RE316SERIES

Photoelectric Smoke And/Or ROR &


Fixed Temperature Heat Detector
Installation Wiring Diagram
TYPICAL WIRING DIAGRAM
Figure 1(a) shows the typical wiring diagram of the 2-wire
multiple-station smoke/heat detector system.

LOOP RECTANGULAR LED


MAGNET TEST

6 2 6 2 EOL
DETECTOR HEAD

COMPATIBLE
CONTROL 5 4 5 4 RESISTOR

PANEL BRACKET

OPTIONAL REMOTE LED OPTIONAL REMOTE LED


OPTIONAL RETURN WIRING
LED ALIGNMENT MARK
RE316 2 WIRE DETECTORS WIRING DIAGRAM

Figure 1(b) shows the typical wiring diagram of the 4-wire Fig. 2 Mating detector head onto base
multiple-station smoke/heat detector system.
ADJUSTING THE RELAY FOR NO/NC
The default condition of relay output is “normally open” (NO).

1. To adjust the default condition of relay to “normally closed” (NC),


take the screw out located on the side between the front cover and
base.

2. Refer to figure 3. There is a jumper head next to the relay on the


PCB. Remove the jumper head and re-insert it in the NC position.

3. replace the front JUMPER SETTING


cover. Carefully
RELAY

Relay contact SMOKE CHAMBER


rating:
1A@30VDC,
0.5A@125VAC. MAGNET TEST

DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS OF


TERMINALS 2 AND 5 TO PROVIDE POWER SUPERVISION.
WARNING
TO PREVENT DETECTOR CONTAMINATION AND SUBSEQUENT
WARRANTY CANCELLATION, THE SMOKE DETECTOR MUST
REMAIN COVERED UNTIL THE AREA IS CLEAN AND DUST
FREE.
INSTALLING THE BASE LED
1. To insure proper installation of the detector head to the base, all
the wires should be properly addressed at installation:
(A) Position all the wires flat against terminals.
(B) Fasten the wires away from connector terminals. Fig. 3 Schematic of detector structure
2. If you use a jumper wire to connect the poles of terminal 2 and 5 When front cover is open.
when testing the detector loop continuity, be sure to remove the
TESTING
jumper wire prior to the installation of the detector head.
3. The end-of-line device shown in fig. 1(a) and 1(b) should be 1. All the alarm signal services, releasing device and extinguisher
compatible with the control unit. system should be disengaged during the test period and must be
4. Open area smoke detectors are intended for mounting on a ceiling re-engaged immediately at the conclusion of testing.
or a wall in accordance with the fire standard in your country. 2.After energizing the detector head for approximately 60 seconds,
5. The base of the smoke detector can be mounted directly onto an check to see the indicator red LED flashing once every 4~5
electrical junction box such as an octagonal (75mm, 90mm or seconds. If red LED fails to flash, it indicates the non-functioning of
100mm), a round (75mm), or a square (100mm) box without using the detector or faulty wiring. Re-check the wiring or replace the
any type of mechanical adapter. detector if necessary.
INSTALLING THE HEAD
1. Align the components as shown in Figure 2.
2. Mate the detector head onto the base and twist clockwise to REED SWITCH TESTING
secure it. Take the magnet against the position of top cover marked in Fig.2.
3. Do not install the detector head until the area is thoroughly the detector will alarm after flashing once every 1.1seconds
cleaned of construction debris, dusts, etc. continuously for several times. If the detector fails to alarm, please
re-check the magnet close to the mark on the toper or replace the
detector if necessary.
SMOKE SENSOR TESTING SPECIFICATION
Allow smoke from a cotton wick or a test smoke aerosol to enter Fixed Temperature Sensor: 138F (59C)
the detector-sensing chamber for several seconds. When Rate-of-Rise Temperature Sensor: 20℉/min(11.1C /min)
sufficient smoke has entered the chamber, the detector will signal Humidity Range: 0% to 95% Relative Humidity, non condensing
Operating Temperature Range: -10°C to 37.8°C
an alarm, this being visible by a continuous illumination of the LED. The maximum number of detectors allowed to be connected to each
Reset each detector and/or control unit before attempting to test initiating device circuit of the control unit is 32.
any additional detectors in the same zone. If the alarm fails in this Compatible Panel: Ravel Electronics Pvt Ltd., RE -2504 / 08.
step, it indicates a defective unit, which requires service. Height: 1.8 inches (46 mm) with base
Diameter: 3.93 inches (100 mm) with base
HEAT SENSOR TESTING Detail as shown in Form.1
The detector to be tested should be subject to a flow of warm air at a
temperature of between 65°C and 80°C. (This requirement can be Smoke detectors are not to be used with detector guards unless
met by some domestic hair dryers). the combination as been evaluated and found suitable for that
Proceed as follows: purpose.
1. Switch on the warm airflow and check that temperature is correct
and stable. MAINTENANCE
2. From a distance of several inches, direct the airflow at the guard The recommended minimum requirement for detector maintenance
protecting the thermistor. The detector should alarm within 60 consists of an annual cleaning of dust from the detector head by
seconds. using a vacuum cleaner cleaning program should be agreed to the
3. Upon alarm, immediately remove the heat source and check individual environment in conformance with NFPA-72A standard.
that the red LED of the detector is illuminated. Reset the detector
from the control panel. CAUTION: DO NOT ATTEMPT TO DISASSEMBLY OF THE
4.If detector fails to go into alarm mode within 60 seconds it is too FACTORY SEALED SMOKE DETECTOR. THIS ASSEMBLY IS
insensitive and needs to be returned to the distributor for servicing. SEALED FOR YOUR PROTECTION AND IS NOT INTENDED TO
BE OPENED FOR SERVICING BY USERS. OPENING THE
5. After testing, check that the system is set for normal operation and DETECTOR HEAD WILL VOID THE WARRANTY.
notify the appropriate authorities that the testing operation is
complete and the system is active again.
REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO.
NBTB20081017, REV.F
Model 2/4 Thermal Voltage Standby Alarm Surge Start-up Reset Reset Sample Smoke Heat Reed Relay Remote Base model
Wire Current Current Current Time Time Voltage Cycle Sensor Sensor Switch Outpu LED
t
RE316S-2 2 - 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ RE-312
RE316S-2M 2 - 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ RE-312
RE316S-4 4 - 9~33V 50uA 40mA 170uA 60s 3s <1V 5s √ √ RE-314
RE316S-4M 4 - 9~33V 50uA 40mA 170uA 60s 3s <1V 5s √ √ √ RE-314
RE316S-2L 2 - 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ RE-314
RE316S-2LM 2 - 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ √ RE-314
RE316H-2 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ RE-312
RE316H-2M 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ RE-312
RE316H-4 4 59C 9~33V 50uA 40mA 170uA 60s 3s <1V 5s √ √ RE-314
RE316H-4M 4 59C 9~33V 50uA 40mA 170uA 60s 3s <1V 5s √ √ √ RE-314
RE316H-2L 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ RE-314
RE316H-2LM 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ √ RE-314
RE316SH-2 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ RE-312
RE316SH-2M 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ √ RE-312
RE316SH-4 4 59C 9~33V 50uA 40mA 170uA 60s 3s <1V 5s √ √ √ RE-314
RE316SH-4M 4 59C 9~33V 50uA 40mA 170uA 60s 3s <1V 5s √ √ √ √ RE-314
RE316SH-2L 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ √ RE-314
RE316SH-2LM 2 59C 9~33V 50uA 90mA 170uA 60s 3s <1V 5s √ √ √ √ RE-314
RE316 USER’s MANUAL ,REV.F
Form.1
Note: * 1 If a model with the “-2” suffix, the Base model no. is RE-312
*2 If a model with the “-2L” or “-4” suffix, the Base model no. is RE-314

LIMITED WARRANTY STATEMENT


RAVEL ELECTRONICS, Inc. represents that this product is free from defects in material and workmanship. And it will repair or replace any product or
part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from the date of purchase but not to exceed
eighteen (18) months after shipment by the manufacturer. For a full description of RAVEL ELECTRONICS’S LIMITED WARRANTY, which, among
other things, limits the duration of warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages.
Please read the entire LIMITED WARRANTY on the RAVEL quotation. Acceptance of order and/or original invoice which will become part of your sales
agreement. Please contact RAVEL ELECTRONICS directly for a return merchandise authorization (RMA) number before returning goods to the factory
in Chennai, India R.O.C. Shipment must be prepaid and RAVEL will repair or replace your returned detector.

RAVEL ELECTRONICS PRIVATE LIMITED.

150A, Electronic Industrial Estate, Perungudi, Chennai – 600 096. Tamil Nadu, India.

Tel: +91-44-2496-1004 / 0825 / 3241 / 3251; Fax: +91-44-4204-9599

http://www.ravelfirepanels.com

ISSUE NO.NBUM 20081017 REV.F