QATAR PILLAR FIRE HYDRANT

Salwa Beach Resort ELANCIO DN100 PN16

TECHNICAL DATA SHEET


ABOVE GROUND PILLAR HYDRANT - TRAFFIC MODEL WITH PROTECTION HOOD - DN 100-PN16
Reinforced type

TCRFH 1/5
12/2012
QATAR PILLAR FIRE HYDRANT

Salwa Beach Resort ELANCIO DN100 PN16

TECHNICAL DATA SHEET


ABOVE GROUND PILLAR HYDRANT - TRAFFIC MODEL WITH PROTECTION HOOD - DN 100-PN16
Reinforced type
Item Description Unit Manufacturer's technical specifications

1 Manufacturer :
· Name · SAINT-GOBAIN PAM
· City / Country · Toul / FRANCE
· Manufacturer’s catalogue, pillar · ELANCIO VR DN 100
hydrant model :
· Type of fire hydrant : · Traffic model and dry barrel above ground
pillar hydrant, designed for a depth of cover of
1 meter, fitted with a hand wheel and sheltered
with a protection hood .
2 Applicable standards :
· Outlets complying with B.S.336
· Raised face flange to
EN 1092-2 PN16
ISO 7005-2 PN16
· Hydrostatic test according to ISO 5208:1993
· Comply to EN 14384
· CE Marking
3 Quantity and size :

· Size: DN 100
· Quantity as required (refer to BOQ)
4 Type of inlet connection :
· flanged inlet duck foot bend · DN 100 swivelling flange
drilled to ISO 7005 - 2 table 9 PN16

5 Pressure rating :

bar · 16

TCRFH 2/5
12/2012
QATAR PILLAR FIRE HYDRANT

Salwa Beach Resort ELANCIO DN100 PN16

TECHNICAL DATA SHEET


ABOVE GROUND PILLAR HYDRANT - TRAFFIC MODEL WITH PROTECTION HOOD - DN 100-PN16
Reinforced type
Item Description Unit Manufacturer's technical specifications

6 Hydrostatic test pressures :

· According to ISO 5208:1993

· Body test pressure bar · 25


· Seat test pressure bar · 17.6

7 Fire hydrant body outlets equipment :


· 2 fire hose couplings made of gunmetal to
EN 1982 grade CuSn5Pb5(old BS 1400 LG2),
complying with B.S. 336 and consisting of :
Þ 2 side outlets of size 2 1/2 inches :
instantaneous female fire hose coupling with
a gunmetal cap.

8 Materials of construction :

· Upper body · Ductile iron complying with


EN 1563, ISO 1083
· Valve box / duckfoot bend · Made in one single casting, in ductile iron
complying with EN 1563, ISO 1083
· Underground barrel (tube) · Ductile iron complying with EN545
· Bearing · Aluminium bronze to EN 1982 grade Cu Al
Ni3 Fe2 with two EPDM O-ring
· Upper spindle (drive shaft) and · Stainless steel to EN 10088-3
lower spindle (operating stem) grade X2CrNiMo17-12-2 material 1.4404
316L
· Operating stem-nut · Gunmetal to EN 1982 grade CuSn5Zn5 Pb5
· Main valve shutter · Ductile iron, fully EPDM rubber encapsulated
(with non-toxicity certificate)
· Valve seat ring · Gunmetal to EN 1982 grade CuSn6Zn4Pb2
· Hood / protection cover · Made of Composite Fibbers Glass Reinforced
Polyester

· Protected with a Red polyurethane + varnish

TCRFH 3/5
12/2012
QATAR PILLAR FIRE HYDRANT

Salwa Beach Resort ELANCIO DN100 PN16

TECHNICAL DATA SHEET


ABOVE GROUND PILLAR HYDRANT - TRAFFIC MODEL WITH PROTECTION HOOD - DN 100-PN16
Reinforced type
Item Description Unit Manufacturer's technical specifications

9 Surface protection :
· Inside and outside, upper and lower body of
pillar hydrant
· Non-toxic fusion bonded epoxy powder coating
· Coating material
· Upper and lower body of pillar hydrant :
· Dry film thickness
local thickness : minimum of 300µm.
Definition of local thickness :
see factory coating check plan
· Excluded areas :
swivelling flange, upper body/lower body bolting
holes
local thickness : minimum of 150µm
· Refer factory coating check plan
· Yes for epoxy in permanent contact with water
· Non-toxicity certificate

10 Pillar hydrant marking :


· Nominal diameter : DN 100
· Cast on body and cover :
· An arrow indicating opening direction
· Number of turns to open : 13
· Manufacturer’s logo
· Manufacturing references
· On engraved aluminium label , glued
on body, protected with cover
· An arrow indicating opening direction
· Cast on handwheel :
· Number of turns of operation : 13
· Manufacturer’s logo
11 Rate of flow :
· Conforms to the European Standards EN
14384 and CE marking
=> Minimum flow rate :
140 m3/h taken at the two outlets 2”1/2
for 1 bar headloss through the pillar hydrant
12 Valve packing :
· Wooden crates

TCRFH 4/5