Equipment Grounding
Equipment Grounding
1
TABLE 1: Minimum Size Equipment Conductors for Grounding
Raceway and Equipment
Rating or Setting of
Automatic Overcurrent Grounding Conductor Size (mm2)
Device in Circuit Ahead
of Equipment, Not Copper Wire Aluminum or Copper-
Exceeding (Amperes) Clad Aluminum Wire
15 2 3.5
20 3.5 5.5
30 5.5 8
40 5.5 8
60 5.5 8
100 8 14
200 14 22
300 22 30
400 30 38
600 38 60
800 50 80
1000 60 100
1200 80 125
1600 100 200
2000 125 200
2500 200 325
3000 200 325
4000 250 400
5000 400 600
6000 400 600
2
1. ANSI / IEEE Std. 242-1986 Excerpts
8.4 Short-Circuit Protection of Cables: A cable must be protected
from overheating due to excessive short-circuit current flowing in its
conductor.
8.4.1.2 Maximum Short-Circuit Currents: Generally, the subtransient
current of a system is used to designate the maximum available short-circuit
current in the cables protected by the instantaneous overcurrent relays and the
medium-voltage switchgear circuit breakers. For cables protected by fuses, or
low-voltage and instantaneous trip circuit breakers, the asymmetrical current
value is used. For delayed tripping of 0.2 second or longer, the rms value of
the delayed current over the flow period of fault current is used.
234.5 T2
2
I SC
t 1.18 10 5 log 10
A 234.5 T1
Where:
ISC = Short circuit current in amperes
A = Size of cable in mm2
t = Tripping time of the protective device in second
T2 = Short-circuit current temperature rating of the cable in 0C
T1 = Continuous temperature rating of the cable in 0C
3
Table 2: Estimated Clearing Times of Protective Devices
4
5