Clean Agent System
Clean Agent System
Clean Agent System
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 2 of 17
CONTENTS
3.7 PAINTING
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 3 of 17
The work shall include electrically actuated automatic Clean Agent Fire
Extinguishing System complete with clean agent cylinders, manifolds, pressure
reducing devices, cylinder valves, directional valves, pipes, discharge nozzles,
brackets supports, hangers and such other fittings as necessary for complete
installation of the system including chipping of existing RCC/brick walls of control
room buildings, fixing fasteners, etc. The system shall also comprise of both
Automatic and Manual actuation, cancellation facility etc. with necessary control
panel.
Complete Fire Detection and alarm system is in the scope of this requisition. The
clean agent shall be discharged/actuated automatically after a adjustable time delay
based on the detection signal received. The delay shall be maximum 180 seconds,
however it shall be adjustable from 0 to 180 seconds.
It may be noted that clean agent system to be provided shall meet the requirements
of NFPA-2001 (Latest). Hence any thing specified as “mandatory” in NFPA-2001,
although not specifically mentioned in this specification, shall form part of this
specification and scope of work for the job to be executed.
Vendor shall design the system to meet the minimum requirements of total flooding
fire extinguishing clean agent system as per NFPA-2001 and having design
concentration as specified at 70°F(21 °C).
The system design shall be centralised and shall protect other risk as defined in the
requirements and scope of work of the project.
The centralised system of a station shall be designed to protect any of the risk
(volume wise) in a particular room of a building as defined in Annexure-I to this
specification.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 4 of 17
The quantity of Clean Agent gas provided shall be sufficient to protect the single
largest risk in each building with 100% standby filled up cylinders. The system shall
have its own storage, distribution piping, nozzles, alarm, and actuation system, etc.
Integrity / leakage test shall be done prior to discharge and all major leakage
sealed. The design concentration shall take into account all leakage.
Both primary and standby supply shall be permanently connected to the distribution
piping through manifold and arranged for easy and auto changeover.
As the system is designed for the largest risk and there are several risks varying in
size in particular building, the system shall permit use of required no. of cylinders for
any individual risk involved so that the concentration of gas in that risk does not
exceed the design concentration specified in the table below.
TABLE
PROPERTIES OF INERT GAS AGENTS USED AS FIRE EXTINGUISHING AGENTS
The min. Oxygen concentration shall be maintained after release of clean agent (IG)
as 16%.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 5 of 17
FM/UL/LPC/VDS) and TAC. The system design shall be within the manufacturers
listed limitations. System design including computerised flow calculations , piping &
storage layout of Clean Agent System shall be submitted along with the technical
bids.
Minimum design concentration of Clean Agent gas shall be 37.5%(min) for IG-541,
55, 01 and 100 at 70°F by volume unless otherwise specified by the agent
manufacturer for clean agent fire extinguishing system.
The Clean Agent storage cylinders shall be designed to hold clean agent at ambient
temperatures. Container shall be of approved type and freshly imported. Minimum
container design level working pressure of storage container shall be as per clause
2.1.4 and table A-2-1.4.1 of Appendix-A to NFPA-2001. The containers shall not be
charged to a fill density or superpressurisation ( superpressurisation means the
addition of a gas to fire suppression agent container necessary to achieve the
pressure required for proper system operation) level different from manufacturer’s
listing.
The vendor shall standardised the capacity of cylinder for better replacement &
inter-changeability.
The design pressure for cylinders shall be suitable for the maximum pressure
developed at 130° F (55°C) at the max. controlled temperature limit.
Each container shall have a permanent name plate specifying the agent, tare and
gross weight in addition to the pressurisation level, and nominal agent volume.
All clean agent cylinders shall be seamless and bear the mark of manufacturer,
serial number and shall be duly listed by a competent approval authority of country
of origin (FM/UL/VDS/LPC) in addition to approval by CCE Nagpur (India).
Cylinders without the approval will not be accepted. A reliable means of
indication, other than weighing shall be provided to determine the pressure in
refillable containers.
Each container shall have pressure relief valve to protect the cylinders against
excess pressure conditions.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 6 of 17
ii) A reserve battery of cylinders with manifold, directional valve and automatic
change over to any of the two banks after actuation shall be provided. The
reserve of standby Clean Agent battery shall be 100% of the quantity
required for the single largest risk as per scope of work.
Automatic means such as check valve shall be provided to prevent agent loss if the
system is operated when any containers are removed for maintenance.
The manifolded containers referred to above shall be securely mounted on the floor
and suitably supported in a rack with provision for convenient individual servicing
and content weighing according to the manufacturers installation manual. Such
servicing or weighing shall be possible without shutting down the system.
---------------------------------------------------------------------------------------------------------------------------------------------------------------
PR : STANDS FOR PRESSURE REDUCER ; WLD : STANDS FOR WELDED CONNECTION
PIPE THICKNESS CALCULATION SHALL BE AS PER ASME B31.1 POWER PIPING CODE AND FITTINGS SHALL CONFORM TO ANSI
B1.20.
Discharge nozzles shall conform to cl.2.2.5 of NFPA. Discharge nozzles used in this
system shall be listed for the use intended for discharge characteristics. The
selection of nozzle orifice shall be such that the 95% of of IGs is discharged within
60 seconds through the number of nozzles of the system. Each nozzle shall be
permanently marked to identify by the part number, orifice code, or other suitable
marking as specified by the authority having jurisdiction.
The vender to note that the clean agent piping to be laid in existing building, hence
the clean agent piping and nozzles etc. shall have to be planned clearing other
facilities coming in the areas where clean agent protection is being envisaged. The
different items that are to be provided for efficient functioning of the automatic clean
agent system have been indicated but not the quantity of any of them, which has to
be worked out by the contractor.
The clean agent piping shall have to clear:
The vendor shall have to lay the clean agent piping in existing building. All
necessary civil works including breaking the Blast resistant RCC wall and brick
walls and making them good shall be in the scope of work.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 7 of 17
Fire detection, actuation and alarm system for the system shall be as per NFPA-
2001 latest revision.
There shall alarm in clean agent local control panel at the time of gas release.
3.7 PAINTING
d) The clean agent cylinders shall be mounted on front and firmly supported
in brackets in a manner that they will not be easily subjected to
mechanical chemical or other damage, which would render the system
in-operative.
g) i) A signal shall be provided from the clean agent control panel to shut
off the air handling unit and air conditioning dampers/louvres.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 8 of 17
The system shall have a main control console and shall consist of:
I) Two alarms and one fault indicator lamp for each zone
to be protected.
The following additional provisions shall be made in the main control panel:
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 9 of 17
APPROVAL OF INSTALLATION
The completed system shall be tested to meet the approval of Owner. The entire
clean agent system shall be TAC (Tariff Advisory Committee, India) approved &
vendor to obtain the same. Only listed or approved equipment and devices shall be
used in the systems. All critical equipments such as cylinders, cylinder valves,
directional valves, pressure reducers, nozzles, actuation controls, pressure gauges
etc. shall have listings(FM/UL/Vds/LPC) To determine that the system has been
properly installed and will function as specified, the following tests shall be
performed:
a. A thorough visual inspection of the installed system and hazard area. The
piping, operational equipment and discharge nozzles shall be inspected for
proper size and location. The locations of alarms and manual emergency
releases shall be confirmed. The configurations of the hazard shall be
compared, to the original hazard specification. The hazard shall be inspected
closely for unclosable openings and sources of agent loss which may have been
overlooked in the original specifications.
Vendor shall provide suitable safety measures against increase in pressure inside
the protected area due to release of clean agent.
- System design including computerised system flow calculations, piping & storage
layout .
- Certificates of agencies who have accorded approval for the elements offered.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 10 of 17
- Calculations for pipe sizes, time of discharge, flow, nozzle rate of discharge etc.
- GA and dimensional drawings of the areas showing storage, piping and nozzles
for various areas.
- If the vendor is collaborating with any foreign party for basic engineering, design
etc., he should provide certificate of collaboration and first submission of design
and detailed drawing shall be approved by the collaborator.
- List of drawings.
The bid must include in the quoted price the following mandatory spares to be
supplied with the clean agent system:
Recommended Spares:
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 11 of 17
c) Fire alarm and detection system with back up consultant for inert gas
- The bidder shall very clearly mention in his offer that he has considered total
flooding centralised system with directional valves and also have offered 100%
standby Cylinders.
- All equipment shall be approved by FM/UL/VDS/LPC & TAC and cylinder shall be
seamless and CCE approved.
- Vender not having direct experience, shall produce along with offer the
collaboration Certificate.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 12 of 17
ANNEXURE-I
FF : FALSE FLOOR
FC : FALSE CEILING
MR : MAIN ROOM
NOTE: The actual size of rooms and height of FF, FC & MR shall be reviewed
from architectural drawings and actual Clean Agent quantities shall
be Calculated by Contractor before execution of the job.
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 13 of 17
ANNEXURE-II
a) Manufacturer : C
c) Capacity :
(Preferably:- IG-01,55,541 &100 : 435cuft filled with 439cuft of gas
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 14 of 17
a) Manufacturers
iii. Valves : C
c) Design Code
f) Directional Valve
g) Discharge Nozzles
h) Pressure Gauge
i. Make : C
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 15 of 17
i) Pressure Reducer
i. Make : C
j) Cylinder valve
i. Make : C
i. Make : C
3.6.2 Detectors
i. Manufacturer : C
ii. Type : C
iii. Number : C
i. Type : C
ii. Manufacturer : C
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 16 of 17
i. Manufacturer : C
ii. Code/Standard : C
iii. Type : C
iv. Size : C
v. Rating : C
i. Manufacturer : C
v. Cable Entry : C
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved
DOCUMENT No.
SPECIFICATION FOR CLEAN
AGENT SYSTEM (2001) 6544-00-16-47-SP02 Rev. B
Page 17 of 17
i) Alarm Accept : C
ii) Reset : C
p) Painting (External/Internal) : C
d) Non-destructive operational
tests for all devices included. : C
Format No. EIL 1641-1924 Rev. 1 Clean Agent- spec. Copyright EIL – All rights reserved