7sa5222 Setting Sheet

This document provides settings and calculations for distance protection relays on a 220kV transmission line. It includes details like: 1) Line parameters such as length, impedance values, and fault current ratings 2) Relay settings for zones 1 through 4 including reach, resistance, and reactance values 3) Calculations for load impedance used to block trips during power swings

Uploaded by

Ramees Mhd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
279 views7 pages

7sa5222 Setting Sheet

This document provides settings and calculations for distance protection relays on a 220kV transmission line. It includes details like: 1) Line parameters such as length, impedance values, and fault current ratings 2) Relay settings for zones 1 through 4 including reach, resistance, and reactance values 3) Calculations for load impedance used to block trips during power swings

Uploaded by

Ramees Mhd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

SMG-2 INPUT DETAILS FOR LINE PROTECTION

1 System Voltage : 220 kV

2 Voltae transformer primary : 220 kV

3 Voltae transformer secondary : 110 V

4 CT ratio Pri : 600 A

5 CT ratio sec : 1 A

6 Maximum power flow : 230 MVA

7 System frequency : 50 Hz

8 3Ø Fault Current : 50000 A

9 Line Details : ACSR Drake

Line Data's
Details Parameters Actual shortest Longest

Length KM 86 40 157

Resistance 0.0804 0.0804 0.0804


+ve sequence
Reactance 0.3999 0.3999 0.3999

Resistance 0.229 0.229 0.229


zero sequence
Reactance 1.246 1.246 1.246
SMG-2 Distance Protection(21)

Relay details
Relay Type : 7SA522
Make : SIEMENS
Rated current : 1A

CT Details
CT Ratio : 600 A
Adopted Ratio : 600
CT Secondary : 1A

System Details
VT Primary : 220kV
VT Secondary : 110V
Voltage Level : 220kV
Frequency : 50Hz

Zone Reach Details


Main-1 Protection - Distance Protection - Make SIEMEN'S-7SA522
The relay shall work in Permissive Over Reach (POR) mode with the following settings:

Zone Details (As per CEA specifications)

Zone 1 : 80% of the protected Line


Zone 2 : 100% of the protected Line + 50% of Adjacent shortest line
Zone 3 : 100% of the protected Line + 100% of Adjacent Longest line
Zone 4 : 20% of protected line (reverse reach)

VT Ratio : 220x1000 / 110


: 2000
CT Ratio : 600 / 1 A
: 600
Transformation Ratio N = CT Ratio / VT Ratio
= 0.300

Calculated Sec Impedance Zsec = N x Z prim in ohm


Zprim = Primary Impedance in ohm

OHL Data:
BASE kV : 220kV
BASE MVA : 230.0 MVA
Line Length : 86.0Km

ARC and Tower Footing Resistance

A separate arc Resistance tolerance can be set for earth faults.An resistance of 4.9 Ohms
and Tower footing resistance of 9.5 Ohms (Primary Values)

Arc Resistance : 4.9 Ohm(Primary)


Tower footing Resistance : 9.5 Ohm(Primary)
Calculation
Setting for Earth Impedance Ratio

Resistance Ratio RE/RL = 1/3((R0/R1)-1)


R0 = 0.229
R1 = 0.0804
= 0.62

Reactance Ratio XE/XL = 1/3((X0/X1)-1)


X0 = 1.246
X1 = 0.400
= 0.705

Line Angle Setting Tan φ = XL/RL


φ = Tan -1 (X1/R1)
= 78.63 Degree

Zone 1 Reach Values:


Positive Sequence Reactance = X1 x N x Line length x (% )of zone 1
X(Z1) = 8.2539
Set at X(Z1) = 8.2539 ohm

Positive Sequence Resistance = ((R1 x (%) of zone 1 x KM) + (1/2*Rarc)) X N


R(Z1) 2.394
Set at R(Z1) = 2.394 ohm

Combination of Arc Resistance and Tower footing Resistance


RE (Z1) = ((R1 x (%) of zone 1 x KM) + (Rarc + RT)) X N
Set at RE (Z1) = 5.979 ohm

Zone 2 Reach Values:


Positive Sequence Reactance = ((X1 x 100% of the protected Line) + (X1 x 50% of
Adjacent Shortest Line)X N)
X(Z2) = 12.717
Set at X(Z2) = 12.717 ohm

Positive Sequence Resistance = ((R1 x 100% of the protected Line) + (R1 x 50% of
the Adjacent shortest Line)+(1/2*Rarc)) x N

R(Z2) 3.292
Set at R(Z2) = 3.292 ohm

Combination of Arc Resistance and Tower footing Resistance


RE (Z2) = ((R1 x 100% of the protected Line) + (R1 x 50% of
the Adjacent shortest Line)+(Rarc + RT)) x N

Set at RE (Z2) = 6.877 ohm


Zone 3 Reach Values:
Positive Sequence Reactance = ((X1 x 100% of the protected line)+(X1 x 100% of
the Adjacent Longest line) x N)
X(Z3) = 29.153
Set at X(Z3) = 29.153 ohm

Positive Sequence Resistance = ((R1 x 100% of the protected line) + (R1 x 100%
Adjacent longest Line) + (1/2*Rarc)) x N
R(Z3) 6.596
Set at R(Z3) = 6.596 ohm

Combination of Arc Resistance and Tower footing Resistance


RE (Z3) = ((R1 x 100% of the protected line) + (R1 x 100%
Adjacent longest Line) + (Rarc + RT)) x N
Set at RE (Z3) = 10.181 ohm

Zone 4 Reach Values:


Positive Sequence Reactance = X1 x N x Line length x (% )of zone 4
X(Z4) = 2.063
Set at X(Z4) = 2.063 ohm

Positive Sequence Resistance = ((R1 x KM x (%) of zone 4) + (1/2*Rarc)) x N


R(Z4) 1.150
Set at R(Z4) = 1.150 ohm

Combination of Arc Resistance and Tower footing Resistance


RE (Z4) = ((R1 x KM x (%) of zone 4) + (Rarc + RT)) x N
Set at RE (Z4) = 4.735 ohm

Zone Z1B Reach Values: (POTT)


Positive Sequence Reactance = ((X1 x 100% of the protected Line) + (X1 x 50% of
Adjacent Shortest Line)X N)
X(Z1B) = 12.717
Set at X(Z1B) = 12.717 ohm

Positive Sequence Resistance = ((R1 x 100% of the protected Line) + (R1 x 50% of
the Adjacent shortest Line)+(1/2*Rarc)) x N

R(Z1B) 3.292
Set at R(Z1B) = 3.292 ohm

Combination of Arc Resistance and Tower footing Resistance


RE (Z1B) = ((R1 x 100% of the protected Line) + (R1 x 50% of
the Adjacent shortest Line)+(Rarc + RT)) x N

6.877
Set at RE(Z1B) = 6.877 ohm

Zone Timer Setting:

ZONE 1- t1 PP : 0.00 sec


ZONE 1- t1 PE : 0.00 sec
ZONE Z1B- t1 PP : 0.00 sec
ZONE Z1B- t1 PE : 0.00 sec
ZONE 2- t1 PP : 0.40 sec
ZONE 2- t1 PE : 0.40 sec
ZONE 3- t1 PP : 0.80 sec
ZONE 3- t1 PE : 0.80 sec
ZONE 4- t1 PP : 1.20 sec
ZONE 4- t1 PE : 1.20 sec
Power Swing:

Set to Z2 and Higher Zones blocked and no trip during Power swing

Load Impedance and Load Angle Calculation

Maximam Load current = 603.611 A


120% of Maximam Load current = 724.330 A
Minimum Operating Voltage = 0.9 x Un
= 198000
= 198000 V
Load Impedance ZLoad = Umin / sqrt(3) x Imax
= 198000 / sqrt(3) x 724.33
RLoad Primary Ph-Ph = 157.82 Ohm
RLoad Secondary = 47.35 Ohm
RLoad Secondary = 47.35 ohm
Rload (Ph-Ph) = RLoad Secondary - Security Margin 10%
Rload (Ph-Ph) = 42.6150 Ohm

IE POLE OPEN / IMAX = 0.4


For the double circuit lines, Ph-E load impedance will be
Ratio between Healthy Line IE and Imax when parallel line with Single pole Open condition

THE RATIO FOR THE LINE LENGTH ABOVE 25KM = 0.4 (As per Manual)
THE RATIO FOR THE LINE LENGTH BELOW 25KM = 0.6

RL PRIMARY PH-E = RL PRIMARY/(1+((IE POLE OPEN/IMAX)*(1+(RE/RL))))


= 95.856 Ohm

RL SECONDARY PH-E = 28.757 Ohm


Rload (Ph-E) = Rload(PH-E) Secondary - Security Margin 10%
= 26 Ohm

Minimum Power Factor Cosφmin = 0.85


φmin = 31.78 deg
Set Load Angle = φmax + 5
= 31.78 + 5"
= 37.0 deg

Line Reactance per Unit Length X' = Positive Seq reactance * CTR/PTR

X' = 0.11997 Ohms

HIGH SPEED SOTF OVER CURRENT

SOTF CURRENT SETTING SHOULD BE SET 2.5 TIMES OF RATED CT CURRENT


OF THE FEEDER
RATED CURRENT PRIMARY = 600 A
RATED CURRENT SECONDARY = 1 A
SOTF CURRENT SETTING = 2.5 A
DIRECTIONAL EARTH FAULT
THE EARTH FAULT CURRENT SETTING IS CONSIDER 30% OF FULL LOAD CURRENT

EARTH FAULT CURRENT = 30% OF FULL LOAD CURRENT


= 180 A
= 0.30 A
RELAY MINIMUM CURRENT = 0.05 A
CORRESPONDING PRIMARY = 30 A
TIME DIAL
THE TIME DELAY SHOULD BE CHOOSEN GREATER THAN ZONE-3 DELAY.
WE KEPT ZONE 3 TIME DELAY IS 0.8 sec

SO WE KEEP THE TIME DELAY OF 1 SEC WITH SAFETY MARGIN.

ADOPTED CURVE = IEC NORMAL INVERSE

PRIMARY FAULT CURRENT = 50000 A


SECONDARY FAULT CURRENT = 83.333 A

THE IDMT CURVE SHALL SATURATE 20 TIMES OF PICKUP CURRENT.SO WE HAD TAKEN THIS
CURRENT FOR TMS CALCULATION
20 TIMES OF PICKUP CURRENT = 20*180 A
= 3600 A
TMS = 0.53
Directional Angle = -45˚

50BF - BREAKER FAILURE PROTECTION = 0.2 A

Ip> pickup setting = 0.1 Sec

T1 Delay after 1Pole start = 0.1 Sec

T1 Delay after 3Pole start = 0.2 Sec

T2 Delay os 2hd stage = Parallel with delay Time T1

T2 Start criteria

FUSE FAIL MONITORING

MEASURMENT SUPERVISION = ON
IF THE FUSE FAIL FUNCTION OPERATES, IT WILL BLOCK THE DISTANCE PROTECTION.
MINIMUM VOLTAGE THRESHOLD U> = 30 V
MAXIMAM CURRENT THRESHOLD I< = 0.1 A
MINIMUM VOLTAGE THRESHOLD U< = 15 V
DELTA CURRENT THRESHOLD = 0.1 A
VOLTAGE FAILURE SUPERVISION = WITH CURRENT SUPERVISION
DELAY VOLTAGE FAILURE SUPERVISION = 3 SEC
DIRECT TRIP SEND

DT SEND FOR OVER VOLTAGE STAGE-2 AND DEF

DIRECT TRIP RECEIVE = 0.02 Sec

TIME DELAY AFTER RECEIVED THE DT RECEIVE INPUT

OVERVOLTAGE PROTECTION- PH-PH


STAGE -1 = 110% OF NOMINAL VOLTAGE
STAGE -1 = 121 V
TIME DELAY = 5 Sec

STAGE-2 = 140% OF NOMINAL VOLTAGE


STAGE-2 = 154 V
TIME DELAY = 0.1 Sec

AUTO RECLOSING FUNCTION


79 Auto Reclosing Function = ON
52-Ready interrogation at 1st trip = ON
Reclaim time after successful AR cycle = 20 Sec
AR Blocking during after manual close = 1 Sec
Evolving fault recognition = With Trip
Evolving fault (during the dead time) = Starts 3pole Ar-cycle
AR start - signal monitering time = 0.2 Sec
Circuit breaker (CB) Supervision time = 3 Sec
Send delay for remote close command = oo
Maximum dead time extention = oo
Start od AR Allowed in this cycle = YES
Action time = 0.2 Sec
Deat time after 1pole trip = 1 Sec
Deat time after 3pole trip = 1 Sec
Deat time after evolving fault = 1 Sec
52-Ready interrogation before reclosing = NO
Request for synchro check after 3pole AR = NO
Start AR with 21 (Distance protection) = YES

SYNCHRONIZING SETTINGS
MINIMUM VOLTAGE LIMIT = 99 V (90% OF NOMINAL VOLTAGE)
MAXIMUM VOLTAGE LIMIT = 121 V (110% OF NOMINAL VOLTAGE)
THRESHOLD V1,V2 WITHOUT VOLTAGE = 5.5 V
THRESHOLD V1,V2 WITH VOLTAGE = 88 V (80% OF NOMINAL VOLTAGE)
SWITCHING AT SYNCHRONOUS CONDITION = YES
ON COMMAND AT V1< AND V2> = YES
ON COMMAND AT V1> AND V2< = YES
ON COMMAND AT V1< AND V2< = NO
MAXIMUM VOLTAGE DIFFERENCE = 11 V
MAXIMUM FREQUENCY DIFFERENCE = 0.1 Hz
MAXIMUM ANGLE DIFFERENCE = 10 Deg
RELEASE DELAY AT SYNCH CONDITIONS = 0 Sec

NOTE:
These settings are applicable if the protection is enabled only in the configuration
If the protection is disabled in the configuration menu please ignore.