
FileName: 451153242.xls
Page 6 of 7
WorkSheet: Foundation Design - 2
March 12, 2002
Art Montemayor API 650 Storage Tank
Rev: 0
DETAILED FOUNDATION DESIGN:
9" - 0"
12" 8"
USE - # 4 @ 6" c/c Bars in Footng
Well-Compacted Gravel
95% Compacted
50 / 100 % Passing # 4 Sieve
1'-3" Wall
15"
3' - 0"
NOTES:
1. Oiled sand to be mixture of sand and liquid asphalt (mc70):
2. Use 10 gallons of asphalt per cubic yard of sand:
3. Top of concrete to be smooth and level with 1/8" +/- in any 30 feet of circumferential length:
4. Maximum Deiation to be less than 1/4" overall:
FileName: 451153242.xls
Page 7 of 7
WorkSheet: Foundation Design - 3