Manufacturring List
Manufacturring List
Manufacturring List
1 POWER TRANSFORMERS
ABB Bilbao SPAIN-Bilbao Yes Based on TS&SD letter# 09-F01546/03-03032301 dated 19th.
Aug 2009, it is pre-qualified for Power Transformer up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:
BEST TURKEY-Balikesir (ASB Factory) Yes Based on TS&SD Letter # 06-789-03032300 dated July 25,
2006, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
Page 1 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
CG Electric Systems Zrt. (previously GANZ HUNGARY-Budapest Yes Based on TS&SD Letter 11-01981-1-03032301 dated July 11,
Transelektro Electric Co., Ltd.) 2011, it is pre-qualified for Power Transformers rated up to
132kV/100MVA as conforming to SEC Specification #
53-TMSS-01, Rev.0, with the following condition:
CROMPTON GREAVES INDIA Yes SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
GETRA Power S.P.A ITALY-Marcianise (CE) Yes Based on S&SD Letter # 14-04523-01-03504401 dated 7th July
2014, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes
Page 2 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ILJIN Electric Co. Ltd. SOUTH KOREA-- Yes Based on S&SD Letter 12-03077-30504401 dated September
15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is pre-qualified for
Power Transformers 33kV & 34.5kV rated up to 30MVA as
conforming to SEC Specification # 53-TMSS-01, Rev.0, with the
following conditions:
Koncar D&ST Inc. CROATIA-Zagreb Yes Based on S&SD Letter # 14-03217-1-30504401 dated May 18,
2014, it is pre-qualified for Power Transformer up to 67MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
Page 3 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Koncar Power Transformers Ltd. CROATIA-Zagreb Yes Based on S&SD Letter # 14-08041-01-03504401 dated
13/02/2014 & 14-08041-02-03504401 dated 25/03/2014, it is
pre-qualified for Power Transformer up to 100MVA, 132kV as
confirming to National Grid SA specification # 53-TMSS-01,
Rev.01 with the following conditions:
Page 4 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
PJSC Zaporozhtransformator (ZTR) Ukraine-Zaporizhia Yes Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Power Transformers rated up to
100 MVA, 132 kV as conforming to National Grid SA specification
# 53-TMSS-01, Rev.01, with the following conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements together (with
Thermal & Dynamic short-circuit calculations per IEC 60076-5)
shall be carried out on the next unit to be supplied to SEC/
National Grid SA in an Accredited Testing Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-2261 dated August 15,
2011.
Page 5 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Schneider Enerji Endustrisi San VE TIC A.S TURKEY-Cayirova-Kocaeli Yes Based on S&SD letter# 14-02364-1-30504401 dated April 01,
2014, it is pre-qualified for Power Transformers up to 67 MVA,
132 kV conforming to National Grid SA specification
53-TMSS-01, Rev. 01, with the following conditions:
Total = 31
1 .2 69 KV PRIMARY
Page 6 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB Bilbao SPAIN-Bilbao Yes Based on TS&SD letter# 09-F01546/03-03032301 dated 19th.
Aug 2009, it is pre-qualified for Power Transformer up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:
BEST TURKEY-Balikesir (ASB Factory) Yes Based on TS&SD Letter # 06-789-03032300 dated July 25,
2006, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 7 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
GETRA Power S.P.A ITALY-Marcianise (CE) Yes Based on S&SD Letter # 14-04523-01-03504401 dated 7th July
2014, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
Page 8 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ILJIN Electric Co. Ltd. SOUTH KOREA-- Yes Based on S&SD Letter 12-03077-30504401 dated September
15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is pre-qualified for
Power Transformers 69kV rated up to 67 MVA as conforming to
SEC Specification # 53-TMSS-01, Rev.0, with the following
conditions:
Koncar D&ST Inc. CROATIA-Zagreb Yes Based on S&SD Letter # 14-03217-1-30504401 dated May 18,
2014, it is pre-qualified for Power Transformer up to 67MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
Page 9 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Koncar Power Transformers Ltd. CROATIA-Zagreb Yes Based on S&SD Letter # 14-08041-01-03504401 dated
13/02/2014 & 14-08041-02-03504401 dated 25/03/2014, it is
pre-qualified for Power Transformer up to 100MVA, 132kV as
confirming to National Grid SA specification # 53-TMSS-01,
Rev.01 with the following conditions:
Page 10 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
PJSC Zaporozhtransformator (ZTR) Ukraine-Zaporizhia Yes Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Power Transformers rated up
to100 MVA, 132 kV as conforming to National Grid SA
specification # 53-TMSS-01, Rev.01, with the following
conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements together (with
Thermal & Dynamic short-circuit calculations per IEC 60076-5)
shall be carried out on the next unit to be supplied to SEC/
National Grid SA in an Accredited Testing Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-2261 dated August 15,
2011.
Page 11 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Schneider Enerji Endustrisi San VE TIC A.S TURKEY-Cayirova-Kocaeli Yes Based on S&SD letter# 14-02364-1-30504401 dated April 01,
2014, it is pre-qualified for Power Transformers up to 67 MVA,
132 kV conforming to National Grid SA specification
53-TMSS-01, Rev. 01, with the following conditions:
TOSHIBA CORPORATION, T&D JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total = 33
Page 12 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB Bilbao SPAIN-Bilbao Yes Based on TS&SD letter# 09-F01546/03-03032301 dated 19th.
Aug 2009, it is pre-qualified for Power Transformer up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:
ALSTOM Grid TURKEY-Gebze Yes Previously AREVA T&D-Turkey [The name has been changed
based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].
AREVA GERMANY Yes
BEST TURKEY-Balikesir (ASB Factory) Yes Based on TS&SD Letter # 06-789-03032300 dated July 25,
2006, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
Page 13 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
BEST TURKEY-Balikesir (OSB Factory) Yes Based on S&SD Letter # 14-07386/03-030504401 dated
December 21, 2014, it is pre-qualified for Power Transformer up
to 133MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-02, Rev.01 with the following
conditions:
CROMPTON GREAVES INDIA Yes SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD.
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 14 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
GETRA Power S.P.A ITALY-Marcianise (CE) Yes Based on S&SD Letter # 14-04523-01-03504401 dated 7th July
2014, it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes
Page 15 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Hyundai Heavy Industries Co. Bulgaria Bulgaria-Sofia Yes Based on TS&SD letter # 11-00438-03-03032301 dated
15/05/2011, it is prequalified for Power Transformers up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, Rev.0 with the following conditions:
Page 16 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Koncar D&ST Inc. CROATIA-Zagreb Yes Based on S&SD Letter # 14-03217-1-30504401 dated May 18,
2014, it is pre-qualified for Power Transformer up to 67MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
Page 17 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Liaoning - Efacec Electrical Equipment Co., Ltd CHINA-Liaoning Province Yes SUSPENDED for all SEC/National Grid SA ongoing and
(LEEEC) forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.
PJSC Zaporozhtransformator (ZTR) Ukraine-Zaporizhia Yes Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Power Transformers rated up to
100MVA, 132 kV as conforming to National Grid SA specification
# 53-TMSS-01, Rev.01, with the following conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements together (with
Thermal & Dynamic short-circuit calculations per IEC 60076-5)
shall be carried out on the next unit to be supplied to SEC/
National Grid SA in an Accredited Testing Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-2261 dated August 15,
2011.
Page 18 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SC ELECTROPUTERE SA Romania-Craiova Yes Based on TS&SD letter # 11-002054-1-03032300
dated10/7/2011, it is prequalified for Power Transformer up to
132kV, 100MVA, as conforming to National Grid SA specification
# 53-TMSS-01, Rev.0 with the following condition:
Page 19 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SIEMENS AG (NURNBERG) GERMANY-NURNBERG Yes
Total = 37
1 .4 230 KV PRIMARY
Page 20 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB Elektrik Sanayi A.S. [previously ABB ESAS] TURKEY-Istanbul/Kartal Yes Based on S&SD letter# 14-02898/03-030504401 dated June
17, 2014, it is pre-qualified for Power Transformer up to 380kV,
250MVA as confirming to National Grid SA specification #
53-TMSS-02, Rev.01 with the following conditions:
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HAWKER SIDDELEY United Kingdom Yes
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 21 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on TS&SD fax#09-F01255/02-03032301 dated 25th.
July 2009, it is pre-qualified for Power Transformer up to
380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
• All type, design, special & routine tests as per SEC
specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the presence of
three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.
• Seven (7) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
HYUNDAI KOREA, Republic of-Ulsan Yes
ILJIN Electric Co. Ltd. SOUTH KOREA-- Yes Based on S&SD Letter 12-03077-30504401 dated September
15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is pre-qualified for
Power Transformers 230kV rated up to 166.7MVA only as
conforming to SEC Specification # 53-TMSS-02, Rev.0, with the
following conditions:
Page 22 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Siemens AG (Dresden) GERMANY-Dresden Yes based on TS&SD letter# 09-01501-03032301 dated 25th May
2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0 with
the following conditions:
• All type, special & routine tests for each voltage class as
per SEC specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the presence
of three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
SIEMENS AG (NURNBERG) GERMANY-NURNBERG Yes
Total = 20
1 .5 380KV PRIMARY
Page 23 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB Cordoba SPAIN-Cordoba Yes Based on TS&SD letter# 09-F011657/03-03032301 dated
August 16, 2009. It is pre-qualified for Power Transformer up
to 380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
Page 24 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ALSTOM Grid TURKEY-Gebze Yes First Unit to be Type Tested in the presence of 3 SEC Engineers
& 1 SEC approved Independent Inspector; Extended Warranty
of Six years.
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HAWKER SIDDELEY United Kingdom Yes
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on TS&SD fax#09-F01255/02-03032301 dated 25th.
July 2009, it is pre-qualified for Power Transformer up to
380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
• All type, design, special & routine tests as per SEC
specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the presence of
three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.
• Seven (7) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
HYUNDAI KOREA, Republic of-Ulsan Yes
MITSUBISHI JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total = 16
Page 25 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on TS&SD letter # 11-03272-03032301 dated
16/11/2011 and S&SD letter # 14-02494-01-30504401 dated
24/04/2014, it is prequalified for Station Service Transformer up
to 2.5MVA as conforming to SEC/National Grid SA specification
# 51-TMSS-01, Rev.01 with the following condition:
KONCAR D&ST Croatia/Hrvatska Yes UP TO 2.5 MVA. Complete Type, Routine / Sample tests for first
order & 10 Years Warranty from the date of PAC is required.
Saudi Federal Transformers L.L.C. Saudi Arabia-Riyadh Yes Based on S&SD Letters# 12-01572-2-30504401 dated May 27,
2012 & 13-06464-1-30504401 dated December 11, 2013, it is
pre-qualified for Power Transformers rated up to 36KV & 2MVA
as confirming to SEC Specification # 51-TMSS-01, Rev.0, with
the following condition:
United Transformers Electric Co. (UTEC) Saudi Arabia-Riyadh Yes Prequalified up to 2.5 MVA
Total = 8
Page 26 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
* --- Yes ALL APPROVED POWER TRANSFOREMER MANUFACTURERS,
EXCEPT DISTRIBUTION TRANSFORMER MANUFACTURERS ARE
ALSO ACCEPTABLE FOR GROUNDING TRANSFORMERS
ABB United States Yes
CROMPTON GREAVES INDIA Yes SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD
Total = 9
4 .1 36 KV PRIMARY
Total = 3
5 COMPACT SUBSTATION
Total = 2
5. 2. 1 UNIT SUBSTATION, 110 - 132 KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY Applicable Standards:
Page 27 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB ( T& D) United States-N/A Yes
Total = 1
6 REACTOR
ALSTOM Grid TURKEY-Gebze Yes Previously AREVA T&D-Turkey [The name has been changed
based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].
AREVA_(ST. QUEN) FRANCE-(ST. QUEN) Yes
CG Power Systems Belgium NV BELGIUM-Mechelen Yes Based on S&SD letter# 14-08521-2-30504401 dated December
10, 2014, it is pre-qualified for Shunt Reactors rated up to
132kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.1, with the following conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements [excluding Short
circuit test ] shall be carried out on the first unit to be supplied
to SEC/National Grid SA in the manufacturer Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter #Nil dated November 10,
2012.
Page 28 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
Page 29 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
PJSC Zaporozhtransformator (ZTR) Ukraine-Zaporizhia Yes Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Shunt Reactors rated up to 132
kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.0, with the following conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements shall be carried
out on the first/next unit to be supplied to SEC/National Grid SA
in an Accredited Testing Laboratory in the presence of three (3)
National Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was confirmed
in writing by the manufacturer through their letter 1/115-3553
dated December 14, 2011.
Total = 14
ALSTOM Grid TURKEY-Gebze Yes Previously AREVA T&D-Turkey [The name has been changed
based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].
AREVA_(ST. QUEN) FRANCE-(ST. QUEN) Yes
Page 30 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
CG Power Systems Belgium NV BELGIUM-Mechelen Yes Based on S&SD letter# 14-08521-2-30504401 dated December
10, 2014, it is pre-qualified for Shunt Reactors rated up to
132kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.1, with the following conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements [excluding Short
circuit test ] shall be carried out on the first unit to be supplied
to SEC/National Grid SA in the manufacturer Laboratory in the
presence of three (3) National Grid SA Engineers & one (1)
National Grid SA approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter #Nil dated November 10,
2012.
Page 31 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
Page 32 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
PJSC Zaporozhtransformator (ZTR) Ukraine-Zaporizhia Yes Based on S&SD letter# 13-07568-30504401 dated December
31, 2013, it is pre-qualified for Shunt Reactors rated up to
132kV as conforming to National Grid SA specification #
58-TMSS-01, Rev.0, with the following conditions:
• All Type, Special & Routine tests as per latest National Grid SA
Specifications/Standards & IEC requirements shall be carried
out on the first/next unit to be supplied to SEC/National Grid SA
in an Accredited Testing Laboratory in the presence of three (3)
National Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was confirmed
in writing by the manufacturer through their letter 1/115-3553
dated December 14, 2011.
Total = 14
ALSTOM Grid TURKEY-Gebze Yes Previously AREVA T&D-Turkey [The name has been changed
based on S&SD/P&SFD letter # 12-01064-30504401 dated
March 14, 2012].
AREVA_(ST. QUEN) FRANCE-(ST. QUEN) Yes
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 33 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
Total = 12
Page 34 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB SWEDEN Yes
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 35 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National Grid
SA specification # 58-TMSS-01, Rev.01 with the following
conditions:
Total = 12
Page 36 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Page 37 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
TRENCH CANADA CANADA-Scarborough, Ontario Yes Based on TS&SD letter 10-01317-1-03032301 dated May 10,
2010. TRENCH CANADA is pre-qualified for Air Core Series
Reactors as confirming to SEC Specification 58-TMSS-02, Rev.0
with the following conditions:
• Extended Warranty: Seven (7) years Extended Warranty
shall be applicable for the Air Core Series Reactors to be
supplied to SEC by TRENCH CANADA as confirmed through their
letter # NIL dated April 28, 2010.
• Test Witnessing: Factory Tests on the first batch of Air Core
Series Reactors to be supplied to Contract # 20931030/00 for
Taif BSP & Kayber/Bawat S/S shall be conducted in presence of
three (3) SEC Engineers and one (1) IIA Inspector, under the
sole expense of the Manufacturer as confirmed through their
Letter # NIL dated April 27, 2010.
• Free Replacement: TRENCH CANADA shall supply one
complete three phase set of Reactors (3 units) to SEC (Tabouk
City) free of charge as already confirmed through their letter #
NIL dated November 06, 2009.
Total = 4
Power Economy Middle East Co. United Arab Emirates-Abu Dhabi Yes Limited to 34.5kV Only; First unit of 34.5kV Air Core Reactor
shall be type tested in an independent lab. in the presence of 3
SEC Engineers & 1 SEC Approved Independent Inspection
Agency; 10 years of Extended Warranty.
Total = 2
7 SWITCHGEARS
Page 38 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB/AEIL Saudi Arabia Yes For 33kV AIS:
classic ZS3 type with current rating up to 2500A@ 40°C; CB
type VD43620-25(2000A), VD43612-25(1250A & 800A); ES
type EK5, 3007N280.
• Out Going Feeder (CT on lower side of CB) with rated current
991A and 648A @ 40°C, 60Hz, 25kA (3s).
• All VD4 Poles and Interrupters are from ABB Calor Emg,
Germany (DECMS).
Page 39 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
AEL -SIEMENS Saudi Arabia-JEDDAH Yes For 13.8kV AIS:
type 8BK20 with CB type 3AH.
for 33kV AIS:
type 8BT2 is not acceptable, as the VT is situated in a separate
compartment and connected by cable.
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on TS&SD letter# 09-02613-01-03032301 dated 13th
September 2009, ALFANAR ELECTRICAL SYSTEMS from Saudi
Arabia-Riyadh for 13.8kV Switchgear type NES-H with degree
protection IP4X; vacuum CB (rating 3150A & 1250A) and ES
from LSIS (South Korea) - details of types are mentioned in the
TS&SD letter; as confirming to SEC specification # 32-TMSS-01,
rev.0 with the following condition:
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.
ELEKTROBUDOWA SA Poland-Konin Yes based on TS&SD letter# 09-01092-03032301 dated 18th. April
2009 it is prequalified for for 13.8kV Air Insulated Switchgear
type D-17P with SCC of 25kA/3sec, degree of protection IP4X
and rated current of 3000A @ 40oC, 60Hz; CB type VD4 which
approved by SEC from ABB-Germany (3000A) & ABB-Italy
(2500A); ES type UMR from ELECTROBUDOWA SA-Poland as
confirming to SEC specification # 32-TMSS-01, rev.0 with Ten
(10) years warranty from the date of PAC of the Turnkey
project in case of contract award or date of delivery in case of
direct material supply order.
Page 40 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
EPS LTD. (GROUPE SCHNEIDER) Saudi Arabia-RIYADH Yes For 13.8kV AIS:
Pre-qualified since 24/02/1420H for 13.8kV SWG type MC-Set
with CB type LF3-3150-(2500A), LF2- 2500 (2000A), LF2-1250
(800A), LF2-630 (400A) and warranty of (7)years from
commissioning date of the first delivery for any onward project
or order in the first two years and then shall be (3)years from
PAC.
Old version:
33kV AIS type F400G with current rating up to 2500A @ 40°C
with CB type SF & SF2
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
KONCAR Croatia/Hrvatska Yes LIMITED TO DTA ONLY; FOR CTA PREQUALIFICATION UNDER
PROGRESS
MITSUBISHI JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
POWER CON United States Yes SWITCHGEAR NOT YET TYPE TESTED
TOSHIBA CORPORATION, T&D JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Page 41 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Total = 19
New Version:
Based on TS&SD letter # 11-00455-5-03032301 dated April 04,
2011, the new version 145kV GIS type ELK-04 with CB type
ELK-CB0 (Hydraulic Spring Mech. HMB-1), DS type
ELK-DE0-3POS, MES type ELK-DE0, HSES type ELK-ES0 (Motor
Spring Mech.) is pre-qualified as conforming to SEC specification
# 32-TMSS-02, Rev.01 with the following condition:
•Ten (10) Years Extended Guarantee/Warranty from the date
of PAC of project (in case of contract award) and from date of
delivery for the direct material supply order. This was confirmed
in writing by ABB Germany via their letter # PTPH/GVS.Nb,
10_year-warranty.doc dated May 14, 2010.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES
ABB SWITZERLAND Yes CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
Page 42 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ALSTOM Grid AG SWITZERLAND-Oberentfelden Yes New version:
Based on S&SD letter# 13-4433-01-30504401, dated 16
January 2013, it is pre-qualified for 145kV GIS type F35 with
rated current, 3150A @40°C, 60Hz, CB type- F35-CB4 / Opr.
Mech: FK3-2 (spring charged), Line & Busbar DS-F35-DES-4/
Opr. Mech: ME1-3, MES-F35-DES-4/ Opr. Mech: ME1-3,
HES-F35-EFZ/Opr. Mech:MF-3 (spring charged), CT-F35-CT4,
against specification # 32-TMSS-02, Rev.1 with the following
condition:
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES
Old Version:
145kV GIS type B65 with CB type B65-CB Motor spring
mechanism; DS type B65-DS; ES type B65-ES; HES type
B65-EF.
Old version:
145kV GIS type SDA5 (SDA514) with CB type BAK5, Hydraulic
mechanism.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
Page 43 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES
Page 44 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYUNDAI KOREA, Republic of-Ulsan Yes New version: 145kV GIS type 145SP-1 with CB type 145SP-K1
Motor spring mechanism; BDS type 145SP-3PS1; LDS type
145SP-3PS2; MES type 145-3PS2; HES type 145SP-LES2.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: NO
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
KONCAR Croatia/Hrvatska Yes GIS & ADAPTORS; LIMITED TO DTA ONLY; FOR CTA
PREQUALIFICATION UNDER PROGRESS
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
LS Industrial System Co. SOUTH KOREA-Cheongju Yes Based on S&SD letter# 13-07921-2-30504401 dated January
06, 2014,it is pre-qualified for 145kV GIS type GESG-1440NHS
with rated current, 3150A, 60Hz, CB type- GEDB-1440NHS /
Opr. Mech. Type: GGA204155 (spring charged), LDS type-
GESG 1440-ACSF/ Opr. Mech: Motor, BDS type-GESG
1440-ACSB / Opr. Mech: Motor, MES type- GESG 1440-ACSB/
Opr. Mech: Motor, HES type- GESG 1440-MSES /Opr. Mech:
Motor spring & CT- JK GIS, against specification # 32-TMSS-02,
Rev.1 with the following condition:
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES
Page 45 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
MITSUBISHI JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
New version 145kV GIS type 100GMKD with CB type
120-SFMT-40CJ; DS type 120GRD/GLD; MES type
120GRED/GRE; HES type 120 GRED/GRE-A.
Old version: 145kV GIS 120GMKM with CB type 120-SFMT-40,
Pneumatic mechanism; DS type 120-GR-20,
120-GL-20; MES type 120-GRE, 120-GREC; HES type
120-GREA.
Old version: 145kV GIS 100GMKD with CB type 120-SFMT-40CE
Motor spring mechanism; DS type 120GLD; HES type 120-GREA.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: NO
SIEMENS FRANCE-GRENOBLE Yes New version:
145kV GIS type TH7m with CB type TH7m AF8ER(Motor spring);
BDS type CM002, CM003 (3-position); LDS type CM002, CM003
(2-position); MES type CM002,CM003; HES type CM002,
CM003.
Old version: 145kV GIS type HEXABOLIC-TH7 with CB type
DTH7 Hydraulic mechanism; BDS type SITH7; LDS type ITH7, SI
TH7; ES type ST TH7.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
SIEMENS GERMANY Yes New version: 145kV GIS type 8DN8-II with CB type 8DN8 Motor
spring mechanism; DS type 8DN8; ES type 8DN8.
Old version: 145kV GIS type 8DN8 with CB type 8DN6(P1)
Motor spring mechanism; DS type 8DN8; ES type 8DN8.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
TOSHIBA CORPORATION, T&D JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
145kV GIS type with CB type GSPK-145AP; BDS type
KTM-120PW, DTM-120PW, DLM-120PW; LDS type KTM-120PW,
DTM-120PW; MES type EBM-120W; HES type EAP-120W.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
Total = 13
Page 46 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB SWITZERLAND Yes Based on S&SD letter # 14-00064-30504101 dated January 26,
2014 and ABB Letter # PPHV-300GIS CH-05 dated February 02,
2014, the designation has been corrected to the following:
Old Designation:
230kV GIS Type: ELK-1, CB Type: ELK SP2-1.
ALSTOM Grid SAS FRANCE-AIX-LES BAINS Yes 230kV GIS type B105 with CB type B105-CB; DS type CLT
Previously "AREVA T&D– FRANCE-(AIX-LES BAINS) ", the name
has been changed to ALSTOM Grid SAS-France based on
ALSTOM Grid-France letter # Nil, dated December 07, 2012.
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 47 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SIEMENS GERMANY-Berlin Yes Based on S&SD letter # 13-05708-1-30504401, dated October
10, 2013, it is pre-qualified for 245kV GIS type 8DN9 with rated
current, 3150A @40°C, 60Hz, CB type- 8DN9-245kV-50kA/Opr.
Mech: spring charged, Line & Busbar
DS-8DN9-245kV-50kA/Opr. Mech: Motor,
MES-8DN9-245kV-50kA/Opr. Mech: Motor,
HES-8DN9-245kV-50kA/Opr. Mech: spring charged, as
conforming to National Grid SA specification # 32-TMSS-02,
Rev.01, with the following conditions:
New Version
Based on TS&SD letter # 11-00267/01-03032301 dated
02/02/2011, it is pre-qualified for 300kV GIS type 8DN9, rated
current 4000A, short time current rating of 63kA, CB (Single
Break) type 8DN9-300-63-4000 with motor spring mechanism,
Busbar & line DS type 8DN9-300-63-4000 with motor drive
mechanism, MES type 8DN9-300-63-with motor drive
mechanism & HES type 8DN9-300-63-4000 with motor drive
mechanism as confirming to SEC specification #
32-TMSS-02,Rev.01, with the following conditions:
TOSHIBA CORPORATION, T&D JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total = 9
Page 48 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB SWITZERLAND Yes Based on S&SD letter # 13-00748-30504101 dated November
06, 2013, it is pre-qualified for 420 kV GIS type ELK-3/420
(1HC0071250M0070) @ 4000A, 60Hz, CB type ELK-SP3/420,
Operating Mechanism-HMB8, Line & Busbar DS type
ELK-TK3/420, Operating Mechanism-ELK-BAC, MES type
ELK-TK3/420, Operating Mechanism-ELK-BAC, HES type
ELK-EB3 420, Operating Mechanism-ELK-BAE, CT type ELK-CN3,
Cable compartment type ELK-HK3.
HYBRID GIS:
Base on S&SD letter # 14-03182-01-30504401, dated
29-01-2015, Pre-qualified ABB, Switzerland GIS type ELK-3/420
(1HC0071250M0070) with its components are acceptable for
Hybrid GIS up to current rating @ 3150A, 55°C, 60Hz.
ALSTOM Grid SAS FRANCE-AIX-LES BAINS Yes 420kV GIS type T155 with CB type FB2T (Hydraulic Mech.)
Previously "AREVA T&D– FRANCE-(AIX-LES BAINS) ", the name
has been changed to ALSTOM Grid SAS-France based on
ALSTOM Grid-France letter # Nil, dated December 07, 2012.
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
Page 49 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on TS&SD letter # 10-F-02299/02-03032301 dated
25/10/2010, it is pre-qualified for 420kV GIS type HSG 426A,
63kA, CB (Single Break) type HCHY 426A with Hydraulic
Mechanism, Busbar DS type HDMO 426A, Line DS type HDMO
426B,ES type HEMO 426A&H-ES type HEMS 426A as
confirming to SEC specification # 32-TMSS-02,Rev.01, with the
following conditions:
SIEMENS FRANCE-GRENOBLE Yes 420kV GIS type YGII with CB type SPD; DS ype YGII
Page 50 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SIEMENS GERMANY Yes New version:
550kV GIS type 8DQ1 with CB type 8DQ1-P2; DS type 8DQ1;
ES type 8DQ1. with the following conditions:
HYBRID GIS:
Base on S&SD letter # 15-05204-01-30504401, dated
28-01-2015, Pre-qualified Siemens, Germany 550kV GIS type
8DQ1 with its components are acceptable for Hybrid GIS up to
current rating 3150A, 55 °C, 60Hz.
Old version:
420kV GIS type 8DQ1 with CB type 8DQ1-T2, DOUBLE BREAK,
Hydraulic mechanism; DS type 8QD1
Page 51 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Siemens AG GERMANY-Berlin Yes Based on S&SD letter# 14-00569-2-30504401 dated February
09, 2014,it is pre-qualified for 420KV GIS, type 8DQ1-6, 63KA,
Single Break with rated current 4000A, 60Hz, CB type-8DQ1
6-P1 (Single break)/ Opr. Mech. Type: Spring type (FA5), LDS
type- 8DQ1 6 DS / Opr. Mech: Motor, BDS type-8DQ1 6 DS /
Opr. Mech: Motor, MES type- 8DQ1 6 ES / Opr. Mech: Motor,
HES type- 8DQ1 6 HSES /Opr. Mech: Motor spring & CT- 8DQ1
6 against specification # 32-TMSS-02, Rev.1 with the following
condition:
HYBRID GIS:
Base on S&SD letter # # 15-05204-01-30504401, dated
28-01-2015, Pre-qualified Siemens, Germany 420 kV GIS type
8DQ1-6 with its components are acceptable for Hybrid GIS up
to current rating 3150A, 55 °C, 60Hz.
Page 52 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
TOSHIBA CORPORATION, T&D JAPAN-- Yes Based on S&SD letter # 14-05807-2-30504401, dated
September 08, 2014, it is pre-qualified for 420 kV GIS type GID,
Rated current 3150A @ 40 °C, 60Hz, 63kA (1s).
Total = 11
Page 53 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB SWITZERLAND Yes Based on S&SD letters 14-00741-30504101dated December 08,
2014 & 14-00043-30504101, dated January 20, 2015, it is
pre-qualified for 550 kV GIS type ELK-3/550
(1HC0071250M0100) @ 4000A, 40 °C, 60Hz, CB type
ELK-SP3/550 (1HC0071250M0100), Operating Mechanism-HMB8
(1HC0071250M0100), Busbar DS type ELK-
TE3/550(1HC0071250M0100), Operating
Mechanism-DH(1HC0071250M0100), Line disconnector type
ELK-TV3/550(1HC0071250M0100), Operating
Mechanism-DH(1HC0071250M0100), MES type
ELK-EM3/550(1HC0071250M0100), Operating
Mechanism-DH(1HC0071250M0100), HES type
ELK-EB3/550(1HC0071250M0100), Operating
Mechanism-DB(1HC0071250M0100), Cable compartment type
ELK-HK3/550(1HC0071250M0100) as confirming SEC
Specification 32-TMSS-02, Rev.01 with following condition:
Page 54 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
HYOSUNG (HICO) KOREA, Republic of-Changwon Yes Based on S&SD letters 14-00743-30504101 dated December
08, 2014 & 14-00783-30504101, dated 23 December, 2014, it
is pre-qualified for 550 kV GIS type 550 HSG @ 4000A, 40 ? C,
60Hz, CB type 550 SPR50, Operating Mechanism-HOM-110,
Busbar and Line DS type 550 SDSV, Operating
Mechanism-Motor/DYA0400134, MES type 550 SESM, Operating
Mechanism-Motor DYA0400134, HES type 550 HESA, Operating
Mechanism-Motor-Spring/DYA0400133, Cable compartment
type as confirming SEC Specification 32-TMSS-02, Rev.01 with
following conditions:
Total = 3
Page 55 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SIEMENS GERMANY Yes Based on S&SD letter # 15-0186-01-30504401, dated January
22, 2015 and TS&SD Letter # 10-02461-02-03032301, dated
August 31, 2010, the manufacturer is prequalified for 36kV GAS
Insulated Medium Voltage SWGR Type 8DA10, rated current
2500A @ 40°C, 60Hz and short time current rating of
25kA(3sec),
Total = 1
8 BATTERY EQUIPMENT
ENERSYS S.A.R.L. FRANCE-- Yes PREVIOUSLY KNOWN AS HAWKER S.A.R.L - FRANCE; FIVE
YEARS OF EXTENDED WARRANTY
EXIDE United States Yes
Page 56 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
YUASA JAPAN Yes
Total = 12
8. 2. 0 BATTERY LEAD ACID, VALVE REGULATED LEAD ACID (VRLA) Applicable Standards: 46-TMSS-04
AEG Power Solutions SAS FRANCE-- Yes originally was SAFT Power System SAS-France
Total = 11
Emerson Network Power Industrial Systems FRANCE-Lyon Yes Previously "CHOLORIDE ", the name has been changed to
Emerson Network Power Industrial Systems - France based on
Emerson Network Power Industrial Systems letter # nill dated
12/04/2013.
EMISA SPAIN Yes
GAZ Gerate- und Akkumulatorenwerk Zwickau GERMANY-Zwickau Yes Based on TS&SD fax ref.#08-F02675/03-03032301 dated
GmbH 10/01/2009. Pre-Qualified for Nicd Battery with this conditions:
-First batch shall be type tested in Independent Laboratory iin
presence of (3) SEC engineers & (1) independent inspector.
-(07) years warranty
Page 57 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
GNB United States Yes
Total = 9
8 .4 BATTERY CHARGER
AEG Power Solutions SAS FRANCE-- Yes Originally was SAFT Power System SAS-France
Benning Elektrotechnik & Elektronik GmbH & GERMANY-- Yes Previously "Theo-Benning-Germany", the name has been
Co.kG. changed to Benning Elektrotechnik & Elektronik GmbH & Co. KG
-Germany based on TS&SD/ESD letter # 11-00334-03032301
dated 30/01/2011.
BORRI S.P.A ITALY-Arezzo Yes Based on S&SD Letter # 14-03226-01-030504401 dated June
4, 2014, it is pre-qualified for Battery Charger (125VDC, Type
RTB.e) as conforming to National Grid SA specification #
46-TMSS-02, Rev.0 with the following conditions:
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order. This has been confirmed in writing
by the manufacturer through letter # Nil dated May 23, 2011.
BRAGA MORO ITALY Yes Based on S&SD Letter 12-03794-01-30504401 dated November
18, 2012, Braga Moro- Italy is pre-qualified for Battery
Chargers 125V DC as conforming to National Grid SA
Specification # 46-TMSS-02, Rev.0, with the following
conditions:
Page 58 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
C&D United States Yes
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order
Emerson Network Power Industrial Systems FRANCE-Lyon Yes Previously "CHOLORIDE ", the name has been changed to
Emerson Network Power Industrial Systems - France based on
Emerson Network Power Industrial Systems letter # nill dated
12/04/2013.
Emerson Network Power Industrial Systems FRANCE-Lyon Yes Previously "AEES ", the name has been changed to Emerson
Network Power Industrial Systems - France based on Emerson
Network Power Industrial Systems letter # nill dated
12/04/2013.
EMISA (ELECTRO MERCANTIL INDUSTRIAL SPAIN Yes
S.A. SPAIN)
ERSKINE United Kingdom Yes
JESUS MARIA AGUIRRE SA (JEMA) SPAIN-Lasarte-Oria Yes Based on S&SD Letter 12-00193-030504001 dated January 17,
2012. It is prequalified for Battery Charger as conforming to
SEC Specification# 46-TMSS-02, Rev.0 with the following
conditions:
•All Type, Routine and Special testes shall be carried out on the
first batch of each types of Battery Chargers in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated June 17, 2011.
Page 59 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Statron AG SWITZERLAND-Maegenwil Yes Based on S&SD Letter 12-03254-01-30504401 dated August
29, 2012, it is pre-qualified for Battery Chargers 125V DC
(Models BDT) as conforming to SEC Specification #
46-TMSS-02, Rev.0 with the following conditions:
Total = 15
BORRI S.P.A ITALY-Arezzo Yes Based on S&SD Letter # 14-03226-01-030504401 dated June
4, 2014, it is pre-qualified for UPS, 5 THROUGH 100 kVA as
conforming to National Grid SA specification # 46-TMSS-03,
Rev.0 with the following conditions:
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order. This has been confirmed in writing
by the manufacturer through letter # Nil dated May 23, 2011.
Page 60 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
BRAGA MORO ITALY Yes Based on S&SD Letter 12-03794-01-30504401 dated November
18, 2012, Braga Moro- Italy is pre-qualified for UPS as
conforming to National Grid SA Specification # 46-TMSS-03,
Rev.0, with the following conditions:
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.
GUTOR ELECTRONIC LTD. SWITZERLAND Yes
JESUS MARIA AGUIRRE SA (JEMA) SPAIN-Lasarte-Oria Yes Based on S&SD Letter 12-00193-030504001 dated January 17,
2012. It is prequalified for UPS up to 100kVA as conforming to
SEC Specification# 46-TMSS-03, Rev.0 with the following
conditions:
•All Type, Routine and Special testes shall be carried out on the
first batch of each types of UPS up to 100kVA in an
Independent Testing Laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated June 17, 2011.
Page 61 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Statron AG SWITZERLAND-Maegenwil Yes Based on S&SD Letter 12-03254-01-30504401 dated August
29, 2012, it is pre-qualified for UPS (S2000 series) as
conforming to SEC Specification # 46-TMSS-03, Rev.0 with the
following conditions:
Total = 6
AEG Power Solutions SAS FRANCE-- Yes originally was SAFT Power System SAS-France
Page 62 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
BRAGA MORO ITALY Yes I. Prequalified for BATTERY CHARGER, 48 VDC (For Telecom
Applications).
Page 63 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ERSKINE United Kingdom Yes Based on TS&SD letter# 09-F02210/03-03032301 dated 1st .
September 2009, ERSKIN System Ltd. (a division of Dale Power
Solution plc) from United Kingdom-Scarborough for 48V DC
battery Charger as confirming to SEC specification #
46-TMSS-05, rev.0 with the following conditions:
• All type, design, special & routine tests as per SEC
specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the manufacturer's
laboratory in the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
EXIDE United States Yes SCR TYPE ONLY
Total = 12
9 LV DISTRIBUTION PANELS
Page 64 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ABB/AEIL Saudi Arabia Yes
ETA-PCS United Arab Emirates-DUBAI Yes • Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
META Switchgear Company Saudi Arabia-Riyadh Yes Based on based on S&SD letter # 14-02218-01-30504401
dated March 23, 2014 & TS&SD letter
#11-F03210/01-03032301 dated 29/11/2011, it is pre-qualified
for AC&DC Panels as confirming to SEC specification #
31-TMSS-02, Rev.0 with the following conditions:
Page 65 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Waha Electric Supply Co. of Saudi Arabia- Saudi Arabia-Dammam Yes Based on TS&SD Letter # 11-01751/01-03032301 dated
(WESCOSA)-Dammam 27/06/2011, it is pre-qualified for Auxiliary AC & DC Panels up
to 132kV only as confirming to SEC specification # 31-TMSS-02,
Rev.0 with the following conditions:
Total = 12
Total = 7
10 .2 RMU, 15 KV
Page 66 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
AREVA FRANCE Yes
Total = 10
Total = 1
11 .1 NER, UP TO 33 KV
Total = 5
12 BARE CONDUCTORS
Page 67 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on S&SD letter# 13-02020-01-30504401 dated July 30,
2013, it is pre-qualified for ACSR, ACAR and AAAC type Bare
Overhead Line Conductors conforming to National Grid SA
specification # 10-TMSS-01, Rev.01 with the following
conditions:
Page 68 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
APAR Industries Ltd-SILVASSA INDIA-SILVASSA Yes Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010 & Letter # 14-03608/02-030504401 dated 04th
June 2014, it is pre-qualified for Bare Conductors as confirming
to SEC/National Grid SA specification # 10-TMSS-01, Rev.01
with the following conditions:
OMAN CABLE INDUSTRIES MUSCAT-- Yes FIRST LOT OF EACH TYPE SHALL BE TYPE TESTED IN AN
INDEPENDENT LABORATORY PER 10-TMSS-01 & OTHER INTL.
STANDARDS, IN PRESENCE OF SEC ENGINEERS AND ALL COST
SHALL BE BORNE BY THE MANUFACTURER.10 YEARS
EXTENDED WARRANTY.
RIYADH CABLES Saudi Arabia-RIYADH Yes
Page 69 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
STERLITE (INDIA) INDIA-- Yes Based on TS&SD Letter # 10-F001691/01-03032301 dated
June 19, 2010 and S&SD Letter 12-02686-1-30504401 dated
July 23, 2012, it is pre-qualified for Bare Conductors types
(ACAR, ACSR & AAAC) as confirming to SEC Specification #
10-TMSS-01, Rev.01 with the following condition:
• Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.
Total = 11
12 .2 TYPE ACSR/AW
APAR Industries Ltd-NALAGARH INDIA-NALAGARH Yes Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Bar Conductors as confirming
to SEC specification # 10-TMSS-01, Rev.01 with the following
conditions:
Page 70 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
APAR Industries Ltd-SILVASSA INDIA-SILVASSA Yes Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Bar Conductors as confirming
to SEC specification # 10-TMSS-01, Rev.01 with the following
conditions:
OMAN CABLE INDUSTRIES MUSCAT-- Yes FIRST LOT OF EACH TYPE SHALL BE TYPE TESTED IN AN
INDEPENDENT LABORATORY PER 10-TMSS-01 & OTHER INTL.
STANDARDS, IN PRESENCE OF SEC ENGINEERS AND ALL COST
SHALL BE BORNE BY THE MANUFACTURER.10 YEARS
EXTENDED WARRANTY.
RIYADH CABLES Saudi Arabia-RIYADH Yes
Page 71 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
STERLITE (INDIA) INDIA-- Yes Based on TS&SD Letter # 10-F001691/01-03032301 dated
19/06/2010, it is pre-qualified for Bare Conductors type
(ACSR/AW) as confirming to SEC specification # 10-TMSS-01
Rev.01 with the following condition:
Total = 11
12 .3 GROUND WIRE
APAR Industries Ltd-NALAGARH INDIA-NALAGARH Yes Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Overhead Ground Wire
(OGW) of Aluminum Clad Steel (ACS) Type only as confirming to
SEC specification # 10-TMSS-03, Rev.0 with the following
conditions:
Page 72 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
APAR Industries Ltd-SILVASSA INDIA-SILVASSA Yes Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Overhead Ground Wire
(OGW) of Aluminum Clad Steel (ACS) Type only as confirming to
SEC specification # 10-TMSS-03, Rev.0 with the following
conditions:
Total = 10
12. 4. 1 COPPER CLAD STEEL GROUNDING CONDUCTOR AND GROUNDING ROD Applicable Standards: 10-TMSS-05
FM Sudafix United Kingdom-Nottingham Yes Including Exothermic Welding and Grounding connectors.
Page 73 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SAUDI ELECTRIC INDUSTRIES CO. LTD. Saudi Arabia-JEDDAH Yes
Total = 7
AFL TELECOMMUNICATIONS EUROPE LTD United Kingdom-- Yes PREVIOUSLY ALCOA FUJIKURA LTD (AFL).
Jiangsu Zhongtian Technology Co.Ltd (ZTT) CHINA-Nantong Yes Based on TS&SD Letter # 10-01654-03032301 dated June 05,
-China 2010 and S&SD Letter 12-05204-1-30504401 dated February
04, 2013. It is prequalified for OPGW as conforming to National
Grid SA specification # 10-TMSS-04, Rev.0, with the following
conditions:
Page 74 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
LS CABLES KOREA, Republic of Yes Based on TS&SD letter # 10-02583-03032301 dated
19/09/2010, it is pre-qualified for OPGW as confirming to SEC
specification # 10-TMSS-04,Rev.0, with the following
conditions:
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes Based on TS&SD letter# 09-F00730/03-03032301 dated 24th
August 2009, Taihan Electric Wire Co. Ltd. from South
Korea-Anyang for OPGW as confirming to SEC specification #
10-TMSS-04, rev.0 with the following conditions:
• All type, design, special & routine tests as per SEC
specifications/standards shall be carried out on the first batch
to be supplied to SEC in securing an order in the manufacturer's
laboratory in the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
Total = 13
Page 75 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
FUJIKURA VISCAS CORP JAPAN Yes IT IS A CONSORTIUM OF FUJIKURA & FURUKAWA. ONLY
INVAR CONDUCTORS PER CLAUSE 1.3 & 1.4 OF 10-TMSS-06.
FIRST LOT TO BE TYPE TESTED IN THE PRESENCE OF 3 SEC
ENGRS AND IIA INSPECTOR; EXTENDED WARRANTY FOR 10
YEARS.
J-Power System Corporation JAPAN-Hitachi Yes Based on S&SD letter # 15-00017-1-30504401 dated 8th
February 2015, the manufacturer is prequalified for INVAR
Conductor Type ZTACIR/AS (Super-Thermal Resistant Aluminum
Alloy Conductor Aluminum Clad Invar Alloy Steel Reinforced) as
conforming to National Grid SA specification # 10-TMSS-06,
Rev.01 with the following condition:
Old Remark
Based on TS&SD letter# 09-00649-1-03032301 dated 28 March
2009 it is pre-qualified for GTACSR & GZTACSR.
Page 76 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
LS CABLES KOREA, Republic of Yes Based on TS&SD letter # 10-02584-03032301 dated
19/09/2010, it is pre-qualified for Heat Resistance Aluminum
Alloy Conductors, Gap& Non Gap type as confirming to SEC
specification # 10-TMSS-06,Rev.0, with the following
conditions:
Total = 3
13 .1 13.8 KV
Page 77 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on S&SD Letter 13-05014-2-3050440 dated September
08, 2013, it is pre-qualified for Insulated Conductor Cable
(XLPE) as conforming to National Grid SA Specification #
11-TMSS-04, Rev.0 with the following conditions:
ELSEWEDY EGYTECH CABLE CO. EGYPT-- Yes Including Joints & Terminations
JEDDAH CABLE CO. Saudi Arabia-JEDDAH Yes Including Joints & Terminations
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes Including Joints & Terminations
Total = 9
13 .2 33 & 34.5 KV
Page 78 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on S&SD Letter 13-05014-2-30504401 dated September
08, 2013, it is pre-qualified for Insulated Conductor Cable
(XLPE) as conforming to National Grid SA Specification #
11-TMSS-04, Rev.0 with the following conditions:
DEMIRER KABLO/SAUDI CABLE CO. TURKEY-- Yes Including Joints & Terminations
DUBAI CABLE CO. United Arab Emirates-DUBAI Yes Including Joints & Terminations
ELSEWEDY EGYTECH CABLE CO. EGYPT-- Yes Including Joints & Terminations
JEDDAH CABLE CO. Saudi Arabia-JEDDAH Yes Including Joints & Terminations
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes Including Joints & Terminations
Total = 15
13 .3 XLPE CABLES – 69 KV
Page 79 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
DAINICHI-NIPPON CABLES (MITSUBISHI) JAPAN Yes Including Joints & Terminations
DEMIRER KABLO/SAUDI CABLE CO. TURKEY-- Yes Including Joints & Terminations
ELSEWEDY EGYTECH CABLE CO. EGYPT-- Yes TO CARRY OUT ALL TYPE/DESIGN AND ROUTINE/SAMPLE
TESTS AT SEC APPROVED INDEPENDENT LABORATORY IN
PRESENCE OF A REPRESENTATIVE OF 3RD PARTY INSPECTION
AGENCY & THREE ENGINEERS OF SEC FOR FIRST CONTRACT;
10 YEARS OF EXTENDED GUARANTEE/WARRANTY; FOR
JOINTS & TERMINATIONS ALSO;
FUJIKURA CABLES JAPAN Yes Including Joints & Terminations
FURUKAWA ELECTRIC CO. LTD. JAPAN Yes Including Joints & Terminations
JEDDAH CABLE CO. Saudi Arabia-JEDDAH Yes Based on TS&SD letter # 10-02784-01-03032301 dated
24/10/2010, it is pre-qualified for 69kV, 1x630mm² XLPE Power
Cable as confirming to SEC specification # 11-TMSS-01, Rev.0,
with the following condition:
PIRELLI KABEL AND SYSTEM GMBH GERMANY-BERLIN Yes Including Joints & Terminations
Total = 14
13 .4 110KV TO 132 KV
DEMIRER KABLO/SAUDI CABLE CO. TURKEY-- Yes Including Joints & Terminations
Page 80 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
ELSEWEDY EGYTECH CABLE CO. EGYPT-- Yes TO CARRY OUT ALL TYPE/DESIGN AND ROUTINE/SAMPLE
TESTS AT SEC APPROVED INDEPENDENT LABORATORY IN
PRESENCE OF A REPRESENTATIVE OF 3RD PARTY INSPECTION
AGENCY & THREE ENGINEERS OF SEC FOR FIRST CONTRACT;
10 YEARS OF EXTENDED GUARANTEE/WARRANTY; FOR
JOINTS & TERMINATIONS ALSO;
FUJIKURA JAPAN Yes Including Joints & Terminations
FURUKAWA ELECTRIC CO. LTD. JAPAN Yes Including Joints & Terminations
JEDDAH CABLE CO. Saudi Arabia-JEDDAH Yes Based on TS&SD letter # 10-02784-01-03032301 dated
October 10,2014 and S&SD letter# 14-04876-01-30504401
dated July 16, 2014. it is pre-qualified for 132kV, 1x2500mm²
CU/XLPE/CWS/LAT/HDPE Power Cable as confirming to National
Grid specification # 11-TMSS-02, Rev.1, with the following
condition:
PIRELLI KABEL AND SYSTEM GMBH GERMANY-BERLIN Yes Including Joints & Terminations
SAUDI CABLE Saudi Arabia-JEDDAH Yes • Based on S&SD letter # 15-00585-01-30504401 dated
February 10, 2015, the manufacturer is prequalified for
110/115/132KV, 1X1200mm² CU/XLPE Power Cable as
conforming to National Grid SA specification # 11-TMSS-02,
Rev.01.
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes Including Joints & Terminations
Total = 15
13 .5 230 K V
Page 81 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
BRUGG SWITZERLAND Yes Including Joints & Terminations; COMPLETE TYPE, SPECIAL &
ROUTINE TESTS FOR THE FIRST ORDER , ALSO 10 YEARS
WARRANTY FROM THE DATE OF PAC ARE REQUIRED
DAINICHI-NIPPON CABLES (MITSUBISHI) JAPAN Yes Including Joints & Terminations
DEMIRER KABLO/SAUDI CABLE CO. TURKEY-- Yes Including Joints & Terminations
FURUKAWA ELECTRIC CO. LTD. JAPAN Yes Including Joints & Terminations
SAUDI CABLE Saudi Arabia-JEDDAH Yes based on TS&SD letter# 09-01366-03032301 dated 10th. May
2009, it is pre-qualified as conforming to SEC specifications #
11-TMSS-02, rev.0 with the following conditions:
• All type/design and routine/sample tests shall be carried
out on the first batch of 230kV XLPE power cable to be supplied
to SEC in securing an order in an independent testing
laboratory as per IEC/AEIC and SEC standards in the presence
of three (3) SEC engineers & one (1) approved independent
inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
SUDKABEL GERMANY-GERMANY Yes PREVIOUSLY ABB. Including Joints & Terminations
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes • Including Joints & Terminations.
• Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Total = 11
13 .6 380 KV
BRUGG SWITZERLAND Yes Including Joints & Terminations; COMPLETE TYPE, SPECIAL &
ROUTINE TESTS FOR THE FIRST ORDER , ALSO 10 YEARS
WARRANTY FROM THE DATE OF PAC ARE REQUIRED
DAINICHI-NIPPON CABLES (MITSUBISHI) JAPAN Yes Including Joints & Terminations
Page 82 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
DEMIRER KABLO/SAUDI CABLE CO. TURKEY-- No Based on TS&SD letter 11-01374-03032301 dated April 27,
2011. It is DISQUALIFIED for 380KV XLPE Cable.
J-POWER SYSTEM CORP. JAPAN Yes Including Joints & Terminations
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order, as confirmed by the manufacturer
through letter # Nil dated 12/02/2013.
NKT GERMANY Yes Including Joints & Terminations
Page 83 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes Based on S&SD letter # 14-08139-01-30504401 dated January
07, 2015, the manufacturer is prequilified to supply power
cables rated 380 kV with conductor cross section of 1X2500
mm², XLPE, with copper wires metallic shield as per
11-TMSS-02, Rev.01 along with the cable accessories with the
following drawings numbers:
Total = 11
14 .1 110 TO 132 KV
FURUKAWA ELECTRIC CO. LTD. JAPAN Yes Including Joints & Terminations
Page 84 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
KABEL RHEYDT (AEG) GERMANY Yes Including Joints & Terminations
LS CABLES KOREA, Republic of Yes PREVIOUSLY LG; Including Joints & Terminations
PIRELLI KABEL AND SYSTEM GMBH GERMANY-BERLIN Yes Including Joints & Terminations
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes Including Joints & Terminations
Total = 16
14 .2 230 KV
FURUKAWA ELECTRIC CO. LTD. JAPAN Yes Including Joints & Terminations
PIRELLI KABEL AND SYSTEM GMBH GERMANY-BERLIN Yes Including Joints & Terminations
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes • Including Joints & Terminations.
• Complete Type, Routine / Sample tests for first order.
• Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Total = 10
14 .3 380 KV
Page 85 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
CANADA WIRE CANADA Yes Including Joints & Terminations
FURUKAWA ELECTRIC CO. LTD. JAPAN Yes Including Joints & Terminations
PIRELLI KABEL AND SYSTEM GMBH GERMANY-BERLIN Yes Including Joints & Terminations
STANDARD TELEFON OG KABELFABRIK A/S NORWAY Yes Including Joints & Terminations
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes • Including Joints & Terminations.
• Complete Type, Routine / Sample tests for first order.
• Ten (10) years extended warranty from the date of PAC of
the First turnkey project in case of contract award or date of
the First delivery in case of direct material supply order.
Total = 17
Page 86 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
AK POWER SOLUTONS PTY LTD AUSTRALIA-Huntingwood, NSW Yes Previously HAYCOLEC SWITCHGEAR PTY – Australia-NSW [The
name has been changed to AK POWER SOLUTONS PTY LTD-
Australia-Huntingwood, NSW based on S&SD/P&SFD letter #
13-07444-30504401 dated December 11, 2013 and based on
AK POWER SOLUTONS PTY LTD- Australia-NSW-Huntingwood
Letter # NG251113 dated November 25, 2013].
AL SHAHRANI EST. Saudi Arabia-RIYADH Yes
MOHAMMAD AL –OJAIMI FACTORY Saudi Arabia-RIYADH Yes PAD MOUNTED STAINLESS STEEL BOXES AND UNDER GROUND
FIBER GLASS BOXES UP TO 132KV ACCEPTABLE. EXTENDED
GUARANTEE FOR 10 YEARS FOR THE FIRST SUPPLY AND IT
WILL BE REDUCED YEARLY IN CASE OF FUTURE PROJECT
AWARDS.
PIRELLI GERMANY-BERLIN Yes
Power and Telecommunication Equipments Saudi Arabia-Jeddah Yes Based on TS&SD fax ref# 09-00396-1-03032301 dated
Factory (P.T.E. Co.) (CEPCO) 17/02/2009 P.T.E is prequalified for Link Boxes rated up to
380kV.
* (10) years extended warranty.
STEINER GERMANY Yes
Total = 13
AK POWER SOLUTONS PTY LTD AUSTRALIA-Huntingwood, NSW Yes Previously HAYCOLEC SWITCHGEAR PTY – Australia-NSW [The
name has been changed to AK POWER SOLUTONS PTY LTD-
Australia- Huntingwood, NSW based on S&SD/P&SFD letter #
13-07444-30504401 dated December 11, 2013 and based on
AK POWER SOLUTONS PTY LTD- Australia-NSW-Huntingwood
Letter # NG251113 dated November 25, 2013].
Total = 2
Page 87 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
FUJIKURA VISCAS CORP JAPAN Yes
Total = 6
15. 1. 0 NON-METALLIC FIBER OPTIC (F/O) CABLE & ACCESSORIES Applicable Standards: 48-TMSS-02
AFL TELECOMMUNICATIONS EUROPE LTD United Kingdom-- Yes PREVIOUSLY ALCOA FUJIKURA LTD. (AFL)
Page 88 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Oman Fiber Optic Cable Company Oman-Rusayl Yes Based on TS&SD letter# 10-00909-2-03032300 dated April 06,
2010. It is pre-qualified for Non Metallic Fiber Optic Cable per
SEC Specification 48-TMSS-02, Rev.0 with the following
conditions:
• Type Test: The first batch of each type of Non Metallic Fiber
Optic Cable to be supplied to SEC shall be type tested per
relevant International and SEC Specifications in presence of
three (3) SEC Engineers and one (1) SEC approved IIA
Inspector and all cost pertaining to the test shall be borne by
the Manufacturer as confirmed through Letter# Nil dated
September 12, 2009.
R & M Reichle & De-Massari AG SWITZERLAND-Wetzikon Yes Based on S&SD Letter 13-02127-030504401 dated May 19,
2013, R & M Reichle & De-Massari AG, Wetzikon, Switzerland is
pre-qualified for "Accessories only" fiber optic and copper
passive components (Structure Cabling) as conforming to
National Grid SA specification # 01-TMSS-01, Rev.01, with the
following conditions:
Page 89 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SAUDI CABLE Saudi Arabia-JEDDAH Yes Based on S&SD Letter 12-03896-30504401 dated November
10, 2012, SAUDI CABLE Co. - Saudi Arabia-Jeddah is
pre-qualified for Non-Metallic Fiber Optic Cable (F/O) Cable &
Accessories as conforming to SEC Specification # 48-TMSS-02,
Rev.0, with the following condition:
TE Connectivity Ltd. United States-- Yes Based on S&SD Letter 12-03688-01-30504401 dated January
03, 2012. The name of the manufacturer has been changed
from ADC- United States to TE Connectivity Ltd.-United States.
TELECT Poland-Wroclaw Yes based on TS&SD letter# 09-01095-03032301 dated 18th. April
2009 for the following accessories:
- Management Rack E-9000 series
- Distribution & Termination Unit LCX.
- Wall mounted unit LanLinxs.
Total = 29
16 .0
16. 0. 0 PILOT WIRE CABLES & ACCESSORIES Applicable Standards: 48-TMSS-01,48-TMSS-03,48-TMSS-04,48-TMSS-05
Page 90 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Total = 11
17 .0
17. 0. 0 SHIELDED CABLE FOR INSTRUMENTATION Applicable Standards:
SAUDI CABLE Saudi Arabia-JEDDAH Yes Based on TS&SD fax ref.#08-02969-3-03032301 dated
07/01/2009. Pre-Qualified for Shielded Instrumentation &
Thermocouple Cables with this conditions:
-First batch shall be type, designe, special, acceptance &
routine tests in the factory test laboratory in presence of (3)
SEC engineers & (1) independent inspector.
-(10) years warranty
TEKAB Co. Ltd. United Arab Emirates-Sharjah Yes APPROVED FOR CABLES WITHOUT METALLIC SHEATH; TYPE
TEST CERTIFICATE FROM INDEPENDENT LAB TO BE
SUBMITTED FOR 1ST ORDER; EXTENDED QUARANTEE FOR 10
YEARS.
Total = 6
18 .0
18. 0. 0 POWER /OR CONTROL CABLE (0.6/1KV) Applicable Standards: 11-TMSS-10
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on TS&SD letter# 09-01432-03032301 dated 16th. May
2009 is pre-qualified for Low Voltage Power & Control Cables
0.6/1kV as conforming to SEC specifications # 11-TMSS-10,
rev.0 with the following conditions:
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
Page 91 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
BAHRA CABLES Co. Saudi Arabia-Jeddah Yes Based on S&SD letter # 15-01562-1-30504401 dated March 18
2015, the manufacturer is prequalified for LV power cables as
conforming to National Grid SA specification # 11-TMSS-10,
Rev.01 with the following condition:
ELSEWEDY EGYTECH CABLE CO. EGYPT-- Yes based on TS&SD fax ref# 09-00303/01-03032301 dated
18/02/2009.
JEDDAH CABLE CO. Saudi Arabia-JEDDAH Yes
Middle East Specialized Cable Co. MESC Jordan-- Yes Previously JORDAN NEW CABLE COMPANY- JORDAN-AMMAN
[The name has been changed based on S&SD/P&SFD letter #
14-01869-30504401 dated March 24, 2014].
OMAN CABLE INDUSTRIES MUSCAT-- Yes Based on TS&SD letters # 10-02435-03032301 dated
06/09/2010 & 10-02611-03032301 dated 02/10/2010, it is
pre-qualified for LV Power& Control Cables (0.6/1kV) rating as
confirming to SEC specification # 11-TMSS-10,Rev.0, with the
following condition:
Page 92 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
TEKAB Co. Ltd. United Arab Emirates-Sharjah Yes Based on S&SD letter# 13-07588-30504401 dated December
11, 2013, it is pre-qualified for Power and/or Control Cable
Copper 600/1000 V Rating as conforming to National Grid SA
specification # 11-TMSS-10, Rev.01, with the following
conditions:
Total = 12
19. 1. 1 CABLE SPLICE & TERMINATION KITS UP TO 132 KV Applicable Standards: 12-TMSS-10
G&W United States Yes SUSPENDED FOR ALL ONGOING & FUTURE PROJECTS DUE TO
FREQUENT FAILURE & VERY POOR FOLLOWUP RESPONSE
FROM THE MANUFACTURER.
J-POWER SYSTEM CORP. JAPAN Yes
RAYCHEM Saudi Arabia-DAMMAM Yes LIMITED TO 69KV ONLY. UNDER THE GROUP OF TYCO
Page 93 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
TAIHAN ELECTRIC WIRE COMPANY KOREA, Republic of Yes
Total = 15
19. 2. 1 CABLE SPLICE & TERMINATION KITS UP TO 230 KV Applicable Standards: 12-TMSS-10
Total = 2
19. 3. 0 CABLE SPLICE & TERMINATION KITS UP TO 380 KV Applicable Standards: 12-TMSS-10
• Ten (10) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order, as confirmed by the manufacturer
through letter #Nil dated 12/02/2013.
Total = 4
20 .0
Page 94 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
DALEKOVOD PROIZVODNJA Croatia/Hrvatska-Zagreb Yes Based on TS&SD fax # 10-01179-03032301 dated April 20,
2010, this manufacturer is pre-qualified for Compression Type
Connectors for O/H T/L per 12-TMSS-02, Rev.0 with the
following conditions:
• Each new design of Compression Type Connectors for O/H T/L
which has NOT been type tested/supplied to SEC before, shall
be type tested as per 12-TMSS-02.
• Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.
Page 95 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
Lorunser Austria GmbH SLOVAKIA-ML Production Myjava Yes Based on S&SD letter# 13-062982-2-30504401 dated
December 04, 2013, it is pre-qualified for Substation
Connectors as conforming to National Grid SA specification #
12-TMSS-02 Rev. 01, with the following conditions:
a. AL-T-Connector: 1AB012-002-031.
e. AL-Bus-Support: 1JB008-160-004.
Page 96 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SA_RA Energy, Construction, Trade and TURKEY-ADANA Yes Based on S&SD letter# 14-09052-01-30504401 dated 11th
Industry Co. Inc. December 2014, this manufacturer is pre-qualified for
compression connectors up to 380kV conforming to 12-TMSS-02
Rev.01 with the following conditions.
Total = 16
21 INSULATORS
21 .1 PORCELAIN INSULATORS
21. 1. 1 STATION POST INSULATOR PORCELAIN, UP TO 132 KV, 230 KV and 380 KV Applicable Standards: 15-TMSS-01
Page 97 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
PPC INSULATORS AUSTRIA Yes Based on TS&SD/ESD e-mail dated 07/07/2010 and PPC
Insulators (Austria) Letter # Nil dated 4th July 2010, it is
pre-qualified for Station Post Insulator Porcelain, up to 132kV,
230kV&380kV as confirming to SEC specification # 15-TMSS-01,
Rev.0 with the following conditions:
Total = 7
Total = 5
Page 98 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
PPC INSULATORS (ELEKTROKERAMIK GERMANY Yes Based on TS&SD/ESD e-mail dated 07/07/2010 and PPC
SONNEBERG) Insulators (ELEKTROKERAMIK SONNEBERG, Germany) Letter #
Nil dated 4th July 2010, it is pre-qualified for Long Rod Porcelain
Insulators up to 380kV as confirming to SEC specification #
15-TMSS-04, Rev.01 with the following conditions:
C) Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.
SIEMENS GERMANY Yes
Total = 4
SEDIVER BRAZIL-- Yes COMPLETE SAMPLE, TYPE & ROUTINE TESTS FOR THE FIRST
ORDER IS REQUIRED.
SEDIVER ITALY Yes Complete Sample, Type & Routine Tests for the first order is
required.
Page 99 of 239
METERIAL / EQUIPMENT Pre-Qualified
SER DESCRIPTION MANUFACTURER FACTORY LOCATION Manufacturers REMARKS
By SEC
SGD LA GRANJA VIDRIERIA, S.L. SPAIN-Segovia Yes Based on S&SD letter# 13-07206-01-30504401 dated
November 09, 2013, it is pre-qualified for Glass Insulator as
conforming to National Grid SA specification # 15-TMSS-02 ,
Rev.01, with the following conditions:
Total = 3
E.B.REBOSIO S.r.L ITALY Yes Up To 132 kV only. Complete Type, Routine / Sample tests for
first order & 10 Years Warranty from the date of PAC is
required.
FCI (FURUKAWA COMPOSITE INSULATORS HUNGARY-BUDAPEST Yes
LTD)
LAPP GERMANY-ROSENTHAL Yes
B) Any new type of Insulators (other than the types which are
mentioned in A) offered by PFISTERRER SEFAG AG –
Switzerland shall be Type Tested in presence of three (3) SEC
Engineers and one (1) Approved Independent Agency
Inspector.
Total = 7
LAPP GERMANY-ROSENTHAL Yes FIRST BATCH OF EVERY NEW TYPE OF 380KV INSULATOR TO
BE TYPE TESTED IN PRESENCE OF 3 SEC ENGINEERS AND ONE
SEC APPROVED INDEPENDENT INSPECTOR; EXTENDED
WARRANTY OF 10 YEARS
MACLEAN POWER SYSTEM United States-ILLINOIS Yes *All type/design & special tests were performed for first batch
at Independent lab. in presence of SEC/IIA Inspectorbased on
TS&SD fax#09-F00306-030323001 dated 17/02/2009.
-Extended 10(ten) year guarantee/warranty is required.
B) Any new type of Insulators (other than the types which are
mentioned in A) offered by PFISTERRER SEFAG AG –
Switzerland shall be Type Tested in presence of three (3) SEC
Engineers and one (1) Approved Independent Agency
Inspector.
Total = 4
Dow Corning Corporation United States-Auburn Yes Based on S&SD letter # 14-04590-02-30504401, dated 16th
September 2014, it is prequalified for RTV Silicone Rubber
Insulator Coating Material “Xiameter” ECE Sylgard HVIC as
conforming to National Grid SA Material Specification
15-TMSS-07,Rev.0 with the following conditions:
Total = 1
22 .1 HARDWARE FITTINGS
DERVAUX FRANCE Yes Previously "SM-CI-France", the name has been change to
DERVAUX-France based on DERVAUX-France letter # Nil dated
13/10/2009.
Hubbell Power Systems, Inc. United States-Columbia Yes Previously A B CHANCE [The name has been changed based on
S&SD/P&SFD letter# 14-010193-30504401 dated January 06,
2015 and based on Hubbell Power System Grid Letter # Nil
dated December 18, 2014]
INDUSTRIAS ARRUTI SPAIN Yes
• Each new design of Line Hardware which has not been type
tested, shall be type tested as per latest revision of
12-TMSS-01.
Total = 16
Total = 8
Al Yamamah Electric Powers Factory Saudi Arabia-Jeddah Yes Based on TS&SD letter # 11-03472-03032301 dated
09/01/2011, it is pre-qualified for Substation Steel Structure
(Latticed) up to 132kV as confirming to SEC specification #
20-TMSS-01, Rev.0 with the following conditions:
AL-BABTAIN POWER&TELECOM CO. EGYPT-N/A Yes FIRST LOT OF EACH TYPE OF STRUCTURE SHALL BE TYPE
TESTED IN AN INDEPENDENT LAB IN PRESENCE OF SEC
ENGINEERS; 10 YEARS EXTENDED WARRANTY.
Alfanar Steel Saudi Arabia-Riyadh Yes Based on TS&SD letter# 08-1058/1-03032301 dated 25th May
2009 it is pre-qualified for Transmission Towers for projects up
to 132kV, Substation & Gantry Steel Structures up to 380kV and
Communications Tower for transmission sector as confirming to
SEC specification # 20-TMSS-01, rev.0 with the following
conditions:
• All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in the manufacturer's testing laboratory in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
ARABIAN INTERNATIONAL CO. Saudi Arabia-JEDDAH Yes
KEC INTERNATIONAL LTD. INDIA-- Yes NAGPUR-BUTIPORI, JABALPUR, JAIPUR PLANTS ARE
ACCEPTABLE; ALL THE TESTS SHALL BE CARRIED OUT FOR
FIRST CONTRACT/PROJECT IN PRESENCE OF THREE (3) SEC
ENGINEERS; 10 YEARS OF EXTENDED WARRANTY.
LARSEN & TOUBRO LTD. INDIA-CHENNAI Yes
SA_RA Energy, Construction, Trade and TURKEY-Polath/ANKARA & ADANA Yes Based on S&SD letter# 14-09052-01-30504401 dated 11th
Industry Co. Inc. December 2014, this manufacturer is pre-qualified for
Substation Steel Structures up to 380kV conforming to
Company Specifications 20-TMSS-01 Rev.01 with the following
condition:
Total = 13
AL-BABTAIN POWER&TELECOM CO. EGYPT-N/A Yes FIRST LOT OF EACH TYPE OF STRUCTURE SHALL BE TYPE
TESTED IN AN INDEPENDENT LAB IN PRESENCE OF SEC
ENGINEERS; 10 YEARS EXTENDED WARRANTY.
Alfanar Steel Saudi Arabia-Riyadh Yes Based on TS&SD letter# 08-1058/1-03032301 dated 25th May
2009 it is pre-qualified for Transmission Towers for projects up
to 132kV, Substation & Gantry Steel Structures up to 380kV and
Communications Tower for transmission sector as confirming to
SEC specification # 20-TMSS-01, rev.0 with the following
conditions:
• All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in the manufacturer's testing laboratory in
the presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
AL-SALAM INSDUTRIES AND TRADING Saudi Arabia-JEDDAH Yes ONE TRIAL PROJECT FOR 110/132 KV SHORT LINE.
EST./ADVANCE TECHNOLOGIES.
ARABIAN INTERNATIONAL CO. Saudi Arabia-JEDDAH Yes
KALPATARU Power Transmission Ltd. INDIA-Gujarat Yes Based on TS&SD letter 09-00665/1-03032301 dated 16th.
March 2009 for Galvanised Transmission line Lattice Steel Tower
up to 380kV as conforming to SEC specifications # 20-TMSS-01,
rev.0; with the following conditions:
• Ten (10) years extended warranty.
• Improvement needs indicated in the plant survey report.
• All the tests shall be carried out for first contract/project in
presence of three (3) sec engineers & independent Inspector.
KEC INTERNATIONAL LTD. INDIA-- Yes • Only NAGPUR-BUTIPORI, JABALPUR & JAIPUR Plants are
acceptable.
SA_RA Energy, Construction, Trade and TURKEY-Polath/ANKARA & ADANA Yes Based on S&SD letter# 14-09052-01-30504401 dated 11th
Industry Co. Inc. December 2014, this manufacturer is pre-qualified for T/L Steel
Structures up to 380kV conforming to Company Specifications
20-TMSS-01 Rev.01 with the following conditions:
Total = 13
Energya Steel Solution (Hesham Helal El Saudi Arabia-Rabigh Yes Based on TS&SD Letter # 10-0331/06-03032301 dated
Sewedy & Partners for Steel Industries Co.) 28/06/2010, it is pre-qualified for Steel Poles, Tubular up to
230kV as confirming to SEC specification # 20-TMSS-02. Rev.0
with the following conditions:
• All Type, Routine and Special Tests including the load test
per SEC specification # 20-TMSS-02 and all relevant
International Standards shall be conducted on the first batch in
presence of three (3) SEC Engineers and one (1) SEC approved
independent inspection agency (IIA) Inspector and related cost
pertaining to the test shall be borne by Hesham Helal EL
Sewedy & Partners for Steel Industries Co.(Energya Steel
Solutions) as confirmed by manufacturer through letter #
SEC/WK/100524 dated 24th May 2010.
Total = 7
23 .5 WOOD POLES
Total = 7
Total = 7
24 .0 .
Total = 4
25 RACEWAYS
25. 1. 0 METAL ENCLOSED BUS DUCT, 4.16 – 13.8 KV OR 34.5 KV Applicable Standards:
Total = 3
AL-AMAL CO. Saudi Arabia-RIYADH Yes FOR LADDERS & ACCESSORIES ALSO; 10 YEARS OF EXTENDED
WARRANTY;
ELECTROLINK Co. Ltd. Saudi Arabia-Riyadh Yes based on TS&SD letter 09-00524/1-03032301 dated 16th.
March 2009 for Metallic Cable Tray Systems as conforming to
SEC specifications # 24-TMSS-01, rev.0; with the following
conditions:
• Eight (8) years extended warranty.
• Improvement needs indicated in the plant survey report.
Specialized Factory for Steel Products (SFSP) Saudi Arabia-Jeddah Yes Based on S&SD Letter # 15-01409-01-30504401, dated 18th
March 2015 the manufacturer is prequalified for Cable trays,
Cable Ladders and Accessories as conforming to National Grid
SA Material Specification 24-TMSS-01, Rev. 01, with the
following conditions:
26 CONDUIT FITTINGS
Total = 2
27 SWITCHES
Alstom Grid S. p .A ITALY-Venice - Noventa di Piave Yes Based on S&SD letter# 13-04035-02-30504401 dated July 22,
2013, it is pre-qualified for Disconnect Switches 420kV, 4000A
(S3CD, S3CDT & S3CD2T) only and Standalone Grounding
Switches (STB) 420kV, 63kA only as conforming to National Grid
SA specification # 30-TMSS-01, Rev.0, with the following
conditions:
SOUTHERN STATES United States Yes SOUTHERN STATES/ USA HAS ACQUIRED SIEMENS SWITCH
FACTORY
Total = 12
27 .2 LV AUTO-TRANSFER SWITCH
Total = 3
Total = 1
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes Based on TS&SD letter# 09-01251-03032301 dated 03rd. May
2009 UP TO 380KV as confirming to SEC specification #
31-TMSS-01, rev.0 with Ten (10) years warranty from the date
of PAC of the Turnkey project in case of contract award or
date of delivery in case of direct material supply order.
Alstom Grid Integration & Testing Facility Saudi Arabia-Alkhobar Yes Based on S&SD letter # 14-04579-2-030504401, dated
30/06/2014, it is prequalified for Integration & Testing of Relay
& Control Panels confirming to National Grid SA Material
Specification 31-TMSS-01, Rev.0, with the following conditions:-
ETA-PCS United Arab Emirates-DUBAI Yes It is pre-qualified for Relay & Control Panels as conforming to
SEC specification # 31-TMSS-01, Rev.0 with the following
condition:
• Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order.
JAL INTERNATIONAL Saudi Arabia-KHOBAR Yes • Up to 132kV only.
• Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or date of
delivery in case of first direct material supply order.
Koncar Elektricni Uredaji d.d CROATIA-Dicmo Yes Based on S&SD letter# 14-1456-03-30504401 dated April 15,
2014, it is pre-qualified for Relay & Control Panel up to 380 kV
as conforming to National Grid SA specification # 31-TMSS-01,
Rev.0, with the following condition:
System House Factory for Electric Panels (SEP) Saudi Arabia-Riyadh Yes Based on TS&SD letter# 09-01500-03032301 dated May 25,
2009, 10-01055/02-03032301 dated May 03, 2010 & S&SD
Letter 12-03596-02-30504401 dated April 29, 2012. It is
prequalified for Relay & Control Panel up to 380kV as
conforming to SEC specification # 31-TMSS-01, Rev.0 with the
following condition:
• Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award or the date
of first delivery in case of direct material supply order. This was
confirmed in writing by the manufacturer through their letter #
Nil dated December 11, 2011.
TIEPCO Saudi Arabia-DAMMAM Yes
Total = 23
28 .2 ANNUNCIATOR SYSTEM
Total = 12
APM TECHNOLOGIES INC KOREA, Republic of-Seoul Yes Based on S&SD letter # 14-08866-2-30504401 dated December
11, 2014, it is pre-qualified for Partial Discharge Monitoring
System (PDMS) APM5000 & APM2000 (Portable) as conforming
to National Grid SA specification # 38-TMSS-07, Rev.0, with the
following condition:
Total = 2
ELPRO INTL. LTD INDIA Yes Upto 132 kV Only - Complete Type, Routine / Acceptance tests
for first order & 10 Years Warranty from the date of PAC is
required.
MITSUBISHI JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
TOSHIBA CORPORATION, T&D JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total = 14
30 CIRCUIT BREAKER
AREVA United States-CHARLEROI Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
FUJI Electric Co. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
GE-HITACHI HVB United States-GEORGIA Yes
HITACHI Ltd. JAPAN-- Yes Originally JAPAN AE POWER SYSTEM CORP and subsequent
change affected as per HITACHI letter # XAE-VR-121213,
dated 13-12-2012 and FUJI letter # AT-LTR-121115-1, dated
18-12-2012.
MITSUBISHI JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total = 8
AREVA T&D Inc.-USA United States-Charleroi Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
SIEMENS GERMANY-Berlin Yes Based on S&SD Letter 12-2202-01-30504401 dated July 24,
2012, it is pre-qualified for Dead Tank Circuit Breaker type 3AP1
DT 72.5KV & 145KV as conforming to National Grid SA
Specification # 37-TMSS-01, Rev.0 with the following
conditions:
Total = 10
AREVA United States-CHARLEROI Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
TOSHIBA CORPORATION, T&D JAPAN-- Yes ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total = 7
Total = 6
30. 2. 2 LIVE TANK, 110 - 132 KV SF6 BREAKER Applicable Standards: 37-TMSS-02
Total = 4
Total = 3
Total = 3
31 .1 LINE TRAP
Total = 2
31 .2 LINE TUNER
Total = 1
KONCAR INSTRUMENT TRANSFORMERS INC. Croatia/Hrvatska-- Yes Limited up to 132kV only. All Type, Special, Routine tests per
SEC Standards and IEC to be performed at KONCAR-Electrical
Institute Inc. as independent and accredited testing laboratory.
Extended guarantee/warrenty for 10 years.
NISSIN JAPAN Yes
PFIFFNER SWITZERLAND Yes Based on TS&SD letter# 09-01105-03032301 dated 24th June
2009, it is pre-qualified for CT & CVT rated up to 380kV as
confirming to SEC specification # 50-TMSS-01, rev.0 & #
50-TMSS-02, rev.0 respectively with the following conditions:
• All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in an independent testing laboratory in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
RITZ United States Yes TYPE TEST REQUIRED IN FIRST SUPPLY
Total = 13
EFACEC Sistemas de Elctronica, S.A PORTUGAL-Maia Yes Based on TS&SD letter# 09-01819-03032301 dated 23rd June
2009, it is prequalified for for RTU type CLP500 as confirming to
SEC specification # 38-TMSS-03, rev.0 with the following
condition:
• Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.
FOXBORO AUSTRALIA Yes
Global Energy Technologies Ltd. United Arab Emirates-Dubai Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.
LSIS KOREA, Republic of-- Yes SEVEN (7) YEARS EXTENDED WARRANTY.
MICROSOL LTD. Ireland-DUBLIN Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.
SAT AUSTRIA Yes
Total = 14
Global Energy Technologies Ltd. United Arab Emirates-Dubai Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.
MICROSOL LTD. Ireland-DUBLIN Yes SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on Standards & Specifications Dept.
Manager letter # 14-02646-02-30504401 dated July 17, 2014.
RONAN ENGINEERING United States-LOS ANGELES, CA Yes X500E/1000
Total = 7
31 .6 TRANSDUCERS
Total = 2
Total = 1
TYCO ELECTRONICS (UK) Ltd - CROMPTON United Kingdom-- Yes Based on TS&SD Letters (08-F00975/01-03032301 dated June
INSTRUMENTS 04, 2008), (10-F00230/01-03032301 dated February 03, 2010)
& (11-F03017/01-03032301 dated October 16, 2011). Integra
1560 is prequalified for Transducers as confirming to SEC
Specification # 40-TMSS-02, Rev.0 with the following condition:
Total = 5
Total = 3
Total = 4
Total = 4
31 .7 PROTECTIVE RELAYS
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6X0-D1
A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’s+12BO’s
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6X0-D1
A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’s+12BO’s
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6B6-D1
A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6B6-D1
A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering Code:
P54631NH7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’s+12BO’s
8CT+4VT+16BI’s+16BO’s
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
MiCOM P546
Ordering Code:
P54631NK7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’s+12BO’s
8CT+4VT+16BI’s+16BO’s
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’S+12BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W73(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-U67-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-U67-W73(*) (*) CH2 to be
attenuated to fit SDH
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
0411L1X6X1C7CDXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
SEL 411L
Ordering code:
0411L1X6X1C7CEXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0H+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’S+12BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
7SD522
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0J+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
Total = 6
Ordering code:
RET670*1.2-B30X00-A02D03E01P01-B1X-C-B-KB-B-B3B3-D1A-
XE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
14xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Relay Type:
RET 670
Ordering code:
RET670*1.2-B40X00-A01A02D04E01P01-B1X-C-B-KB-B-B3B3-D
1A-XE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
Hardware:
3-WINDING:
14xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Ordering code:
P64332NA6M0040K
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC Supply Supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT (Ph) + 4xCT (Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Relay Type:
MiCOM P 643
Ordering code:
P64532NA6M0040K
Built in Functions:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
Hardware:
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-PXX-U8N-WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
15xCT(Ph)+5xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING:
IEC 61850 2-ports
Relay Type:
T 60
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-P6T-U8N-WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
Hardware:
3-WINDING:
15xCT(Ph)+5xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ordering code:
0487E3X648XXC2X4H624XXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
60
DFR/SOE
Hardware:
2-WINDING:
8xcontact inputs
4xcontact outputs
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
IEC 61850 2 ports
Ordering code:
7UT6331-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Relay Type:
7UT6
Ordering code:
7UT6351-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
Hardware:
3-WINDING:
12xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Ordering code:
8IDVK4F22Z104SKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout Coil Supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT(Ph)+2xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING
IEC 61850 2 ports
Relay Type:
IDV
Ordering code:
8IDVD4F22Z904VKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
50 BF
49T
74 DC supply supervision.
74 Lockout Coil Supervision.
CT Super (All windings)
DFR/SOE
Total = 7
Ordering code:
REB500-CU03-V76-S30-P0-B0-CA3-CB3
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
REB500 CU
Ordering code:
REB500-CU03-V76-S50-P0-B0-CA3-CB3
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
48 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
REB500 PU
Ordering code:
REB500-BU03-C2-A40-P0-F1-BB2-IO0-R0-OC0-BFP1-EFP1-PD0-
DR0-L0-T0+1MRB150073R0052
Built in Function:
50BF: stage1
50BF: stage2
Hardware:
PU: 4CT+16BI’S+12BO’S
Alstom United Kingdom--- Yes Relay Type:
MICOM P740 PU
Ordering code:
P74137NA6M0510K
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage2
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’S+8BO’S
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
MICOM P740
Ordering code:
P74331NA6M0510K
Built in Function:
50BF: stage1
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
HMI
DFR/SOE
Hardware:
PU: 4CT+16BI’s+12BO’S
IEC 61850, 2-PORTS
Ordering code:
7SS5220-4AB92-1CA0+L0R
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
7SS52x CU
Ordering code:
7SS5220-4AB92-1FA0+L0R
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
48 PU connected to CU
IEC 61850, 2-PORTS
Ordering code:
7SS5231-5CA01-1AA1
*BO=6 with double contact
Built in Function:
87BB: Biased Current Differential high speed BBP with built in
check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
PU: 4CT+16BI’s+12BO’S
Total = 3
Ordering code:
REL670*1.2-A31X00-H07P01-B1X-AX-KB-B-B6X0-D1A-XX-XE
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ordering code:
04214611XC2X43224XXXX
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
15BI+23 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Ordering code:
7SA6311-5BB92-2DM4+L0S
*with 20BI+09BO
**ONLY 67N
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67N
49 Thermal Overload
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total = 4
Ordering code:
HBFJAEAGNEA1BAA1XE
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Ordering code:
F650-NFD-F2G1-HI-6E
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Ten (10) years extended warranty from the date of PAC of the
first turnkey project in case of contract award and
subsequently reduced yearly in case of future project award .
This was confirmed in writing by the manufacturer through their
letter # NR-SEC-20110829-CL2 dated August 29, 2011.
Relay Type:
PCS 9611
Ordering code:
PCS-9611-A1C-1B1B3A3A2A
Built in Function:
Control & Mimic
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase unbalance 46
Under Current 37
27/59
Auto reclosure 79
50BF
Trip Circuit Supervision 74TC
Inrush Blocking
Under / over frequency 81
CT Supervision
60 (VT Fuse Supervision )
Sensitive earth element function
Second harmonic detection
DFR / SOE
Hardware:
16 BI+ 07 BO
3CT(Ph) + 1CT(GD)+3VT
IEC 61850, 2-Optical Ports PRP
Ordering code:
SEP888S84J33TNTLA
Along with Ordering Code, following optional modules needs to
be ordered..
1. MES120 (59715) #2 nos.
2. ACE850F0 interface module (59659) # 2 no.
3. ACE850 communication cable (CCA614) # 2 no.
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
14BI+6 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Ordering code:
04515611XC2X4H244XXXX
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Ordering code:
7SJ6411-5EB92-1FG1+L0S
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
15BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total = 6
Ordering code:
1MRK 002 814-AC
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BI’s+24BO’s
IEC 61850,2-PORTS
GE Multilin CANADA-Markham Yes Relay Type:
C70
Ordering code:
C70-K03-HKH-F8N-H6D-M8V-P67-U6D-W67
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BI’s+20BO’s
IEC 61850,2-PORTS
Ordering code:
0487V0X6111XC2X4H424XXX
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+15BI’s+23BO’s
IEC 61850,2-PORTS
Total = 3
Ordering code:
MVAJ101RA0802A
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Relay Type:
MVAJ
Ordering code:
MVAJ105RA0802A
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Ordering code:
LOR/HR-7810F
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Relay Type:
LOR
Ordering code:
LOR/SR-7868FD
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Ordering code:
TR241-7PG1524-1JC60-1AF0
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Relay Type:
TR
Ordering code:
TR212-7PG1521-2JC60-1AF0
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max of
5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Ordering code:
P54331NA7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs – 16 Inputs
Binary Outputs 14
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
MiCOM P543
Ordering code:
P54331NC7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs – 16 Inputs
Binary Outputs 14
CH-1 1300nm, CH-2 1300nm (up to 50km)
IEC 61850 -2 Ports
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-W77
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-W2B
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
•Type tests shall be carried out on the MiCOM P40 relays as per
Ordering code:
0411L1X6X1C7CCXH5C424XX (2KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
SEL411L
Ordering code:
0411L1X6X1C7DDXH5C424XX (24KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0A+N0A
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1.5km)
IEC 61850 -2 Ports
Relay Type:
7SD52
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0G+N0G
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports
Total = 6
Ordering code:
REC670*1.2-A30X00-A02C31P02-B1-AA-KB-B-B6X0-D1A-XXX-X
E
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+6U
24BO
16BI
IEC 61850,2-Optical Ports (PRP)
Relay Type:
REB650
Ordering code:
1MRK006520-AD
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+4U
27BO
18BI
IEC 61850,2-Optical Ports (PRP)
Ordering code:
MCAG34VCD*****A
Built in Function:
87 3-Phase High Z Differential (Current Base)
External CT Bus Wire Supervision
External stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
3 CT Inputs
2 Output Contacts
Relay Type:
MCAG
Ordering code:
MCAG14SSD**** *A
Built in Function:
87 3-Phase High Z Differential
(Current Base)
External CT Bus Wire Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 CT Phase Inputs
2 Output Contacts
Relay Type:
MFAC
Ordering code:
MFAC34V1B*0001A
Built in Function:
87 3-Phase High Z Differential
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
3 elements / phases voltage based
2 Output Contacts
Relay Type:
MFAC
Ordering code:
MFACI4S1B*0001A
Built in Function:
87 3-Phase High Z Differential.
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 elements / phases voltage based
4 Output Contacts
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Ordering code:
7SJ6411-5EB92-1FE0+L0S
Built in Function:
87 3-Phase High Z Differential
(based on current)50/51N
Internal CT Bus Wire Supervision
(based on current )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
4 CT Inputs
13BO
15BI
IEC 61850, 2-Optical Ports (PRP)
Total = 4
Ordering code:
RK 251 204-AP (125V DC)
RK 251 204-AN (110v DC)
Built in Function:
CT Shorting
Hardware:
Alstom United Kingdom--- Yes Relay Type:
MVTP31
Ordering code:
MVTP31V1CB0751E
Built in Function:
CT Supervision
Hardware:
Relay type VDF- 10, ordering code VDF- 10 125 VDC, built-in
function: Trip circuit supervision - single phase, LED indication
and two contacts.
Relay type VDJ- 30, ordering code VDJ- 30 125 VDC, built-in
functions: Trip circuit supervision - three phase, LED indication
and two contacts.
Relay type RJ-8, ordering code RJ-8 125 VDC Op: 01101,
built-in functions: Auxiliary Control, Self-Reset and (8)
contacts.
Relay type RF-4, ordering code RF-4 125 VDC Op: 01101,
built-in functions: Auxiliary Control, Self-Reset and (4)
contacts.
Relay type BJ-8 RP, ordering code BJ-8 RP 125 VDC, built-in
functions: CT shorting application, flag indication, electrical and
hand reset and (8) contacts.
Relay type BF-4 RP, ordering code BF-4 RP 125 VDC, built-in
functions: CT shorting application, flag indication, electrical and
hand reset and (4) contacts.
Ordering code:
7PG1110-7AE10-0AF0
Built in Function:
CT Shorting
Hardware:
Total = 4
31. 7. 11 Bus Coupler and Bus Section 110 kV to 380 KV Applicable Standards:
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Total = 1
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Total = 1
•Type tests shall be carried out on the MiCOM P40 relays as per
new IEC 61850-10 (2012-12) edition 2 in the approved
Independent Testing laboratory witnessing by three (3)
National Grid SA engineers and one (1) approved Independent
Agency Inspector (IIA). All costs of witnessing the tests shall
be borne by the manufacturer as per their confirmation through
letter # Nil dated October 23, 2013.
Total = 1
Total = 1
Total = 1
31 .8 TERMINAL BLOCK
Wieland Electric GmbH GERMANY-Bamberg Yes Based on S&SD letter# 13-05908-30504401 dated December
04, 2013, it is pre-qualified for terminal blocks as conforming to
National Grid SA specification # 31-TMSS-06, Rev.0 with the
following condition:
Total = 5
31 .9 FAULT RECORDERS
Total = 2
Total = 3
SAS Equipment:
3. Bay Controller Unit (BCU) type SEL 451 from SEL –U.S.A is
with ordering code 04515611XC2X4H64444X1.
SAS Equipment:
Total = 6
32 METERS
• Software for both meters [(E650 (ZXD) & E850 (ZXQ)] shall be
MAP120 and MAP110 .
SIEMENS GERMANY Yes
Total = 7
Total = 7
ADVANCE ELECTRONICS CO., LTD. Saudi Arabia-Riyadh Yes Based on approval of Executive Directive for TS&SD Letter #
08-1105-03032301 dated 20/10/2008, it is pre-qualified for
Energy Meters Type (ADDAD-4) & Quality Meters Type
(SEL-734).
ALFANAR ELECTRICAL SYSTEMS Saudi Arabia-RIYADH Yes (AMI)
AMR
· ITS Integration & Test Facility: as per item# 3.a of ITS letter#
L1-NG01-J13-003 dated January 26, 2013.
• E650 (ZXD) & E850 (ZXQ) [This meters are approved for
Revenue Meter application only].
• Software for both meters [(E650 (ZXD) & E850 (ZXQ)] shall be
MAP120 and MAP110 .
Total = 7
33 CAPACITOR
33 .1 SHUNT CAPACITOR
Seven (7) years warranty from the date of PAC of the turnkey
project in case of contract award or date of delivery in case of
direct material supply order.
ALSTOM Grid Ltd. FINLAND-Tampere Yes Previously " Nokian Capacitors Ltd. –Finland", the name has
been changed to Areva T&D Ltd. –Finland based on TS&SD/ESD
Letter # 10-00145-03032301 dated January 16, 2010 and
Areva T&D Ltd.-Finland Letter # Nil dated January 04, 2010,
then the name has been changed again to ALSTOM Grid Ltd. –
Finland based on Dept Mgr, S&SD E-mail dated February 26,
2012 and ALSTOM Grid Ltd. letter # RN-2012-02-18 dated
February 18, 2012.
COOPER (MCGRAW-ED) United States Yes
Total = 6
34 ELECTRONIC COMPONENTS
Total = 1
35 INSTRUMENT TRANFORMERS
KONCAR INSTRUMENT TRANSFORMERS INC. Croatia/Hrvatska-- Yes All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.
KUHLMAN ELECTRIC CORPORATION United States Yes RING/SPLIT CORE TYPE
MEMF Saudi Arabia-RIYADH Yes TS&SD letter# 09-00918-03032301 dated 29 March 2009 it is
prequalified for CT up to 36kV with the following conditions:
TYPE TEST SHALL BE DONE AT AN INTL. TESTING LAB IN
PRESENCE OF 3RD PARTY INSPECTOR;
EXTENDED GUARANTEE/ WARRANTY FOR 10 YEARS FROM
PAC.
PFIFFNER SWITZERLAND Yes RING/SPLIT CORE TYPE
SADTEM FRANCE Yes RING/SPLIT CORE TYPE & BLOCK TYPE CTs UP TO 36kV.
Total = 12
35 .2 69KV CTS
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply; 10 Years Warranty from the
date of PAC is required.
Electrotecnica Arteche SPAIN-Mungia Yes Based on S&SD Letter 12-03192-02-30504001 dated February
19, 2012, it is pre-qualified for 69 kV Current Transformers
(CTs) as confirming to SEC Specification # 50-TMSS-01 Rev.0
with the following conditions:
KONCAR INSTRUMENT TRANSFORMERS INC. Croatia/Hrvatska-- Yes All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.
KUHLMAN ELECTRIC CORPORATION United States Yes RING/SPLIT CORE TYPE
TRENCH ITALIA ITALY-N/A Yes PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL
TYPE
Total = 19
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
Electrotecnica Arteche SPAIN-Mungia Yes Based on S&SD Letter 12-03192-02-30504001 dated February
19, 2012, it is pre-qualified for 110 – 132 kV Current
Transformers (CTs) as confirming to SEC Specification #
50-TMSS-01 Rev.0 with the following conditions:
TRENCH ITALIA ITALY-N/A Yes PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL
TYPE
Total = 16
35 .4 230KV CTS
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
Total = 14
35 .5 380KV CTS
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
PFIFFNER SWITZERLAND Yes Based on TS&SD letter# 09-01105-03032301 dated 24th June
2009, it is pre-qualified for CT & CVT rated up to 380kV as
confirming to SEC specification # 50-TMSS-01, rev.0 & #
50-TMSS-02, rev.0 respectively with the following conditions:
• All type, routine & special tests including the load test shall
be carried out on the first batch to be supplied to SEC in
securing an order in an independent testing laboratory in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.
• Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of delivery in
case of direct material supply order.
SADTEM FRANCE Yes RING/SPLIT CORE TYPE
TRENCH ITALIA ITALY-N/A Yes PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO); OIL
TYPE
Total = 14
36 POTENTIAL TRANSFORMER
Electrotecnica Arteche SPAIN-Mungia Yes Based on S&SD Letter 12-03192-02-30504001 dated February
19, 2012, it is pre-qualified for 33 kV & 34.5 kV Potential
Transformers (PT) as confirming to SEC Specification
#50-TMSS-03 Rev.0 with the following conditions:
• All Type, Routine and Special testes shall be carried out the
complete tests in one (1) sample of the first batch of 33 kV &
34.5 kV Potential Transformers (PT) in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
KONCAR INSTRUMENT TRANSFORMERS INC. Croatia/Hrvatska-- Yes All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.
Total = 14
36 .2 69 KV POTENTIAL TRANSFORMERS
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
• All Type, Routine and Special testes shall be carried out the
complete tests in one (1) sample of the first batch of 69 kV
Potential Transformers (PT) in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
KONCAR INSTRUMENT TRANSFORMERS INC. Croatia/Hrvatska-- Yes All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.
NISSIN JAPAN Yes
Total = 11
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
• All Type, Routine and Special testes shall be carried out the
complete tests in one (1) sample of the first batch of 110 – 132
kV Potential Transformers (PT) in an Independent Testing
Laboratory in the presence of three (3) SEC Engineers & one
(1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed by the manufacturer through
their letter # Nil dated April 28, 2011G.
KONCAR INSTRUMENT TRANSFORMERS INC. Croatia/Hrvatska-- Yes All Type, Special, Routine tests per SEC Standards and IEC to
be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.
NISSIN JAPAN Yes
Total = 11
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
Total = 10
ALSTOM Grid United States-Waynesboro Yes Type test required in first supply;10 Years Warranty from the
date of PAC is required.
Total = 8
37 INSULATING OIL
PETROMIN CORPORATION (Petrolube) Saudi Arabia-Jeddah Yes Previously "PETROLUBE", the name has been change to
PETROMIN CORPORATION (Petrolube) - Saudi Arabia based on
PETROMIN CORPORATION letter # Nil dated 30/06/2010.
SAVITA INDIA Yes
SHELL GERMANY-Hamburg Yes - previously Shell (France), The location has been changed to
Hamburg, Germany Based on the manufacturer email dated
19/08/2013.
Total = 7
37. 2. 0 INSULATING OIL FOR LOW PRESSURE OIL FILLED (LPOF) CABLES Applicable Standards:
39 TELECOMMUNICATION EQUIPMENT
39. 1. 1 SYSTEM INTEGRATION AND TESTING OF COMMUNICATION/SCADA EQUIPMENT Applicable Standards: 48-TMSS-06
ABB Automation Co. Ltd Saudi Arabia-Riyadh Yes Based on S&SD letter # 15-01367-01-30504401 dated 8th
March-2015, the manufacturer is prequalified for ‘Integration
(Assembly) & Testing of Communication Equipment from Original
Equipment Manufacturer (OEM) type tested & approved by
SEC/National Grid SA’ as conforming to National Grid SA
specification # 48-TMSS-06, Rev.0 with the following condition:
Total = 3
-----------------------------------------------------------------------
GE Industrial System CANADA-Ontario Yes Based on TADD letter# 09-0297-030225 dated 28th March
2009; (Note: GE Industrial System, Canada has bought only the
Lentronics business from Nortel, Canada that manufactures
TN1U SHD Fiber Optic Terminal Equipment and MUX)
HUAWEI TECHNOLOGIES CO.LTD. CHINA-Shenzhen Yes Based on TS&SD Letter # 10-F01736/02-03032301 dated
18/08/2010 & S&SD Letter # 14-06894-01-30504401 dated
22/10/2014, it is prequalified for (OSN
Series:1500,2500,3500,7500,9500 and iManager T2000NMS)
with the following conditions:
Total = 17
Total = 4
39 .2 DWDM SYSTEM
Alcatel Lucent ITALY-Trieste Yes Based on S&SD letter # 15-0010-02-30504401 dated 12th
February 2015, the manufacturer is prequalified for DWDM
equipment Type 1830 PSS-32 as conforming to National Grid SA
specification # 48-TMSS-08, Rev.0 with the following condition:
Total = 1
39. 3. 1 SYSTEM INTEGRATION AND TESTING OF SDH EQUIPMENT Applicable Standards: 48-TMSS-09
Total = 2
39 .8 DC POWER SYSTEMS
Total = 4
39 .9 TELEPHONE EXCHANGE
Total = 3
Total = 1
Total = 1
39. 9. 4 PABX”S TELEPHONE SETS, COMMUNICATION CABLES AND ACCESSORIES Applicable Standards:
Total = 5
Total = 1
Total = 6
39 . 11 TELE-PROTECTION SYSTEM
DIMAT SPAIN-Barcelona Yes Based on TS&SD Letters# 09-01439-2-03032301 dated 7th July
2009 & 10-00845-1-03032301 dated April 04, 2010. It is pre-
qualified for Tele-protection Equipment type TPU-1 with the
following conditions:
• Five (5) years Extended Warranty.
SIEMENS GERMANY Yes
Total = 4
Total = 1
39 . 12 VF INTERFACE EQUIPMENT
Total = 2
Total = 8
39 . 14 TEST EQUIPMENT
Total = 8
Total = 1
Total = 2
Total = 1
Total = 8
39 . 19 UHF RADIO
Total = 3
Total = 3
40 .1 FM 200 SYSTEM
Total = 2
•All Type, Routine and Special testes shall be carried out on the
first batch of Fire Protective Signaling Panel in an Independent
Testing Laboratory in the presence of three (3) SEC Engineers
& one (1) SEC approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated January 09,
2011.
Total = 11
40. 2. 1 DELUGE VALVE, SPRAY NOZZLE, ALARM VALVE AND SPRINKLERS Applicable Standards:
Total = 5
Total = 5
AURORA United States Yes LOCAL AGENT –SAUDI PUMP >= 500 GPM
FAIRBANK MORSE United States Yes LOCAL AGENT –SAUDI PUMP >=500GPM
Total = 8
40 .5 FOAM SYSTEM
Total = 3
40 .6 FIRE EXTINGUISHER
Total = 2
Total = 3
Total = 2
Total = 1
Siemens Building Technologies – Fire Safety United States-New Jersey Yes Originaly was PYROTRONICS from USA.
Local Agents are: Siemens Building Technologies (SBT) &
SASEEQ
SIMPLEX United States Yes LOCAL AGENT –NAFISCO
Total = 7