Sprinkle & Trickle Irrigation Lecture Notes PDF
Sprinkle & Trickle Irrigation Lecture Notes PDF
Sprinkle & Trickle Irrigation Lecture Notes PDF
Lecture Notes
BIE 5110/6110
Fall Semester 2004
Copyright Notice
These lecture notes are formatting for printing on both sides of the page, with
odd-numbered pages on the front. Each lecture begins on an odd-numbered
page, so some even-numbered pages are blank.
Sprinkle Irrigation
1 Course Introduction.................................................................................... 9
2 Types of Sprinkler Systems; Soil-Water-Plant Relationships;
Planning Factors ...................................................................................... 11
3 Sprinkler Characteristics; Application Rates ............................................ 25
4 Set Sprinkler Uniformity & Efficiency........................................................ 39
5 Layout of Laterals & Mainline for Set Sprinklers; Pipe Hydraulics............ 51
6 Economic Pipe Selection Method............................................................. 59
7 Set Sprinkler Lateral Design .................................................................... 71
8 Set Sprinkler Lateral Design & Analysis................................................... 85
9 Mainline Pipe Design ............................................................................. 101
10 Minor Losses, Pressure Requirements & Pumps................................... 111
11 Pumps & System Curves; Affinity Laws & Cavitation ............................. 123
12 Center Pivot Design & Operation ........................................................... 145
13 Center Pivot Nozzling & Hydraulic Analysis ........................................... 155
14 Center Pivot Uniformity Evaluation; Linear Move Systems .................... 169
15 Maximizing Linear Move Field Length; Design Example ........................ 179
Trickle Irrigation
16 Components & Layout; Pressure Control & Flow Regulation ................. 189
17 Filtration for Trickle Irrigation Systems ................................................... 197
18 Trickle Irrigation Planning Factors; Salinity in Trickle Irrigation .............. 207
19 Water Requirements; Coefficient of Variation & System Capacity ......... 215
20 Emitter Selection & Design; Design Approach & Example ..................... 225
21 Pipe Specifications & Lateral Design; Manifold Location ....................... 231
22 Numerical Solution for Manifold Location; Derivations ........................... 241
23 Manifold Hydraulic Design ..................................................................... 253
24 Hydraulic Design of Mainline & Supply Line........................................... 275
6.89 kPa/psi
1 cb = 1 kPa
10 mb/kPa, or 100 kPa/bar
2.308 ft/psi, or 9.81 kPa/m (head of water)
14.7 psi = 101.3 kPa = 10.34 m (head of water) = 1,013 mbar = 1 atm
62.4 lbs/ft3, or 1000 kg/m3 (max density of pure water at 4°C)
0.1333 kPa/mmHg
0.7457 kW/HP
1 langley = 1 cal/cm2
0.0419 MJ/m2 per cal/cm2
0.3048 m/ft
1.609 km/mile
2.471 acre/ha
43,560 ft2/acre
1,233 m3/acre-ft
57.2958 degrees/radian
π ≈ 3.14159265358979323846
e ≈ 2.71828182845904523536
ºC = (ºF – 32)/1.8
ºF = 1.8(ºC) + 32
Ratio of weight to mass at sea level and 45° latitude: g = 9.80665 m/s2
I. Course Overview
V. Units
Important Advantages
Important Disadvantages
Hand-Move
End-Tow
Side-Roll
Side-Move
• almost the same as side-roll, but lateral pipe is not axle: it is mounted on A frames
with two wheels each
• clearance is higher than for side-roll
• not as common as side-roll sprinklers
Gun
Boom
• have big gun sprinklers mounted on rotating arms, on a trailer with wheels
• arms rotate due to jet action from nozzles
• arms supported by cables
• large water drops; commonly used on pastures, but also on other crops
• Perforated Pipe
• Hose-Fed Sprinklers
• Orchard Sprinklers
Traveler
Center Pivot
• cost is typically $35,000 ($270/ac or $670/ha), plus $15,000 for corner system
• easily automated
• typical maximum (fastest) rotation is about 20 hrs
• don’t rotate in 24-hr increment because wind & evaporation effects will concentrate
• returns to starting point after each irrigation
• typical lateral length is 1320 ft (400 m), or ¼ mile (quarter “section” area)
• laterals are about 10 ft above the ground
• typically 120 ft per tower (range: 90 to 250 ft) with one horsepower electric motors
(geared down)
• IPS 6” lateral pipe is common (about 6-5/8 inches O.D.); generally 6 to 8 inches, but
can be up to 10 inches for 2640-ft laterals
• typical flow rates are 45 - 65 lps (700 to 1000 gpm)
• typical pressures are 140 - 500 kPa (20 to 70 psi)
• older center pivots can have water driven towers (spills water at towers)
• end tower sets rotation speed; micro switches & cables keep other towers aligned
• corner systems are expensive; can operate using buried cable; corner systems don’t
irrigate the whole corner
• w/o corner system, π/4 = 79% of the square area is irrigated
• for 1320 ft (not considering end gun), area irrigated is 125.66 acres
• with corner system, hydraulics can be complicated due to end booster pump
• center pivots are ideal for allowing for effective precipitation
• ignore soil water holding capacity (WHC)
• requires almost no labor; but must be maintained, or it will break down
• can operate on very undulating topography
• known to run over farmers’ pickups (when they leave it out there)!
• many variations: overhead & underneath sprinklers; constant sprinkler spacing;
varied sprinkler spacing; hoses in circular furrows, etc.
• sprinkler nearest the pivot point may discharge only a fine spray; constant radial
velocity but variable tangential speeds (fastest at periphery)
• some center pivots can be moved from field to field
Linear Move
I. Irrigation Depth
MAD
dx = Wa Z (1)
100
where dx is the maximum net depth of water to apply per irrigation; MAD is
management allowed deficit (usually 40% to 60%); Wa is the water holding
capacity, a function of soil texture and structure, equal to FC – WP (field
capacity minus wilting point); and Z is the root depth
• For most agricultural soils, field capacity (FC) is attained about 1 to 3 days
after a complete irrigation
• The dx value is the same as “allowable depletion.” Actual depth applied may
be less if irrigation frequency is higher than needed during peak use period.
• MAD can also serve as a safety factor because many values (soil data, crop
data, weather data, etc.) are not precisely known
• Assume that crop yield and crop ET begins to decrease below maximum
potential levels when actual soil water is below MAD (for more than one day)
• Water holding capacity for agricultural soils is usually between 10% and 20%
by volume
• Wa is sometimes called “TAW” (total available water), “WHC” (water holding
capacity), “AWHC” (available water holding capacity)
• Note that it may be more appropriate to base net irrigation depth calculations
on soil water tension rather than soil water content, also taking into account
the crop type – this is a common criteria for scheduling irrigations through the
use of tensiometers
dx
fx = (2)
Ud
• The value of ET during the peak use period depends on the crop type and on
the weather. Thus, the ET can be different from year to year for the same
crop type.
• Some crops may have peak ET at the beginning of the season due to land
preparation requirements, but these crops are normally irrigated by surface
systems.
• When a system is to irrigate different crops (in the same or different
seasons), the crop with the highest peak ET should be used to determine
system capacity.
• Consider design probabilities for ET during the peak use period, because
peak ET for the same crop and location will vary from year-to-year due to
weather variations.
Merkley & Allen Page 16 Sprinkle & Trickle Irrigation Lectures
• Consider deficit irrigation, which may be feasible when water is very scarce
and or expensive (relative to the crop value). However, in many cases
farmers are not interested in practicing deficit irrigation.
• Leaching may be necessary if annual rains are not enough to flush the root
zone, or if deep percolation from irrigation is small (i.e. good application
uniformity and or efficiency).
• If ECw is low, it may not be necessary to consider leaching in the design
(system capacity).
• Design equation for leaching:
EC w
LR = (4)
5ECe − EC w
dn
LR ≤ 0.1: d= (5)
Ea
0.9 dn
LR > 0.1 d= (6)
(1 − LR)Ea
• When LR < 0.0 (a negative value) the irrigation water is too salty, and the
crop would either die or suffer severely
• Standard salinity vs. crop yield relationships (e.g. FAO) are given for
electrical conductivity as saturation extract
• Obtain saturation extract by adding pure water in lab until the soil is
saturated, then measure the electrical conductivity
• Here are some useful conversions: 1 mmho/cm = 1 dS/m = 550 to 800 mg/l
(depending on chemical makeup, but typically taken as 640 to 690). And, it
can usually be assumed that 1 mg/l ≈ 1 ppm, where ppm is by weight (or
mass).
Suppose ECw = 2.1 mmhos/cm (2.1 dS/m) and ECe for 10% reduction in crop
yield is 2.5 dS/m. Then,
EC w 2.1
LR = = = 0.20 (7)
5ECe − EC w 5(2.5) − 2.1
Thus, LR > 0.1. And, assuming no loss of water due to application nonuniformity,
the gross application depth is related to the net depth as follows:
dn
d = dn + (LR)d = (8)
1 − LR
and,
dn
d= = 1.25dn (9)
1 − 0.20
• The authors of the textbook only devote a few paragraphs to this topic, but it
is one of great importance
• A complete understanding of the distinctions between farm and field systems
comes only through years of experience
• Variability in design, operation and management conditions is limitless
• visit the field site personally if at all possible, and talk with the farmer
• get data on soil, topography, water supply, crops, farm schedules, climate, energy,
etc.
• be suspicious of parameter values and check whether they are within reasonable
ranges
• this step is unnecessary for automated fixed systems and center pivots
(a) determine Se, qa, nozzle size, and P for optimum application rate
(Tables 6.4 to 6.7)
(b) determine number of sprinklers to operate simultaneously to meet Qs
(Nn = Qs/qa) (Chapter 7)
(c) decide upon the best layout of laterals and mainline (Chapter 7)
(d) Adjust f, d, and/or Qs to meet layout conditions
(e) Size the lateral pipes (Chapter 9)
(f) Calculate the maximum pressure required for individual laterals
9. Calculate the mainline pipe size(s), then select from available sizes
10. Adjust mainline pipe sizes according to the “economic pipe selection method”
(Chapter 10)
Sprinkle & Trickle Irrigation Lectures Page 19 Merkley & Allen
11. Determine extreme operating pressure and discharge conditions (Chapter 11)
12. Select the pump and power unit (Chapter 12)
13. Draw up system plans and make a list of items with suggestions for operation
III. Summary
• Note that MAD is not a precise value; actual precision is less than two
significant digits; this justifies some imprecision in other values (don’t try to
obtain very precise values for some parameters when others are only rough
estimates)
• Why use f to determine Qs but f’ to determine net application depth?
(because Qs must be based on gross requirements; not irrigating 24 hrs/day
and 7 days/week does not mean that the crop will not transpire water 7
days/week)
• When determining the seasonal water requirements we subtract Pe from U.
However, to be safe, the value of Pe must be reliable and consistent from
year to year, otherwise a smaller (or zero) value should be used.
• Note that lateral and sprinkler spacings are not infinitely adjustable: they
come in standard dimensions from which designers must choose. The same
goes for pipe diameters and lengths.
• Note that design for peak Ud may not be appropriate if sprinklers are used
only to germinate seeds (when later irrigation is by a surface method).
Given:
Crop is alfalfa. Top soil is 1.0 m of silt loam, and subsoil is 1.8 m of clay loam.
Field area is 35 ha. MAD is 50% and ECw is 2.0 dS/m. Application efficiency is
estimated at 80%, and the soil intake rate is 15 mm/hr. Lateral spacing is 15 m and
lateral length is 400 m. Assume it takes ½ hour to change sets. Seasonal effective
rainfall is 190 mm; climate is hot. Assume one day off per week (irrigate only 6
days/week).
Hot climate, table 3.3 gives............Ud = 7.6 mm/day, and U = 914 mm/season
Top soil, table 3.1 gives ...........................................................Wa = 167 mm/m
Sub soil, table 3.1 gives ...........................................................Wa = 183 mm/m
Root depth, table 3.2 gives .........................................Z = (1.2 + 1.8)/2 = 1.5 m
Salinity for 10% yield reduction, table 3.5 gives ........................ECe = 3.4 dS/m
1. Average water holding capacity in root zone:
MAD ⎛ 50 ⎞
dx = Wa Z = ⎜ ⎟ (172.3 )(1.5 ) = 129.2 mm (11)
100 ⎝ 100 ⎠
dx 129.2 mm
fx = = = 17.0 days (12)
Ud 7.6 mm/day
17 days is just over two weeks, and depending on which day is off, there
could be 3 off days in this period. So, with one day off per week, we will
design the system capacity to finish in 17 - 3 = 14 days. Thus, f = 14 days.
But, remember that we still have to apply 17 days worth of water in these 14
days (we irrigate 6 days/week but crop transpires 7 days/week)
ECw 2.0
LR = = = 0.13 (15)
5ECe − ECw 5 ( 3.4 ) − 2.0
With 167.1 mm to apply and a soil intake rate of 15 mm/hr, this gives 11.14
hrs minimum set time (so as not to exceed soil intake rate). Then, we can
make the nominal set time equal to 11.5 hours for convenience. With 0.5 hrs
to move each set, there are a total of 12.0 hrs/set, and the farmer can
change at 0600 and 1800 (for example).
At this point we could take the lateral spacing, Sl, sprinkler spacing, Se, and
actual application rate to determine the flow rate required per sprinkler.
From the above, we can see that there would be two sets/day.
35 ha
= 2.08 laterals (17)
16.8 ha/lateral
Normally we would round up to the nearest integer, but because this is so
close to 2.0 we will use two laterals in this design.
U − Pe 914 mm - 190 mm
= = 5.6 irrigations (18)
dn 129.2 mm/irrig
with 11.5 hours operating time per set and two sets per day, the system runs
23 hrs/day...
Qs = 2.78
Ad
= 2.78
( 35 ha )(167.1 mm ) = 50.5 lps (800 gpm)
fT (14 days )( 23 hrs/day ) (19)
1. Sprinkler selection
2. Design of the system layout
3. Design of the laterals
4. Design of the mainline
5. Pump and power unit selection
• Rotating sprinklers have lower application rates because the water is only
wetting a “sector” (not a full circle) at any given instance...
• For the same pressure and discharge, rotating sprinklers have larger wetted
diameters
• Impact sprinklers always rotate; the “impact” action on the stream of water is
designed to provide acceptable uniformity, given that much of the water
would otherwise fall far from the sprinkler (the arm breaks up part of the
stream)
• Check out Web sites such as www.rainbird.com
Sprinkle & Trickle Irrigation Lectures Page 25 Merkley & Allen
III. Precipitation Profiles
• Typical examples of low, correct, and high sprinkler pressures (see Fig 5.5).
Pressure is OK
1. nozzle pressure
2. nozzle shape & size
3. sprinkler head design
4. presence of straightening vanes
5. sprinkler rotation speed
6. trajectory angle
7. riser height
8. wind
uniform! uniform!
lateral
lateral
lateral
• When winds are consistently recurring at some specific hour, the system can
be shut down during this period (T in Eq. 5.4 is reduced)
• For center pivots, rotation should not be a multiple of 24 hours, even if there
is no appreciable wind (evaporation during day, much less at night)
• If winds consistently occur, special straightening vanes can be used
upstream of the sprinkler nozzles to reduce turbulence; wind is responsible
for breaking up the stream, so under calm conditions the uniformity could
decrease
• For periodic-move systems, laterals should be moved in same direction as
prevailing winds to achieve greater uniformity (because Se < Sl)
• Laterals should also move in the direction of wind to mitigate problems of salt
accumulating on plant leaves
• Wind can be a major factor on the application uniformity on soils with low
infiltration rates (i.e. low application rates and small drop sizes)
• In windy areas with periodic-move sprinkler systems, the use of offset
laterals (½Sl) may significantly increase application uniformity
• Alternating the time of day of lateral operation in each place in the field may
also improve uniformity under windy conditions
• Occasionally, wind can help increase uniformity, as the randomness of wind
turbulence and gusts helps to smooth out the precipitation profile
0-3 mph wind: reduce manufacturer’s listed diameter of throw by 10% for an
effective value (i.e. the diameter where the application of
water is significant)
⎣ (
diam = diammanuf ⎡0.9 − 0.025 windmph − 3 ⎤
⎦ ) (21)
or,
diam = diammanuf ⎡⎣0.9 − 0.056 ( windm / s − 1.34 ) ⎤⎦ (22)
80 ft - (0.10)(0.80) = 72 ft (23)
• Equation 5.1:
q = Kd P (26)
P V2 q2
= = (27)
γ 2g 2gA 2
2gA 2P
= Kd P = q (28)
ρg
where the elevations are the same (z1 = z2) and the conversion through the
nozzle is assumed to be all pressure to all velocity
• Kd can be separated into an orifice coefficient, Ko, and nozzle bore area, A:
q = KoA P (29)
whereby,
Ko = 2 / ρ (30)
where the value of Ko is fairly consistent across nozzle sizes for a specific
model and manufacturer
4q
d= (31)
πK o P
3. Some sprinkler companies have invested much into the design of such
devices for low-pressure sprinkler nozzles
4. Low-pressure nozzles can be more expensive, possibly with reduced
uniformity and increased application rate, but the trade-off is in operating cost
dn
d= , for LR ≤ 0.1 (33)
Epa
where Epa is the “designer” application efficiency (decimal; Eq. 6.9). And,
0.9 dn
d= , for LR > 0.1 (34)
(1 − LR)Epa
• The gross application depth is the total equivalent depth of water which must
be delivered to the field to replace (all or part of) the soil moisture deficit in
the root zone of the soil, plus any seepage, evaporation, spray drift, runoff
and deep percolation losses
• The above equations for d presume that the first 10% of the leaching
requirement will be satisfied by the Epa (deep percolation losses due to
application variability). This presumes that areas which are under-irrigated
during one irrigation will also be over-irrigated in the following irrigation, or
that sufficient leaching will occur during non-growing season (winter) months.
• When the LR value is small (ECw ≤ ½ECe), leaching may be accomplished
both before and after the peak ET period, and the first equation (for LR ≤ 0.1)
can be used for design and sizing of system components. This will reduce
the required pipe and pump sizes because the “extra” system capacity during
the non-peak ET periods is used to provide water for leaching.
Ad
Qs = K (35)
fT
where,
Qs = system capacity;
T = hours of system operation per day (obviously, T≤ 24; also, t = fT)
K = coefficient for conversion of units (see below)
d = gross application depth (equals Ud/Eff during f’ period)
f = time to complete one irrigation (days); equal to f’ minus the days
off
A = net irrigated area supplied by the discharge Qs
3600qR e
I= (36)
SeSl
where I is the application rate (mm/hr); q is the flow rate (lps); Se is the
sprinkler spacing (m); Sl is the lateral spacing (m); and Re is the fraction of
water emitted by the nozzle that reaches the soil (takes into account the
evaporative/wind loss)
• If the velocity in the vertical direction at the nozzle, Vy, is taken as zero at
time t1, then,
( Vy )t
1
= V0 sin α − g t1 = 0 (39)
where V0 is the velocity of the stream leaving the nozzle (m/s); α is the angle
of the nozzle; t1 is the time for a drop to travel from the nozzle to the highest
point in the trajectory (s); and g is the ratio of weight to mass (9.81 m/s2)
• Note that the term Vosin α in Eq. 37 is the initial velocity component in the
vertical direction, and the term gt1 is the downward acceleration over time t1
• The above equation can be solved for t1
• The initial velocity, V0, can be calculated based on the sprinkler discharge
and the nozzle diameter
• Values of α can be found from manufacturers’ information
Merkley & Allen Page 36 Sprinkle & Trickle Irrigation Lectures
• Now, what is the highest point in the trajectory?
• First, solve for t1 in the previous equation:
Vo sin α
t1 = (40)
g
then,
x1 = V0 cos α t1 (42)
solving for h2,
gt 22
h2 = hr + h1 = Vy t 2 +
2 (43)
where hr is the riser height (m); t2 is the time for a drop of water to travel from
the highest point in the trajectory to impact on the ground; and Vy = 0
• Then, x2 is defined as:
2 (hr + h1 )
x 2 = V0 cos α t 2 = V0 cos α (44)
g
R j = x1 + x 2
(45)
• In summary, if air resistance is ignored and the sprinkler riser is truly vertical,
the theoretical value of Rj is a function of:
1. Angle, α
2. Nozzle velocity (qa/A)
3. Riser height, hr
• And, qa is a function of P
1. Application uniformity
2. Losses (deep percolation, evaporation, runoff, wind drift, etc.)
⎛
⎜ ∑
n
j=1 (
abs z j − m ) ⎟⎞
CU = 100 1.0 − (47)
⎜ ⎟
∑
n
⎜ z ⎟
⎝ j=1 j ⎠
where z are the individual catch-can values (volumes or depths); n is the
number of observations; and m is the average of all catch volumes.
⎛ σ 2⎞
CU = 100 ⎜ 1.0 − ⎟⎟ (49)
⎜ m π
⎝ ⎠
∑ z − m = nσ 2/ π (50)
• By the way, the ratio σ/m is known in statistics as the coefficient of variation
• Following is the approximate relationship between CU and DU:
• These equations are used in evaluations of sprinkler systems for both design
and operation
• Typically, 85 to 90% is the practical upper limit on DU for set systems
• DU > 65% and CU > 78% is considered to be the minimum acceptable
performance level for an economic system design; so, you would not
normally design a system for a CU < 78%, unless the objective is simply to
“get rid of water or effluent” (which is sometimes the case)
• For shallow-rooted, high value crops, you may want to use DU > 76% and
CU > 85%
CUa ≈ 10 CU
(53)
DUa ≈ 10 DU
• The above are also valid for “double” alternate sets (Sl/3)
• Use of alternate sets is a good management practice for periodic-move
systems
• The use of alternate sets approaches an Sl of zero, which simulates a
continuous-move system
V. System Uniformity
• The uniformity is usually less when the entire sprinkler system is considered,
because there tends to be greater pressure variation in the system than at
any given lateral position.
⎡1
( ⎤
system CU ≈ CU ⎢ 1 + Pn / Pa ⎥
⎣2 ⎦
) (54)
⎡1
( ⎤
system DU ≈ DU ⎢ 1 + 3 Pn / Pa ⎥
⎣4 ⎦
) (55)
where Pn is the minimum sprinkler pressure in the whole field; and Pa is the
average sprinkler pressure in the entire system, over the field area.
2Pn + Px
Pa = (56)
3
Design Efficiency:
Epa = DEpaReOe
(57)
• The design efficiency, Epa, is used to determine gross application depth (for
design purposes), given the net application depth
• In most designs, it is not possible to do a catch-can test and data analysis –
you have to install the system in the field first; thus, use the “design
efficiency”
• The subscript “pa” represents the “percent area” of the field that is
adequately irrigated (to dn, or greater) – for example, E80 and DE80 are the
application and distribution efficiencies when 80% of the field is adequately
irrigated
• Question: can “pa” be less than 50%?
U
80% of area overirrigated
C
w
Lo
Relative Applied Depth
h CU
Hig
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
Area Receiving at Least the Desired Application
• These losses are typically from 5% to 10%, but can be higher when the air is
dry, there is a lot of wind, and the water droplets are small
• Effective portion of the applied water, Re. This is defined as the percentage
of applied water that actually arrives at the soil surface of the irrigated field.
• This is based on:
• climatic conditions
• wind speed
• spray coarseness
⎛ P1.3 ⎞
CI = 0.032 ⎜
⎜ B ⎟⎟
(58)
⎝ ⎠
where P is the nozzle pressure (kPa) and B is the nozzle diameter (mm)
CI > 17 17 ≥ CI ≥ 7 CI < 7
fine spray between fine and coarse coarse spray
• Allen and Fisher (1988) developed a regression equation to fit the curves in
Fig. 6.8:
Epa = DEpaReOe
(61)
where DEpa is in percent; and Re and Oe are in fraction (0 to 1.0). Thus, Epa
is in percent.
1. Compute the average catch depth over the wetted area (if a single
sprinkler), or in the area between four adjacent sprinklers (if in a
rectangular grid)
2. Multiply the sprinkler flow rate by the total irrigation time to get the volume
applied, then divide by the wetted area to obtain the gross average
application depth
3. Divide the two values to determine the effective portion of the applied
water
• In Chapter 6 of the textbook there are several tables that provide guidelines
for nozzle sizes for different:
• Wind conditions
• Application rates
• Sprinkler spacings
• For selected values of wind, application rate, and spacing, the tables provide
recommended nozzle sizes for single and double-nozzle sprinklers,
recommended sprinkler pressure, and approximate uniformity (CU)
• Recall that the maximum application rate is a function of soil texture, soil
structure, and topography (Table 5.4)
• For a given spacing and application rate, the sprinkler discharge, qa, can be
determined from Eq. 5.5
I ( SeSl ) d S SO
qa = = n e l e (62)
3600 3600EpaSto
where qa is in lps; I is in mm/hr; dn is in mm; Sto is the operating time for each
set, in hours; and Sl and Se are in m
• Why is the Oe term included in the above equation? (because Epa includes
Oe, as previously defined, and must be cancelled out when considering an
individual sprinkler)
• After calculating the system capacity and the design flow rate for sprinklers,
the number of sprinklers that will operate at the same time is:
Qs
Nn = (63)
qa
1. friction loss
2. elevation change
• The fundamental basis upon which sprinkler laterals are designed is:
• This is a design assumption that has been used for many years, and is
based on a great deal of experience
• The 20% for pressure variation is not an “exact” value; rather, it is based on
judgment and some cost comparisons
• A designer could change this value, but it would affect system performance
(uniformity), initial system cost, operating cost, and possibly other factors
• Computer programs could be written to search for an “optimal” percent
pressure variation according to initial and operating costs, and according to
crop value -- such an “optimal” value would vary from system to system
1. both friction loss and elevation are working to reduce pressure toward
the end of the lateral, and length is more restricted if the 20% rule is
still used
2. However, for small slopes, running laterals uphill may be required to
reduce the total length of the mainline pipe
• Note that V2/2g in the lateral pipe is normally converted into total head as the
water flows through the nozzle body. Therefore, the velocity head (and EL)
should normally be considered in lateral design. However, since a portion of
the velocity head is lost during deceleration of the water at the entrance into
risers and as turbulence inside the sprinkler head, and since V2/2g in a
lateral pipe is typically small (< 1 ft of head, or 0.2 psi, or 0.3 m head, or 3
kPa), it is normally neglected during design, and the HGL is used.
• Aside from limits on pressure variation, laterals should be oriented so that
they move in the direction of the prevailing winds -- this is because of salinity
problems and application uniformity
Qs 532
Ns = = = 111 sprinklers
qa 4.78 (65)
• Number of laterals,
1320 ft / lateral
= 33 sprinklers / lateral
40 ft / sprinkler (66)
111 sprinklers
= 3.36 laterals
33 sprinklers / lateral (67)
14 sets
f= = 7 days (69)
2 sets / day
⎛ 8 days ⎞
Qs = ⎜ ⎟ (532 gpm) = 608 gpm (71)
⎝ 7 days ⎠
• You might say that we are “effectively” finishing in somewhat less than 7
days, because the last set has only two laterals in operation, giving a system
capacity of 608 instead of 631
• Consider this calculation: there are 2 x 13 + 2 x 14 = 54 sets, but the last 2
sets have only 2 laterals. So, (52/54) x 631 = 608 gpm, as calculated above.
• Which is correct?
I. Review
0.25
f= 2
(72)
⎡ ⎛ ε 5.74 ⎞ ⎤
⎢log10 ⎜ + 0.9 ⎟ ⎥
⎣ ⎝ 3.75D NR ⎠ ⎦
which is valid for turbulent flow in the range: 4,000 ≤ NR ≤ 1.0(10)8. The ratio
ε/D is called “relative roughness.” The roughness height, ε, varies widely
• We will also use the Blasius equation (Eq. 8.6) to determine the value of “f,”
in some cases, for “smooth pipes”
total
minimum
total
Cost
Energy costs =
annualized fixed costs
fixed energy
• To balance these costs and find the minimum cost we will annualize the fixed
costs, compare with annual energy (pumping) costs
• We can also graph the results so that pipe diameters can be selected
according to their maximum flow rate
• We will take into account interest rates and inflation rates to make the
comparison
• This is basically an “engineering economics” problem, specially adapted to
the selection of pipe sizes
1. Determine the equivalent annual cost for purchasing each available pipe
size
2. Determine the annual energy cost of pumping
Sprinkle & Trickle Irrigation Lectures Page 59 Merkley & Allen
3. Balance the annual costs for adjacent pipe sizes
4. Construct a graph of system flow rate versus section flow rate on a log-
log scale for adjacent pipe sizes
• We will use the method to calculate “cut-off” points between adjacent pipe
sizes so that we know which size is more economical for a particular flow
rate
• We will use HP and kW units for power, where about ¾ of a kW equals a HP
• Recall that a Watt (W) is defined as a joule/second, or a N-m per second
• Multiply W by elapsed time to obtain Newton-meters (“work”, or “energy”)
1. Select a period of time over which comparisons will be made between fixed
and annual costs. This will be called the useful life of the system, n, in years.
2. For several different pipe sizes, calculate the uniform annual cost of pipe per
unit length of pipe.
where P is the cost per unit length of pipe; i is the annual interest rate
(fraction); and n is the number of years (useful life)
• Of course, i could also be the monthly interest rate with n in months, etc.
• Make a table of UAC values for different pipe sizes, per unit length of pipe
• The CRF value is the same for all pipe sizes, but P will change depending
on the pipe size
• Now you have the equivalent annual cost for each of the different pipe
sizes
• Note that the maximum possible value of Ot is 8,760 hrs/year (for 365
days)
• Note also that the “gross depth” is annual, so if there is more than one
growing season per calendar year, you need to include the sum of the
gross depths for each season (or fraction thereof)
• The total plant efficiency is the product of pump efficiency, Epump, and
motor efficiency, Emotor
Ep = EpumpEmotor
(76)
QH
WHP = (77)
102
where Q is in lps; H is in m of head; and WHP is in kilowatts (kW)
• Note that for fluid flow, “power” can be expressed as ρgQH = γQH
• Observe that 1,000/g = 1,000/9.81 ≈ 102, for the above units (other
conversion values cancel each other and only the 102 remains)
• The denominator changes from 102 to 3,960 for Q in gpm, H in ft, and
WHP in HP
OtCf
E=
Ep
(78)
• For electricity, the value of Cf is usually in dollars per kWh, and the value
used in the above equation may need to be an “average” based on
potentially complex billing schedules from the power company
• For example, in addition to the energy you actually consume in an electric
motor, you may have to pay a monthly fee for the installed capacity to
delivery a certain number of kW, plus an annual fee, plus different time-
of-day rates, and others
• Fuels such as diesel can also be factored into these equations, but the
power output per liter of fuel must be estimated, and this depends partly
on the engine and on the maintenance of the engine
• The units of E are dollars per WHP per year, or dollars per kW per year;
so it is a marginal cost that depends on the number of kW actually
required
Merkley & Allen Page 62 Sprinkle & Trickle Irrigation Lectures
6. Determine the marginal equipment cost:
• Note that Cf can include the “marginal” cost for the pump and power unit
(usually an electric motor)
• In other words, if a larger pump & motor costs more than a smaller pump,
then Cf should reflect that, so the full cost of friction loss is considered
• If you have higher friction loss, you may have to pay more for energy to
pump, but you may also have to buy a larger pump and/or power unit
(motor or engine)
• It sort of analogous to the Utah Power & Light monthly power charge,
based solely on the capacity to deliver a certain amount of power
Cf ($/kWh) = energy cost + marginal cost for a larger pump & motor
• This is not really an “energy” cost per se, but it is something that can be
taken into account when balancing the fixed costs of the pipe (it falls
under the operating costs category, increasing for decreasing pipe costs)
• That is, maybe you can pay a little more for a larger pipe size and avoid
the need to buy a bigger pump, power unit and other equipment
MAC =
(
CRF $big − $small )
(
Ot kWbig − kWsmall ) (79)
where MAC has the same units as Cf; and $big -$small is the difference in
pump+motor+equipment costs for two different capacities
• The difference in fixed purchase price is annualized over the life of the
system by multiplying by the CRF, as previously calculated
• The difference in pump size is expressed as ∆BHP, where ∆BHP is the
difference in brake horsepower, expressed as kW
• To determine the appropriate pump size, base the smaller pump size on a
low friction system (or low pressure system)
• For BHP in kW:
QsHpump
BHP =
102Ep
(80)
⎡ (1 + e )n − (1 + i )n ⎤ ⎡ i ⎤
EAE = ⎢ ⎥⎢ ⎥ (81)
⎢ e −i ⎥ ⎢ (1 + i )n − 1⎥
⎣ ⎦⎣ ⎦
where e is the annual inflation rate (fraction), i is the annual interest rate
(fraction), and n is in years
• Recall that the velocity limit is usually taken to be about 5 fps, or 1.5 m/s
9. Determine the difference in WHP between adjacent pipe sizes by equating the
annual plus annualized fixed costs for two adjacent pipe sizes:
∆WHPs1−s2 =
(UACs2 − UACs1)
E' (84)
10. Determine the difference in friction loss gradient between adjacent pipe sizes:
⎛ ∆WHPs1− s2 ⎞
∆Js1− s2 = 102 ⎜ ⎟
⎝ Qs ⎠ (85)
• This is the head loss difference needed to balance fixed and annual costs
for the two adjacent pipe sizes
• The coefficient 102 is for Qs in lps, and ∆WHP in kW
• You can also put Qs in gpm, and ∆WHP in HP, then substitute 3,960 for
102, and you will get exactly the same value for ∆J
• As before, ∆J is a head loss gradient, in head per 100 units of length (m
or ft, or any other unit)
• Thus, ∆J is a dimensionless “percentage”: head, H, can be in m, and
when you define a unit length (e.g. 100 m), the H per unit meter becomes
dimensionless
• This is why you can calculate ∆J using any consistent units and you will
get the same result
11. Calculate the flow rate corresponding to this head loss difference:
∆J =
800 f q2
gπ 2 (Ds1−5 − Ds2−5 ) (87)
0.54
⎡ ⎤
∆J
q = C⎢ ⎥
( )
(88)
⎢ 16.42(10)6 D−4.87 − D−4.87 ⎥
⎣ s1 s2 ⎦
• This is the flow rate for which either size (Ds1 or Ds2) will be the most
economical (it is the balancing point between the two adjacent pipe sizes)
• For a larger flow rate you would choose size Ds2, and vice versa
12. Repeat steps 8 through 11 for all other adjacent pipe sizes.
13. You can optionally create a graph with a log-log scale with the system flow
rate, Qs, on the ordinate and the section flow rate, q, on the abscissa:
• Find the needed flow rate in a given section of the pipe, q, make an
intersection with the maximum system capacity (Qs, on the ordinate), then
see which pipe size it is
• You can use the graph for different system capacities, assuming you are
considering different total irrigated areas, or different crop and or climate
values
• Otherwise, you can just skip step 13 and just do the calculations on a
spreadsheet for the particular Qs value that you are interested in
• The graph is perhaps didactic, but doesn’t need to be constructed to
apply this economic pipe selection method
1. If any of the economic factors (interest rate, inflation rate, useful life of the
system) change, the lines on the graph will shift up or down, but the slope
remains the same (equal to the inverse of the velocity exponent for the head
loss equation: 1.852 for Hazen-Williams and 2.0 for Darcy-Weisbach).
2. Computer programs have been developed to use this and other economic
pipe selection methods, without the need for constructing a graphical solution
on log-log paper. You could write such a program yourself.
5. Note that the equivalent annual pipe cost considers the annual interest rate,
but not inflation. This is because financing the purchase of the pipe would be
done at the time of purchase, and we are assuming a fixed interest rate. The
uncertainty in this type of financing is assumed by the lending agency.
6. This method is not normally used for designing pipe sizes in laterals. For
one thing, it might recommend too many different sizes (inconvenient for
operation of periodic-move systems). Another reason is that we usually use
different criteria to design laterals (the “20%” rule on pressure variation).
7. Other factors could be included in the analysis. For example, there may be
certain taxes or tax credits that enter into the decision making process. In
general, the analysis procedure in determining pipe sizes can get as
complicated as you want it to – but higher complexity is better justified for
larger, more expensive irrigation systems.
• It is often a good idea to apply more than one pipe selection method and
compare the results
• For example, don’t accept a recommendation from the economic selection
method if it will give you a flow velocity of more than about 10 ft/s (3 m/s),
otherwise you may have water hammer problems during operation
• However, it is usually advisable to at least apply the economic selection
method unless the energy costs are very low
• In many cases, the same pipe sizes will be selected, even when applying
different methods
4Q
D= (89)
πV
• The following tables show maximum flow rates for specified average velocity
limits and different pipe inside diameters
• The basic design criterion is to size lateral pipes so that pressure variation
along the length of the lateral does not exceed 20% of the nominal design
pressure for the sprinklers
• This criterion is a compromise between cost of the lateral pipe and
application uniformity in the direction of the lateral
• Note that the locations of maximum and minimum pressure along a lateral
pipe can vary according to ground slope and friction loss gradient
∑i=1∑ j=1(hf ) j
n i
(hf )a =
n +1 (91)
where n is the number of sprinklers; (hf)total is the total friction head loss from
0 to L; (hf)i is the friction head loss in the lateral pipe between sprinklers i-1
and i; and (hf)a is the friction loss from the lateral inlet to the location of ha
• As indicated above, (hf)a occurs over approximately the first 40% of the
lateral
• Note that between sprinklers, the friction head loss gradient is linear in the
lateral pipe
• Note also that (hf)0 = 0, but it is used in calculating (ha)f, so the denominator
is (n+1), not n
Hazen-Williams Equation:
1.852
12 ⎛ Q ⎞
J = 1.21(10) ⎜ ⎟ D−4.87 (93)
⎝C⎠
for J in meters of friction head loss per 100 m (or ft/100 ft); Q in lps; and D in
mm
⎛q ⎞
Q = Ql − ⎜ a ⎟ x (94)
⎝ Se ⎠
for multiple, equally-spaced sprinkler outlets spaced at Se (m) from each
other, with constant discharge of qa (lps). Ql is the flow rate at the lateral
inlet (entrance).
• To find the location of minimum pressure, let J = S, where S is the ground
slope (in %, because J is per 100 m), which is negative for downhill-sloping
laterals
• Combining the two above equations and solving for x,
x=
Se ⎡
qa ⎣
(
Ql − 3(10)−7 C ( −S)0.54 D2.63 ⎤
⎦ ) (95)
where x is the distance, in m, from the lateral inlet to the minimum pressure
Merkley & Allen Page 74 Sprinkle & Trickle Irrigation Lectures
• S is in percent; Se and x are in m; D is in mm; and Ql and qa are in lps
• Note that the valid range of x is: 0 ≤ x ≤ L, and that you won’t necessarily get
J = S over this range of x values:
• This means that the above equation for x is valid for all ground slopes: S = 0,
S > 0 and S < 0
• Except for the most unusual circumstances (e.g. non-uniform downhill slope
that exactly matches the shape of the hf curve), the pressure will vary with
distance in a lateral pipe
• According to Keller & Bliesner’s design criterion, the required inlet pressure
head to a sprinkler lateral is that which makes the average pressure in the
lateral pipe equal to the required sprinkler pressure head, ha
3 1
hl = ha + hf + ∆he (96)
4 2
• hl is the required pressure head at the lateral inlet
• Strictly speaking, we should take approximately 0.4∆he in the above
equation, but we are taking separate averages for the friction loss and
elevation gradients – and, this is a design equation
• Of course, instead of head, h, in the above equation, pressure, P, could be
used if desired
• For steep downhill slopes, where the minimum pressure would be at the
lateral inlet, it is best to let
hf = −∆he (97)
• We now have an equation to calculate lateral inlet pressure based on ha, hf,
and he
• This is the same as saying that we will not allow pipes that are too small, that
is, pipes that would produce a large hf value
• An additional head term must be added to the equation for hl to account for
the change in elevation from the lateral pipe to the sprinkler (riser height):
3 1
hl = ha + hf + ∆he + hr (100)
4 2
or, in terms of pressure…
3 1
Pl = Pa + Pf + ∆Pe + Pr (101)
4 2
V. Friction Losses in Pipes with Multiple Outlets
• Pipes with multiple outlets have decreasing flow rate with distance (in the
direction of flow), and this causes the friction loss to decrease by
approximately the square of the flow rate (for a constant pipe diameter)
• Sprinkler and trickle irrigation laterals fall into this hydraulic category
• Multiply the head loss for a constant discharge pipe by a factor “F” to reduce
the total head loss for a lateral pipe with multiple, equally spaced outlets:
JFL
hf = (102)
100
where F is from Eq. 8.9a
1 1 b −1
F= + + (103)
b + 1 2N 6N2
for equally spaced outlets, each with the same discharge, and going all the
way to the end of the pipe.
• All of the flow is assumed to leave through the outlets, with no “excess”
spilled out the downstream end of the pipe
• N is the total number of equally spaced outlets
• The value of b is the exponent on Q in the friction loss equation
NF − (1 − α)
F(α) = (104)
N − (1 − α)
where 0 < α ≤ 1
• If the minimum pressure is at the end of the lateral, which is the case for no
ground slope, uphill, and slight downhill slopes, then the change in pressure
head over the length of the lateral is:
∆h = h f + ∆h e (105)
JaFL
0.20ha − ∆he = (107)
100
and,
⎛ 0.20ha − ∆he ⎞
Ja = 100 ⎜ ⎟ (108)
⎝ FL ⎠
hf = −∆he (109)
⎛ −∆he ⎞
Ja = 100 ⎜ ⎟ (110)
⎝ FL ⎠
1. hmax is either at the lateral inlet or at the end of the lateral, and
2. hmin is somewhere between the lateral inlet and the end
• Given a value of Ja, the inside diameter of the lateral pipe can be calculated
from the Hazen-Williams equation:
0.205
⎡ K ⎛ Q ⎞1.852 ⎤
D=⎢ ⎜ l⎟ ⎥ (111)
⎢⎣ Ja ⎝ C ⎠ ⎥⎦
where Ql is the flow rate at the lateral inlet (Nqa) and K is the units coefficient
in the Hazen-Williams equation
Nn = 396/12 = 33 sprinklers
F = 0.36
Ql = (0.315)(33) = 10.4 lps
∆he = SL = (-0.0253)(396) = -10.0 m
Now, 0.3ha < -∆he (steep downhill). Therefore, may want to use hf = -∆he.
Then, Ja is:
⎛ −∆he ⎞ ⎛ −( −10.0m) ⎞
Ja = 100 ⎜ ⎟ = 100 ⎜ ⎟ = 7.01m /100m (112)
⎝ FL ⎠ ⎝ (0.36)(396) ⎠
For now, let’s use Ja = 7.01 m/100 m. Then, the minimum pipe inside
diameter is (C ≈ 130 for aluminum):
0.205
⎡ 1.21E12 ⎛ 10.4 ⎞1.852 ⎤
D=⎢ ⎜ ⎟ ⎥ = 77.7mm (114)
⎢⎣ 7.01 ⎝ 130 ⎠ ⎥⎦
However, it would be a good idea to also try the 3” size and see how the
lateral hydraulics turn out (this is done below; note also that for Ja = 11.6,
D = 70.0 mm).
1.852
⎛ 10.4 ⎞
J = 1.21E12 ⎜ ⎟ ( 99.1 mm)−4.87 = 2.14m /100m (115)
⎝ 130 ⎠
JFL (2.14)(0.36)(396)
hf = = = 3.06 m (116)
100 100
The required lateral inlet pressure head is:
hl = ha + 0.75hf + 0.5∆he + hr
(117)
hl = 320 / 9.81 + 0.75(3.06) + 0.5( −10.0) + 1.0 = 30.9 m
VI.5. Calculate the pressure and head at the end of the lateral pipe
which is equal to 371 kPa. Thus, the pressure at the end of the lateral
pipe is greater than the pressure at the inlet.
To determine the pressure at the last sprinkler head, subtract the riser
height to get 37.8 m – 1.0 m = 36.8 m (361 kPa)
x=
Se ⎡
qa ⎣
(
Ql − 3(10)−7 C( −S)0.54 D2.63 ⎤
⎦ )
(119)
x=
12 ⎡
0.315 ⎣
(
10.4 − 3(10)−7 130(2.53)0.54 (99.1)2.63 ⎤ = −39.6 m
⎦ )
The result is negative, indicating that that minimum pressure is really at
the entrance (inlet) to the lateral pipe. The minimum sprinkler head
pressure is equal to hl – hr = 30.9 – 1.0 = 29.9 m, or 293 kPa.
The maximum pressure is at the last sprinkler (end of the lateral), and the
minimum pressure is at the first sprinkler (lateral inlet). The percent
pressure variation is:
That is, 21% pressure variation at the sprinklers, along the lateral
This is larger than the design value of 0.20, or 20% variation. But it is
very close to that design value, which is somewhat arbitrary anyway.
VI.8. Redo the calculations using a 3” lateral pipe instead of the 4” size
In this case, the location of the minimum pressure in the lateral pipe is:
x=
12 ⎡
0.315 ⎣
(
10.4 − 3(10)−7 130(2.53)0.54 (73.7)2.63 ⎤ = 196 m
⎦ ) (121)
There are about 196/12 = 16 sprinklers from the lateral inlet to the
location of minimum pressure, and about 17 sprinklers from x to the end
of the lateral.
1.852
⎛ (17)(0.315) ⎞
Jx −end = 1.21E12 ⎜ ⎟ ( 73.7 )−4.87 = 2.65 m /100 m
⎝ 130 ⎠ (122)
(2.65)(0.38)(396 − 196)
(hf )x −end = = 2.01 m (123)
100
Friction loss from the inlet to the end is:
1.852
⎛ 10.4 ⎞
Jinlet −end = 1.21E12 ⎜ ⎟ ( 73.7 )−4.87 = 9.05 m /100 m (124)
⎝ 130 ⎠
hl = ha + 0.75hf + 0.5∆he + hr
(127)
hl = 320 / 9.81 + 0.75(12.9) + 0.5(−10.0) + 1.0 = 38.3 m
giving Pend of (35.4)(9.81) = 347 kPa, which is less than Pl. So, the
maximum lateral pipe pressure is at the inlet.
which turns out to be slightly less than the design value of 20%
⎛ 0.20ha − ∆he ) ⎞
Ja = 100 ⎜ ⎟
⎝ FL ⎠
(131)
⎛ 0.2(320 / 9.81) − 10.0 ⎞
= 100 ⎜ ⎟ = −2.44m /100m
⎝ (0.36)(396) ⎠
which is negative because ∆he > 0.2ha, meaning that it is not possible to
have only a 20% variation in pressure along the lateral, that is, unless
flow control nozzles and or other design changes are made.
Either the 3” or 4” aluminum pipe size could be used for this lateral
design. The 4” pipe will cost more than the 3” pipe, but the required
lateral inlet pressure is less with the 4” pipe, giving lower pumping costs,
assuming pumping is necessary.
Note that it was assumed that each sprinkler discharged 0.315 lps, when
in reality the discharge depends on the pressure at each sprinkler. To
take into account the variations in sprinkler discharge would require an
iterative approach to the mathematical solution (use a computer).
Most sprinkler laterals are laid on slopes less than 2.5%, in fact, most are
on fields with less than 1% slope.
1. a reduction in hf
2. an increase in hf
• In either case, the basic objective is to reduce pressure variations along the
lateral pipe by arranging the friction loss curve so that it more closely
parallels the ground slope
• It is not normally desirable to have more than one pipe size in portable
laterals (hand-move, wheel lines), because it usually makes set changes
more troublesome
• For fixed systems with buried laterals, it may be all right to have more than
two pipe diameters along the laterals
• For dual pipe size laterals, approximately 5/8 of the pressure loss due to
friction occurs between the lateral inlet and the location of average pressure
• Case 1: a lateral on level ground where one pipe size is too small, but the
next larger size is too big...
• The composite friction loss curve for d1 and d2 more closely parallels the
ground slope than the curve with only d1, which means that the pressure
variation along the lateral is less with the dual pipe size design
Section Flow Distance Diameter hf Sum (hf) d(he) head diff from hf/(hf)total
(lps) (m) (cm) (m) (m) (m) (m) ha (%)
1 40.00 9.00 15.00 0.31 0.31 0 49.69 12.08 0.016
2 39.60 18.00 15.00 0.31 0.62 0 49.38 11.77 0.032
3 39.20 27.00 15.00 0.30 0.92 0 49.08 11.47 0.048
4 38.80 36.00 15.00 0.29 1.21 0 48.79 11.18 0.064
5 38.40 45.00 15.00 0.29 1.50 0 48.50 10.89 0.079
6 38.00 54.00 15.00 0.28 1.79 0 48.21 10.61 0.094
⎛ J FL J F x ⎞ ⎛ J F x ⎞
hf = ⎜ 1 1 − 2 2 2 ⎟ + ⎜ 3 2 2 ⎟ (132)
⎝ 100 100 ⎠ ⎝ 100 ⎠
where,
hf = total lateral friction head loss for dual pipe sizes
for,
⎛ 20%ha − ∆he ⎞
Ja = 100 ⎜ ⎟
⎝ FL ⎠ (136)
1 ⎛ 4 ⎞
F1 ≈ 0.351 + ⎜ 1 + ⎟ (137)
2N1 ⎝ 13N1 ⎠
1 ⎛ 4 ⎞
F2 ≈ 0.351 + ⎜1 + ⎟ (138)
2N2 ⎝ 13N2 ⎠
where
L
N1 = (139)
Se
L − x1
N2 = (140)
Se
1.852
⎛Q ⎞
J1 = K ⎜ 1 ⎟ D1−4.87 (141)
⎝C⎠
1.852
⎛Q ⎞
J2 = K ⎜ 2 ⎟ D1−4.87 (142)
⎝ C ⎠
1.852
⎛Q ⎞
J3 = K ⎜ 2 ⎟ D2−4.87 (143)
⎝ C ⎠
where
⎛ L ⎞
Q1 = ⎜ ⎟ qa (144)
⎝ e⎠
S
⎛ L − x1 ⎞
Q2 = ⎜ ⎟ qa (145)
⎝ e ⎠
S
• The coefficient K in Eqs. 141-143 is 1,050 for gpm & inches; 16.42(10)6 for
lps and cm; or 1.217(10)12 for lps and mm
Sprinkle & Trickle Irrigation Lectures Page 89 Merkley & Allen
• Combine the above equations and set it equal to zero:
f ( x1 ) = α1 ⎡α 2 − α3 (L − x1 ) F2 ⎤ − 0.2ha + ∆he = 0
2.852
(146)
⎢⎣ ⎥⎦
where
K
α1 = (147)
100 C1.852
1.852
⎛q L⎞
α2 = ⎜ a ⎟ D1−4.87F1 L (148)
⎝ Se ⎠
1.852
α3 = ( D1−4.87 − D2−4.87 ) ⎛ qa ⎞
⎜ ⎟
⎝ Se ⎠
(149)
df(x1)
=
dx1
(150)
⎡ S (L − x1)0.852 ⎛ 8Se ⎞ ⎤
= α1α3 ⎢ 2.852F2 (L − x1)1.852 − e ⎜ 1 + ⎟⎥
⎢⎣ 2 ⎝ 13(L − x1) ⎠ ⎥⎦
• Note that the solution may fail if the sizes D1 & D2 are inappropriate
• To make things more interesting, give the computer program a list of inside
pipe diameters so that it can find the most appropriate available values of D1
& D2
• Note that the Darcy-Weisbach equation could be used instead of Hazen-
Williams
• In Eq. 146 you could adjust the value of the 0.2 coefficient on ha to determine
its sensitivity to the pipe diameters and lengths
• The following screenshot is of a small computer program for calculating
diameters and lengths of dual pipe size sprinkler laterals
5 1
hl = ha + hf + ∆he + hr
8 2 (151)
• This is the same as the lateral inlet pressure head equation for single pipe
size, except that the coefficient on hf is 5/8 instead of 3/4
• Remember that for a downhill slope, the respective pressure changes due to
friction loss and due to elevation change are opposing
where hcv is the pressure head loss through the flow control device
• For a lateral with flow control devices, the average pressure is not equal to
the nominal sprinkler pressure
havg ≠ ha
(153)
2
⎛q ⎞
ha = ⎜ a ⎟
⎝ Kd ⎠ (154)
• Valves are available for preventing flow through sprinklers until a certain
minimum pressure is reached
• These valves are installed at the base of each sprinkler and are useful where
sprinkler irrigation is used to germinate seeds on medium or high value crops
• The valves help prevent seed bed damage due to low pressure streams of
water during startup and shutdown
• But, for periodic-move, the lines still must be drained before moving
• The question is, for known inlet head, H0, pipe diameter, D, sprinkler spacing,
Se, ground slope, So, sprinkler discharge coefficient, Kd, riser height, hr, and
pipe material (C factor), what is the flow rate through each sprinkler?
• Knowing the answer will lead to predictions of application uniformity
• In this case, we won’t assume a constant qa at each sprinkler
Hazen-Williams equation:
JL
hf = (155)
100
1.852
6⎛Q⎞
J = 16.42 (10 ) ⎜ ⎟ D−4.87
⎝C⎠ (156)
1.852
JSe ⎛Q⎞
= 16.42 (10 ) Se ⎜ ⎟ D−4.87
4
hf =
100 ⎝C⎠ (157)
or,
hf = hw Q1.852 (158)
where Q is the flow rate in the lateral pipe between two sprinklers, and
typically,
q = Kd h (160)
where q is the sprinkler flow rate in lps; h is the pressure head at the
sprinkler in m; and Kd is an empirical coefficient: Kd = KoA, where A is the
cross sectional area of the inside of the pipe
• Suppose there are only four sprinklers, evenly spaced (see the above figure)
• Suppose that we know H0, Kd, C, D, hr, So, and Se
(Q − Q )
2 2
⎛q ⎞
q1 = K d H1 − hr → H1 = hr + ⎜ 1 ⎟ = hr + 1 2 2 (161)
⎝ Kd ⎠ Kd
(Q − Q )
2 2
⎛q ⎞
q2 = K d H2 − hr → H2 = hr + ⎜ 2 ⎟ = hr + 2 2 3 (162)
⎝ Kd ⎠ Kd
(Q − Q )
2 2
⎛q ⎞
q3 = K d H3 − hr → H3 = hr + ⎜ 3 ⎟ = hr + 3 2 4 (163)
⎝ Kd ⎠ Kd
2
⎛ q4 ⎞ Q42
q4 = K d H4 − hr → H4 = hr + ⎜ ⎟ = hr + 2 (164)
⎝ Kd ⎠ Kd
where,
Se
∆he = (169)
So−2 +1
( Q 2 − Q3 ) 2 = H 1.852
1 − h w Q2 − ∆he − hr (171)
K d2
Q4 2
= H3 − hw Q41.852 − ∆he − hr (173)
K d2
f1 = H0 −
( Q1 − Q2 )
2
−h 1.852
− ∆he − hr = 0
w Q1 (174)
K 2d
f2 =
( Q1 − Q2 )
2
−
( Q2 − Q3 )
2
−h 1.852
− ∆he − hr = 0
w Q2 (175)
K 2d K 2d
f3 =
( Q2 − Q3 )
2
−
( Q3 − Q4 )
2
−h 1.852
− ∆he − hr = 0
w Q3 (176)
K 2d K 2d
f4 =
( Q3 − Q4 )
2
−
Q 42
−h 1.852
− ∆he − hr = 0
w Q4 (177)
K 2d K 2d
⎡ ∂f1 ∂f1 ⎤ ⎡ ⎤ ⎡ ⎤
⎢ ∂Q ∂Q2 ⎥ ⎢ δQ1 ⎥ ⎢ f1 ⎥
⎢ 1 ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ∂f2 ∂f2 ∂f2 ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ∂Q ∂Q2 ∂Q3 ⎥ ⎢ δQ2 ⎥ ⎢ f2 ⎥
⎢ 1 ⎥ ⎢ ⎥ =⎢ ⎥ (178)
⎢ ∂f3 ∂f3 ∂f3 ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ⎥ ⎢ δQ3 ⎥ ⎢ f3 ⎥
⎢ ∂Q2 ∂Q3 ∂Q4 ⎥
⎢ ⎥ ⎢ ⎥
⎢ ∂f4 ∂f4 ⎥ ⎢ δQ ⎥ ⎢ f4 ⎥
⎢ ⎥ ⎢ 4
⎥ ⎢ ⎥
⎣ ∂Q3 ∂Q4 ⎦ ⎣ ⎦ ⎣ ⎦
where the two values in the first row of the square matrix are:
∂f1 −2 ( Q1 − Q2 )
= − 1.852hw Q10.852 (179)
∂Q1 2
Kd
∂f1 2 ( Q1 − Q2 )
= (180)
∂Q2 K 2d
∂fn 2 ( Qn−1 − Qn )
= (181)
∂Qn−1 K 2d
∂fn −2Qn−1
= − 1.852hw Qn0.852 (182)
∂Qn 2
Kd
and the three values in each intermediate row of the matrix are:
∂fi 2 ( Qi−1 − Qi )
= (183)
∂Qi−1 K 2d
∂fi 2 ( Qi − Qi+1 )
= (185)
∂Qi+1 K 2d
• The problem could be further generalized by allowing for different pipe sizes
in the lateral, by including minor losses, by allowing variable elevation
changes between sprinkler positions, etc.
• However, it is still a problem of solving for x unknowns and x equations
• For pumped systems (not gravity, as above), we could include a
mathematical representation of the pump characteristic curve to determine
the lateral hydraulic performance; that is, don’t assume a constant H0, but
replace it by some function
• There is a computer program that will do the above calculations for a gravity-
fed lateral with multiple sprinklers
• But, if you want to write your own program in a simpler way, you can do the
calculations by “brute-force” as follows:
I. Split-Line Laterals
Sprinkle & Trickle Irrigation Lectures Page 101 Merkley & Allen
• In the above case, and for only a single lateral on the mainline, the design of
the mainline is relatively simple – it is easy to find the most extreme
operating position
• However, the friction loss along the mainline is about four times greater than
for the split-line configuration
• Note that for the above two configurations the first sprinkler on the laterals
would be at 0.5Se from the inlet, unless the mainline is laid upon a roadway
in the field
Merkley & Allen Page 102 Sprinkle & Trickle Irrigation Lectures
• Buried mainlines tend to last longer, because they are not handled and
banged up after installation
• See example 10.1 from the textbook, an uphill mainline design for two split-
line laterals
• For design, consider the two extreme lateral positions:
• Divide the mainline into two logical lengths, at the mid-point, according to the
two extreme lateral positions
• Determine the total allowable head loss due to friction in each of these logical
lengths, then find two adjacent pipe sizes for each length
• Determine the lengths of each pipe size so that the total head loss is just
equal to the allowable head loss
• This is somewhat analogous to the procedure for designing dual pipe size
laterals
• This is the system layout (shown with both laterals at position B):
Sprinkle & Trickle Irrigation Lectures Page 103 Merkley & Allen
• Pump provides at least 172 ft of head at P
• Lateral inlet pressure head is given as 125 ft of head (Eq. 9.2)
• Supply line and mainline are to be aluminum, in 30-ft lengths
• The figure below shows the hydraulic schematic for this mainline, with
separate friction loss profiles for the two extreme lateral positions
• The mainline is tentatively divided into sizes D1 and D2 for the first half (L1),
and D3 and D4 for the second half (L2). So, there are potentially four different
pipe sizes in the mainline from A to C.
Merkley & Allen Page 104 Sprinkle & Trickle Irrigation Lectures
II. Select the Size of the Supply Line
• We need to select the size of the supply line to know what the head loss is
from P to A (pressure at P is given as 172 ft of head)
• Assume no elevation change between P and A
4Q 4 (1.11 cfs )
D= = = 0.53 ft (186)
πV π ( 5 fps )
• This is 6.4 inches. In Table 8.4, the 6-inch pipe has an inside diameter of
5.884 inches. With this size, the velocity at 500 gpm would be 5.9 ft/s, which
we will accept (could use 8-inch pipe, but 6-inch is probably OK)
• From Table 8.4, the head loss gradient in the 6-inch supply line at 500 gpm is
2.27 ft/100 ft. Then,
• We will tolerate (hf)1 head loss over section L1 of the mainline when both
laterals are operating at B. This will give the required hl at B.
• We can see that (hf)1 is defined as:
⎛ 30 ft ⎞
( Ja )L1 = 100 ⎜ ⎟ = 5 ft per 100 ft (190)
⎝ 600 ft ⎠
• From Table 8.4, this is between the 5- and 6-inch pipe sizes, which have
respective loss gradients of 5.54 ft/100 ft and 2.27 ft/100 ft for the 500 gpm
flow rate. Therefore, choose D1 = 6 inch and D2 = 5 inch.
Sprinkle & Trickle Irrigation Lectures Page 105 Merkley & Allen
• Now we must find out how long D1 should be so that the friction loss is really
equal to 30 ft of head...
• With the adjusted lengths, we will get 30.3 ft of head loss over section L1 for
500 gpm (this is close enough to the allowable 30 ft)
• We will tolerate (hf)3 + (hf)4 head loss over the whole length of the mainline
when one lateral is operating at A and the other at C
• We can calculate (hf)4 straight away because we already know the pipe sizes
and lengths in section L1...
hf 4 =
( 90 ft )( 0.63 ) + ( 510 ft )(1.53 ) = 8.37 ft (194)
100
where the friction loss gradients for 250 gpm are 0.63 ft/100 ft (6” size) and
1.53 ft/100 ft (5” size). These values were taken from Table 8.4.
• Now we need to know the allowable loss for (hf)3, such that the pressure in
the mainline at C will be equal to hl (we know that the pressure at A is 162 ft -
- it is more than enough)...
⎛ 14.6 ft ⎞
( Ja )L2 = 100 ⎜ ⎟ = 2.43 ft per 100 ft (197)
⎝ 600 ft ⎠
Merkley & Allen Page 106 Sprinkle & Trickle Irrigation Lectures
• From Table 8.1, this is between the 4- and 5-inch pipe sizes, which have
respective loss gradients of 4.66 ft/100 ft and 1.53 ft/100 ft for the 250 gpm
flow rate. Therefore, choose D3 = 5 inch and D4 = 4 inch.
• Now we must find out how long D3 should be so that the friction loss is really
equal to 14.6 ft of head...
• With the adjusted lengths, we will get 14.8 ft of head loss over section L2 for
250 gpm (this is close enough to the allowable 14.6 ft)
• Just to be sure, suppose that one lateral is operating halfway between A and
B, and the other halfway between B and C
• The allowable friction loss from point A to the furthest lateral is (hf)2 + ¼∆he,
or 23.0 ft + 3.5 ft = 26.5 ft. The actual friction loss would be:
• OK, the head in the mainline at the furthest lateral is more than enough
• See the figure below for a graphical interpretation of the two laterals in
intermediate positions
Sprinkle & Trickle Irrigation Lectures Page 107 Merkley & Allen
VI. Comments About the Mainline Design
• The lateral inlet pressure will be just right when both laterals operate at B
• The lateral inlet pressure will be just right for a lateral operating at C
• The lateral inlet pressure will always be too high for a lateral operating
between A and B (the inlet pressure to the mainline, at A, is always 162 ft)
• We designed D1 and D2 for the condition when both laterals are at B. This is
a more demanding condition for L1 than when one lateral is at A and the
other at C (in this case, only half the system flow rate is in L1). So, we don’t
need to “check” D1 and D2 again for the case when the laterals are at A and
C.
• We didn’t consider the hydrant loss from the mainline into the sprinkler
lateral, but this could be added to the requirements (say, effective hl)
• This design could be also done using the economic pipe selection method (or
another pipe selection method. It would be a good idea to check to see if the
Merkley & Allen Page 108 Sprinkle & Trickle Irrigation Lectures
172 ft at the pump (point A) could be reduced by using larger supply and
mainline pipes, thus reducing the annual energy costs. However, if the 172 ft
were due to gravity supply, the design would still be all right.
• However, the velocity in the 5-inch pipe at 500 gpm is too high, at 8.5 fps
(always check velocity limits when sizing pipes!)
• How would the mainline design change if it were not split line operation, and
both laterals were operating at location C?
• In this case, intuition and past experience tells us location C is the critical
lateral position – if you don’t agree, then you should test other lateral
positions to convince yourself
• We will tolerate (hf)2 head loss over the entire 1,200-ft length of the mainline
when both laterals are operating at C. This will give the required hl at C.
• We can see that (hf)2 is defined as:
• The allowable loss gradient over the length of the mainline for both laterals
operating at C is
⎛ 23 ft ⎞
Ja = 100 ⎜ ⎟ = 1.92 ft per 100 ft (204)
⎝ 1,200 ft ⎠
• From Table 8.4, this is between the 6- and 8-inch pipe sizes, which have
respective loss gradients of 2.27 ft/100 ft and 0.56 ft/100 ft for the 500 gpm
flow rate
• Determine the respective pipe lengths so that the friction loss is really equal
to 23 ft of head...
Sprinkle & Trickle Irrigation Lectures Page 109 Merkley & Allen
Merkley & Allen Page 110 Sprinkle & Trickle Irrigation Lectures
Lecture 10
Minor Losses & Pressure Requirements
I. Minor Losses
• Minor (or “fitting”, or “local”) hydraulic losses along pipes can often be
estimated as a function of the velocity head of the water within the particular
pipe section:
V2
hml = Kr (208)
2g
where hml is the minor loss (m or ft); V is the mean flow velocity, Q/A (m/s or
fps); g is the ratio of weight to mass (9.81 m/s2 or 32.2 ft/s2); and Kr is a
coefficient, dependent on the type of fitting (valve, bend, transition,
constriction, etc.)
• In using Tables 11.1 and 11.2 for hydrants, the nominal diameter (3, 4, 5,
and 6 inches) is the diameter of the hydrant and riser pipe, not the diameter
of the source pipeline
• Use the diameter of the hydrant for Kr and for computing Vr. However, for
line flow past a hydrant, use the velocity in the source pipeline, as indicated
above.
• Always use the largest velocity along the path which the water travels – this
may be either upstream or downstream of the fitting
• Do not consider velocities along paths through which the water does not flow
Sprinkle & Trickle Irrigation Lectures Page 111 Merkley & Allen
( )
2
Kr = 0.7 1 − Dr2 (209)
( )
2
Kr = K f 1 − Dr2 (210)
and f is the angle of the expansion or contraction in the pipe walls (degrees
or radians), where f ≥ 0
Expansion
Contraction
• For a sudden (abrupt) expansion, the head loss can also be approximated as
a function of the difference of the mean flow velocities upstream and
downstream:
Merkley & Allen Page 112 Sprinkle & Trickle Irrigation Lectures
hml =
( Vus − Vds )
2
(212)
2g
• An extreme (albeit unrealistic) case is for Vds = 0 and hml = Vus2/2g (total
conversion of velocity head)
• Various other equations (besides those given above) for estimating head loss
in pipe expansions and contractions have been proposed and used by
researchers and engineers
0.070 m3 / s
V200 = = 2.23 m / s (213)
⎛ π(0.200 m)2 ⎞
⎜⎜ ⎟⎟
⎝ 4 ⎠
0.070 − 0.016 m3 / s
V150 = = 3.06 m / s (214)
⎛ π(0.150 m)2 ⎞
⎜⎜ ⎟⎟
⎝ 4 ⎠
0.016 m3 / s
Vhydrant = = 3.62 m / s (215)
⎛ π(0.075 m)2 ⎞
⎜⎜ ⎟⎟
⎝ 4 ⎠
Sprinkle & Trickle Irrigation Lectures Page 113 Merkley & Allen
• Note that V200 and V150 are both above the normal design limit of about 2 m/s
• The head loss past the open hydrant is based on the higher of the upstream
and downstream velocities, which in this example is 3.06 m/s
• From Table 11.1, the Kr for flow past the open hydrant (line flow; 6” mainline)
is 0.5; thus,
(3.06)2
(hml )past = 0.5 = 0.24m (216)
2(9.81)
• The head loss due to the contraction from 200 mm to 150 mm diameter (at
the hydrant) depends on the transition
• If it were an abrupt transition, then:
2
⎡ ⎛ 150 ⎞2 ⎤
Kr = 0.7 ⎢1 − ⎜ ⎟ ⎥ = 0.13 (217)
⎢⎣ ⎝ 200 ⎠ ⎥⎦
• Thus, the total minor loss in the mainline in the vicinity of the open hydrant is
about 0.24 + 0.06 = 0.30 m (0.43 psi).
• The loss through the hydrant is determined by taking Kr = 8.0 (Table 11.1; 3”
hydrant):
(3.62)2
(hml )through = 8.0 = 5.3m (219)
2(9.81)
• This is a high loss through the hydrant (about 7.6 psi), so it may be advisable
to use a larger diameter hydrant.
• The pressure in the mainline downstream of the hydrant is (9.81 kPa/m):
⎛ V200
2 2 ⎞
− V150
P150 = P200 − γ (hml )past + γ⎜ ⎟
⎜ 2g ⎟
⎝ ⎠
(220)
⎛ (2.23) − (3.06)
2 2 ⎞
P150 = 300 − (9.81)(0.24) + 9.81⎜ = 295kPa
⎜ 2(9.81) ⎟⎟
⎝ ⎠
Merkley & Allen Page 114 Sprinkle & Trickle Irrigation Lectures
II. Total Dynamic Head
• The Total Dynamic Head (TDH) is the head that the pump “feels” or “sees”
while working, and is calculated to determine the pump requirements
• It includes the elevation that the water must be lifted from the source (not
necessarily from the pump elevation itself) to the outlet, the losses due to
“friction”, the pressure requirement at the outlet, and possibly the velocity
head in the pipeline
• For a sprinkler system, the value of TDH depends on the positions of the
laterals, so that it can change with each set. Pump selection is usually made
for the “critical” or extreme lateral positions, that is, for the “worst case
scenario”.
• Keller & Bliesner recommend the addition of a “miscellaneous” loss term,
equal to 20% of the sum of all “friction” losses. This accounts for:
• The system curve determines the relationship between TDH and flow rate
• This curve is approximately parabolic, but can take more complex shapes
• Note that head losses in pipe systems are approximately proportional to the
square of the flow rate (Q2 or V2)
• For the Hazen-Williams equation, these losses are actually proportional to
Q1.852 or V1.852
• For standard, non-FCN, sprinkler nozzles, the head at the sprinkler is also
proportional to Q2
• Sprinkler systems can have a different system curve for each position of the
lateral(s)
• Defining the system curve, or the “critical” system curve, is important for
pump selection because it determines, in part, the operating point (TDH and
Q) for the system
Sprinkle & Trickle Irrigation Lectures Page 115 Merkley & Allen
IV. Valving a Pump
I. Types of Pumps
1. Positive Displacement
• Piston pumps
• Rotary (gear) pumps
• Extruding (flexible tube) pumps
2. Variable Displacement
• Centrifugal pumps
• Injector pumps
• Jet pumps
Merkley & Allen Page 116 Sprinkle & Trickle Irrigation Lectures
Positive Displacement Pumps
Axial-Flow Impeller
Jet Pump
Sprinkle & Trickle Irrigation Lectures Page 117 Merkley & Allen
• But, with positive displacement pumps, the required pumping energy is a
linear function of the pressure
• Positive displacement pumps can be used with thick, viscous liquids. They
are not commonly used in irrigation and drainage, except for the injection of
chemicals into pipes and for sprayers
• Piston-type pumps can develop high heads at low flow rates
• Air injection, or jet pumps are typically used in some types of well drilling
operations. The air bubbles effectively reduce the liquid density and this
assists in bringing the drillings up out of the well. Needs a large capacity air
compressor.
• Homologous pumps are geometrically similar pumps, but of different sizes
1. Volute Case This is the most common type of irrigation and drainage pump
(excluding deep well pumps). Produce relatively high flow rates at low
pressures.
2. Diffuser (Turbine) The most common type for deep wells. Designed to lift
water to high heads, typically using multiple identical “stages” in series,
stacked up on top of each other.
3. Mixed Flow Uses a combination of centrifugal and axial flow action. For high
capacity at low heads.
4. Axial Flow Water flows along the axis of impeller rotation, like a boat
propeller. Appropriate for high discharge under very low lift (head). An
example is the pumping plant on the west side of the Great Salt Lake.
• In general, larger pumps have higher maximum efficiencies (they are more
expensive, and more effort is given toward making them more efficient)
• Impellers can be open, semi-open, or closed. Open impellers are usually
better at passing solids in the pumped liquid, but they are not as strong as
closed impellers
• Double suction inlet pumps take water in from both sides and can operate
without axial thrust
Merkley & Allen Page 118 Sprinkle & Trickle Irrigation Lectures
Closed Impeller Semi-Open Impeller Open Impeller
Characteristic Curve
Efficiency
Cha
ra cte
risi
cC
urv
Shut-Off Head
Power
0
0 Flow Rate, Q
Sprinkle & Trickle Irrigation Lectures Page 119 Merkley & Allen
III. Centrifugal Pumps in Parallel
• Pumps in PARALLEL
p
from the pumps
converging to a single
discharge pipe
• If only one of the
pumps operates, some 0
type of valve may be 0 Flow Rate, Q
required so that flow does not flow backwards through the idle pump
• Flow rate is additive in this case
pump 1
pump 2
Two Pumps in Parallel
• Pumps in SERIES means that the total flow passes through each of two or
more pumps in line
• Typical installations are for increasing pressure, such as with a booster pump
• Head is additive in this case
Merkley & Allen Page 120 Sprinkle & Trickle Irrigation Lectures
Total Dynamic Head, TDH
Two
in Se
rie
s
One P
ump
0
0 Flow Rate, Q
• It is common for turbine (well) pumps to operate in series
• For centrifugal pumps, it is necessary to exercise caution when installing in
series because the efficiency can be adversely affected
• May need straightening vanes between pumps to reduce swirling
• Note that the downstream pump could cause negative pressure at the outlet
of the US pump, which can be a problem
pump 1 pump 2
Sprinkle & Trickle Irrigation Lectures Page 121 Merkley & Allen
Merkley & Allen Page 122 Sprinkle & Trickle Irrigation Lectures
Lecture 11
Pumps & System Curves
where brake horsepower refers to the input power needed at the pump shaft
(not necessarily in “horsepower”; could be watts or some other unit)
QH
WHP = (222)
3956
where WHP is in horsepower; Q in gpm; and H in feet of head. The
denominator is derived from:
1 HP=0.746 kW (225)
P V2
TDH = ∆Elev + hf + + (226)
γ 2g
Sprinkle & Trickle Irrigation Lectures Page 123 Merkley & Allen
where the pressure, P, and velocity, V, are measured at the pump outlet, and
hf is the total friction loss from the entrance to the exit, including minor losses
P
TDH = ∆Elev + (227)
γ
but recognizing that in some cases P/γ is zero for a zero flow rate
Merkley & Allen Page 124 Sprinkle & Trickle Irrigation Lectures
Consider a centrifugal pump:
• Determine TDH and WHP for a centrifugal pump discharging into the air...
Sprinkle & Trickle Irrigation Lectures Page 125 Merkley & Allen
ε 1.5(10)−6
= = 0.0000051 (229)
D 0.295
Average velocity,
Q 4(0.102)
V= = = 1.49 m/s (230)
A π(0.295)2
⎛ 1,530 ⎞ (1.49 )
2
L V2
hpipe =f = 0.0141⎜ ⎟ = 8.27 m (232)
D 2g ⎝ 0.295 ⎠ 2 ( 9.81)
Kinematic Viscosity
Water Temperature (°C)
(m2/s)
0 0.000001785
5 0.000001519
10 0.000001306
15 0.000001139
20 0.000001003
25 0.000000893
30 0.000000800
40 0.000000658
50 0.000000553
60 0.000000474
( )
−1
ν = 83.9192 T 2 + 20,707.5 T + 551,173 (233)
Merkley & Allen Page 126 Sprinkle & Trickle Irrigation Lectures
From Table 11.2, for a 295-mm (12-inch) pipe and long radius 45-deg flanged
elbow, the Kr value is 0.15
V2 (1.49)2
helbow = Kr = (0.15) = (0.15)(0.11) = 0.017 m (234)
2g 2(9.81)
For the screen, assume a 0.2 m loss. Then, the total head loss is:
With the velocity head of 0.11 m, the total dynamic head is:
QH (102 lps )( 40 m )
WHP = = = 40 kW (54 HP)
102 102 (237)
WHP 40 kW
BHP = = ≈ 53 kW (71 HP)
Epump 0.76
(238)
• This BHP value would be used to select a motor for this application
• These calculations give us one point on the system curve (Q and TDH)
• In this simple case, there would be only one system curve:
System Curve
60
50
Total Dynamic Head (m)
40
30
20
10
0
0 20 40 60 80 100 120 140 160 180
Discharge (lps)
Sprinkle & Trickle Irrigation Lectures Page 127 Merkley & Allen
III. System Curves
• Most sprinkle and trickle irrigation systems have more than one system curve
because either the sprinklers move between sets (periodic-move systems),
move continuously, or “stations” (blocks) of laterals are cycled on and off
• The intersection between the system and pump characteristic curves is the
operating point (Q and TDH)
• A few examples of system curves:
Merkley & Allen Page 128 Sprinkle & Trickle Irrigation Lectures
2. Mostly Static Lift, Little Friction Loss
Sprinkle & Trickle Irrigation Lectures Page 129 Merkley & Allen
4. Two Different Static Lifts in a Branching Pipe
• The figure below shows two center pivots supplied by a single pump on a
river bank
• One of the pivots (#1) is at a higher elevation than the other, and is
further from the pump – it is the “critical” branch of the two-branch pipe
system
• Center pivot #2 will have excess pressure when the pressure is correct at
Center pivot #1, meaning it will need pressure regulation at the inlet to the
pivot lateral
• Use the critical branch (the path to Center pivot #1, in this case) when
calculating TDH for a given operating condition – Do Not Follow Both
Branches when calculating TDH
• if you cannot determine which is the critical branch by simple inspection,
you must test different branches by making calculations to determine
which is the critical one
• Note that the system curve will change with center pivot lateral position
when the topography is sloping and or uneven within the circle
• Of course, the system curve will also be different if only one of the center
pivots is operating
Merkley & Allen Page 130 Sprinkle & Trickle Irrigation Lectures
Center pivot #1
Center pivot #2
275 kPa
833 m
275 kPa
750 m
308 m river
pump
Sprinkle & Trickle Irrigation Lectures Page 131 Merkley & Allen
lateral #5 (critical lateral)
lateral #4
lateral #3
mainline
uphill
lateral #2
lateral #1
pump
Merkley & Allen Page 132 Sprinkle & Trickle Irrigation Lectures
Total Dynamic Head, TDH
1 2
Unstable Stable
A
B
urv e
te mC
Sys
0
0 Flow Rate, Q
I. Affinity Laws
2 3
Q1 N1 H1 ⎛ N1 ⎞ BHP1 ⎛ N1 ⎞
= =⎜ ⎟ =⎜ ⎟ (239)
Q2 N2 H2 ⎝ N2 ⎠ BHP2 ⎝ N2 ⎠
where Q is flow rate; N is pump speed (rpm); H is head; and BHP is “brake
horsepower”
2. Impeller diameter:
Sprinkle & Trickle Irrigation Lectures Page 133 Merkley & Allen
2 3
Q1 D1 H1 ⎛ D1 ⎞ BHP1 ⎛ D1 ⎞
= =⎜ ⎟ =⎜ ⎟ (240)
Q2 D 2 H2 ⎝ D2 ⎠ BHP2 ⎝ D2 ⎠
Comments:
• The affinity laws are only valid within a certain range of speeds, impeller
diameters, flow rates, and heads
• The affinity laws are more accurate near the region of maximum pump
efficiency (which is where the pump should operate if it is selected correctly)
2
H1 ⎛ Q1 ⎞
=⎜ ⎟ (241)
H2 ⎝ Q2 ⎠
• If this relationship is plotted with the pump characteristic curve and the
system curve, it is called the “equal efficiency curve”
• This is because there is typically only a small change in efficiency with a
small change in pump speed
• Note that the “equal efficiency curve” will pass through the origin (when Q is
zero, H is zero)
• Follow these steps to adjust the: (1) speed; or, (2) impeller diameter, such
that the actual operating point shifts up or down along the system curve:
Merkley & Allen Page 134 Sprinkle & Trickle Irrigation Lectures
2
⎛Q ⎞
H1 = H2 ⎜ 1 ⎟ (242)
⎝ Q2 ⎠
3. Plot the values from this table on the graph that already has the
pump characteristic curve
4. Locate the intersection between the pump characteristic curve
and the “equal efficiency curve”, and determine the Q3 and H3
values at this intersection
5. Use either of the following equations to determine the new
pump speed (or use equations involving D to determine the trim
on the impeller):
⎛Q ⎞ H2
Nnew = Nold ⎜ 2 ⎟ or, Nnew = Nold (243)
⎝ Q3 ⎠ H3
• You cannot directly apply any of the affinity laws in this case because you will
either get the right discharge and wrong head, or the right head and wrong
discharge
Apply Affinity
Law from Here
e
rv
Cu
m
te
ys
3 S Operating Point
Head
m
p
Cu
g!
C
ron
y
nc
ur
W
cie
ve
ffi
l E
ua
Eq
0
0 Flow Rate
Sprinkle & Trickle Irrigation Lectures Page 135 Merkley & Allen
III. Specific Speed
2πN Q
Ns = (244)
(gH)0.75
IV. Cavitation
• Air bubbles will form (the water boils) when the pressure in a pump or
pipeline drops below the vapor pressure
• If the pressure increases to above the vapor pressure downstream, the
bubbles will collapse
• This phenomenon is called “cavitation”
• Cavitation often occurs in pumps, hydroelectric turbines, pipe valves, and
ship propellers
• Cavitation is a problem because of the energy released when the bubbles
collapse; formation and subsequent collapse can take place in only a few
thousandths of a second, causing local pressures in excess of 150,000 psi,
and local speeds of over 1,000 kph
• The collapse of the bubbles has also been experimentally shown to emit
small flashes of light (“sonoluminescence”) upon implosion, followed by rapid
expansion on shock waves
• Potential problems:
Patmospheric
Pvapor
1. Large suction pipe to reduce friction loss and increase NPSHa, especially
where NPSHa is already too close to NPSHr (e.g. high-elevation pump
installations where the atmospheric pressure head is relatively low)
2. Eccentric reducer to avoid accumulation of air bubbles at the top of the
pipe
Sprinkle & Trickle Irrigation Lectures Page 137 Merkley & Allen
Required NPSH
• Data from the manufacturer are available for most centrifugal pumps
• Usually included in this data are recommendations for required Net Positive
Suction Head, NPSHr
• NPSHr is the minimum pressure head at the entrance to the pump, such that
cavitation does not occur in the pump
• The value depends on the type of pump, its design, and size
• NPSHr also varies with the flow rate at which the pump operates
• NPSHr generally increases with increasing flow rate in a given pump
• This is because higher velocities occur within the pump, leading to lower
pressures
• Recall that according to the Bernoulli equation, pressure will tend to
decrease as the velocity increases, elevation being the same
• NPSHr is usually higher for larger pumps, meaning that cavitation can be
more of a problem in larger pump sizes
Available NPSH
V2
NPSHa = hatm − hvapor − hf − hlift − (245)
2g
Merkley & Allen Page 138 Sprinkle & Trickle Irrigation Lectures
Vapor Pressure Head
Static Lift
Velocity Head
Available NPSH
• If the pump could create a “perfect vacuum” and there were no losses, the
water could be “sucked up” to a height of 10.34 m (at mean sea level)
• Average atmospheric pressure is a function of elevation above msl
perfect
vacuum
10.34 m
sea level
water
Sprinkle & Trickle Irrigation Lectures Page 139 Merkley & Allen
11
10
9
Vapor Pressure Head (m)
8
7
6
5
4
3
2
1
0
0 10 20 30 40 50 60 70 80 90 100
Water Temperature (C)
Straight line:
hatm = 10.3 − 0.00105 z (247)
Exponential curve:
5.26
⎛ 293 − 0.0065 z ⎞
hatm = 10.33 ⎜ ⎟ (248)
⎝ 293 ⎠
where hatm is atmospheric pressure head (m of water); and z is elevation
above mean sea level (m)
Merkley & Allen Page 140 Sprinkle & Trickle Irrigation Lectures
10.50
10.00
Mean atmospheric pressure (m)
9.50
Straight Line (m)
Exponential Curve (m)
9.00
8.50
8.00
7.50
7.00
6.50
0 500 1000 1500 2000 2500 3000
Elevation above msl (m)
Sprinkle & Trickle Irrigation Lectures Page 141 Merkley & Allen
1. Head Loss due to Friction
ε 0.2 mm
= = 0.000556 (249)
D 360 mm
flow velocity,
Q 0.100 m3 / s
V= = = 0.982 m/s (250)
π
A
( 0.36 ) 2
4
Reynold’s Number,
VD ( 0.982 )( 0.36 )
NR = = = 353,000 (251)
ν 1.003(10)−6
velocity head,
V 2 (0.982)2
= = 0.049 m (252)
2g 2g
L V2 ⎛ 8.1 ⎞
(hf )pipe =f = 0.0184 ⎜ ⎟ ( 0.049 ) = 0.0203 m (253)
D 2g ⎝ 0.36 ⎠
local losses, for the bell-shaped entrance, Kr = 0.04; for the 90-deg elbow, Kr =
0.14. Then,
finally,
(hf )total = (hf )pipe + (hf )local = 0.0203 + 0.0088 = 0.0291 m (255)
Merkley & Allen Page 142 Sprinkle & Trickle Irrigation Lectures
2. Vapor Pressure
3. Atmospheric Pressure
5. Available NPSH
V2
NPSHa = hatm − hvapor − (hf )total − hlift −
2g (256)
NPSHa = 10.1 − 0.25 − 0.0291 − 3.0 − 0.049 = 6.77 m
Sprinkle & Trickle Irrigation Lectures Page 143 Merkley & Allen
Merkley & Allen Page 144 Sprinkle & Trickle Irrigation Lectures
Lecture 12
Center Pivot Design & Operation
• Center pivots are used on about half of the sprinkler-irrigated land in the USA
• Center pivots are also found in many other countries
• Typical lateral length is 1,320 ft (400 m), or ¼ mile
• The lateral is often about 10 ft above the ground
• Typically, 120 ft pipe span per tower (range: 90 to 250 ft), often with one-
horsepower electric motors (geared down)
• At 120 ft per tower, a 1,320-ft lateral has about 10 towers; with 1-HP motors,
that comes to about 10 HP just for moving the pivot around in a circle
• The cost for a ¼-mile center pivot is typically about $55,000 (about $435/ac
or $1,100/ha), plus about $20,000 (or more) for a corner system
• For a ½-mile lateral, the cost may be about $75,000 (w/o corner system)
• In the state of Nebraska there are said to be 43,000 installed center pivots,
about 15% of which have corner systems
• Center pivots are easily (and commonly) automated, and can have much
lower labor costs than periodic-move sprinkler systems
• Center pivot maintenance costs can be high because it is a large and fairly
complex machine, operating under “field” conditions
• The typical maximum complete rotation is 20 hrs or so, but some (120-acre
pivots) can go around in only about 6 hrs
• IPS 6” lateral pipe is common (about 6-5/8 inches OD); lateral pipe is
generally 6 to 8 inches, but can be up to 10 inches for 2,640-ft laterals
• Long pivot laterals will usually have two different pipe sizes
• Typical lateral inflow rates are 45 - 65 lps (700 to 1,000 gpm)
• At 55 lps with a 6-inch pipe, the entrance velocity is a bit high at 3 m/s
• Typical lateral operating pressures are 140 - 500 kPa (20 to 70 psi)
• The end tower sets the rotation speed; micro switches & cables keep other
towers aligned
• Corner systems are expensive; can operate using buried cable; corner
systems don’t necessarily irrigate the whole corner
• Without a corner system or end gun, π/4 = 79% of the square area is
irrigated
• For a 1,320-ft lateral (without an end gun), the irrigated area is 125.66 acres
• For design purposes, usually ignore soil WHC (WaZ); but, refill root zone at
each irrigation (even if daily)
• Center pivots can operate on very undulating topography
• Some center pivots can be moved from field to field
• Below are some sample center pivot arrangements
Sprinkle & Trickle Irrigation Lectures Page 145 Merkley & Allen
Merkley & Allen Page 146 Sprinkle & Trickle Irrigation Lectures
Sprinkle & Trickle Irrigation Lectures Page 147 Merkley & Allen
• Some pivots have an end gun that turns on in the corners, in which all other
sprinklers shut off via individual solenoid-actuated valves. The pivot stops in
the corner while the end gun runs for a few minutes.
• Others just slow down in the corners, turning on an end gun, but leaving the
other sprinklers running (at lower discharges)
• Many farmers like extra capacity in the center pivot so they can shut off
during windy times of the day, and still complete the irrigations in time
• Corner systems have angle detectors so that sprinklers in the corner arm
turn on and off individually (or in groups) as the arm swings out and then
back in again
• Center pivots have safety switches to shut the whole thing off if any tower
gets too far out of alignment. Some also have safety switches to shut them
off if the temperatures gets below freezing (ice builds up and gets heavy,
possibly collapsing the structure). Some have safety switches connected to
timers: if a tower has not moved in a specified number of minutes, the
system shuts down. There may also be safety switches associated with the
chemical injection equipment at the lateral inlet location.
Merkley & Allen Page 148 Sprinkle & Trickle Irrigation Lectures
II. System Capacity
• The general center pivot design equation for system capacity is based on Eq.
5.4 from the textbook:
Ad R2d R2Udk f
Qs = K = = (257)
fT k1fT k1TEpa
where,
• The gross application depth, d, is equal to dn/Epa, where Epa is the design
application efficiency, based on uniformity and percent area (pa) adequately
irrigated
• The operating time, T, is generally 20-22 hrs/day during the peak-use period
• R is the effective radius, based on the wetted area from the center pivot
• The effective radius is about 400 m for many pivots
• R ≈ L + 0.4w, where L is the physical length of the lateral pipe, and w is the
wetted diameter of the end sprinkler
• This assumes that approximately 0.8 of the sprinkler radius beyond the
lateral pipe is effective for crop production
• Note that, for center pivots, Qs is proportional to Ud, and d and f are generally
not used, which is similar to drip irrigation design
• If a center pivot is operated such that the water holding capacity of the soil is
essentially ignored, and water is applied frequently enough to satisfy peak-
use crop water requirements, then use dn/f = Ud, and
k f Ud k f Ud
d' = = (258)
Epa DEpaReOe
Sprinkle & Trickle Irrigation Lectures Page 149 Merkley & Allen
where d' is the gross application depth (mm/day or inches/day); and kf is a
peak-use period evaporation factor, which accounts for increased soil and
foliage evaporation due to high frequency (daily) irrigation
• When LR > 0.1, the LR can be factored into the equation as:
0.9k f Ud
d' = (259)
(1 − LR)DEpaR eOe
which is the same as Eq. 14.1b from the textbook, except that DEpa, Re and
Oe are all as fractions (not percent)
• Values of kf can be selected for the peak period from Table 14.1 of the
textbook for varying values of frequency, f
• Values for non-peak periods can be computed as described in the textbook
on page 314:
where kf and PT are for the peak-use period (Table 14.1), and k'f and PT' are
the frequency coefficient and transpiration percentage (PT) for the non-peak
period
T
PT = (261)
ET
• PT and PT' can be thought of as the basal crop coefficient (Kcb), or perhaps
Kcb - 0.1 (relative to alfalfa, as per the note in Table 14.1)
• It represents the transpiration of the crop relative to an alfalfa reference
• A major design difficulty with a center pivot is maintaining the application rate
so that it is less than the intake rate of the soil
• This is especially critical near the end of the lateral where application rates
are the highest
• As one moves along the center pivot lateral, the area irrigated by each unit
length of the lateral (each 1 ft or 1 m of length) at distance r from the pivot
point can be calculated as:
q a 2 πr 2r
= = = (263)
Qs A πR 2 R 2
or,
2rQs
q= (264)
R2
where q can be in units of lps per m, or gpm per ft
• This gives the amount of water which should be discharging from a specific
unit length of lateral at a radial distance r from the pivot point
• The q value at the end of the lateral (r = R) per ft or m is:
2Qs
qend = (265)
R
• Use q to select the nozzle size, where qnozzle = q Se
V. End-Gun Discharge
• This last equation is very similar to Eq. 14.20a, except for the omission of the
Sj term
• Equation 14.20b is for the end gun discharge, assuming that the end gun is
used primarily to compensate for the lack of pattern overlap at the end of the
lateral
• Equation 14.20b can be justified as follows:
• Assuming the “basic” circle discharge, Qb, includes the end gun discharge,
qg, we can write:
Qb qg
≈ (266)
πL2 ∆L ( 2πL' )
Sprinkle & Trickle Irrigation Lectures Page 151 Merkley & Allen
or, perhaps more precisely,
Qb qg
≈ (267)
πL2 ∆L ( 2π (L '+ ∆L / 2 ) )
but ∆L/2 is generally very small compared to L’, and this is ostensibly
assumed in Eq. 14.20b, so after solving the above for qg you will arrive at Eq.
14.20b:
2L' ∆L
qg ≅ Qb ; for ∆L < 0.03L (268)
L2
VI. Application Rate
• For a center pivot, Se = 1 (based on a unit distance along the lateral) and Sl =
w (wetted width in the tangential direction), so the average application rate
(called AR) at a distance r along the lateral is:
k f d k f (Ud − Pe )
U'd = = (270)
f DEpa
Merkley & Allen Page 152 Sprinkle & Trickle Irrigation Lectures
• At the end of the lateral (r = R), the average application rate can be
calculated as:
2πRU'd ReOe
ARr =R = (271)
60 T w
where ARx is the maximum application rate (in the center of the pattern) (ARx
is in mm/min for U’d in mm/day)
• In the above equation, k3 is 1.61 for English units, or 60 for metric units
• It is usually a better approximation to assume an elliptical pattern under the
sprinklers than to assume a rectangular pattern, even though both are only
approximations
(400)(9)(0.95)(1.0)
AR x = = 0.69 mm / min (273)
(7.5)(22)(30)
• ARx is the peak AR (at the top of the ellipse, or directly beneath the lateral),
so an “average” (ARav) can be calculated, representing the average AR
beneath the wetted area perpendicular to the lateral pipe
• The calculated value of 0.69 mm/min is 41.4 mm/hr, which could be tolerated
only by a very sandy soil
Sprinkle & Trickle Irrigation Lectures Page 153 Merkley & Allen
• For a rectangular pattern, ARav = ARx
• For an elliptical pattern, ARav = (π/4)ARx
• Therefore, in the example, ARav = (π/4)(0.69) = 0.54 mm/min
• If d were 10 mm, it would take tt = 10/0.54 = 18 minutes to apply the water at
the rate ARav. (may want to use d Re Oe instead of just d in such a
calculation)
• Re can be taken from Fig. 6.8 or from examples in Table 14.3
• Guidelines for determining CI are given in Table 14.4
• The center pivot speed (at the end of the lateral) is w/tt, where tt is the time of
wetting
• In the preceding example, w is 30 m and tt is 18 min
• Therefore, the speed should be about 30 m/18 min = 1.7 m/min at the end
• Note that with spray booms, w is larger, and AR is smaller for the same q
value
Merkley & Allen Page 154 Sprinkle & Trickle Irrigation Lectures
Lecture 13
Center Pivot Nozzling
• The wetted width of the application package can be reduced closer to the
pivot point because the towers are moving at a slower speed at inner points;
therefore, the application intensity (AR) is less (qr ∝ r)
• Generally, if spray booms are required near the end of the center pivot, spray
drops can be used toward the center, and the spray drops nearest the pivot
point will produce something like a fine mist
• At the far end of the lateral the application may be more like a torrential rain
• Generally, impact and spray sprinklers would not be mixed on a center pivot
because the pressure requirements are substantially different
• The minimum wetted width at any radius r along the pivot (for an elliptical
pattern) can be calculated as:
8r Ud
wr = (274)
60 T AR x DEpa
r U'dReOe
ARr ≤ (275)
7.5 T w d
• The term “ReOe” is included in the above equation to account for evaporation
and wind drift losses, and pipe leakage
• Note that 60/8 = 7.5 and that we are using f = 1 day
• Divide by Re in the above equation to obtain AR at the nozzle
• The wetting time at any radius r (assuming an elliptical pattern) along the
lateral is:
4D f
( t t )r = (276)
π ARr
where Df is the total cumulative application (d Re Oe)
Sprinkle & Trickle Irrigation Lectures Page 155 Merkley & Allen
II. Center Pivot Nozzling Example
Given:
Ud = 8 mm/day
Pe = 0 mm/day
T = 22 hrs/day
Qs = 73.6 lps
R = 400 m
Speed = 21.6 hrs/revolution
ARx = 2.3 mm/min (allowable)
kf = 1.02
DEpa = 0.74
Re = 0.94
Oe = 0.99
Calculations:
• Calculate Ud’:
k f (Ud − Pe ) 1.02 ( 8 − 0 )
U'd = = = 11.0 mm/day (277)
DEpa 0.74
2πr
Sr = (278)
t
where Sr is the speed in m/min; t is the minutes per full-circle revolution; and
r is the radius from the pivot point in m
wr
τ= (279)
Sr
• The values of wd can be selected from available boom lengths, which in this
case is 6, 8, 10, and 12 m. For less than 4-m width, no boom is required.
Select wd values such that ARx is not exceeded.
Merkley & Allen Page 156 Sprinkle & Trickle Irrigation Lectures
• Spreadsheet calculations:
r q wr wd ARr tau Qr
(m) (lps/m) (m) (m) (mm/min) (s) (lps)
0 0.0000 73.6
40 0.0368 1.14 3 0.829 928 72.9
80 0.0736 2.28 3 1.658 464 70.7
120 0.1104 3.42 6 1.244 619 67.0
160 0.1472 4.56 6 1.658 464 61.8
200 0.1840 5.70 6 2.073 371 55.2
240 0.2208 6.84 8 1.866 413 47.1
280 0.2576 7.98 8 2.177 354 37.5
320 0.2944 9.12 10 1.990 387 26.5
360 0.3312 10.26 10 2.239 344 14.0
400 0.3680 11.39 12 2.073 371 0.0
• Most manufacturers prefer to specify the actual nozzle sizing and spacing
along center pivots at the factory (rather than have the buyer specify these)
for reasons of liability (they have specialized computer programs which
attempt to maximize uniformity)
• Therefore, the designer will generally only specify the flow rate, pressure,
and type of nozzle (spray drop, booms, impacts, etc.), and the manufacturer
will specify individual nozzle sizes
• The following figure shows a center pivot with booms (the booms are greatly
exaggerated in width to show the concept)
Sprinkle & Trickle Irrigation Lectures Page 157 Merkley & Allen
III. Sprinkler/Nozzle Configurations
Merkley & Allen Page 158 Sprinkle & Trickle Irrigation Lectures
2. Uniform Sprinkler Size where the distance between sprinklers decreases
with r
3. Combination of 1 and 2
Sprinkle & Trickle Irrigation Lectures Page 159 Merkley & Allen
Sizing Individual Nozzles:
1. Determine q for each spacing along the lateral (see Eq. 14.20a):
2Qs
qr = r Sr (280)
R2
where R is the maximum effective radius of the center pivot (approximately
equal to L + 0.4w); Sr is the sprinkler spacing at a distance r from the pivot
point; and r, Sr and R have the same units (m or ft)
2. Beginning at the design pressure at the end of the lateral, L (where q is
known), determine Pr:
where (hfr)end is the friction loss from point r to the far (downstream) end of
the lateral. Note that (∆He)end-r often averages out to zero as the pivot makes
its way around the circle, if the field slope is uniform (see the next figure).
Merkley & Allen Page 160 Sprinkle & Trickle Irrigation Lectures
3. Select the best nozzle size to provide qr at a pressure of Pr
4. Return to Step 1 and repeat for the next r-Sr location
5. The required pressure at the pivot point is Pr = 0
no slope
uniform slope
centered on a hill
centered on a depression
IV. Trajectory Angles of Impact Sprinklers
• For center pivots, sprinklers with 6° to 18° trajectory angles (low angle) are
preferred because drift losses are minimized (see Table 14.3 in the textbook)
• Other things being the same, wind drift and evaporation losses can be higher
with center pivots than with other types of sprinkler systems because of the
relative height of the sprinklers above the ground
• But, you can use drop-down sprayers on a “goose-neck” pipe – some of
these may be only a few centimeters from the mature crop canopy
V. End Guns
• The discharge for an end gun can be computed as (see Eq. 14.21):
Sprinkle & Trickle Irrigation Lectures Page 161 Merkley & Allen
⎛ 2Sr Q ⎛ Sr ⎞⎞
⎜ 2 ⎜ L + ⎟⎟
R ⎝ ⎠⎠
Qg = ⎝
2
(282)
0.93
where L is the lateral length; R is the effective length of the pivot (R = L + Sr);
Qg is the end gun discharge; Q is the total center pivot flow rate (includes
Qg); Sr is R - L, which equals the effective wetted radius (or 75% of the gun
radius)
⎛ L2 ⎞
Qg ≈ Q ⎜ 1 − 2 ⎟ (283)
⎜ R ⎟
⎝ ⎠
2 (R − L ) Q [L + 0.5(R − L)]
=
0.93R2
2QL (R − L ) + Q (R − L )
2
(284)
2
0.93 R
Q ⎛ L2 ⎞
= ⎜ 1 − ⎟
0.93 ⎜⎝ R2 ⎟⎠
• A part circle rotation (typically about 150°) is generally used to achieve best
uniformity under the area covered by the gun sprinkler, which is beyond the
end of the lateral pipe
• If the rotation of the end gun covered 180° or more, it might make it too
muddy for the wheels of the end tower – so with 150° (or so) the path in front
of the end tower stays relatively dry
Merkley & Allen Page 162 Sprinkle & Trickle Irrigation Lectures
Booster Pump
• The total discharge in the lateral pipe (not the flow rate from sprinklers at r) at
any point r is approximately:
⎛ r2 ⎞
Qr = Qs ⎜ 1 − 2 ⎟ (285)
⎜ R ⎟
⎝ ⎠
Friction Loss
1.852
⎛Q⎞
hf = khFpL ⎜ ⎟ D−4.87 (286)
⎝C⎠
Sprinkle & Trickle Irrigation Lectures Page 163 Merkley & Allen
where kh is 10.50 for hf and L in ft, Q in gpm, and D in inches; kh is
16.42(10)4 for hf and L in m, Q in lps, and D in cm
• Fp is the multiple outlet friction factor for a center pivot (see Fig. 14.12)
• Fp = 0.555 for a center pivot with a “large” number of outlets and no end gun
when using the Hazen-Williams equation.
• Other sources suggest using Fp = 0.543
• The value of C is about 130 for galvanized steel, or 145 for epoxy-coated
steel
Compute friction loss as though the center pivot were R m long rather than L,
and then subtract the non-existent friction past the point L, where R is the
effective (wetted) radius and L is the physical length of the lateral pipe.
A traditional way to consider the effects of an end gun on friction loss is:
1.852 1.852
⎛Q⎞ −4.87 ⎛ Qg ⎞
hf = khFpR ⎜ ⎟ D − khFg (R − L) ⎜ ⎟ D−4.87
⎝C⎠ ⎝ C ⎠ (287)
where Q is the total flow rate of the pivot plus the end gun; and Qg is the flow
rate of the end gun
• A center pivot may be assembled with dual pipe sizes (8- and 6-inch pipe, or
8- and 6 5/8-inch, for example)
Merkley & Allen Page 164 Sprinkle & Trickle Irrigation Lectures
• One requirement to note is that the tower spacing must be closer for the 8-
inch pipe due to the added weight of water in the 8-inch pipe, and traction
problems from towers which are too heavy and sink into the soil
• Therefore, balance the savings in hf with added cost for the system
• Tower spacing is often 100 ft (30 m) for 8-inch pipe, and 150 ft (45 m) for 6-
inch pipe
• Weight per tower = Wt of tower + Wt of 1 span (steel) + Wt of water in the
span
where Hl is the pressure head required at ground level, at the pivot point; Ha is
the pressure head requirement of the last nozzle (or end gun); hf is the total
friction loss along the pivot lateral; ∆He is the elevation increase between the
pivot point and lateral end; Hr is the height of the lateral pipe less the vertical
length of any drop tubes; and Hminor is the sum of all minor losses along the
lateral
n
( )
Hl = Hend + ∑ ⎡ hfi + ∆Hei + Hr + Hmin or ⎤
⎣ ⎦
i=0 (289)
where Hend is the desired nozzle pressure head at the pivot end; i is the outlet
number along the lateral (i = 0 at the end, and i = n at the pivot point); n is
the number of outlets (sprinklers) on the lateral; ∆Hei is the elevation
Sprinkle & Trickle Irrigation Lectures Page 165 Merkley & Allen
difference between two adjacent points (i and i+1) along the lateral; and hfi is
the friction loss between outlet i and i+1, where i+1 is upstream of i. This last
term is defined as:
Ji ∆Li
hfi = (290)
100
where,
1.852
12 ⎛ Qi
⎞
Ji = 1.21(10) ⎜ ⎟ Di−4.87 (291)
⎝C⎠
and,
i
Qi = ∑ q j (292)
j= 0
• Hminor includes short hose connections between pipe segments (at towers)
• Therefore, actual computed hj values should be used with the selected
nominal nozzle size (or FCN size), where hj is the pressure head at outlet j
• The desired qj is:
⎛ 2Q ⎞ ⎛ 2Q ⎞
q j = rjSrj ⎜ 2 ⎟ = rj∆Li ⎜ 2 ⎟ (293)
⎝R ⎠ ⎝R ⎠
L 2π r (He ) r,α
Hew = ∫ ∫ 2πL2
dr dα (294)
r =0 α
Merkley & Allen Page 166 Sprinkle & Trickle Irrigation Lectures
where r is a weighting term; and (He)r,α is the elevation at radius r and pivot
rotation angle α.
Sprinkle & Trickle Irrigation Lectures Page 167 Merkley & Allen
Merkley & Allen Page 168 Sprinkle & Trickle Irrigation Lectures
Lecture 14
Center Pivot Uniformity Evaluation
I. Introduction
• The calculation of an application uniformity term must take into account the
irrigated area represented by each catch container
• It is more important to have better application uniformity further from the pivot
point than nearer, because the catch containers at larger distances represent
larger irrigated areas
• If the catch containers are equally spaced in the radial direction, the area
represented by each is directly proportional to the radial distance
⎛ ⎛ ⎞⎞
∑ i=1( diri ) ⎟⎟ ⎟⎟
n
⎜ n ⎜
⎜ ∑ r d −
i=1⎜ i i
∑i=1ri ⎟⎠ ⎟⎟
n
CU = 100 ⎜ ⎜ (295)
⎜ 1.0 − ⎝
⎜ ⎟
∑ i=1( diri )
n
⎜ ⎟
⎝ ⎠
• If the radial distances, ri, are equal, the sequence number of the can
(increasing with increasing radius) can be used instead of the actual distance
for the purpose of calculating application uniformity
• Consider the following two figures:
Sprinkle & Trickle Irrigation Lectures Page 169 Merkley & Allen
slope?
catch containers
leg # #1
3 g
le
slope?
leg #
2
catch containers
level field?
no wind?...
CU = 100%
Merkley & Allen Page 170 Sprinkle & Trickle Irrigation Lectures
III. Standard Uniformity Values
• You can also calculate the “standard” CU or DU if you weight each catch
value by multiplying it by the corresponding radial distance
• To obtain the low ¼, rank the unweighted catches, then start summing radii
(beginning with the radius for the lowest catch value) until the cumulative
value is approximately equal to ¼ of the total cumulative radius
• This may or may not be equal to ¼ of the total catch values, because each
catch represents a different annular area of the field
• Finally, divide the sum of the catches times the radii for this approximately ¼
area by the cumulative radius
• This gives the average catch of the low ¼
• Don’t rank the weighted catches (depth x radius) because you will mostly get
the values from the low r values (unless the inner catches are relatively high
for some reason), and your answer will be wrong
• Don’t calculate the average of the low ¼ like this…
(because the lowest ¼ of the catches generally represents
something different than ¼ of the irrigated area):
• Actually, the equation at the right is all right, except for the
value “n/4”, which is probably the wrong number of ranked
values to use in representing the low ¼
• You can set up a table like this in a spreadsheet application:
largest
Totals: ---- ----
• Note that when you rank the depths, the radius values should stay with the
same depth values (so that the radius values will now be “unranked”; all
mixed up)
• To get the average weighted depth for the whole pivot area, divide the total
“Cumulative d*r” by the total “Cumulative r” (column 5 divided by column 2)
• Find the row corresponding closest to ¼ of the total “Cumulative r” value, and
take the same ratio as before to get the weighted average of the low ¼ area
• Look at the example data analysis below:
Sprinkle & Trickle Irrigation Lectures Page 171 Merkley & Allen
Ranked catches
Radius, r Cum. r Depth, d d*r Cum. d*r
120 120 0.52 62.6 62.6
900 1,020 0.95 851.9 915
160 1,180 1.29 205.8 1,120
340 1,520 1.31 445.6 1,566
1000 2,520 1.46 1,456.3 3,022
1040 3,560 1.46 1,514.6 4,537
240 3,800 1.48 355.3 4,892
800 4,600 1.50 1,203.9 6,096
860 5,460 1.53 1,315.0 7,411
480 5,940 1.58 757.3 8,168
1280 7,220 1.58 2,019.4 10,188
980 8,200 1.60 1,569.9 11,758
540 8,740 1.63 878.2 12,636
360 9,100 1.65 594.2 13,230
460 9,560 1.67 770.4 14,000
880 10,440 1.70 1,495.1 15,496
320 10,760 1.72 551.5 16,047 1/4 area (11,055)
1140 11,900 1.75 1,992.2 18,039
1160 13,060 1.75 2,027.2 20,067
280 13,340 1.82 509.7 20,576
720 14,060 1.82 1,310.7 21,887
1300 15,360 1.82 2,366.5 24,253
200 15,560 1.84 368.9 24,622
420 15,980 1.84 774.8 25,397
440 16,420 1.89 833.0 26,230
1020 17,440 1.89 1,931.1 28,161
1200 18,640 1.92 2,301.0 30,462
600 19,240 1.94 1,165.0 31,627
640 19,880 1.94 1,242.7 32,870
1060 20,940 1.94 2,058.3 34,928
1100 22,040 1.94 2,135.9 37,064
220 22,260 1.97 432.5 37,497 1/2 area (22,110)
1080 23,340 1.97 2,123.3 39,620
380 23,720 1.99 756.3 40,376
740 24,460 1.99 1,472.8 41,849
920 25,380 1.99 1,831.1 43,680
1220 26,600 1.99 2,428.2 46,108
300 26,900 2.01 604.4 46,713
180 27,080 2.03 364.8 47,077
820 27,900 2.04 1,671.8 48,749
1260 29,160 2.04 2,568.9 51,318
660 29,820 2.06 1,361.7 52,680
1180 31,000 2.06 2,434.5 55,114
680 31,680 2.09 1,419.4 56,534
940 32,620 2.11 1,985.0 58,519
560 33,180 2.14 1,196.1 59,715
260 33,440 2.16 561.7 60,276
1120 34,560 2.18 2,446.6 62,723
700 35,260 2.23 1,563.1 64,286
760 36,020 2.23 1,697.1 65,983
100 36,120 2.25 224.5 66,208
960 37,080 2.26 2,167.0 68,375
520 37,600 2.28 1,186.4 69,561
620 38,220 2.28 1,414.6 70,976
1240 39,460 2.28 2,829.1 73,805
500 39,960 2.33 1,165.0 74,970
140 40,100 2.35 329.6 75,300
400 40,500 2.40 961.2 76,261
780 41,280 2.52 1,968.9 78,230
40 41,320 2.57 102.9 78,333
80 41,400 2.57 205.8 78,538
840 42,240 2.79 2,344.7 80,883
580 42,820 2.82 1,633.0 82,516
60 42,880 3.23 193.7 82,710
1320 44,200 3.79 4,998.1 87,708
20 44,220 3.83 76.7 87,784
Merkley & Allen Page 172 Sprinkle & Trickle Irrigation Lectures
• Notice that the depth values (3rd column) are ranked from low to high
• Notice that the maximum value of cumulative r is 44,220 & maximum
cumulative d*r is 87,784. Then, the weighted average depth for the entire
center pivot is equal to 87,784/44,220 = 1.985 (whatever units)
• One quarter of 44,220 is equal to 11,055 which corresponds most closely to
the row in the table with depth = 1.72. For the same row, divide the two
cumulative columns (Col 5/Col 2) to get 16,047/10,760 = 1.491, which is
approximately the average of the low ¼.
• Finally, estimate the distribution uniformity for this data set as:
⎛ 1.491 ⎞
DU ≅ 100 ⎜ ⎟ ≅ 75% (297)
⎝ 1.985 ⎠
• Note that in this example, the average of the low ¼ was, in fact, based on
approximately the first n/4 ranked values
14000
12000
Weighted Catch Values
10000
8000
6000
4000
2000
0
0 10 20 30 40 50 60 70
Sprinkle & Trickle Irrigation Lectures Page 173 Merkley & Allen
IV. The Field Work
• It may take a long time for the full catch in containers near the pivot point,
and because these represent relatively small areas compared to the total
irrigated area, it is usually acceptable to ignore the inside 10% or 20% of the
radius
• The pivot quickly passes the outer cans, but takes longer to completely pass
the inner cans, so you can collect the data from the outer cans sooner
• The pivot should not be moving so fast that the application depth is less than
about 15 mm
• Catch containers can be placed beyond the physical length of the lateral
pipe, but if they are so far out that the catches are very low, these can be
omitted from the uniformity calculations
• Catch containers should be spaced in the radial direction no further than
about 30% of the average wetted diameter of the sprinklers
• There is often an access road leading to the pivot point for inspection,
manual operation, maintenance, and other reasons
• If the crop is dense and fairly tall (e.g. wheat or maize) it will be difficult to
perform the evaluation unless the cans are placed on the access road
• Otherwise, you can wait until the crop is harvested, or do the test when the
crop is still small
• Some people recommend two radial rows of catch cans, or even two parallel
rows, to help smooth out the effects of the non continuous movement of
towers (they start and stop frequently to keep the pivot lateral in alignment)
• Some have used troughs instead of catch cans to help ameliorate this
problem.
• Note that if the field is sloping or undulating, the results from one radial row
of catch cans may be quite different from those of a row on another part of
the irrigated circle
• See Merriam and Keller (1978)
Merkley & Allen Page 174 Sprinkle & Trickle Irrigation Lectures
Linear Move Systems
I. Introduction
Water Supply
Sprinkle & Trickle Irrigation Lectures Page 175 Merkley & Allen
• Hose-fed systems require periodic manual reconnection to hydrants on a
mainline – it is kind of like a period-move system, and you have to ask
yourself whether the linear move machine is worth the cost in this case!
• With the automatic hydrant coupling machines (see Fig. 15.3) there are two
arms with pipes and an elbow joint that bends as the linear move travels
down the field. The two arms alternate in connecting to hydrants so as not to
disrupt the irrigation nor the forward movement of the machine. These are
mechanically complex.
• The advantage of hose-fed and automatic coupling linear moves is that you
don’t need to have a small, uniform slope in the direction of travel, because
water is supplied from a pressurized mainline instead of an open channel
• On ditch-fed systems there can be a structure at the end of the field that a
switch on the linear move contacts, shutting down the pump and reversing
the direction of movement so that it automatically returns to the starting end
of the field.
• The advantages and disadvantages of the ditch-feed system are:
Pros
• Low pressure (energy) requirement
• Totally automated system
• More frequent irrigations than hose-fed, since no one needs to be
available to move the hose
Cons
• Trash and seeds and sediment pass through screen and may plug
nozzles
• The pump must be on (move with) the lateral, causing extra weight
• Should have uniform slope along the lateral route
Pros
• Easy irrigation of a rectangular field (important if land is expensive, but
not important if land is cheap and water is scarce)
• Application rate is uniform over length of lateral, rather than twice the
average value at the end of the center pivot
• No end gun is required
Cons
• The lateral does not end up right back at the starting point immediately
after having traversed the irrigated area – you either have to
“deadhead” back or irrigate in both directions
• May be more expensive than a pivot due to extra controls, pump on
ditch feed, or more friction loss in the flexible feed hose (the hose is
fairly expensive)
Merkley & Allen Page 176 Sprinkle & Trickle Irrigation Lectures
II. System Costs
• A main strategy in linear move design is to minimize the cost per unit area.
This is done by maximizing the area covered per lateral (length of field)
• Generally, the lateral length is limited to 400 to 800 m. Therefore, the major
difficulties and objectives in linear design are to:
1. Maximize the irrigated area per lateral (this minimizes $/area). In other
words, how large a field can be irrigated by one machine?
2. Prevent runoff by matching ARx with Isoil + SS/ti (this tends to limit the field
length, because if AR is small, it won’t be possible to finish in f’ days),
where SS is the allowable surface storage in (mm or inches); and, ti is the
time of irrigation
3. Determine whether spray nozzles can be used without causing runoff
4. Minimize labor (for moving hoses and supervising)
as long as possible
• The allowable surface storage, SS, is the maximum amount of ponding
without incurring surface runoff
• SS is a function of the general topography and the microtopography, and of
the amount of foliar interception (water can “pond” on the crop leaves too)
Sprinkle & Trickle Irrigation Lectures Page 177 Merkley & Allen
• SS is usually less than about 5 mm unless small basins are created along
furrows, for example
• ARx limits the field length because it corresponds to some minimum time to
finish an irrigation, for a given gross application depth, whereby a maximum
interval (f) is calculated in the preliminary design steps
Pa 3 1
Hl = + hf + Hr + ∆He + (hf )minor + (hf )hose (298)
γ 4 2
• Or, if using flow control nozzles, with a minimum pressure required at the end
(assuming the minimum pressure occurs at the end):
Pend
Hl = + hf + Hr + ∆He + (hf )minor + (hf )hose (299)
γ
where Hr is the height of the lateral or spray boom above the ground; and,
(hf)minor are the hydrant coupler and tower connection losses.
• The parameter (hf)hose is the loss in the flexible hose connection on a hose-
fed system
• Note that (hf)hose may be a major loss, since the hose diameter is usually less
than 5” or 6".
1.852
⎛Q⎞
hf = khFL ⎜ ⎟ D−4.87 (300)
⎝C⎠
where kh = 10.50 for hf and L in ft, Q in gpm, and D in inches; Kh = 1.21(10)10
for hf and L in m, Q in lps, and D in mm. F is the multiple outlet friction factor
for a linear move (F ≈ 0.36).
• For hose-fed systems, the maximum hose length for dragging the hose is
220 ft. Therefore, there could be about 400 ft between hydrants.
• For hose-fed systems with a cable/winch system for assisting in dragging the
hose (towers only have a moderate amount of tractive power), the maximum
hose length is 330 feet (640 feet between hose hydrants).
• Flexible hoses normally come in 5-inch ($18/ft) and 6-inch ($25/ft) diameters
• The Hazen-Williams C value for the hose can usually be taken as 150
Merkley & Allen Page 178 Sprinkle & Trickle Irrigation Lectures
Lecture 15
Maximizing Linear Move Field Length
I. The Procedure
• The following procedure for maximizing field length is from Allen, 1983, Univ.
Idaho and Allen, 1990 (Irrig. Symp. Paper), and is used in the USUPIVOT
computer program
• The basic strategy is to examine different application depths and different w
values to maximize the area covered by the sprinkler system, and or to
minimize labor requirements
dn = f (Ud)
d = dn/Epa
(Df)max = d.Re
df = (i/10)(Df)max where i = 1 to 10
and,
f' = df DEpa/(100 Ud)
f = f' - days off (days off may be zero because the system is automatic),
where f' = irrigation frequency for depth df. DEpa is used here (in percent)
because Ud is net, not gross
Sprinkle & Trickle Irrigation Lectures Page 179 Merkley & Allen
5. Determine the maximum ARx for a particular df value using the following
two equations (assuming an elliptical pattern):
⎛ ( SF )( AR x ) ⎞ ⎛ n+1 n ⎞
1 n
⎜1− ⎜
⎟ k (n + 1)n+1 (D − SS − c )n+1 ⎟
⎝ k ⎠⎝⎜ ⎟
AR x = ⎠ (301)
2 2
⎛π⎞ ⎛ D ⎞
1.05 − 1.6 ⎜ ⎟ ⎜ − 0.5 ⎟
⎝ 2 ⎠ ⎝ df ⎠
where,
−n−1
⎛⎛ −0.5 ⎞
2 2⎞ ⎛ 2 ⎞
⎜⎜ ⎛ π ⎞ ⎛ D ⎞ ⎛ π ⎞ ⎛ D ⎞ ⎟
2 2 ⎟ ⎜ −1.6 AR2x ⎜ ⎟ ⎜ − 0.5 ⎟ ⎟ ⎟
⎜ ⎜ 1.05 AR x − 1.6 AR x ⎜⎝ 2 ⎟⎠ ⎜ d − 0.5 ⎟ ⎟ ⎜
⎜⎝ ⎝ f ⎠ ⎠ ⎝ ⎝ 2 ⎠ ⎝ df ⎠ ⎟⎠ ⎟
D=⎜ ⎟
⎛ ( SF )( AR x ) ⎞ ⎛ −1 ⎞ ⎛ 1 ⎞
⎜ ⎟
⎜
df n ⎜ 1 − ⎟ ⎜⎜ ( n + 1) n+1 ⎟⎟ ⎜ k n+1 ⎟ ⎟
⎜ ⎝ k ⎠⎝ ⎠ ⎝⎜ ⎟
⎠ ⎟
⎝ ⎠
+SS + c
(302)
and ARx is the peak application per pass (mm/min); D is the applied depth
at time t = ∫ (AR) dt (mm); SS is the allowable surface storage (after
ponding) before runoff occurs (usually less than about 5 mm); c is the
instantaneous soil infiltration depth, from SCS soil intake families (mm); k
is the coefficient in the Kostiakov-Lewis equation; and df is the total depth
of water applied to the ground surface (mm)
• The parameter “n” is defined as: n = a -1, where “a” is the Kostiakov
exponent (see NRCS soil curves at www.wcc.nrcs.usda.gov/nrcssirrig)
• Note that SS is a function of the field topography and micro-topography,
and is affected by foliar interception of applied water
• These last two equations have π in them because there is an inherent
assumption of an elliptical water application profile from the sprinklers or
sprayers
• Recall that ARav = (π/4)ARx for an elliptical pattern
• SF is a relative sealing factor (in terms of soil water infiltration), and may
have values in the range of 0 to about 0.36
Merkley & Allen Page 180 Sprinkle & Trickle Irrigation Lectures
• The higher values of SF tend to be for freshly tilled soils, which are
generally most susceptible to surface sealing from the impact of water
drops
• Lower values of SF are for untilled soils and vegetative cover, such as
alfalfa or straw, which tend to reduce the impact of water drops on the soil
and help prevent runoff too
• If the linear move irrigates in both directions (no deadheading), then df is
one-half the value from these two equations
df
ti = (303)
π
( AR x )
4
7. Compute the speed of the system for the required ti:
If S ≥ Smax (this may occur for a high intake soil or for a very light
application with surface storage) then reduce the application rate and
increase time as follows:
w
ti = (304)
Smax
4 df
AR x = (305)
π ti
Thus,
S = Smax (306)
60 f T − 2 treset
X= (307)
⎛ 1 1 t ⎞
⎜⎜ + + hose ⎟
⎟
⎝ S wet Sdry 100 ⎠
where,
Sprinkle & Trickle Irrigation Lectures Page 181 Merkley & Allen
X = maximum length of field (m);
f = system operating time per irrigation (days);
T = hours per day system is operated (21-23);
treset = time to reset lateral at each end of the field (min);
those = time to change the hose (min/100 m);
Swet = maximum speed during irrigation (m/min); and
Sdry = maximum dry (return) speed (m/min)
labor =
(
2 treset + 0.01X those + 2 t super ) (308)
60 f
where labor is in hrs/day; and tsuper is minutes of supervisory time per 100
m of movement
60 f T − 2 treset
X= (309)
⎛ 1 t ⎞
2⎜ + hose ⎟
⎝ S wet 100 ⎠
XL
Areamax = (310)
10,000
labor
Lha = (311)
Areamax
12. Repeat steps 4-11 for a new w (different application device or different
operating pressure)
13. Select the nozzle device and application depth which maximizes the field
length (or fits available field length) and which minimizes labor
requirements per ha
Merkley & Allen Page 182 Sprinkle & Trickle Irrigation Lectures
14. System capacity:
π AR x w L
Qs = (312)
4k 3 Re
where k3 = 96.3 for L and w in ft, Qs in gpm, and ARx in in/hr; and k3 = 60
for L and w in m, Qs in lps, and ARx in mm/min
df w L
Qs = (313)
ti k 3 R e
• There is no “surge” effect of soil surface sealing due to a brief time period
between irrigation passes (when irrigating in both directions)
• The infiltration curve used represents soil moisture conditions
immediately before the initiation of the first pass
• The infiltration curve used holds for all frequencies (f) or depths (df)
evaluated, while in fact, as f↑, θ↓, so that the Kostiakov coefficients will
change. Therefore, the procedure (and field ring infiltration tests) should
be repeated using coefficients which represent the Kostiakov equation for
the soil moisture condition which is found to be most optimal in order to
obtain the most representative results.
Sprinkle & Trickle Irrigation Lectures Page 183 Merkley & Allen
Linear Move Design Example
I. Given Parameters
• Hose-fed linear move, irrigating in only one direction in a 64-ha field (400 m
wide and 1,600 m long)
• The pressure is 140 kPa (20 psi) for spray booms with a preliminary w if 10
m (33 ft)
• The soil infiltration characteristics are defined for the Kostiakov-Lewis
equation as:
Z = 5.43τ0.49 (314)
Ud = 7.7 mm/day
MAD = 50%
Z = 0.9 m
Wa = 125 mm/m
Oe = 1.00
Re = 0.94
Epa = 85%
dx = (0.5)(0.9)(125) = 56 mm (315)
dx 56
f' = = = 7.3 ⇒ f ' = 7 days (316)
Ud 7.7
Merkley & Allen Page 184 Sprinkle & Trickle Irrigation Lectures
2. Net and gross application depths:
dn = f Ud = (7)(7.7) = 54 mm (317)
dn 54
d= = = 64 mm (318)
Epa 0.85
D f = dR e = (64)(0.94) = 60 mm (319)
⎛ i ⎞
df = D f ⎜ ⎟ (320)
⎝ 10 ⎠
Assume no days off (no down time during the peak use period)
4 df 4(24)
ti = = = 34 min (323)
π AR x π (0.91)
60 f T − 2 treset
X= =
⎛ 1 1 t ⎞
⎜⎜ + + hose ⎟
⎟
⎝ S wet Sdry 100 ⎠ (325)
60(2.8)(22) − 2(30)
= = 970 m
⎛ 1 1 10 ⎞
⎜ + + ⎟
⎝ 0.3 3.5 100 ⎠
(
2 treset + 0.01 those + 2 t sup er X ) =
60 f
(326)
2(30) + 0.01[10 + 2(5)][970]
= = 1.5 hrs / day
60(2.8)
where treset is the reset time at the end of the field (min); those is the hose
reconnection time (min/100 m); and tsuper is the “supervisory” time
(min/100 m)
Merkley & Allen Page 186 Sprinkle & Trickle Irrigation Lectures
12. Repeat steps 4-11 for a new w (different application device or operating
pressure). (not done in this example).
13. Select the nozzle, device and application depth that maximizes the field
length (or fits the available field length), and which minimizes labor
requirements per ha.
Note: 38.8 ha << 64 ha, which is the size of the field, (970 m << 1600 m
which is the length of the field). Therefore, it is important to continue
iterations (steps 11 and 12) to find an application depth and or new w
(different sprinkler or spray device) to reach 1600 m and 64 ha, if
possible.
Additional Observations:
• For a 6-m spray boom, applying a 12-mm depth per each 1.4 days
would almost irrigate the 64 ha. However, the labor requirement is
doubled, as the machine must be moved twice as often. This
additional cost must be considered and weighed against the larger
area irrigated with one linear move machine.
• If larger spray booms were used (w = 16 m rather than 10 m) (these
would be more expensive) then 18 mm could be applied each 2.1
days, and all 64 ha could be irrigated with one machine.
• If low pressure impact sprinklers were used (these would be less
expensive than spray booms, but energy costs would be higher), then
w = 22 m, and 30 mm could be applied each 3.5 days (more water
can be applied since the application rate is spread over a wider area
from the lateral), and all 64 ha could be irrigated. In addition, ETc
would be less since the soil would be wetted less often. Also, the soil
intake rate would be higher each irrigation because of a drier
antecedent moisture at the time of irrigation.
• Notice that required wetting time for rotation times (f) greater than 2
days are identical between all types of spray devices. This is
because, for the large depths applied, a minimum wetting time is
required. The system speed is adjusted to fit the w value of the water
application device.
• If no acceptable solution for this problem were found, then
alternatives to be evaluated would be to irrigate in both directions, or
to consider a ditch-fed linear move (this requires a leveled ditch, but
does not required time for moving hoses and hose friction losses).
• You could also consider a “robot” controlled machine that
automatically connects alternating arms to hydrants on a buried
mainline (but this is a very expensive alternative)
• You might begin to wonder whether an investment in a linear move
machine is justifiable when there is a significant labor requirement for
reconnecting the supply hose, resetting at the end of the field, and
Sprinkle & Trickle Irrigation Lectures Page 187 Merkley & Allen
supervising operation. That is, why not put in a center pivot or a side
roll system instead?
• If one linear move cannot cover the entire field length in the available
period, “f” (days), you could consider two linear move machines for
the same field
π AR x w L π (0.91)(10)(400)
Qs = = = 51 lps (809 gpm)
4k 3Re 4(60)(0.94) (327)
alternatively,
df wL (24)(10)(400)
Qs = = = 51 lps (809 gpm) (328)
ti k 3R e (33.6)(60)(0.94)
Note that the computed Qs is larger than one based strictly on Ud and T,
because the machine is shut off during reset and hose moving
Ad (38.3)(24)
Qs = 2.78 = 2.78 = 44 lps (700 gpm) (16)
fT (2.8)(22)(0.94)
But this flow rate is too low – it does not consider hose moving and
reset time. So, the 51 lps system capacity should be used for design
Merkley & Allen Page 188 Sprinkle & Trickle Irrigation Lectures
Lecture 16
Trickle Irrigation System Components & Layout
• “Trickle” and “drip” are terms used to describe what can be generally called
“micro-irrigation systems”, in which water is applied in relatively precise
quantities and precise times and at precise locations
• Land-leveling costs notwithstanding, trickle irrigation systems are usually the
most expensive types of on-farm water application system to install
• They can also be expensive to operate and maintain
• Usually, trickle irrigation systems are installed in areas where water is scarce
and or expensive, crop value is very high, or topographical and other
conditions might preclude the successful use of other types of irrigation
systems
• Not all micro-irrigation systems are complex and expensive
• Labor-intensive forms of micro-irrigation continue to be practiced in many
areas of the world, especially for vegetable and other “cash” crops
• For example, people may carry water in buckets or shoulder harnesses to
carefully pour at each plant in a field
• Or, porous pots are buried at regular intervals along rows and filled with
water individually, which seeps out into the surrounding soil
• Sometimes water is merely splashed onto crop beds by hand
Advantages
Sprinkle & Trickle Irrigation Lectures Page 189 Merkley & Allen
Disadvantages
1. Systems are expensive to purchase and install ($1,000 to $6,000 per ha)
2. Susceptibility to clogging of emitters, which usually have very small
openings – so, it is important to spend time and money on maintaining the
system, applying chemicals, and keeping filters clean
3. Possibly low distribution uniformity due to low operating pressures and
possibly due to steep slopes, especially along laterals, and due to clogging
4. Where laterals are on steep slopes, the water will drain out the downhill end
at every startup and shut-down.
5. Soils with very low intake rates will exhibit ponding and runoff
6. Salt tends to accumulate at the soil surface and around the wetted area --
when it rains, these accumulated salts may be driven into the root zone
7. These systems tend to require more capable and diligent management
because of the susceptibility to clogging, and because the systems are
usually designed to operate continuously during peak ET periods (can’t
afford to let the system shut down during these periods). These systems do
not usually take full advantage of the soil storage (buffer) capacity.
Merkley & Allen Page 190 Sprinkle & Trickle Irrigation Lectures
5. Other equipment
• Valves & air vents
• Vacuum Relief Valves
• Pressure Relief Valves
• Various Pipe Fittings and Appurtenances
• Not all trickle irrigation systems will have all of these components
• For example, some systems are gravity-fed and require no pumping
• Simple systems may not have submains and manifolds
• Some systems do not have pressure relief or other types of safety valves
• Systems with relatively dirty water will have multiple levels of filtration, others
may have only minimal screening
1. Drip Emitters
Sprinkle & Trickle Irrigation Lectures Page 191 Merkley & Allen
• Double chamber with orifices between chambers and orifices to
discharge water into the soil (acts something like a manifold to
control pressures and provide greater uniformity)
• Can be removed and reused next year (typically 4-5 years life)
• Can be “disked up” and left in the field as chunks of plastic
• Porous or “leaky” pipe, made from old tires or new materials
3. Micro-Sprayers
Merkley & Allen Page 192 Sprinkle & Trickle Irrigation Lectures
VI. Typical Trickle System Layouts
• The discharge equation for emitters is similar to that used for sprinkler
nozzles, but the exponent on the head or pressure term is variable
• An exponent of ½ corresponds to orifice flow, which is how some, but not all,
emitters are designed
• The general emitter equation is:
q = K dHx (329)
• The two basic emitter design objectives, other than energy dissipation, are:
⎛ q'n ⎞
EU' = 100 ⎜ ⎟ (330)
⎜ qa ⎟
⎝ ⎠
where EU’ is the field test emission uniformity; qn’ is the average discharge of
the low ¼ emitters from the sampling; and qa is the average discharge of all
emitters sampled
• EU’ should be at least 95% for properly designed and properly maintained
trickle irrigation systems
• Note that it is impossible to calculate EU’ based on field measurements if the
system is being designed (hasn’t been installed yet) – in this case there are
other equations to approximate EU (recall the design efficiency for sprinkler
systems)
• Most nonuniformity in micro irrigation systems is caused by: (1) emitter
plugging, wear, and manufacturing variations; and, (2) nonuniform pressure
distribution in pipes and hoses
Merkley & Allen Page 194 Sprinkle & Trickle Irrigation Lectures
X. Manufacturer’s Coefficient of Variation
• Emitters of the same type and manufacture have variations in discharge (at
the same operating pressure) due to small differences from manufacturing
tolerances. Some variation is allowed in the interest of cost savings.
• The manufacturer’s coefficient of variation is defined as:
s
ν= (331)
qa
Sprinkle & Trickle Irrigation Lectures Page 195 Merkley & Allen
XII. Valves & Automation
1. Volumetric Valves
• Manually turned on
• Automatically turn off
2. Sequential Operation
• Manually turned on
• Automatic sequencing from low to high elevation
3. Fully Automatic
• Note that time-based systems may give varying application depths over time
if the system flow rate changes due to clogging of filters
• This can be partially corrected by using pressure compensating emitters
• However, the use of a volume-based system with a flow meter may be best
because the flow rate measurement also gives an indication about filter
clogging
Merkley & Allen Page 196 Sprinkle & Trickle Irrigation Lectures
Lecture 17
Filtration for Trickle Irrigation Systems
I. Introduction
Sprinkle & Trickle Irrigation Lectures Page 197 Merkley & Allen
3. Can provide nutrients which support the growth of bacteria in the
pipes
4. Can accumulate at the ends of pipelines and clog valves
5. Can contain weed seeds which aggravate weed control in the irrigated
area
6. Cost the farmer money
• These filters do not remove salts from the irrigation water (unless reverse
osmosis membranes are used, which are very uncommon in irrigation
systems and are not covered here)
Merkley & Allen Page 198 Sprinkle & Trickle Irrigation Lectures
III. Use of Reservoirs in pre-Filtration
1. To buffer differences in supply and demand rates. The supply from a canal
or well seldom coincides exactly with the system requirements (flow rate and
duration), and the system requirements can change due to different numbers
of stations in operation, “down time”, and duration of sets.
2. To allow for settling of some of the suspended particles. In these cases the
reservoir serves as a “settling basin”. Precipitated sediment can be
periodically removed from the reservoir with equipment or manual labor.
100,000
10,000
Settling velocity (mm/min)
1,000
100
10
0
Coarse sand Medium sand Fine sand Very fine Silt Clay
sand
Longer settling basins will allow more time for suspended particles to fall to
the bottom before arriving at the pump intake.
Sprinkle & Trickle Irrigation Lectures Page 199 Merkley & Allen
3. To aerate water pumped from wells, thereby oxidizing and precipitating
manganese and iron out of the water (some groundwater has manganese
and iron, and these can cause plugging of emitters). Only 1.5 ppm of either
manganese or iron can cause severe clogging problems in trickle laterals
and emitters (see Table 18.1 in the textbook).
4. To allow for air to escape when the water comes from a “cascading” well, in
which air becomes entrained into the water. Air in pipelines can dampen the
effects of water hammer, but also causes surges and blockages of flow.
5. To allow oils to collect on the water surface. Oils can cause rapid clogging of
most types of filters, requiring special cleaning with solvents and possible
replacement of sand media. When pumping from a reservoir the inlet is
below the water, and oil does not enter.
V. Sand Separators
• Sand separators are used to remove sand (but not organic matter) from the
water
• Most work by spinning the water in an enclosed column (or cone) to remove
sand through a centrifuge-type action
• There are no moving parts
• Solid particles with a density of approximately 1.5 g/cm3 can be removed by
these devices (most sand has a density of about 2.65 gm/cm3)
Merkley & Allen Page 200 Sprinkle & Trickle Irrigation Lectures
• Can remove from 70 to 95% of dense particles
• Periodic purging of accumulated sand (manual
or automatic) is necessary to maintain
performance
• Must have the correct flow rate through the
sand separator for proper operation, otherwise
less sand will be removed from the water
• Most sand separators have a pressure loss of
between 5 and 12 psi, from inlet to outlet. This
pressure loss does not change with time, only
with flow rate.
• Some sand separators are designed to fit down
into wells to protect the impellers and pump
bowls, but they are not as efficient as above-
ground sand separators
• Sand separators cannot remove all of the sand, and may pass large amounts
when the system is starting or stopping
• Therefore, screen filters should be installed downstream
• Sand separators are available but are not used as much as they were in the
past because people are using media tanks and other filters instead
• When taking water from a deep well, an alternative to using a sand separator
is to properly develop the well and use a good quality well screen
1. Introduction
• Every installation should have at least two tanks so that back-flushing can
occur during operation, but many designers recommend at least three tanks
in which only one is back-flushed at a time
• New media should be rinsed with clean water before placing it in the tanks
because it may have dust and other particles in it
• Some tanks have not performed well when the installers failed to rinse the
media first (resulting in fine particles passing into the irrigation system when
the tanks are first put into use)
• These filters are very good for removing relatively large amounts of organic
and inorganic matter, but some pre-screening is usually necessary with
surface water supplies
• High volume filtration at 20 to 30 gpm/ft2 (1.3 to 2.0 cm/s)
• Some silt and clay particles can also be removed by sand media filters, but
not by most screen-type filters. However, much silt and clay can pass
through a media filter too.
• Large volumes of particle contaminants can be collected in the sand media
before the media must be cleaned, or “back-flushed”
• In some cases the water must be pre-cleaned before entering the sand tanks
to prevent rapid accumulation of particle contaminants
• Media filters can also remove some sand from the supply water, but this
sand cannot always be effectively back-flushed from the media -- for large
amounts of sand, there should be a sand separator upstream of the media
tanks
• Industrial media filters are often five feet deep (or more), but have smaller
flow rates and less frequent back-flushing than agricultural media filters,
which may be only 14 inches deep
• Many of the particles captured by agricultural media filters stay within the
upper few inches of the sand because they are back-flushed frequently
• Flow through the filter is usually from inside to outside (debris is trapped on
the inside surface during operation) to prevent collapse of the screens
• Cleaning can be manual or automatic, and there are many varieties of
automatic cleaning methods
Sprinkle & Trickle Irrigation Lectures Page 203 Merkley & Allen
• Some filter designs have a rotating suction mechanism to clean the dirty
(inner) side of the screen element
• Manually-cleaned filters can have slow or quick release cover latches -- the
slow release latches are preferred because the quick release version can
“explode” if opened while the system is at operating pressure (dangerous to
personnel)
2. Disc Filters
Merkley & Allen Page 204 Sprinkle & Trickle Irrigation Lectures
Kind of Problem Hazard Level
low moderate severe
suspended solids 50 ppm 50-100 ppm > 100 ppm
pH 7.0 7.0-8.0 > 8.0
salts 500 ppm 500-2,000 ppm > 2,000 ppm
bicarbonate -- 100 ppm --
manganese 0.1 ppm 0.1-1.5 ppm > 1.5 ppm
total iron 0.2 ppm 0.2-1.5 ppm > 1.5 ppm
hydrogen sulfide 0.2 ppm 0.2-2.0 ppm > 2.0 ppm
bacteria count 10,000/liter 10,000-50,000/liter > 50,000/liter
1. Slimy bacteria
These can grow inside pipes and inside emitters.
The chemicals used to kill this bacteria are
chlorine, ozone, and acids.
Sprinkle & Trickle Irrigation Lectures Page 205 Merkley & Allen
5. Plant root entry into underground emitters
This is mainly a problem in permanent (several years) buried trickle
irrigation laterals. Can use acid injection at end of each season for
perennials to kill roots that are in the buried drip tubing. Or, use
herbicides to kill roots in the tubing without damaging the plants.
Some emitters and plastic drainage pipe have herbicide in the plastic
to discourage roots from entering.
• Injection of chemicals should be after the system starts, and stopping before
the system is turned off
• As a rule of thumb, one can assume an average pipe flow velocity of 1 fps, or
0.3 m/s, divide this into the longest pipe distance in the system (from pump to
farthest emitter), and determine the time
• This is the time to wait after starting the pump, and the time to allow for
flushing before turning the pump off
• Chemicals should be injected on a mass basis per set, not time. Thus, one
would want to apply a certain number of lbs or kg of a chemical in an
irrigation set, and it does not matter that it is all applied quickly or over a long
time (provided that the starting and stopping delay discussed above is
adhered to)
• The minimum injection rate can be put into equation form:
qc =
Fr A
=
(kg / ha )(ha ) = lph (332)
ctr Ta ( kg / liter )( 0.8 )( hrs / set )
where Fr is the mass application rate per unit area; A is the area irrigated per
set; c is the concentration of the chemical; tr is some kind of uniformity ratio,
taken to be 0.8; and Ta is the hours per set, or hours of chemical injection, if
shorter than the set time
Merkley & Allen Page 206 Sprinkle & Trickle Irrigation Lectures
Lecture 18
Trickle Irrigation Planning Factors
Widely-Spaced Crops
Closely-Spaced Crops
• The wetted soil area, Aw, is not measured at the soil surface, but from a
horizontal plane about 30 cm below the soil surface (actually, it depends on
root depth and soil type)
• The same is true for Pw
• The reason we are interested in Pw is to calculate the application depth “dx,”
as discussed in the following lecture
• This wetted area is distorted for sloping terrain, but the distortion is uniform
for uniform slopes (all other factors being the same)
• Wetted soil area can be estimated from empirical relationships and tables
(Table 19.1 in the textbook), but it is best to have site-specific field data in
which potential emitters are operated in the design area
• That is, test the emitter(s) and spacings in the field before completing the
irrigation system design
• Calculate percent wetted area, Pw, as follows:
⎛ N pS e w ⎞
Pw = 100 ⎜ ⎟ , for Se < 0.8w (333)
⎜ S pS rPd ⎟
⎝ ⎠
where Np is the number of emission points (emitters) per plant; Se is the
spacing of emitters along a lateral; w is the wetted width along the lateral; Sp
is the spacing of plants along a row; Sr is the spacing between rows; and Pd
is the fraction (not percent) of area shaded (see Lecture 19)
• Note that the numerator of Eq. 333 is wetted area, and the denominator is
actual plant area
• Note also that some emitters have multiple emission points
Merkley & Allen Page 208 Sprinkle & Trickle Irrigation Lectures
• Se is the spacing between emitters on the lateral; however, if Se is greater
than 0.8w, then use 0.8w instead:
⎛ 0.8N p w 2 ⎞
Pw = 100 ⎜ ⎟ , for Se ≥ 0.8w (334)
⎜ S pS r Pd ⎟
⎝ ⎠
• Sample calculation:
• Suppose Sr = Sp = 3.0 m, Pd =
80%, and w = 1.1 m
• Determine Np for Pw ≥ 33%
Np (0.88)(1.1)
0.33 = (336)
(3.0)(3.0)(0.80)
whereby Np = 2.45. Then,
3(0.88)(1.1)
Pw = = 0.40 (337)
(3.0)(3.0)(0.80)
⎛ N S' ( S' + w ) ⎞
Pw = 100 ⎜ ⎟ , for Se ≤ 0.8w
p e e
( )
(338)
⎜ 2 Pd S pS r ⎟
⎝ ⎠
or,
⎛ 1.44 w 2 N ⎞ 72 w 2 N
Pw = 100 ⎜ ⎟=
p p
, for Se ≤ 0.8w
( ) ( )
(339)
⎜ 2Pd S pS r ⎟ Pd S pS r
⎝ ⎠
Sprinkle & Trickle Irrigation Lectures Page 209 Merkley & Allen
Se’=0.8w
0.5w
w
Se ’
0.5w
Se Se
Double laterals
• As in the previous equation, if Se > Se’, use Se’ instead of Se in the above
equation for double laterals
• In the above equation, the denominator has a “2” because Np for double
lateral systems is always at least 2
• For micro-spray emitters, the wetted area is greater than that measured at
the surface (because it is measured below the surface):
⎡ ⎛ Se ⎞ ⎤
⎢ N p ⎜ A s + (PS ) 2 ⎟ ⎥
Pw = 100 ⎢ ⎝ ⎠ ⎥ , for S ≤ 0.8 w (340)
e
⎢ S pS rPd ⎥
⎢ ⎥
⎣ ⎦
where As is the surface area wetted by the sprayer; and PS is the perimeter
(circumference) of the wetted surface area
• In the above equation for Pw, the term in the inner parenthesis is:
Se π w 2 π w Se π w ⎛ w ⎞
A s + (PS ) = + = ⎜ + Se ⎟ (341)
2 4 2 2 ⎝2 ⎠
where w is the diameter corresponding to As, assuming a circular area
Merkley & Allen Page 210 Sprinkle & Trickle Irrigation Lectures
Salinity in Trickle Irrigation
• Salinity control is specialized with trickle irrigation because (usually) less than
100% of the area is wetted, and because water movement in the soil has
significant horizontal components
• Irrigation water always contains salts, and fertilizers add salt to the crop root
zones -- salinity management in the crop root zone is a long-term
management consideration with trickle systems, as it is with any other
irrigation method
• Salts tend to accumulate, or “build up”, at the periphery of the wetted bulb
shape under the soil surface
1. Rain can push salts near the surface down into the crop root area (but
a heavy rain can push them all the way through the root zone)
2. If and when the irrigation system is not operated for a few days, there
can be pressure gradients in the soil that pulls salts from the periphery
up into the root zone
Sprinkle & Trickle Irrigation Lectures Page 211 Merkley & Allen
• Annual leaching with surface irrigation or sprinklers (on a trickle-irrigated
field) may be necessary to clean salts out of the root zone, unless there is a
rainy period that provides enough precipitation to leach the soil
• If the irrigation water has high salinity, trickle systems can provide for higher
crop production because the frequent irrigations maintain the soil salinity
nearer to the ECw (this is often not the case with sprinklers and surface
irrigation systems - salinity concentrates due to ET processes between water
applications)
• According to Keller, the relative crop yield can be estimated as (Eq. 19.6):
• This is the relative crop yield (or production) in terms of soil water salinity
only
• ECw is the electrical conductivity of the irrigation water
• (ECe)max is the zero yield point, and (ECe)min is the 100% yield threshold
value
• (ECe)max may be as high as 32, and (ECe)min can be as low as 0.9
• This is based on the linear relationship between relative yield and salinity as
adopted years ago by FAO and other organizations
• Of course, calculated Yr values must be between 0 and 1
• Salinity of the soil extract, ECe, is measured by taking a soil sample to the
laboratory, adding pure water until the soil is saturated, then measuring the
electrical conductivity -- most published crop tolerance and yield relationships
are based on the ECe as a standard reference
• Crops don’t instantly die when the salinity approaches (ECe)max; the osmotic
potential increases and roots cannot extract the water that is there
• There can also be specific toxicity problems with minerals at high salinity
levels
• According to Allen, the relative yield will be near 100% for ECw less than
about 2(ECe)min, provided that frequent irrigations are applied (maintaining
salinity concentrations in root zone)
where LRt is the leaching requirement under trickle irrigation (fraction); and
ECdw is the electrical conductivity of the “drainage water”, which means the
water that moves downward past the root zone
ECw
LR t = (344)
2 (ECe )max
1. For continuous trickle system operation (daily or once every two days),
the soil water in the root zone is maintained near field capacity, which can be
taken as approximately 50% saturation (θv) for many soils. Thus,
(recall that ECe is measured after adding distilled water to the soil sample
until it is saturated)
3. Substitute this last equation into Eq. 19.7 from the textbook to obtain:
EC w
LR t = (348)
6 (ECe )min − 2ECw
Sprinkle & Trickle Irrigation Lectures Page 213 Merkley & Allen
this is similar to the leaching requirement as calculated for sprinkler
irrigation in Eq. 3.3 (coefficients 5 and 1 instead of 6 and 2), except that
(ECe)min is for 100% yield rather than 10% reduction in yield
Merkley & Allen Page 214 Sprinkle & Trickle Irrigation Lectures
Lecture 19
Water Requirements in Trickle Irrigation
• The daily transpiration rate under a trickle system is based on Ud and the
percent area shaded (covered) by the plant leaves. Eq. 19.9:
Td = 0.1 Ud Pd (349)
1.0
0.9
0.8
0.7
Closely-spaced crops
0.1*sqrt(Pd)
0.6
0.5
pi/4 = 0.785
0.4
0.3
0.2
0.1
0.0
0 10 20 30 40 50 60 70 80 90 100
Pd
Sprinkle & Trickle Irrigation Lectures Page 215 Merkley & Allen
• The reduction from Ud is justified by considering the typical reduction in wet
soil evaporation with trickle irrigation
• The maximum Pd for a mature orchard is usually about π/4 (0.785), which is
the ratio of the area of a square and the circle it encloses:
• Tree spacing is generally such that the trees do not compete for sunlight, and
the area of each tree is equal to the square of the spacing between them (for
a square spacing)
Ts = 0.1 U Pd (350)
(
Dn = (U − Pe − Ms ) 0.1 Pd ) (351)
• This is the same as for sprinkle irrigation (or surface irrigation), but with an
adjustment for percent wetted area. Eq. 19.12 is:
Merkley & Allen Page 216 Sprinkle & Trickle Irrigation Lectures
MAD Pw
dx = Wa Z (352)
100 100
• Essentially, the same net volume of water is applied as with other irrigation
methods, but on a smaller area of the surface (and subsurface)
• Then, the maximum irrigation interval is:
dx
fx = (353)
Td
and f’ (round down from fx to get whole number of days) is less than or equal
to fx, but often assumed to be 1 day for trickle system design purposes.
Then,
• The transmission ratio (peak use period) takes into account the two-
dimensional infiltration pattern, or bulb shape, under trickle irrigation
• Even if the net depth is exactly right, there will almost always be some deep
percolation (more than that which may be required for leaching purposes)
• The transmission ratio, Tr, is used as a factor to increase required gross
application depth from dn
• The transmission ratio is equivalent to the inverse of the distribution
efficiency, DEpa, as given in Chapter 6 of the textbook
• The transmission ratio is lower for heavy-textured (“fine”) soils because there
is more lateral water movement in the soil, and the bulb shape is flatter; thus,
potentially less deep percolation losses
• Table 19.3 gives approximate values of Tr for different soil textures and root
depths (1.0 < Tr < 1.1) – obtain more representative values from the field, if
possible
• Then, for LRt < 0.1, or Tr > 1/(1-LRt), Eq. 19.15a:
⎛d T ⎞
d = 100 ⎜ n r ⎟ (355)
⎝ EU ⎠
• EU takes into account pressure variations due to friction loss and elevation
change, and the manufacturer’s variability in emitter production
• If f’ = 1 day, then dn can be replaced by Td in Eq. 19.15a
Sprinkle & Trickle Irrigation Lectures Page 217 Merkley & Allen
• For LRt > 0.1, or Tr < 1/(1-LRt), Eq. 19.15c:
100dn
d= (356)
EU (1.0 − LR t )
• Equation 19.16:
d
G= SpSr (357)
f'
with d in mm; Sp and Sr in m; and G in liters/day
• Equation 20.11:
G
Ta = (358)
Npqa
Merkley & Allen Page 218 Sprinkle & Trickle Irrigation Lectures
2
1⎛ n ⎞
∑ (qi2 )
n
− ⎜ ∑ qi ⎟
i=1
n ⎜⎝ i=1 ⎟⎠ σ
ν= = (359)
⎛1 n ⎞ qavg
n − 1 ⎜ ∑ qi ⎟
⎜n ⎟
⎝ i=1 ⎠
or,
n
∑ ( qi − qavg )
2
1 i=1
ν= (360)
qavg n −1
• For a large sample (n > 50) the data will usually be normally distributed
(symmetrical “bell-shaped” curve) and,
• The system coefficient of variation takes into account the probability that the
use of more than one emitter per plant will cause an effective decrease in the
combined discharge variability per plant due to differences in the emitters
(not due to pressure variability due to pipe friction losses and elevation
changes)
• On the average, discharge variability due to manufacturer tolerances will
tend to balance out with more emitters per plant
Sprinkle & Trickle Irrigation Lectures Page 219 Merkley & Allen
ν
νs = (361)
N'p
where Np’ is the minimum number of emitters from which each plant receives
water (see page 493 of the textbook)
L w = w + (N − 1)Se (362)
where Lw is the length of the wetted strip; and N is the number of emitters
(assumed to be evenly spaced). Then,
⎛L − w⎞
N = 1+ ⎜ w ⎟ (363)
⎝ Se ⎠
or,
⎛ Sp − w ⎞
Np ' ≈ 1 + ⎜ ⎟ (364)
⎝ Se ⎠
• In new system designs it is not possible to go out to the field to measure the
EU’ (Eq. 17.2) – a different approach is required to estimate EU
• The design EU is defined as (Eq. 20.13):
qn
EU = 100 (1 − 1.27 νs ) (365)
qa
Merkley & Allen Page 220 Sprinkle & Trickle Irrigation Lectures
• EU gives a lower (more conservative) value than EU’, and the equation is
biased toward lower discharges to help ensure that the least watered areas
will receive an adequate application
• Graphical interpretations of these relationships are given in Figs. 20.9 and
20.10
• To use the tabular values of area under the curve (e.g. from a statistics
book), it is necessary to use qavg = 0 and σ = 1 (the alternative is to integrate
the above equation yourself, which can also be done)
• Actually, qavg never equals zero, but for the determination of the 1.27
coefficient it will not matter
• In the tables, for area = 75%, the abscissa value (q, in our case) is about
0.675
• The same tables usually go up to a maximum abscissa of 3.49 (recall that
99.75% of the values are within ±3σ, so 3.49 is usually far enough)
• Anyway, for 3.49, the area is about 99.98%, and that is from -∞ to +3.49 (for
qavg = 0 and σ = 1), for the high ¼
• For the low ¼, take the opposite, changing to q = -0.675 and q = -3.49
• In this case (qavg = 0 and σ = 1), the equation reduces to:
2
e −0.5q
occurrences = (367)
2π
Sprinkle & Trickle Irrigation Lectures Page 221 Merkley & Allen
• For q = 0.675, occurrences = 0.31766718
• For q = 3.49, occurrences = 0.0.00090372
• Finally,
0.31766718 − 0.00090372
= 1.268 (368)
0.9998 − 0.7500
V. System Capacity
A N pq a
Qs = 2.78 (369)
N s S pS r
where Ns is the number of stations (sets); and A is the total net irrigated area.
Or,
A qa
Qs = 2.78 (370)
N s S eS l
Merkley & Allen Page 222 Sprinkle & Trickle Irrigation Lectures
where the coefficient “2.78” is for Qs in lps; A in ha; qa in lph; and Sp, Sr, Se,
and Sl in m (10,000 m2/ha divided by 3,600 s/hr = 2.78)
• The approximate number of hours the system must operate per irrigation
season (or per year, in many cases) is equal to the required gross seasonal
application volume, divided by the system flow rate:
Vs
Ot = K (371)
Qs
Sprinkle & Trickle Irrigation Lectures Page 223 Merkley & Allen
Merkley & Allen Page 224 Sprinkle & Trickle Irrigation Lectures
Lecture 20
Emitter Selection & Design
I. Introduction
g π D4 H
Ac = (372)
ν qK
where lc is the length of the flow path; D is the inside diameter; H is the
pressure head; ν is the kinematic viscosity (a function of water temperature);
q is the flow rate; K is for units conversion; and g is the ratio of force to mass
Sprinkle & Trickle Irrigation Lectures Page 225 Merkley & Allen
• When is it valid to assume laminar flow? Consider that a Reynolds number
of 4,000 is probably as high as you can go without transitioning from laminar
to turbulent flow:
VD 4Q
= < 4,000 (373)
ν π νD
short
long
longest
• In black PE lateral hose, sunlight warms the water significantly as the velocity
slows down, and water viscosity decreases
• Long-path emitters would ideally be progressively longer along the lateral to
compensate and provide a more uniform discharge along the lateral
• Tortuous-path emitters also have long paths, but not laminar flow. This is
because the path has many sharp bends, and is in the form of a maze
• Tortuous-path emitters tend to behave hydraulically like orifices, and so do
many short-path emitters
• Flow rate is nearly independent of the viscosity, at least over typical ranges
in viscosity
• Many short-path emitters have pressure compensating features
Merkley & Allen Page 226 Sprinkle & Trickle Irrigation Lectures
IV. Orifice Emitters
2gHno2
q = a'K
( )
(374)
1 + no2
• Vortex emitters have a whirlpool effect in which the water must exit through
the center of the whirlpool
• Energy is dissipated by the friction from spinning in a chamber, and from
exiting through an orifice in the center
• As mentioned in a previous lecture, the exponent on the pressure head is
approximately equal to 0.4 (in the discharge equation). Thus, these can
usually be considered to be (partially) pressure compensating
Sprinkle & Trickle Irrigation Lectures Page 227 Merkley & Allen
• As defined previously, pressure compensating emitters always have a
pressure head exponent of less than 0.5 (otherwise they aren’t considered to
be pressure compensating)
VIII.Self-Flushing Emitters
• You can calculate the exponent, x, based on a pair of measured flow rates
and pressure heads
• Recall a rule of logarithms: log (ax) = x (log a)
• The solution can be obtained graphically, but is more quickly accomplished
with calculators and electronic spreadsheets
• If you have more than two pairs of q and H, then you can take the logarithmic
transformation of the equation and perform linear regression; however, the
regression will be mathematically biased toward the smaller values
• These are 15 basic steps, following the material presented in Chapters 17-24
of the textbook, that can be followed for the design of many trickle systems
• These are basic steps and represent a summary of the generalized design
process, but remember that each design situation will have some unique
features
1. Collect data on the crop, climate, soil, topography, and irrigation water
quality, field shape & size, water availability.
Merkley & Allen Page 228 Sprinkle & Trickle Irrigation Lectures
2. Select an emitter and determine an emission point layout such that 33% <
Pw < 67%. This will determine the number of emitters per plant, Np.
Emitter selection may involve field testing to determine the wetted width
(or diameter), w.
3. Calculate dx, fx, and Td. Note that fx will almost always be greater than
1.0.
4. Select a target value for EU (usually 70-95%; see Table 20.3) and
estimate the peak-use transmission ratio, Tr (usually 1.00-1.10; see Table
19.3).
5. Calculate the leaching requirement, LRt, based on crop type and irrigation
water quality.
7. Calculate the gross volume of water required per plant per day, G.
⎛ dS pS r ⎞
G = K⎜ ⎟ (375)
⎝ f ⎠
8. Calculate the daily hours of operation, Ta, (per station, or subunit) during
the peak-use period.
G
Ta = (376)
N pq a
If Ta = 24 hrs, then Ns = 1
If Ta = 12 hrs, then Ns = 1 or 2
If Ta = 8 hrs, then Ns = 2 or 3, and so on
10. Adjust Np and qa so that TaNs is equal to, or slightly less than, 90%(24
hrs/day) = 21.6 hrs/day. First, try adjusting qa because this is usually less
expensive than increasing Np. If the emitter is pressure compensating, or
if qa must be greatly altered, you may need to change Np (or you may
need to select a different emitter).
11. Having determined the value of qa, calculate the minimum allowable
emitter discharge, qn
Sprinkle & Trickle Irrigation Lectures Page 229 Merkley & Allen
q a EU
qn = (377)
100 (1.0 − 1.27 νs )
Note that if EU is high and νs is high, it could be that qn > qa (but this
would not be a reasonable calculation result!)
12. Calculate the average (nominal) and minimum lateral pressure heads
1/ x
⎛ q ⎞
h=⎜ ⎟ (378)
⎝ Kd ⎠
1/ x
⎛q ⎞
hn = ha ⎜ n ⎟ (379)
⎝ qa ⎠
15. Finally, size the laterals, headers, manifolds and mainline(s) according to
hydraulic design criteria.
Merkley & Allen Page 230 Sprinkle & Trickle Irrigation Lectures
Lecture 21
Pipe Specifications & Trickle Lateral Design
• All of these pipe materials are called “thermoplastic” because the material
can be repeatedly softened by increasing the temperature, and hardened by
a decrease in temperature
• The pressure rating of plastic pipe (especially PVC) decreases rapidly with
increasing temperature of the pipe and or water
• For example, at about 43°C (109°F) the PVC pressure rating
drops to one-half of the nominal value at 23°C (73°F), and
almost the same amount for PE
• PE pipe temperature can easily reach 43°C on a sunny day
• Unlike most metal pipes, these plastic pipe materials are immune to almost
all types of corrosion, whether chemical or electrochemical
• The resistance to corrosion is a significant benefit when chemigation is
practiced in a pressurized irrigation system
• The dimension ratio (DR) of a plastic pipe is the ratio of average diameter (ID
or OD) to wall thickness
• PVC, ABS and some PE are OD-based, while other PE pipe is ID-based
Sprinkle & Trickle Irrigation Lectures Page 231 Merkley & Allen
• Plastic pipe is currently manufactured up to a maximum diameter of 54
inches
• There are several standard dimension thickness
ratios (SDR) for several values, each with
its own pressure rating (at 23°C)
• Different types of PVC, ABS and PE
compounds exist, some of which are
stronger than others diameter
• Some plastic pipe is manufactured with
non-standard dimension ratios; in these
cases the ratio is called “DR” rather than
“SDR”
• Some pipe sizes are correspond to iron
pipe size (IPS), plastic irrigation pipe (PIP), and others
• These are different standards for indirectly specifying pipe dimension ratios
and pressure ratings
2S 2S
PR = = (OD-based) (381)
SDR − 1 ⎛ OD ⎞
⎜ t − 1⎟
⎝ ⎠
2S 2S
PR = = (ID-based) (382)
SDR + 1 ⎛ ID ⎞
⎜ t + 1⎟
⎝ ⎠
• Common terms used in the industry for PVC pipe include Class 160, Class
200, Schedule 40, Schedule 80 and Schedule 120 (in increasing strength
and decreasing SDR)
• With the “schedule” classification, the higher the schedule, the thicker the
walls, for a given nominal pipe diameter
Merkley & Allen Page 232 Sprinkle & Trickle Irrigation Lectures
• The maximum allowable operating pressure is approximately equal to:
(schedule)SE
P= (383)
1000
where P is the operating pressure (psi); S is the allowable stress in the pipe
material (psi); E is the “joint efficiency”; and “schedule” is the schedule
number (e.g. 40, 80, 120, etc.)
• Joint efficiency (or “joint quality factor”) for PVC is approximately 1.00, due to
the fact that it is seamless
• Class 160 and 200 refer to 160 psi and 200 psi ratings, respectively
• The Schedule 40 and 80 specifications have carried over from classifications
used in iron pipes
• Schedule 80 is seldom used in irrigation because its pressure rating is much
higher than the maximum pressures found in most irrigation systems
• Schedule 40 is commonly used in irrigation
Sprinkle & Trickle Irrigation Lectures Page 233 Merkley & Allen
Abbreviation Meaning
ABS Acrylonitrile-Butadiene-Styrene
DR Dimension Ratio
ID Inside Diameter
IPS Iron Pipe Size
ISO International Organization for Standardization
OD Outside Diameter
PE Polyethylene
PIP Plastic Irrigation Pipe
PR Pressure Rating
PVC Polyvinyl Chloride
SDR Standard Dimension Ratio
• To start a new system design, Keller & Bliesner recommend limiting the
lateral pressure variation to 0.5∆Hs, where ∆Hs is calculated from Eq. 20.14
• Then, 0.5∆Hs remains for the manifolds (if manifolds are subunits, or
“stations”)
• In lateral designs, the pipe diameter is usually chosen (not calculated), and if
the pressure variation or loss is “out of range”, then a different size can be
selected
• There are usually only a few lateral diameters to choose from
Merkley & Allen Page 234 Sprinkle & Trickle Irrigation Lectures
III. Trickle Lateral Hydraulics
7 Q1.75
J = 7.83(10) (384)
D4.75
for J in m/100 m; Q in lps; and D in mm
• The Blasius equation estimates the D-W “f” factor for smooth pipes
• If you want to calculate relative roughness, use ε = 1.5(10)-6 m
⎛S +f ⎞
J' = J ⎜ e e ⎟ (385)
⎝ Se ⎠
where fe is an equivalent length of lateral hose for each emitter, spaced
evenly at a distance of Se
• The fe pipe length is one way that minor hydraulic losses are calculated in
pipes
• From Eq. 8.7a, a dimensionless friction loss equation can be developed (see
Fig. 8.2), which is useful in semi-graphical hydraulic design work for trickle
irrigation laterals
• This is discussed in detail in the following lectures
• For a given lateral pipe size, lateral length, emitter spacing, and nominal
discharge per emitter, the lateral inlet pressure must be determined such that
the average lateral pressure is “correct”
• Then, the manifold can be designed to provide this lateral inlet pressure with
as little variation (with distance) as possible
• Figure 22.1 shows four different hydraulic cases for single lateral designs
• The design of pairs of laterals is essentially a compound single lateral
problem, with the added criterion that the minimum pressure be the same in
both laterals
• Not including riser height, the required lateral inlet pressure is (Eq. 22.6):
H'n = Hl − (h f + ∆he ) − ∆H c
(387)
H'n = H c − ∆H c
• If the ground slope along the direction of the laterals is less than 3% or so, it
is usually recommendable to run laterals off both sides (uphill and downhill)
of each manifold
• If the ground slope along the direction of the laterals is more than 3%, it may
be best to run the laterals only in the downhill direction
• The design objective for a pair of laterals is to have equal values of minimum
pressure, Hn’, in uphill and downhill laterals
• This means that the downhill lateral will always be longer for laterals of equal
pipe size on sloping ground
• The manifold should be located in-between rows of plants (trees), not over a
row
• For laterals on flat ground, the manifold goes in the center of the field (the
trivial solution)
• Use the dimensionless friction loss curves (Fig. 8.2) to locate the optimal
manifold position in a sloping field
• The laterals run along the 0.021 m/m slope
• The combined uphill + downhill lateral length is 315 m
Merkley & Allen Page 236 Sprinkle & Trickle Irrigation Lectures
• The spacing of plants (trees) is
Sp = 4.5 m
315 m
= 210 emitters (388)
1.5 m/emitter
2. Total nominal discharge for the pair of laterals is:
Qpair =
( 210 emitters )( 3.5 lph/emitter ) = 12.25 lpm (389)
( 60 min/hr )
3. From Table 8.2 (page 141), J ≅ 13.3 m/100m. The adjusted J is:
⎛ S e + fe ⎞ ⎛ 1.5 + 0.12 ⎞
J' = J ⎜ ⎟ = 13.3 ⎜ ⎟ = 14.4 m/100 m (390)
⎜ Se ⎟ ⎝ 1.5 ⎠
⎝ ⎠
4. Multiple outlet factor, F = 0.36 for 210 outlets
Sprinkle & Trickle Irrigation Lectures Page 237 Merkley & Allen
7. Ratio of elevation change to friction loss for the pair:
⎛ ∆he ⎞ 6.62
⎜ ⎟ = = 0.41 (393)
⎝ f ⎠pair
h 16.3
8. From the nondimensional graphical solution (Fig. 8.2): x/L = 0.69. Then, x
= (0.69)(315 m) = 217 m. Look at the figure below:
• Looking at the above figure, a straight line was drawn from the origin
(0, 0) to (1.0, 0.41), where 0.41 is the ratio calculated above
• The nondimensional curve was overlapped and shifted vertically so
that the curve was tangent to the same straight line, then traced onto
the graph
• The nondimensional curve was then shifted vertically even more so
that the inverse half-curve (dashed) intersected the (1.0, 0.41) point,
also tracing it onto the graph
• The intersection of the two traced curve segments gave an abscissa
value of about 0.69, which is the distance ratio
Merkley & Allen Page 238 Sprinkle & Trickle Irrigation Lectures
9. Finally, adjust x for tree spacing,
• This manifold position give the same minimum pressure in both the uphill
and downhill laterals
• Minimum pressure in the downhill lateral is located approximately
(0.35)(315 m) = 110 m from the closed end, or 216 - 110 = 106 m from
the manifold.
• Note that this procedure could also be used for sprinklers, but it would
probably only be feasible for solid-set, fixed systems
Sprinkle & Trickle Irrigation Lectures Page 239 Merkley & Allen
Merkley & Allen Page 240 Sprinkle & Trickle Irrigation Lectures
Lecture 22
Numerical Solution for Manifold Location
I. Introduction
• In the previous lecture it was seen how the optimal manifold location can be
determined semi-graphically using a set of non-dimensional curves for the
uphill and downhill laterals
• This location can also be determined numerically
• In the following, equations are developed to solve for the unknown length of
the uphill lateral, xu, without resorting to a graphical solution
• In the uphill lateral, the minimum head is at the closed end of the lateral
(furthest uphill location in the subunit)
• This minimum head is equal to:
where hn’ is the minimum head (m); hl is the lateral inlet head (m); hfu is the
total friction loss in the uphill lateral (m); xu is the length of the uphill lateral
(m); and S is the slope of the ground surface (m/m)
(hfd)1 hfu
(hfd)2
xm xu
h n’ h n’
• In the downhill lateral, the minimum head may be anywhere from the inlet to
the outlet, depending on the lateral hydraulics and the ground slope
• The minimum head in the downhill lateral is equal to:
Sprinkle & Trickle Irrigation Lectures Page 241 Merkley & Allen
where (hfu)1 is the total friction loss in the downhill lateral (m); (hfu)2 is the
friction loss from the closed end of the downhill lateral to the location of
minimum head (m); and xm is the distance from the manifold (lateral inlet) to
the location of minimum head in the downhill lateral (m)
• The location of minimum head is where the slope of the ground surface, S,
equals the friction loss gradient, J’:
S = J' (397)
where both S and J’ are in m/m, and S is positive (you can take the absolute
value of S)
• Using the Hazen-Williams equation, the friction loss gradient in the downhill
lateral (at the location where S = J’) is:
⎡ Se + fe ⎤ ⎡ ⎛ qa (L − xu − xm ) ⎞ ⎤
1.852
⎢ 10 −4.87 ⎥
J' = ⎢ ⎥ 1.212(10) ⎜ ⎟ D (398)
⎣ Se ⎦ ⎢⎣ ⎝ 3,600Se C ⎠ ⎥
⎦
0.571
⎡ 3,600Se ⎤ ⎡⎛ SD4.75 ⎞ ⎛ Se ⎞ ⎤
xm = L − xu − ⎢ ⎥ ⎢⎜⎜ 5 ⎟⎟ ⎜ S + f ⎟
⎥ (400)
⎣ qa ⎦ ⎢⎣⎝ 7.89(10) ⎠ ⎝ e e ⎠ ⎥⎦
• The above three “F” values are as defined by Eq. 8.9 in the textbook
• The friction loss gradients (in m/m) are:
Ju ' = K J ( xu )
1.852
(404)
Jd1 ' = K J (L − xu )
1.852
(405)
Jd2 ' = K J (L − xu − xm )
1.852
(406)
Sprinkle & Trickle Irrigation Lectures Page 243 Merkley & Allen
⎛ Se + fe ⎞ ⎡
1.852 ⎤
− ⎛ q ⎞
⎟ ⎢1.212(10) D ⎥
10 4.87
KJ = ⎜ ⎜
a
⎟ (407)
⎝ S e ⎠ ⎢ ⎝ 3,600S C
e ⎠ ⎥
⎣ ⎦
• Using the definitions above, solve for the length of the uphill lateral, xu
• Then, xd = L - xu
• Note that you might prefer to use the Darcy-Weisbach and Blasius equations
for the manifold calculations; they may be more accurate than Hazen-
Williams
• The “OptManifold” computer program uses the Darcy-Weisbach & Blasius
equations
Merkley & Allen Page 244 Sprinkle & Trickle Irrigation Lectures
Where do these Equations Come From?
L V2
hf = f (408)
D 2g
• Blasius equation, for estimating f for small diameter (D < 125 mm) “smooth
pipes” (e.g. PE & PVC), and based on more complete equations that are
used to plot the Moody diagram
−0.25
f ≅ 0.32NR (409)
VD 4Q
NR = = (410)
ν νπD
• The kinematic viscosity, ν, is equal to about 1.003(10)-6 m2/s for water at
20°C
• Then, for this kinematic viscosity,
−0.25 −0.25
⎛ 4Q ⎞ ⎛Q⎞
f ≅ 0.32 ⎜ ⎟ ≈ 0.0095 ⎜ ⎟ (411)
⎝ νπD ⎠ ⎝D⎠
Sprinkle & Trickle Irrigation Lectures Page 245 Merkley & Allen
• Putting the above into the Darcy-Weisbach equation:
−0.25
⎛Q⎞ L V2
hf = 0.0095 ⎜ ⎟ (412)
⎝D⎠ D 2g
or:
Q1.75
hf ≅ 0.00079L (413)
D4.75
where hf is in m; L is in m; Q is in m3/s; and D is in m
• Eq. 8.7a is obtained by having Q in lps, and D in mm, whereby the above
coefficient changes to 7.9(10)7
• Finally, in the above, use L(x/L) instead of L, and Q(x/L) instead of Q, and
call it “hfx”:
⎡Q ( x / L ) ⎤⎦
1.75
hfx ≅ 0.00079L(x / L) ⎣ (414)
D4.75
• Then,
hfx
= (x / L) ( x / L ) = (x / L)
1.75 2.75
(415)
hf
which is Eq. 8.10b and the basis for the nondimensional friction loss curves,
valid for plastic pipes with D < 125 mm
• The difference between the minimum pressure head and the pressure head
at the closed end of a lateral, ∆Hc, is used to calculate the minimum head in
the lateral, Hn’
• This is because the pressure head at the end of the lateral is easily
calculated as:
H c = H l − h f − ∆he (416)
• But the minimum pressure head does not necessarily occur at the end of the
lateral when the lateral runs downhill
• Thus, in general,
Merkley & Allen Page 246 Sprinkle & Trickle Irrigation Lectures
H'n = H c − ∆H c (417)
1. The minimum pressure in the lateral occurs where the ground slope (for a
uniform slope) equals the slope of the friction loss curve. The dimensionless
friction loss curve is defined as (Eq. 8.10b or Eq. 22.3b):
2.75
⎛ hfx ⎞ ⎛x⎞
⎜ ⎟ =⎜ ⎟ (418)
⎝ hf ⎠pair ⎝ L ⎠
⎛h ⎞
d ⎜ fx ⎟
1.75
⎝ hf ⎠pair ⎛x⎞
= 2.75 ⎜ ⎟ (419)
⎛x⎞ ⎝L⎠
d⎜ ⎟
⎝L⎠
⎛ ∆he ⎞ SL 100S
⎜ ⎟ = = (420)
⎝ hf ⎠pair ⎛ J'FL ⎞ J 'F
⎜ 100 ⎟
⎝ ⎠
4. Then,
100S
= 2.75 ( y )
1.75
(421)
J'F
in which y is the value of x/L where the minimum pressure occurs (0 ≤ y ≤ 1);
S is the ground slope (m/m); J’ is the friction loss gradient for the flow rate in
the pair of laterals (m/100 m); and F is the reduction coefficient for multiple
outlet pipes (usually about 0.36)
Sprinkle & Trickle Irrigation Lectures Page 247 Merkley & Allen
5. Solve for y:
1/ 1.75
⎛ 100S ⎞
y=⎜ ⎟ (422)
⎝ 2.75 J'F ⎠
or,
1/ 1.75
⎛ 100S ⎞
y≈⎜ ⎟ (423)
⎝ J' ⎠
where F ≈ 0.36
Merkley & Allen Page 248 Sprinkle & Trickle Irrigation Lectures
6. Referring to the figure on the previous page, the following equality can be
written:
∆Hc 100 y S
y 2.75 + = (424)
(hf )pair J'F
where,
J'FL
(hf )pair = (426)
100
and y can be approximated as in step 5 above (for F = 0.36)
−0.57
∆Hc = 8.9LS1.57 ( J' ) (427)
for ∆Hc in m; L in m; S in m/m; and J’ in m/100 m. Note that J’ and L are for
the pair of laterals, not only uphill or only downhill
⎛x ⎞
Hl = Ha + α (hf )pair + ⎜ − 0.5 ⎟ ( ∆he )pair (428)
⎝L ⎠
with,
1/ x
⎛q ⎞
Ha = ⎜ a ⎟ (429)
⎝ Kd ⎠
J'FL
(hf )pair = (430)
100
Sprinkle & Trickle Irrigation Lectures Page 249 Merkley & Allen
100S
( ∆he )pair = (hf )pair = SL (431)
J'F
1. Given that for a single lateral approximately ¾ of the friction loss occurs
from the inlet to the point where the average pressure occurs (multiple
outlets, uniform outlet spacing, constant discharge from outlets, single
lateral pipe size) we have the following:
2. Recall that,
2.75
⎛ hfx ⎞ ⎛x⎞
⎜ ⎟ =⎜ ⎟ (433)
⎝ hf ⎠pair ⎝ L ⎠
Then,
2.75
⎛x⎞
(hf )downhill =⎜ ⎟ (hf )pair
⎝L⎠
(434)
2.75
(hf )uphill = ⎛⎜ 1 −
x⎞
(hf )pair
⎝ L ⎟⎠
3. Combining equations:
3 ⎡⎛ x ⎞ ⎛ x ⎞2.75 ⎛ x ⎞⎛ x⎞
2.75 ⎤
α (hf )pair = (hf )pair ⎢⎜ ⎟ ⎜ ⎟ + ⎜1− ⎟ ⎜1− ⎟ ⎥ (435)
4 ⎢⎣⎝ ⎠ ⎝ ⎠
L L ⎝ L ⎠⎝ L ⎠ ⎥⎦
3 ⎡⎛ x ⎞
3.75 3.75 ⎤
⎛ x⎞
α = ⎢⎜ ⎟ + ⎜1− ⎟ ⎥ (436)
4 ⎢⎝ L ⎠ ⎝ L⎠ ⎥⎦
⎣
Merkley & Allen Page 250 Sprinkle & Trickle Irrigation Lectures
• This last equation for α is Eq. 22.25 from the textbook
• See the figure below
Sprinkle & Trickle Irrigation Lectures Page 251 Merkley & Allen
Merkley & Allen Page 252 Sprinkle & Trickle Irrigation Lectures
Lecture 23
Manifold Hydraulic Design
I. Introduction
• Manifolds in trickle irrigation systems often have multiple pipe sizes to:
• In small irrigation systems the reduction in pipe cost may not be significant,
not to mention that it is also easier to install a system with fewer pipe sizes
• Manifold design is normally subsequent to lateral design, but it can be part of
an iterative process (i.e. design the laterals, design the manifold, adjust the
lateral design, etc.)
• The allowable head variation in the manifold, for manifolds as subunits, is
given by the allowable subunit head variation (Eq. 20.14) and the calculated
lateral head variation, ∆Hl
• This simple relationship is given in Eq. 23.1:
• Eq. 23.1 simply says that the allowable subunit head variation is shared by
the laterals and manifold
• Recall that a starting design point can be to have ∆Hl = ½∆Hs, and ∆Hm =
½∆Hs, but this half and half proportion can be adjusted during the design
iterations
• The lateral pressure variation, ∆Hl, is equal to the maximum pressure minus
the minimum pressure, which is true for single-direction laterals and
uphill+downhill pairs, if Hn’ is the same both uphill and downhill
• Equation 20.14 (page 502 in the textbook) gives the allowable pressure head
variation in a “subunit”
• This equation is an approximation of the true allowable head variation,
because this equation is applied before the laterals and manifold are
designed
• After designing the laterals and manifold,
the actual head variation and expected
EU can be recalculated
(
H max − H n = 2 H a − H n ) (438)
(
H max − H n = 4 H a − H n ) (439)
• For a sloping friction loss gradient (multiple outlets) on flat ground with dual
pipe sizes, about 63% of the friction head loss occurs from the lateral inlet to
the location of average pressure. Then 100/(100-63) = 2.7 and,
(
H max − H n = 2.7 H a − H n ) (440)
(
∆Hs = 2.5 H a − H n ) (441)
• After the design process, the final value of ∆Hs may be different, but if it is
much different the deviation should be somehow justified
Merkley & Allen Page 254 Sprinkle & Trickle Irrigation Lectures
III. Pipe Sizing in Manifolds
1. Semi-graphical
2. Hydraulic grade line (HGL)
3. Economic pipe sizing (as in Chapter 8 of the textbook)
• The graphical method uses “standard” head loss curves for different pipe
sizes and different flow rates with equally-spaced multiple outlets, each outlet
with the same discharge
• The curves all intersect at the origin (corresponding to the downstream
closed end of a pipe)
• Below is a sample of the kind of curves given in Fig. 23.2 of the textbook
• Instead of the standard curves, specific curves for each design case could be
custom developed and plotted as necessary in spreadsheets
• The steps to complete a graphical design are outlined in the textbook
• The graphical procedure is helpful in understanding the hydraulic design of
multiple pipe size manifolds, but may not be as expedient as fully numerical
procedures
Sprinkle & Trickle Irrigation Lectures Page 255 Merkley & Allen
3.8
3.6
3.4
3.2
3.0
Friction Head Loss (ft)
2.8
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.25 inch
1.0
1.50 inch
0.8
2.00 inch
0.6
2.50 inch
0.4 3.00 inch
0.2 4.00 inch
0.0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320
Step 1:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Merkley & Allen Page 256 Sprinkle & Trickle Irrigation Lectures
Step 2:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Step 3:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Sprinkle & Trickle Irrigation Lectures Page 257 Merkley & Allen
Step 4:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Step 5:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Merkley & Allen Page 258 Sprinkle & Trickle Irrigation Lectures
Step 6:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
HGL Design Procedure
• The HGL procedure is very similar to the graphical procedure, except that it
is applied numerically, without the need for graphs
• Nevertheless, it is useful to graph the resulting hydraulic curves to check for
errors or infeasibilities
• The first (upstream) head loss curve starts from a fixed point: maximum
discharge in the manifold and upper limit on head variation
• Equations for friction loss curves of different pipe diameters are known (e.g.
Darcy-Weisbach, Hazen-Williams), and these can be equated to each other
to determine intersection points, that is, points at which the pipe size would
change in the manifold design
• But, before equating head loss equations, the curves must be vertically
shifted so they just intersect with the ground slope curve (or the tangent to
the first, upstream, curve, emanating from the origin)
• The vertical shifting can be done graphically or numerically
Sprinkle & Trickle Irrigation Lectures Page 259 Merkley & Allen
• The manifold has multiple outlets (laterals or headers), and the “section flow
rate” changes between each outlet
• The “system flow rate” would be the flow rate entering the manifold
• After completing the manifold pipe sizing, the required manifold inlet pressure
head can be determined (Eq. 23.4):
Hm = Hl + k hf + 0.5∆Em (442)
where k = 0.75 for single-diameter manifolds; k = 0.63 for dual pipe size
laterals; or k ≈ 0.5 for three or more pipe sizes (tapered manifolds); and ∆El
is negative for downward-sloping manifolds
• As with lateral design, the friction loss curves must be shifted up to provide
for the required average pressure
• In the case of manifolds, we would like the average pressure to be equal to
the calculated lateral inlet head, Hl
• The parameter ∆El is the elevation difference along one portion of the
manifold (either uphill or downhill), with positive values for uphill slopes and
negative values for downhill slopes
V. Manifold Design
• Manifolds should usually extend both ways from the mainline to reduce the
system cost, provided that the ground slope in the direction of the manifolds
is less than about 3% (same as for laterals, as in the previous lectures)
• As shown in the sample layout (plan view) below, manifolds are typically
orthogonal to the mainline, and laterals are orthogonal to the manifolds
Merkley & Allen Page 260 Sprinkle & Trickle Irrigation Lectures
• Manifolds usually are made up of 2 to 4 pipe diameters, tapered
(telescoping) down toward the downstream end
• For tapered manifolds, the smallest of the pipe diameters (at the downstream
end) should be greater than about ½ the largest diameter (at the upstream
end) to help avoid clogging during flushing of the manifold
D1 D2 D3>0.5D1
• The maximum average flow velocity in each pipe segment should be less
than about 2 m/s
• Water hammer is not much of a concern, primarily because the manifold has
multiple outlets (which rapidly attenuates a high- or low-pressure wave), but
the friction loss increases exponentially with flow velocity
• The objective is the same as for pairs of laterals: make (Hn)uphill equal to
(Hn)downhill
• If average friction loss slopes are equal for both uphill and downhill manifold
branches (assuming similar diameters will carry similar flow rates):
Downhill side:
( ∆Hm )a = hfd − ∆E ⎛⎜
x⎞
⎟ = hfd − Y∆E (443)
⎝ ⎠
L
Uphill side:
L−x⎞
( ∆Hm )a = hfu + ∆E ⎛⎜ ⎟ = hfu + (1 − Y)∆E (444)
⎝ L ⎠
where x is the length of downhill manifold (m or ft); L is the total length of the
manifold (m or ft); Y equals x/L; and ∆E is the absolute elevation difference of
the uphill and downhill portions of the manifold (m or ft)
Juphill = Jdownhill
hfu h (445)
= fd
L−x x
where J-bar is the average friction loss gradient from the mainline to the end
of the manifold (J-bar is essentially the same as JF)
Sprinkle & Trickle Irrigation Lectures Page 261 Merkley & Allen
Then,
hfd = Jx
(446)
hfu = J(L − x)
and,
( ∆Hm )a = Jx − Y∆E
(447)
( ∆Hm )a = J(L − x) + (1 − Y) ∆E
then,
( ∆Hm )a + Y∆E
=J
x (448)
( ∆Hm )a − (1 − Y) ∆E
=J
L−x
• Equating both J-bar values,
⎛ Qbeg − Qend ⎞
LD = L ⎜ ⎟ (453)
⎝ Q m ⎠
where Qbeg is the flow rate at the beginning of diameter “D” in the EPST (lps
or gpm); Qend is the flow rate at the end of diameter “D” in the EPST, which is
the breakeven flow rate of the next larger pipe size) (lps or gpm); L is the
total length of the manifold (m or ft); and Qm is the manifold inflow rate (lps or
gpm). (see Eq. 23.7)
(d) Determine the total friction loss along the manifold (see Eq. 23.8a):
where,
• The above equation is for four pipe sizes; if there are less than four sizes, the
extra terms are eliminated from the equation
• An alternative would be to use Eq. 23.8b (for known pipe lengths), or
evaluate the friction loss using a computer program or a spreadsheet to
calculate the losses section by section along the manifold
• Eq. 23.8b is written for manifold design as follows:
a −1 ⎛ a
FK Qm x1 x a2 − x1a x 3a − x a2 x a4 − x 3a ⎞
hf = ⎜ + + + ⎟ (455)
100La −1 ⎜⎝ D1c Dc2 D3c Dc4 ⎟⎠
• Again, there may be up to four different pipe sizes in the manifold, but in
many cases there will be less than four sizes
∆Hm = hf + S xu (456)
⎛ 0.36 ⎞
∆Hm = hf + S ⎜ 1 − xd
n ⎟⎠
(457)
⎝
Merkley & Allen Page 264 Sprinkle & Trickle Irrigation Lectures
where n is the number of different pipe sizes used in the branch; and S is the
ground slope in the direction of the manifold (m/m)
(f) if ∆Hm < 1.1 (∆Hm)a, then the pipe sizing is all right. Go to step (g) of this
B B B B B B
EPST). This will artificially increase the break-even flow rates in the
table (chart).
• The new flow rates to use in re-doing the EPST can be estimated for s >
0 as follows:
1/ b
⎛ hf ⎞
Qnew old
= Qs ⎜ ⎟ (458)
s ⎜ ( ∆Hm ) − ∆Em ⎟
⎝ a ⎠
and for s < 0 as:
1/ b
⎛ ⎞
⎜ hf ⎟
old ⎜ ⎟
Qnew
s = Qs (459)
⎜ ∆H ⎛ 0.36 ⎞ ⎟
⎜ ( m )a − ∆El ⎜ 1 − n ⎟ ⎟
⎝ ⎝ ⎠⎠
•The above two equations are used to change the flow rates to compute
the EPST
• The value of Qm remains the same B B
• This will make the laterals shorter, Qm will decrease, and ∆Hl may B B B B
decrease
• This alternative may or may not help in the design process
Sprinkle & Trickle Irrigation Lectures Page 265 Merkley & Allen
(4) Decrease ∆Hl (use larger pipe sizes) B B
(5) Increase Ha B B
• For non-critical manifolds, or where ∆Hm < (∆Hm)a, decrease Qs (or just B B B B B B B B
Fs = 0.38S1.25
f + 0.62 (461)
where Sf = Qlc/Qla; Qlc is the lateral discharge at the end of the manifold
B B B B B B B B
and Qla is the average lateral discharge along the manifold. Then,
B B
⎛ JL ⎞
hf = Fs F ⎜ ⎟
⎝ 100 ⎠ (462)
Merkley & Allen Page 266 Sprinkle & Trickle Irrigation Lectures
(a) Uphill Side of the Manifold
• Get the smallest allowable pipe diameter and use only the one diameter
for this part of the manifold
• First, determine the minimum pipe diameter for the first pipe in the
downhill side of the manifold, which of course will be the largest of the
pipe sizes that will be used
• This can be accomplished by finding the inside pipe diameter, D, that will
give a friction loss curve tangent to the ground slope
• To do this, it is necessary to: (1) have the slope of the friction loss curve
equal to So; and, (2) have the H values equal at this location (make them
B B
• See the following figure, based on the length of the downstream part of
the manifold, xd B B
• Some manifolds will only have a downhill part – others will have both
uphill and downhill parts
H flow direction
(∆Hm)a
hf
e
rv
D1 = ???
cu
ss
lo
i on
fr ict
So ∆Em
1
0
0 manifold flow rate Qm
xd
Sprinkle & Trickle Irrigation Lectures Page 267 Merkley & Allen
• For the above figure, where the right side is the mainline location and the
left side is the downstream closed end of the manifold, the friction loss
curve is defined as:
JFL
H = ( ∆Hm )a + ∆Em − hf + (463)
100
1.852
⎛Q⎞
J = K⎜ ⎟ D−4.87 for 0 ≤ Q ≤ Qm (464)
⎝C⎠
1 1 0.852
F= + + (465)
2.852 2N 6N2
⎛ x ⎞⎛ Q ⎞
N = ⎜ d ⎟⎜ ⎟ for N > 0 (466)
⎝ Sl ⎠ ⎝ Qm ⎠
where N is the number of outlets (laterals) from the location of “Q” in the
manifold to the closed end
⎛ Q ⎞
L = xd ⎜ ⎟ (467)
⎝ Qm ⎠
• The total head loss in the downhill side of the manifold is:
1.852
J F x ⎛Q ⎞
hf = hf hf d = 0.01K ⎜ m ⎟ D−4.87Fhf x d (468)
100 ⎝ C ⎠
dH 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (469)
dQ 100 ⎝ dQ dQ dQ ⎠
where,
Merkley & Allen Page 268 Sprinkle & Trickle Irrigation Lectures
dJ 1.852KQ0.852
= (470)
dQ C1.852D4.87
dF xd ⎛ 1 0.852 ⎞
=− ⎜ + ⎟ (471)
dQ SlQmN2 ⎜⎝ 2 3N ⎟⎠
dL x
= d (472)
dQ Qm
⎛ Q ⎞
H = SoL = So x d ⎜ ⎟ (473)
⎝ Qm ⎠
and,
dH So x d
= (474)
dQ Qm
• Combine the two equations defining H (this makes the friction loss curve
just touch the ground surface):
⎛ Q ⎞ JFL
So x d ⎜ ⎟ = ( ∆Hm )a + ∆Em − hf + (475)
⎝ Qm ⎠ 100
−0.205
⎡ 1.852 ⎛ So x dQ ⎞⎤
⎢ 100C ⎜ − ( ∆H )
m a − ∆ Em ⎟⎥
D= ⎢ ⎝ Qm ⎠⎥
( )
(476)
⎢ K Q 1.852 1.852
FL − Qm Fhf x d ⎥
⎢ ⎥
⎣⎢ ⎦⎥
So x d 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (477)
Qm 100 ⎝ dQ dQ dQ ⎠
Sprinkle & Trickle Irrigation Lectures Page 269 Merkley & Allen
• Combine the above two equations so that the only unknown is Q (note: D
appears in the J & dJ/dQ terms of the above equation)
• Solve for Q by iteration; the pipe inside diameter, D, will be known as part
of the solution for Q
• The calculated value of D is the minimum inside pipe diameter, so find the
nearest available pipe size that is larger than or equal to D:
• Now calculate the equation of the line through the origin and tangent to
the friction loss curve for D1 B B
⎛ Q ⎞
H = StL = St x d ⎜ ⎟ (479)
⎝ Qm ⎠
then,
⎛ Q ⎞ JFL
St x d ⎜ ⎟ = ( ∆Hm )a + ∆El − hf + (480)
⎝ Qm ⎠ 100
St x d 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (481)
Qm 100 ⎝ dQ dQ dQ ⎠
• Then take the next smaller pipe size, D2, and make its B B
JFL
H = H0 + (482)
100
where H0 is a vertical offset to make the friction loss curve tangent to the
B B
Merkley & Allen Page 270 Sprinkle & Trickle Irrigation Lectures
• Equating heads and solving for H0, B B
⎛ Q ⎞ JFL
H0 = St x d ⎜ ⎟− (483)
⎝ Qm ⎠ 100
• Again, set the slope of the friction loss curve equal to St, B B
St x d 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (484)
Qm 100 ⎝ dQ dQ dQ ⎠
• Now you have the equation for the next friction loss curve
• Determine the intersection with the D1 friction loss curve to set the lengthB B
for size D1; this is done by equating the H values for the respective
B B
1.852
Hbig − Hsmall +
FLK ⎛ Q ⎞
⎜ ⎟
100 ⎝ C ⎠
(Dbig
−4.87 −4.87
− Dsmall )=0 (485)
Hsmall = H0 (487)
⎛ Q ⎞
LD1 = x d ⎜ 1 − ⎟ (488)
⎝ Qm ⎠
• Continue this process until you have three or four pipe sizes, or until you
get to a pipe size that has D < ½D1 B B
Sprinkle & Trickle Irrigation Lectures Page 271 Merkley & Allen
Comments about the HGL Method B
• The above equation development could also be done using the Darcy-
Weisbach equation
• Specify a minimum length for each pipe size in the manifold
so that the design is not something ridiculous (i.e. don’t just
blindly perform calculations, but look at what you have)
• For example, the minimum allowable pipe length might be
something like 5Sl
B B
• Below is a screen shot from a computer program that uses the HGL
method for manifold pipe sizing
Merkley & Allen Page 272 Sprinkle & Trickle Irrigation Lectures
Sprinkle & Trickle Irrigation Lectures Page 273 Merkley & Allen
Merkley & Allen Page 274 Sprinkle & Trickle Irrigation Lectures
Lecture 24
Hydraulic Design of Mainline & Supply Line
I. Introduction
Sprinkle & Trickle Irrigation Lectures Page 275 Merkley & Allen
III. Mainline, Supply, and Control Head Design
Merkley & Allen Page 276 Sprinkle & Trickle Irrigation Lectures
• The critical subunit will define the “worst case” for which the
pumping unit should be designed. It may then be possible to
reduce pipe sizes in other subunits if they will have excess head
available.
Example calculation:
• Size sections A-B, B-C and C-D for a trickle irrigation mainline
having three manifolds
• First, decide on the number of stations, Ns B B
This could be 1, 3 or 6:
• Set up a table to see the effect of Ns on the flow rates and Ot per B B B B
Number of Stations
1 2 3
Qs (lps) B B 30 30 30
Ot/station (hrs)
B B 1000 330 165
Ot, CD B B 1000 330 330
QCD B B 10 30 30
Ot, BC B B 1000 660 660
QBC B B 20 30 30
Ot, AB B B 1000 1000 1000
QAB B B 30 30 30
• Ot, CD, for example, is the number of hours that water is flowing in
B B
1. static lift
2. well losses (if applicable)
3. supply line losses (elevation and friction)
4. control head pressure losses
5. losses to the critical subunit plus inlet pressure, (Hm + B B
Hfe)c
B B B B
Sprinkle & Trickle Irrigation Lectures Page 279 Merkley & Allen
Merkley & Allen Page 280 Sprinkle & Trickle Irrigation Lectures