Pvsyst Report
Pvsyst Report
Starobesheve
12 MW (1)
Project : Starobesheve 12 MW
Geographical Site Starobeshevo Country Ukrainia
Situation Latitude 47.8°N Longitude 38.0°E
Time defined as Legal Time Time zone UT+2 Altitude 118 m
Albedo 0.20
Meteo data : Starobeshevo from PVGIS, Synthetic Hourly data
Simulation parameters
Collector Plane Orientation Tilt 32° Azimuth 0°
5Sheds Pitch 7.70 m Collector width 3.35 m
Inactive band Top 0.00 m Bottom 0.00 m
Shading limit angle Gamma 20.07 ° Occupation Ratio 43.5 %
Starobesheve
12 MW (1)
Starobesheve
12 MW (1)
Normalized productions (per installed kWp): Nominal power 12000 kWp Performance Ratio PR
7 1.0
PR : Performance Ratio (Yf / Yr) : 0.773
Lc : Collection Loss (PV-array losses) 0.78 kWh/kWp/day
Ls : System Loss (inverter, ...) 0.05 kWh/kWp/day
Yf : Produced useful energy (inverter output) 2.84 kWh/kWp/day
6
0.8
5
Normalized Energy [kWh/kWp/day]
Performance Ratio PR
0.6
4
3
0.4
0.2
1
0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Legends: GlobHor Horizontal global irradiation EArray Effective energy at the output of the array
T Amb Ambient Temperature E_Grid Energy injected into grid
GlobInc Global incident in coll. plane EffArrR Effic. Eout array / rough area
GlobEff Effective Global, corr. for IAM and shadings EffSysR Effic. Eout system / rough area
PVSYST V5.55 31/05/12 Page 4/4
Starobesheve
12 MW (1)