Quiz #1 Solution

The document contains solutions to two electrical engineering problems. The first problem involves calculating the reactive power required from a parallel capacitor to bring the power factor of a 1φ load up to 0.9. The second problem involves calculating the induced voltage per mile in a telephone line located near a three-phase power line with balanced currents of 100A in each phase.

Uploaded by

蔡欣祐
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views3 pages

Quiz #1 Solution

The document contains solutions to two electrical engineering problems. The first problem involves calculating the reactive power required from a parallel capacitor to bring the power factor of a 1φ load up to 0.9. The second problem involves calculating the induced voltage per mile in a telephone line located near a three-phase power line with balanced currents of 100A in each phase.

Uploaded by

蔡欣祐
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Quiz #1

1.A certain 1ϕ load draws 5 MW at 0.7 power factor lagging. Determine the

reactive power required from a parallel capacitor to bring the power factor of

the parallel combination up to 0.9.

Sol:

𝑆 = 𝑉𝐼∗ = |𝑉||𝐼|𝑒 𝑗∅ = |𝑆|∠∅ = 𝑃 + 𝑗𝑄


𝟓
𝑷 = 𝐒𝟏 𝒄𝒐𝒔 ∅𝟏 → 𝟓 = 𝐒𝟏 × 𝟎. 𝟕 → 𝐒𝟏 =
𝟎. 𝟕

𝒄𝒐𝒔 ∅𝟏 = 𝟎. 𝟕 → ∅𝟏 = 𝟒𝟓. 𝟓𝟕𝟑𝟎


𝟓 𝟓
𝐐𝟏 = 𝑺 𝐬𝐢𝐧 ∅𝟏 → 𝐐𝟏 = × √𝟏 − 𝐜𝐨𝐬 ∅𝟏 𝟐 → 𝐐𝟏 = × √𝟏 − 𝟎. 𝟕𝟐 =
𝟎.𝟕 𝟎.𝟕

𝟓. 𝟏𝟎𝑴𝑽𝑨𝒓

𝒄𝒐𝒔 ∅𝟐 = 𝟎. 𝟗 → ∅𝟐 = 𝟐𝟓. 𝟖𝟒𝟎

𝟓
𝑷 = 𝐒𝟐 𝒄𝒐𝒔 ∅𝟐 → 𝟓 = 𝐒𝟐 × 𝟎. 𝟗 → 𝐒𝟐 =
𝟎. 𝟗
𝟓 𝟓
𝐐𝟐 = 𝐒𝟐 𝐬𝐢𝐧 ∅𝟐 → 𝐐𝟐 = × √𝟏 − 𝐜𝐨𝐬 ∅𝟐 𝟐 → 𝐐𝟐 = × √𝟏 − 𝟎. 𝟗𝟐 =
𝟎.𝟗 𝟎.𝟗

𝟐. 𝟒𝟐𝑴𝑽𝑨𝒓

𝐐 = 𝐐𝟏 − 𝐐𝟐 = 𝟓. 𝟏𝟎 − 𝟐. 𝟒𝟐 = 𝟐. 𝟔𝟖 𝑴𝑽𝑨𝒓
2. A three-phase power line with a flat horizontal spacing of 5 ft between phases ;

the telephone wire spacing is 12 in. The nearest conductors of the two lines

are 20 ft apart. The power line currents are balanced three-phase each of

magnitude 100A. Find the magnitude of the induced “loop” or “round-trip”

voltage per mile in telephone line. Assume that the telephone wire radius is

negligible.

5’ 5’ 20’ 1’
𝒊𝒂 𝒊𝒃 𝒊𝒄

Sol:

想要得到感應電壓,先要計算電源線( A.B.C 相電流)到電話線的通量,然

後再利用法拉第定律算出電壓。

(1)從最左邊的電源線(A 相電流)到電話線的磁鏈為:
𝟑𝟏
𝝁𝒊 𝝁𝒊 𝟑𝟏 𝟏 𝝁𝒊 𝟑𝟏
𝛌𝑰𝑨 = ∫ 𝑩 • dA = ∫ 𝒅𝒙 = ∫ 𝒅𝒙 = 𝒍𝒏
Surface A 𝟑𝟎 𝟐𝝅𝒙 𝟐𝝅 𝟑𝟎 𝒙 𝟐𝝅 𝟑𝟎

(2)從中間的電源線(B 相電流)到電話線的磁鏈為:
𝟐𝟔
𝝁𝒊 𝝁𝒊 𝟐𝟔 𝟏 𝝁𝒊 𝟐𝟔
𝛌𝑰𝑩 = ∫ 𝑩 • dA = ∫ 𝒅𝒙 = ∫ 𝒅𝒙 = 𝒍𝒏
Surface A 𝟐𝟓 𝟐𝝅𝒙 𝟐𝝅 𝟐𝟓 𝒙 𝟐𝝅 𝟐𝟓

(3)從最左邊的電源線(C 相電流)到電話線的磁鏈為:
𝟐𝟏
𝝁𝒊 𝝁𝒊 𝟐𝟏 𝟏 𝝁𝒊 𝟐𝟏
𝛌𝑰𝑪 = ∫ 𝑩 • dA = ∫ 𝒅𝒙 = ∫ 𝒅𝒙 = 𝒍𝒏
Surface A 𝟐𝟎 𝟐𝝅𝒙 𝟐𝝅 𝟐𝟎 𝒙 𝟐𝝅 𝟐𝟎
𝝁 𝟑𝟏 𝟐𝟔 𝟐𝟏
𝛌 = 𝛌𝑰𝑨 + 𝛌𝑰𝑩 + 𝛌𝑰𝑪 = (𝒊𝑨 𝒍𝒏 + 𝒊𝑩 𝒍𝒏 + 𝒊𝑪 𝒍𝒏 )
𝟐𝝅 𝟑𝟎 𝟐𝟓 𝟐𝟎

Let Positive sequence (abc)

μ=4π×10-7

𝟑𝟏 𝟐𝟔 𝟐𝟏
𝛌 = 𝟐 × 𝟏𝟎−𝟕 (𝒊𝑨 𝒍𝒏 + 𝒊𝑩 𝒍𝒏 + 𝒊𝑪 𝒍𝒏 )
𝟑𝟎 𝟐𝟓 𝟐𝟎

= 𝟐 × 𝟏𝟎−𝟕 (𝟎. 𝟎𝟑𝟐𝟖𝒊𝑨 + 𝟎. 𝟎𝟑𝟗𝟐𝒊𝑩 + 𝟎. 𝟎𝟒𝟖𝟖𝒊𝑪 )

𝒅𝝀
𝐕𝒕𝒆𝒍 = = 𝝎 × 𝟐 × 𝟏𝟎−𝟕 (𝟎. 𝟎𝟑𝟐𝟖𝒊𝑨 + 𝟎. 𝟎𝟑𝟗𝟐𝒊𝑩 + 𝟎. 𝟎𝟒𝟖𝟖𝒊𝑪 )
𝒅𝒕

|𝐕𝒕𝒆𝒍 | = 𝟐𝝎 × 𝟏𝟎−𝟕 × 𝟏𝟎𝟎 |𝟎. 𝟎𝟑𝟐𝟖 + 𝟎. 𝟎𝟑𝟗𝟐∠ − 𝟏𝟐𝟎 + 𝟎. 𝟎𝟒𝟖𝟖∠𝟏𝟐𝟎|