SIP5 Operating V07.80 Manual C003-9 en
SIP5 Operating V07.80 Manual C003-9 en
SIP5 Operating V07.80 Manual C003-9 en
Table of Contents
Index
C53000-G5040-C003-9
NOTE
i For your own safety, observe the warnings and safety instructions contained in this document, if available.
Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-
tenance of automation, selective protection and control equipment, and operational crew in electrical installa-
tions and power plants.
Scope
This manual applies to the SIPROTEC 5 device family.
Further Documentation
[dwprefom-221012-01.tif, 3, en_US]
• Device manuals
Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The printed
manual and the online help for the device have the same informational structure.
• Hardware manual
The Hardware manual describes the hardware building blocks and device combinations of the SIPROTEC 5
device family.
• Operating manual
The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.
• Product information
The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each SIPROTEC 5 device.
• Engineering Guide
The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the Engi-
neering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update the
functionality of the SIPROTEC 5 device.
• SIPROTEC 5 catalog
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.
Indication of Conformity
This product complies with the directive of the Council of the European Communities
on harmonization of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use
within specified voltage limits (Low Voltage Directive 2014/35/EU).
This conformity has been proved by tests performed according to the Council Directive
in accordance with the product standard EN 60255-26 (for EMC directive) and with the
product standard EN 60255-27 (for Low Voltage Directive) by Siemens AG.
The device is designed and manufactured for application in an industrial environment.
The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.
Other Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see certified.ul.com
Select Online Certifications Directory and enter E194016 as UL File Number.
[ul_listed_c_us, 1, --_--]
Additional Support
For questions about the system, please contact your Siemens sales partner.
Support
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
E-Mail: [email protected]
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD
Humboldtstraße 59
90459 Nürnberg
Germany
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.
NOTE
i Important information about the product, product handling or a certain section of the documentation
which must be given particular attention.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
• Proper storage, setup and installation
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not
provide any technical support for the Product if it has been modified.
When using DIGSI 5 in online mode, you are provided with the option to go to the main menu Show open
source software information and read and display the Readme_OSS file containing the original license text
and copyright information.
To do this, the following steps are necessary:
• Switch to online mode.
• Select the device.
NOTE
i To read the Readme_OSS file, a PDF viewer must be installed on the computer.
In order to operate SIPROTEC 5 devices, a valid DIGSI 5 license is required.
Preface.......................................................................................................................................................... 3
1 First Steps................................................................................................................................................... 15
1.1 Unpacking, Repacking, Returning, and Storing...................................................................16
1.2 Incoming Inspection .........................................................................................................18
1.3 Electrical Inspection.......................................................................................................... 19
2 Expanding Devices..................................................................................................................................... 21
2.1 Flush-Mounting Devices.................................................................................................... 22
2.1.1 Basic Rules for Expansion............................................................................................. 22
2.1.2 Expanding 1st Device Row........................................................................................... 23
2.2 Surface-Mounted Devices with Integrated On-Site Operation Panel.................................... 24
2.2.1 Basic Rules for Expansion............................................................................................. 24
2.2.2 Expanding 1st Device Row........................................................................................... 25
2.3 Surface-Mounted Devices with Detached On-Site Operation Panel..................................... 28
2.3.1 Basic Rules for Expansion............................................................................................. 28
2.3.2 Expanding 1st Device Row........................................................................................... 29
8.5 Logs................................................................................................................................136
8.5.1 General..................................................................................................................... 136
8.5.2 Operational Log.........................................................................................................137
8.5.3 Fault Log................................................................................................................... 139
8.5.4 Ground-Fault Log...................................................................................................... 140
8.5.5 Setting-History Log.................................................................................................... 142
8.5.6 User Log.................................................................................................................... 144
8.5.7 Security Log.............................................................................................................. 145
8.5.8 Device-Diagnosis Log.................................................................................................146
8.5.9 Communication Log.................................................................................................. 148
8.5.10 Communication-Supervision Log................................................................................149
8.5.11 Motor-Starting Log.................................................................................................... 150
8.5.12 Saving and Deleting the Logs..................................................................................... 152
8.6 Edit Measured and Metered Values..................................................................................154
8.6.1 Overview of Measured and Metered Values................................................................154
8.6.2 Reading Measured Values and Metered Values........................................................... 155
8.6.3 Setting and Resetting Energy Values.......................................................................... 157
8.6.4 Setting and Resetting User-Defined Metered Values................................................... 158
8.6.5 Resetting Min./Max./Average Values...........................................................................159
8.6.6 Setting and Resetting Statistical Values...................................................................... 159
8.7 Fault Recording...............................................................................................................161
8.7.1 General..................................................................................................................... 161
8.7.2 Reading Fault Records................................................................................................161
8.7.3 Displaying Fault Records............................................................................................ 162
8.7.4 Saving and Exporting Fault Records............................................................................163
8.7.5 Deleting Fault Records............................................................................................... 164
8.7.6 Recording a Test Fault Record.................................................................................... 164
8.7.7 Configuration of Fault-Record Channels..................................................................... 164
8.7.8 Configuration of the Start Criterion............................................................................ 165
8.8 Change Device Settings...................................................................................................167
8.8.1 Date and Time Synchronization..................................................................................167
8.8.2 Setting Time and Date .............................................................................................. 167
8.8.3 Setting Time Keeping Parameters ..............................................................................168
8.8.4 Status and Monitoring of Time Keeping .....................................................................170
8.8.5 Setting the Contrast of the Device Display.................................................................. 171
8.8.6 Changing the Language on the Device....................................................................... 171
8.8.7 Changing Confirmation IDs........................................................................................ 173
8.8.8 Setting Function Settings...........................................................................................174
8.8.9 Settings Group Switching...........................................................................................177
8.9 Control System on Site.................................................................................................... 180
8.9.1 General..................................................................................................................... 180
8.9.2 Menu Structure......................................................................................................... 180
8.9.3 Switching Authority .................................................................................................. 181
8.9.4 Switching Mode ........................................................................................................181
8.9.5 Control with Graphic Display......................................................................................182
8.9.6 Control with Small Display......................................................................................... 183
9 Commissioning......................................................................................................................................... 189
9.1 Overview........................................................................................................................ 190
9.2 Test Suite Integrated in the Device.................................................................................. 191
9.2.1 Test Functions........................................................................................................... 191
9.2.2 Testing Current and Voltage Inputs............................................................................ 192
9.2.3 Testing Protection Functions......................................................................................193
9.2.4 Creating Signals for Communication Interfaces.......................................................... 195
9.2.5 Testing Switching Devices..........................................................................................195
9.2.6 Circuit-Breaker Test....................................................................................................197
9.2.7 Device Information and Diagnosis.............................................................................. 197
9.3 Initial Startup.................................................................................................................. 200
9.3.1 Establishing Readiness for Operation State.................................................................200
9.3.2 Using a Project with DIGSI 5....................................................................................... 200
9.3.3 Initializing Device and Verifying Basic Status.............................................................. 201
9.3.4 Testing Readiness for Operation.................................................................................202
9.4 Secondary Tests.............................................................................................................. 203
9.4.1 Scope of Inspection and Methodology....................................................................... 203
9.4.2 Recommendation for Testing of Functions ................................................................ 203
9.4.3 Testing Interfaces in the Compound System...............................................................205
9.5 Primary Tests.................................................................................................................. 206
9.5.1 Testing System Integration........................................................................................ 206
9.5.2 Methodical Procedure for Primary Tests of Functions..................................................208
9.5.3 Testing Measured Values During Operation................................................................ 209
Glossary.................................................................................................................................................... 265
Index.........................................................................................................................................................269
NOTE
i Devices are tested prior to delivery. The test certificate is a component of the devices and can be called up
with DIGSI.
Devices are packed on site in a way that meets the requirements of standard ISO 2248.
² Check the packaging for external transport damage. Damaged packing may indicate that the devices
inside have also sustained damage.
² Unpack devices carefully; do not use force.
² Check the devices via a reception control to ensure they are in perfect mechanical condition.
² Check the enclosed accessories against the delivery note to make sure everything is complete.
² Keep the packing in case the devices must be stored or transported elsewhere.
² Return damaged devices to the manufacturer, stating the defect. Use the original packaging or transport
packaging that meets the requirements of standard ISO 2248.
Repacking a Device
² If you store devices after reception control, they must be packed in appropriate storage packaging.
² If the device is to be transported, pack it in transport packaging.
² Enclose the accessories supplied and the test certificate in the package with the device.
Returning a Device
² Return devices to the manufacturer, stating the defect. Use the original packaging or transport packaging
that meets the requirements of the standard ISO 2248. Send damaged devices to the following address:
Siemens AG
EM DG PRO MF Rückwaren
Rohrdamm 7
13629 Berlin
Germany
² Ensure that the devices are either shipped with the original current and voltage terminals or, alternatively
– if the wired terminals are to remain in the system – with the designated transport safety devices.
If there are green single-row voltage terminals, it is irrelevant in terms of transport whether or not they
are plugged in. They do not require any alternative transport safety device.
² Protect the optical interfaces on the communication or arc protection modules against the ingress of
dust. Use, for example, the protective caps provided in the delivery condition.
Storing a Device
² Only store devices on which you have carried out an incoming inspection, This action ensures that the
warranty remains valid. The incoming inspection is described in the Operating manual.
² SIPROTEC devices must be stored in rooms, which are clean and dry. Devices or associated replacement
modules must be stored at a temperature of -25 °C to +55 °C.
² The relative humidity must be at a level where condensed water and ice are prevented from forming.
² Siemens recommends that you observe a restricted storage temperature range of +10°C to +35°C, in
order to prevent the electrolytic capacitors used in the power supply from aging prematurely.
² If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2 days.
This action will cause the electrolytic capacitors to form on the printed circuit board assemblies again.
² If devices are to be shipped elsewhere, you can reuse the transport packaging. When using different
packaging, you must ensure that the transport requirements according to ISO 2248 are met. Storage
packing of the individual devices is not adequate for transport purposes.
² The lithium batteries contained in SIPROTEC devices meet all international requirements of the hazardous
goods specifications for the various carriers (Special Provision 188 of the UN Recommendations on the
Transport of Dangerous Goods, Special Provision A45 of the IATA Dangerous Goods Regulations, and the
ICAO Technical Instructions). This action only applies to the original battery or genuine replacement
batteries.
Battery Disposal
NOTICE
Battery disposal
² Batteries can only be replaced by ones of the same type or by batteries of another type recommended
by the manufacturer. Replacing with the wrong type can cause an explosion hazard. Comply with the
relevant national/international regulations when disposing of batteries.
² The lithium battery contained in the device can only be replaced by skilled personnel.
² Only replace the battery with VARTA or Panasonic CR 2032 or BR 2032 batteries. If you use a different
type of battery, this can cause a fire or explosion hazard. Observe the safety notes in the manual.
² Caution: The battery used in the device can cause fire or chemical burns if handled improperly. Do not
recharge it, take it apart, or subject it to a temperature in excess of 100 °C.
² Replace dead batteries immediately and keep them out of reach of children.
Safety Notes
! DANGER
Danger during incoming inspection
Noncompliance with the safety notes, can result in death, severe injury or considerable material
damage.
² Comply with all given safety notes when carrying out the incoming inspection.
² Please note that hazardous voltages are present when you perform the incoming inspection.
² If you identify a defect during the incoming inspection, do not rectify it yourself. Repack the device and
return it to the manufacturer, stating the defect. Use the original packaging or transport packaging that
meets the requirements of standard ISO 2248.
! DANGER
Danger when connecting the SIPROTEC 5 device
Noncompliance with the safety notes will result in death, severe injury or considerable material
damage.
² The device must be situated in the operating area for at least 2 hours before you connect it to the
power supply for the first time. This prevents condensate from forming in the device.
² If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to
2 days. This will cause the electrolytic capacitors to form on the printed circuit-board assemblies again.
NOTE
i The battery is covered by a protective film, which also prevents premature discharge.
The battery compartment is located on the rear of the base module. You do not have to take the battery
out of the compartment in order to remove the protective film.
Grounding a Device
The SIPROTEC 5 devices are protection class I equipment must be connected with the system ground prior to
commissioning.
² Ground each module with solid low-impedance system grounding (cross-section ≥ 4.0 mm2
(≥ 0.0062 in2), grounding area ≥ M4, torque: at least 1.2 Nm).
² To ensure the electromagnetic compatibility (EMC) of the device, Siemens recommends fitting the
neutral point of the grounding to the base module.
Connecting a Device
² Connect all cables and lines. Use the connection diagrams in the Hardware and Device manuals.
² Tighten the terminal screws to the prescribed torques .
Safety Notes
! DANGER
Danger during electrical inspection
Noncompliance with the safety notes will result in death, severe injury or considerable material
damage.
² Comply with all given safety notes when carrying out the electrical inspection.
² Please note that hazardous voltages are present when you perform the electrical inspection.
² During the electrical inspection, check that the device becomes ready for operation once it has been
connected to the power supply.
NOTE
[dweinzei-030211-01.tif, 2, --_--]
Preparation
NOTE
i Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre-
sponding extension in the Hardware and Protocols Editor.
Carry out the steps described in this chapter if you wish to expand an installed device later on with expan-
sion modules.
NOTE
• Always fit the on-site operation panel of the base module on the left.
• Always fit the on-site operation panels of the expansion modules from left to right.
• Always fit the on-site operation panel of the expansion module with the key switches in the 1st place
next to the on-site operation panel of the base module.
• Join the on-site operation panels to one another with 2 mounting brackets.
• Always install a power-supply module PS203 on the right as the first unit in the 2nd device row.
• Note that the PS203 must always have the same rated voltage as the base module.
• In the 2nd device row, you do not need any on-site operation panels, mounting brackets, or distance
frames.
NOTE
i When expanding a device in the 1st device row, order 2 mounting brackets that match the width of the
expanded device.
[dwauize1-040211-01.tif, 2, --_--]
Preparation
NOTE
i Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre-
sponding extension in the Hardware and Protocols Editor.
Carry out the steps described in this chapter if you wish to expand an installed device later on with expan-
sion modules.
NOTE
i If the device is an expanded device, then detach the 2 mounting brackets. You must replace these
mounting brackets with 2 new mounting brackets that match the width of the device.
² Use a screwdriver to carefully bend the left and right spring clips on the terminals outwards.
² Completely detach the wired current and voltage terminal blocks from the device.
² Remove all communication lines.
[dwaublo1-040211-01.tif, 2, --_--]
² Place the 2 mounting brackets intended for expansion in parallel to one another on a flat surface.
² Bolt the 1st (left-hand) on-site operation panel to the 2 mounting brackets. Do not firmly tighten the
screws.
² Place the 2nd on-site operation panel on the right of the 1st one and screw these panels onto the 2
mounting brackets. Do not firmly tighten the screws. Make sure that the snap-in spring is engaged!
² Bolt the 2 operation panels to one another through the contact tab. Do not firmly tighten the screws.
² Repeat the last 2 steps for the remaining operation panels. Leave all screws loose.
² Fit the device back onto the wall without fastened on-site operation panels.
² Use the supplied grounding cable to connect the expansion module with the device and reconnect the
device to service ground.
² Fasten the connecting cable for the on-site operation panel on the extreme left-hand operation panel of
those on-site operation panels assembled beforehand into a block.
² Place the block of assembled operation panels on the distance frames of the device. In doing so, guide
the connecting cable for the on-site operation panel through the cut-outs of the distance frame to the
terminal of the base module.
² Fasten the connecting cable for the on-site operation panel to the base module.
² Bolt the operation panels to the distance frames and firmly tighten the screws.
² Tighten all loose screws on the contact tabs and on the mounting brackets.
² Reinstall all plastic screw covers.
² Extend the device configuration in DIGSI and load it to the device.
² Resume operation of the device.
NOTE
• Always fit the on-site operation panel of the base module on the left.
• Always fit the on-site operation panels of the expansion modules from left to right.
• Always install a power-supply module PS203 on the right as the first unit in the 2nd device row.
• Note that the PS203 must always have the same rated voltage as the base module.
• The distance between the device and the on-site operation panel is limited to not more than 5 m (196.85
in) by the length of the connecting cable.
[dwauizei-040211-01.tif, 1, --_--]
[dwabosop-040211-01.vsd, 2, en_US]
Preparation
NOTE
i Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre-
sponding extension in the Hardware and Protocols Editor.
Carry out the steps described in this chapter if you wish to expand an installed device later on with expan-
sion modules.
NOTE
i The device and the on-site operation panel can be expand independently of one another. Therefore, you
need only detach those components that are to be expanded.
² Swivel the expansion module in the direction of the device so that the bottom snap-in spring engages.
² Bolt the on-site operation panels of the 2 modules to one another through the contact tab.
² Check that the bus connection is screwed on at the extreme left of the expansion module.
[dw_z1_1-3, 2, en_US]
Figure 3-1 Cut-Out Widths and Drilling Pattern – 1/3 Device, 1st Device Row
[dw_z1_1-2, 2, en_US]
Figure 3-2 Cut-Out Widths and Drilling Pattern – 1/2 Device, 1st Device Row
[dw_z1_2-3, 2, en_US]
Figure 3-3 Cut-Out Widths and Drilling Pattern – 2/3 Device, 1st Device Row
[dw_z1_5-6, 2, en_US]
Figure 3-4 Cut-Out Widths and Drilling Pattern – 5/6 Device, 1st Device Row
[dw_z1_1-1, 3, en_US]
Figure 3-5 Cut-Out Widths and Drilling Pattern – 1/1 Device, 1st Device Row
All drillings in the area of the specific device cut-out widths (see Table 3-1) must comply with the dimensions
in the corresponding figures.
[dw_z2_2-6, 2, en_US]
Figure 3-6 Cut-Out Widths and Drilling Pattern – 1/3 Device, 2nd Device Row
[dw_z2_3-6, 2, en_US]
Figure 3-7 Cut-Out Widths and Drilling Pattern – 1/2 Device, 2nd Device Row
[dw_z2_4-6, 2, en_US]
Figure 3-8 Cut-Out Widths and Drilling Pattern – 2/3 Device, 2nd Device Row
[dw_z2_5-6, 2, en_US]
Figure 3-9 Cut-Out Widths and Drilling Pattern – 5/6 Device, 2nd Device Row
[dw_z2_6-6, 3, en_US]
Figure 3-10 Cut-Out Widths and Drilling Pattern – 1/1 Device, 2nd Device Row
Figure 3-11 Drilling Pattern – 1/1 Devices, 1st and 2nd Device Row
Siemens recommends a drilling space of at least 55 mm (2.17 in) between the 1st and 2nd device row. Due to
the connecting-cable length, the maximum space may be approx. 80 mm (3.15 in). The length of the cable is
890 mm (35.04 in) from the center of the plug to the center of the plug.
Figure 3-12 Angle Rail for Connection of the 1st and 2nd Device Row
Dimension a
Housing Widths in mm (in Inches)
(Total Width: Housing Width + 4.6 mm (0.18 in))
1/3 device 145 (5.71)
1/2 device 220 (8.66)
2/3 device 295 (11.61)
5/6 device 370 (14.57)
1/1 device 445 (17.52)
[dw_surface_mounting_in, 2, en_US]
Figure 3-13 Flush-Mounting Devices, Dimensions from the Side and Front Views
Preparations
NOTE
i The installation depth for 1 device is at least 275 mm (11.83 in). This dimension includes the necessary
bending radius for the various connectors of the plug-in modules.
The M4 holes are the holes for the fastening screws of the device. The Ø 6 holes are the openings for the
fastening screws of the on-site operation panels on the device.
NOTE
! WARNING
Danger due to device being improperly screw-fastened
Incomplete and careless screw-fastening can lead to death, severe injury, and considerable material
damage.
² Ensure that screw-fastening is complete at all intended bolting points. Tighten the screws to a torque
of 1.2 Nm.
² If no assembly opening is prepared, then cut out the required assembly opening.
² Produce the holes as shown in the drilling plan.
Fitting Devices
² Detach the top and bottom plastic screw covers of each on-site operation panel.
² Insert the device in the installation opening. Make sure that the fastening screws of the on-site operation
panels also protrude exactly into the openings (6-mm diameter (0.24-in diameter)).
² With the M4 oval head cap screws, bolt down the device at the top and bottom at all 4 bolting points of
each module.
² Check for secure attachment.
² Fit the top and bottom plastic screw covers again.
NOTE
i The battery is covered with a protective film to protect it from mechanical damage and against premature
discharge.
The battery need not be removed from the battery compartment for activation.
! DANGER
Danger due to device being improperly grounded
Incomplete and careless grounding leads to death, severe injury, and considerable material damage!
² The device must be situated in the operating area for at least 2 hours before you connect it to the
power supply for the first time. This method prevents condensation of water in the device.
² If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2
days. This will cause the electrolytic capacitors to form on the printed circuit board assemblies again.
² Ground each module with solid low-impedance system grounding (cross-section ≥ 4.0 mm2 (0.16 in2),
grounding area ≥ M4).
Connecting Devices
² Connect all cables and leads. Use the connection diagrams in the Hardware and Device manuals.
² Tighten the terminal screws to the prescribed torques.
NOTE
i Make sure that the cables and lines of extra-low voltage circuits are laid sufficiently far away from power
network circuits.
[dwosopin-070211-01.tif, 3, en_US]
Figure 3-14 1/3 Surface-Mounted Device with Integrated On-Site Operation Panel, Dimensions in the Side
and Front Views
NOTE
i For surface-mounted devices, make sure that the drillings fit for a screw of the size M6.
[dwbohrge-1_3.vsd, 2, en_US]
Figure 3-15 Drilling Pattern of a 1/3 Surface-Mounted Device – 1st Device Row
[dwbohrge-1_2.vsd, 2, en_US]
Figure 3-16 Drilling Pattern of a 1/2 Surface-Mounted Device – 1st Device Row
[dwbohrge-2_3.vsd, 2, en_US]
Figure 3-17 Drilling Pattern of a 2/3 Surface-Mounted Device – 1st Device Row
[dwbohrge-5_6.vsd, 2, en_US]
Figure 3-18 Drilling Pattern of a 5/6 Surface-Mounted Device – 1st Device Row
[dwbohrge-070211-01.tif, 3, en_US]
Figure 3-19 Drilling Pattern of a 1/1 Surface-Mounted Device – 1st Device Row
[dw_z2_bohr_1-3.vsd, 2, en_US]
Figure 3-20 Drilling Pattern of a 1/3 Surface-Mounted Device – 2nd Device Row
[dw_z2_bohr_1-2.vsd, 2, en_US]
Figure 3-21 Drilling Pattern of a 1/2 Surface-Mounted Device – 2nd Device Row
[dw_z2_bohr_2-3.vsd, 2, en_US]
Figure 3-22 Drilling Pattern of a 2/3 Surface-Mounted Device – 2nd Device Row
[dw_z2_bohr_5-6.vsd, 2, en_US]
Figure 3-23 Drilling Pattern of a 5/6 Surface-Mounted Device – 2nd Device Row
[dw_z2_bohr_1-1.vsd, 2, en_US]
Figure 3-24 Drilling Pattern of a 1/1 Surface-Mounted Device – 2nd Device Row
Figure 3-25 Non-Modular Surface-Mounted Device with Integrated On-Site Operation Panel, Dimensions
from the Side and Front Views
NOTE
i For surface-mounted devices, make sure that the drillings fit for a screw of the size M6.
* The 149 mm are valid if several mounted consoles are to be mounted next to each other.
Preparations
NOTE
i Siemens recommends detaching the on-site operation panels before fitting the device. Fit the on-site oper-
ation panels after completing wiring and checks.
NOTE
! DANGER
Danger due to device being improperly screw-fastened
Incomplete and careless screw fitting results in death, severe injury, or considerable material
damage!
² Ensure that screw-fastening is complete at all intended bolting points. Tighten the screws to a torque
of 1.2 Nm.
Fitting Devices
² First bolt the bottom fastening screws into the wall.
² Lower the bottom mounting bracket of the device onto the bottom fastening screws.
² Align the device in the oblong holes. Ensure that screw-fastening is complete at all intended bolting
points.
² Screw the device onto the top mounting bracket with the fastening screws.
² Check for secure attachment of the device on the wall.
NOTE
i The battery is covered with a protective film to protect it from mechanical damage and against premature
discharge.
The battery need not be removed from the battery compartment for activation.
Grounding Devices
! DANGER
Danger due to device being improperly grounded
Incomplete and careless grounding leads to death, severe injury, and considerable material damage!
² The device must be situated in the operating area for at least 2 hours before you connect it to the
power supply for the first time. This method prevents condensation of water in the device.
² If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2
days. This will cause the electrolytic capacitors to form on the printed circuit-board assemblies again.
² Ground each module with solid low-impedance system grounding (cross-section ≥ 4.0 mm2 (≥ 0.16 in2),
grounding area ≥ M4).
Connecting Devices
² Connect all cables and leads. Use the connection diagrams in the Hardware and Device manuals.
² Tighten the terminal screws to the prescribed torques.
NOTE
i Make sure that the cables and lines of extra-low voltage circuits are laid sufficiently far away from power
network circuits.
[dw_z1_osop_1-3, 1, en_US]
Figure 3-27 Drilling Pattern of the On-Site Operation Panel of the 1/3 Device
[dw_z1_osop_1-2, 1, en_US]
Figure 3-28 Drilling Pattern of the On-Site Operation Panel of the 1/2 Device
[dw_z1_osop_2-3, 1, en_US]
Figure 3-29 Drilling Pattern of the On-Site Operation Panel of the 2/3 Device
[dw_z1_osop_5-6, 1, en_US]
Figure 3-30 Drilling Pattern of the On-Site Operation Panel of the 5/6 Device
[dw_z1_osop_1-1, 1, en_US]
Figure 3-31 Drilling Pattern of the On-Site Operation Panel of the 1/1 Device
[dwosopab-070211-01.tif, 3, en_US]
Figure 3-32 Surface-Mounted Device with Detached On-Site Operation Panel, Dimensions in the Side and
Front Views
Preparations
NOTE
i The distance between the installation location of the device and that of the on-site operation panel must
not exceed 5 m.
Join the on-site operation panels to one another with firm contact. Siemens recommends the use of
contact washers on painted metal assembly walls. If the assembly wall is not metallic, place a metal layer,
for example a metal sheet, between the assembly wall and the on-site operation panel; then connect this
sheet to system ground.
NOTE
! DANGER
Danger due to device being improperly screw-fastened
Incomplete and careless screw fitting results in death, severe injury, or considerable material
damage!
² Ensure that screw-fastening is complete at all intended bolting points. Tighten the screws to a torque
of 1.2 Nm.
² Produce the holes in the assembly wall to fit the device. The drill holes must be so large that they can
accept a screw with a shank diameter of 6 mm.
² Produce the holes in the assembly wall to fit the on-site operation panel.
² Cut a recess into the assembly wall for the connecting cable. The connecting cable links the on-site oper-
ation panels to the device.
² Place a metallic layer such as a metal plate on the assembly wall if it is not metallic.
NOTE
i Join several on-site operation panels to one another with firm contact. Siemens recommends the use of
contact washers on painted metal assembly walls. If the assembly wall is not metallic, place a metal layer,
for example a metal sheet, between the assembly wall and the on-site operation panel; then connect this
sheet to system ground.
² Plug the connecting cable into the on-site operation panel of the basic module.
² Guide the connecting cable through the cut-out in the assembly wall.
² Place the 2 contact washers on the top fastening holes.
² Bolt down the on-site operation panels connected to one another on the assembly wall.
² Check for secure attachment of the on-site operation panels on the assembly wall.
NOTE
i The battery is covered with a protective film to protect it from mechanical damage and against premature
discharge.
The battery need not be removed from the battery compartment for activation.
Grounding Devices
! DANGER
Danger due to device being improperly grounded
Incomplete and careless grounding leads to death, severe injury, and considerable material damage!
² The device must be situated in the operating area for at least 2 hours before you connect it to the
power supply for the first time. This method prevents condensation of water in the device.
² If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2
days. This will cause the electrolytic capacitors to form on the printed circuit board assemblies again.
² Ground each module with solid low-impedance system grounding (cross-section ≥ 2.5 mm2 (≥ 0.1 in 2),
grounding area ≥ M4).
Connecting Devices
² Connect all cables and leads. Use the connection diagrams in the Hardware and Device manuals.
² Tighten the terminal screws to the prescribed torques.
NOTE
i Make sure that the cables and lines of extra-low voltage circuits are laid sufficiently far away from power
network circuits.
4.1.1 Fasteners
The fasteners of the plug-in modules are shown in the following figure regarding the example of an installed
module and an empty, covered slot.
[le_fxing_elements, 1, --_--]
4.1.2 Installation
NOTE
i Reordered modules are not contained in the original device configuration. Use DIGSI to perform the corre-
sponding extension in the Hardware and Protocols Editor.
Preparing Installation
! DANGER
Danger due to live voltage when installing the plug-in modules.
Noncompliance with the safety notes will result in death or severe injuries.
² Install plug-in modules on the electrically deactivated device only.
! CAUTION
Exercise caution with laser beams of the optical plug-in modules.
Noncompliance with the safety notes can result in medium-severe or slight injuries.
² Do not look directly into the optical fiber terminals of the active optical plug-in modules, not even with
optical devices. The laser beams can damage the eyes.
NOTE
i When using optical communication modules, Laser class 1 is maintained in compliance with EN 60825-1
and EN 60825-2 when using optical fibers ≤ 62.5 μm/125 μm.
When using the ARC-CD-3FO module, Laser class 1 is maintained in compliance with EN 60825-1 and
EN 60825-2 when using 1 mm plastic optical fibers.
² In the case of a surface-mounted device with integrated on-site operation panel, remove the entire on-
site operation panel.
² Undo the fastening screw and remove the cover plate from the plug-in module position.
Completing Installation
² Resume operation of the device.
4.1.3 Removing
Accessories
NOTE
² Order the module cover plate set of parts to cover the unused plug-in module position.
Preparing Removal
! DANGER
Risk of live voltage when removing the plug-in modules.
Noncompliance with the safety notes will result death or severe injuries.
² Remove plug-in modules on the electrically deactivated device only.
! CAUTION
Exercise caution with laser beams of the optical plug-in modules.
Noncompliance with the safety notes can result in medium-severe or slight injuries.
² Do not look directly into the optical fiber terminals of the active optical plug-in modules, not even with
optical devices. The laser beams can damage the eyes.
NOTE
i Laser class 1 is adhered to in compliance with EN 60825-1 and EN 60825-2, in the case of ≤ 62.5 μm/
125 μm optical fibers.
² In the case of a surface mounting device with integrated on-site operation panel, remove the on-site
operation panel before the base module.
Completing Removal
² In the case of a surface mounting device with integrated local operation panel, fit the on-site operation
panel of the base module again.
² Resume operation of the device.
4.1.4 Replacement
! DANGER
Danger due to live voltage when replacing the plug-in modules.
Noncompliance with the safety notes will result in death or severe injuries.
² Install plug-in modules on the electrically deactivated device only.
! CAUTION
Exercise caution with laser beams of the optical plug-in modules.
Noncompliance with the safety notes can result in medium-severe or slight injuries.
² Do not look directly into the optical fiber terminals of the active optical plug-in modules, not even with
optical devices. The laser beams can damage the eyes.
NOTE
i Laser class 1 is adhered to in compliance with EN 60825-1 and EN 60825-2, in the case of ≤ 62.5 μm/
125 μm optical fibers.
When using the ARC-CD-3FO module, Laser class 1 is maintained in compliance with EN 60825-1 and
EN 60825-2 when using 1-mm plastic optical fibers.
² In the case of a surface-mounted device with integrated on-site operation panel, remove the on-site oper-
ation panel before the base module.
² Remove all communication lines.
² Undo the fastening screw with which the plug-in module is fixed on the device.
² Insert a screwdriver (DIN 4 x 0.8) in the cut-out underneath the elongated hole in the assembly frame
and disengage the plug-in module.
² Carefully pull out the plug-in module.
Completing Replacement
² Place the device is service again and perform a firmware update of the communication modules.
NOTE
i If you have not cabled the optical fiber plug-in modules, then seal the terminals with protective covers. This
prevents soiling of the terminals.
5.1 General 68
5.2 Overview of Operator Elements and Display Elements 69
5.3 Displays for Indication and Control 77
5.4 Structure of the Menu 79
5.5 Menu Tree 80
5.6 Notification Windows and Dialogs 82
5.7 Displaying Device Mode 84
5.8 Display of Routings and Status 86
5.1 General
All SIPROTEC 5 devices can be operated via the DIGSI 5 interface of your PC and via the on-site operation
panel. This is available optionally as an integrated and detached on-site operation panel. The on-site operation
panel is characterized by a flat, compact design.
Variants
The on-site operation panel is composed of different modules depending on the hardware configuration of
the device. Operation is via the membrane keypad and the key switches. LEDs and displays in 2 different sizes
are available as elements of the display.
[dwosopva-040211-01.tif, 2, en_US]
Operating Concept
The operating concept allows you to do the following on-site operator control actions:
• Navigation in the menu tree
• Modification of settings
[le_base_module, 2, --_--]
Figure 5-2 Base and 1/3 Module in Standard, US, and China Design
The following table gives you a detailed explanation of the function of the operator and display elements.
Small display
Resolution: 192 x 128 pixels
Display: Alphanumeric characters
• Top
– Display entry above
• Bottom
– Display entry below
• Right
– Display level below
• Left
– Display level above
• Top
– Move forward by one display length
• Bottom
– Backward by a display length
• Right
– Display level below
• Left
– Back to the default display
Numerical keys
These keys are used to enter values and navigate in menus. According to
the numbering on the right display edge, you can jump directly into
submenus or carry out settings.
NOTE
i Note that terminating the contacts of saved output indications can lead to reactions in the device environ-
ment.
[dwerwmod-040211-01.tif, 2, --_--]
The following table gives you a detailed explanation of the function of the operator and display elements.
Operator Element/Display Element Meaning
16 parameterizable LEDs
• Monochrome (red)
• Monochrome (red)
Keypad
Besides the base module, you can fit an expansion module with key switches. The following table explains the
meanings of the switch positions.
Operator Element/Display Element Meaning
Key switch for on-site switching authority
• Local position
Switching commands for configured equipment are
possible only on site with the control keys or in the control
menu. You cannot execute switching commands remotely
(or from DIGSI).
• Remote position
Switching commands for configured equipment are
possible on site as well as remotely.
In devices with an expansion module with key switches the
corresponding options are static in the control menu.
Key switch for on-site switching mode
• OFF position
Unlocked switching of configured equipment allowed
• Normal position
Switching of configured equipment only with the designed
interlocking conditions
In devices with an expansion module with key switches the
corresponding options are static in the control menu.
• Texts
• Graphical elements
NOTE
Default Displays
In the idle state, that is, provided there is no fault, the display with DIGSI 5 can show configurable operating
information (for example, operational measured values). If preconfigured in DIGSI 5, display images can be
suppressed by spontaneous displays in the event of a fault.
A device ready for operation will show you the following display image after booting. This presupposes you
have not parameterized a display image with DIGSI 5. The standard display image (default display) is parame-
terized and defined in DIGSI 5. If a parameterized and defined display image exists, it is displayed after
booting.
[scligrdi-080413-01.tif, 1, en_US]
You reach the standard display diagram at any time (exception: in case of fault) by holding down the left navi-
gation key.
If several display images are available, you can select them in order of parameterized sequence by pressing the
right and the left navigation keys.
Control Displays
In devices with large graphic display, entire control displays can also be graphically depicted. The control
displays can graphically and dynamically update the switch position of switching objects. In addition, control
displays offer you the possibility of selecting individual switching objects and activating them according to
switching authority and switching mode.
[scabzstb-100211-01.tif, 1, en_US]
A ready-to-run device with large graphic display shows you the control display defined as the standard after
booting. By pressing and holding down the left navigation key, you get to the control display defined as
standard. By pressing the control key, you get to the control mode of the currently displayed control display.
NOTE
i The switching device in control mode is selected by pressing the following navigation keys:
• Top
• Bottom
You can leave control mode via the softkey Exit. If no keys are pressed for 15 minutes, the default display is
automatically activated and control mode is reset.
If there are multiple displays, you can use the left and right navigation buttons to toggle between the displays.
If the device was previously in control mode by pressing the CTRL key, this mode is maintained so that you can
also activate a 2nd and another control display. Control mode is reset after a switching procedure or after a
period of 15 minutes without a switching operation.
For this see the description of the navigation keys in Table 5-1.
[scmnuebr-030914-01, 2, en_US]
Main Menu
The main menu structure is firmly set and is not changeable. The submenus
depend on the hardware configuration and the configuration of functions.
Logs Menu
In the Logs menu, the available logs recording events in the operating state
of the device are offered.
You will find information about reading and deleting logs in chapter
8.4.1 General.
Measurements Menu
Control Menu
NOTE
i The Switching mode and Switching authority submenus are not offered if the device has key switches to
the on-site control.
The Control menu offers all mechanisms for on-site control. Access to indi-
vidual equipment (for example, circuit breakers) and the settings with
respect to interlocking mechanisms, switching authority and switching
mode is via submenus.
You will find information about controlling equipment and resetting saved
binary outputs and LEDs in chapter 8.4.1 General.
Settings Menu
The Settings menu is used for changing and adapting protection settings in the device. The menu follows a
usability (for example, request for acceptance after leaving certain menu levels).
NOTE
i All visible settings are assigned to a certain adjustable settings group. You can view the number of settings
groups and set the activation of one of the settings groups in the General submenu.
Selecting the Binary I/O menu provides you with the option to see the
routing to the binary inputs, binary outputs and signals displayed.
You can find more information in chapter 5.8 Display of Routings and
Status.
Communication Menu
The Communication menu is used for changing and adapting communication settings for the mainboard and
the communication modules in the device. The menu follows a usability (for example, request for acceptance
after leaving certain menu levels).
NOTE
Via the Device functions menu, you can set the operating modes of the
device or of individual functions (for example, test), initiate resetting of
stored LEDs and binary outputs, change passwords and make regional
settings (date and time, display formats).
The Test & Diagnosis menu offers you support during commissioning and
testing. If you wish to test systems and equipment on site, you can read all
necessary information from the corresponding submenus and start actions
such as device reset.
You can find more information on this in chapter 10.5 Test and Diagnostics.
[scmitfen-080413-01.tif, 1, en_US]
Dialogs
Dialogs are interactive notification windows in the base bar. In the dialogs, you are prompted to actively carry
out actions. A dialog consists of the following elements:
• Dialog designation
• Two softkeys (bottom left and right)
[scdialpa-080413-01.tif, 1, en_US]
[scdiawrt-080413-01.tif, 1, en_US]
If a command prompt is shown in the dialog, then you can activate the functions in the following list by
pressing the softkeys below each function.
Softkey Function Softkey Function
Left Right
Delete Delete log Enter Confirm value
Escape Cancel current action OK Confirm action
Log off Log off Log in Log in
Start/Test Start an action Menu Main Menu
Switch Switch equipment Change Change value
NOTE
i If you do not confirm the dialog with a softkey, the action you wish to achieve is canceled after a previously
set time. The prior state is restored.
• Serial number
NOTE
i You may only initialize the device via DIGSI 5 and only then via the USB connection of your SIPROTEC 5
device.
Initialized Device
The device can be in the following modes:
• Commissioning mode
• Simulation mode
• Process mode
• Fallback mode
In normal operation (process mode), the device is presented as described in chapter 5.4 Structure of the Menu
NOTE
i The device can change mode during commissioning, testing or in the event of a device failure. The mode
deviating from normal operation is shown respectively in the title bar of the device display. The name of
the mode is shown flashing in the top line of the device display (except in fallback and process mode):
• Commissioning mode
• Simulation mode
Take note of the information about these modes in chapter 9 Commissioning and chapter 10 Maintenance,
On-the-Spot Assistance and Test.
Commissioning Mode
The commissioning mode of the SIPROTEC 5 device allows you to check the existing wiring without affecting
or blocking the protection functions or other functions of the device. You can select the commissioning mode
manually.
You can find more information in Chapter 9.2.2 Testing Current and Voltage Inputs.
In commissioning mode, you can also check the communication with system-control technology. You can
generate test signals with the communication test in DIGSI by setting signals to be transmitted systematically
in the transmitter and checking their receipt.
You can find more information in chapter 9.4.3 Testing Interfaces in the Compound System.
Simulation Mode
In the simulation mode of the device, you can check the correct setting of protection functions and the
routing of signals. You can perform simple checks without wiring or using DIGSI. To do so, connect the device
to DIGSI and generate test sequences. You can perform the tests on the device without external test equip-
ment. The DIGSI test sequences simulate the change of values at the inputs to the device.
You can also feed in the test signals using a digital test equipment. Digital test equipment offers you multiple
test programs and test sequences.
Process Mode
The process mode is the normal operation of the device.
• Use the navigation keys of the on-site operation panel to navigate within the displayed list and select one
of the 3 following menu entries:
– Binary inputs
– Binary outputs
– LEDs
[scbinipt4-260814-01, 1, en_US]
The following examples show how to proceed when reading the on-site operation panel and how to set the
DIGSI for the binary input in the information routing.
• Select the menu item Binary inputs.
All available binary inputs of the SIPROTEC 5 device will be displayed. Furthermore, following the equal
sign, the current status of the binary input is displayed (see Figure 5-11).
The following table shows the meaning of the status of the individual menu entries Binary inputs, Binary
outputs and LEDs.
Menu Item Status Description
Binary input X Input is active
- Input is not active
Binary output X Output is active (contact is closed)
- Output is not active (contact is open)
LED X LED is switched on
- LED is switched off
The status of the respective binary inputs, binary outputs or the LEDs is updated automatically by the actual
state in the device.
[scbinipt5-260814-01, 1, en_US]
• Use the navigation keys to select the binary input, for example, Binaryinput1.1.
All signals routed to Binaryinput1.1 are displayed as a list (see Figure 5-13).
Example of a Signal
• Go to the information routing in DIGSI 5 and select the properties H or L for the input >Ext. trip
initiation off.
This status will also be displayed on the on-site operation panel of the SIPROTEC 5 device. Figure 5-12 and
Figure 5-13 shows you the routing of the signal >Ext. trip initiation, for stage 1.
[scranma1-260814-01, 1, en_US]
Figure 5-13 shows that [L] active without voltage for the signal >Ext. trip initiation was
parameterized. In the Line function group, the Overvoltage protection (ANSI 59) is also operated. In addi-
tion, the Binaryinput1.1 can also block this protection function. The blocking function will become active with
[H] active with voltage.
[scbinipt1-260814-01, 1, en_US]
[scranma2-260814-01, 1, en_US]
The following figure shows an example of the routing of the circuit-breaker switch position. Here, the Bina-
ryinput1.1 shows the closed circuit-breaker switch position 1. [GH] indicates that the voltage on binary input
1.1 is active and signals a closed circuit breaker.
[scbinipt2-260814-01, 1, en_US]
[scranma3-260814-01, 1, en_US]
The figure below indicates that Binaryinput1.1 displays the position of the transformer tap changer 1.
[scbinipt3-260814-01, 1, en_US]
6.1 General 92
6.2 Operator Actions in the Offline and Online Area 94
6.3 Initializing a Device 96
6.4 Transferring Device Data from the PC to the Device 97
6.5 Changing Data on the Online Device 99
6.6 Retrieving Fault Records and Log Contents 100
6.1 General
DIGSI 5 is the engineering and operating tool for all SIPROTEC 5 devices. With DIGSI 5, you create system
topologies, configure hardware and communication networks and perform many other tasks.
You carry out all engineering tasks offline from your PC without needing a SIPROTEC 5 device. You transfer all
data online to the device later – for example, directly via a communication network or the USB interface. For
communication between DIGSI 5 and the SIPROTEC 5 device, secure TCP-IP connections are used.
Operation of DIGSI in version 5 is even more user-friendly. Project tree, editors, libraries and property window
are integrated smoothly into a common interface. You can adjust this interface to your operation.
[scproans-110413-01.tif, 1, en_US]
DIGSI 5 manages all components of a system and all associated data depending on the project. The following
values are summarized under one project name (extract):
• Topology
• Devices
• Setting values
• Communication settings
• Process data
That means you must open a project file and thus have all data available. Vice versa you save all changes of
any type with only one mouse click.
On the interface you see a project with symbols that are integrated into a hierarchical project structure. These
symbols represent:
• Individual devices
• Editors
• Setting sheets
• Tables
• Actions
• Folder
You have access to all data and tools via the individual symbols. A double-click is enough and the symbols will
show setting values of protection functions, start actions such as loading of parameter values or open one of
the editors.
DIGSI 5 is available in 3 variants. Please refer to the order catalog and the DIGSI 5 online help for the exact
functional scope. DIGSI 5 Premium offers, among others, the following possibilities:
• Managing all SIPROTEC 5 devices of a system in a project
• Defining the primary topology in a Single-Line Editor
• Simple setting of protection settings and control of setting values via zone diagrams
NOTE
i To avoid unintentional changes and switching operations during operation, some operator actions are
protected by a confirmation ID.
Protect access to your protection devices using a secure connection password. This will prevent undesirable
changes by third parties.
• Routing information
• Transferring indications, measured values and fault records from the SIPROTEC device to the PC and
saving in files
NOTE
i If you change setting values or routings in online devices, you must activate them in the device. This
ensures consistent acceptance of data.
NOTE
i Initialization is possible, for example, via the USB interface or port J of the device.
NOTE
i The physical connection between PC and SIPROTEC 5 device may be done only 1 to 1. If your PC has several
free USB interfaces, you can connect only one single SIPROTEC 5 device. Otherwise, no connection to the
devices is established. If you set up a hub between PC and the SIPROTEC 5 devices, no connection to the
devices is established either.
Connect the top USB port on the front panel of the on-site operation panel of the base module of SIPROTEC 5
devices to the engineering PC using a suitable USB cable. If you have connected the protection device to your
PC, you can initialize the device with the help of DIGSI 5.
• Select the relevant offline configuration in a DIGSI 5 project by selecting the device name.
• Open the context menu by right-clicking.
• The offline configuration is thereby transferred to the device and the offline configuration in the DIGSI 5
project connected via the serial number of the device.
Check whether there is a connection between your DIGSI 5 project and your device. If you wish to compare
the serial number in the editor and the device information with the label of the device, proceed as follows:
² Double-click in the project tree the Device information tab under the device. You will find the serial
number in the General section.
NOTE
i If the protection devices are connected to the engineering PC, the transfer of device data to one or more
devices is possible. For this purpose, you must initialize the devices once with DIGSI 5.
If you would like to transfer device data from the PC to the device, then connect the device to the PC. You can
use the following terminals for this purpose:
• USB port on the on-site operation panel of the base module
• Any Ethernet interfaces of the device
² Check whether there is a connection between your DIGSI 5 project and your device.
² Compare the serial number in the editor and the device information to the label of the device.
² To do this, double-click in the project tree the Device information menu item under the device. You will
find the serial number in the General section.
[scipadrs-080413-01.tif, 1, en_US]
² Connect, for example, the Ethernet port J on the rear of the SIPROTEC 5 base module to the engineering
PC using a suitable Ethernet cable.
² In the project tree of your DIGSI 5 project, double-click the Devices and networks menu item.
² In the network view, you will find all devices of your project with the offline configurations. Select the
device with which you would like to connect and click the green-edged field of the displayed device (see
Figure 6-2).
² Enter the IP address, subnet mask and optionally the IP address of a router (standard gateway).
² In the project tree of your DIGSI 5 project, double-click the Load configuration in devices menu item.
Execute this in the corresponding offline configuration of the device.
DIGSI 5 recognizes automatically that the device is connected via Ethernet. The loading of the configuration
from the DIGSI 5 project to the device is then initiated.
NOTE
i If you wish to use another Ethernet interface port other than port J, in Device Information select the inter-
face with which DIGSI 5 should communicate with your SIPROTEC 5 device.
Alternatively, you can select the following path for the setting of the Ethernet address.
[scipruec-030311-01.tif, 1, en_US]
² Connect, for example, the Ethernet port J on the rear of the SIPROTEC 5 base module to the engineering
PC using a suitable Ethernet cable.
² In the project tree of your DIGSI 5 project, double-click the Devices and networks menu item.
² You will find all devices of your project with the offline configurations in the Device view tab. Select the
device with which you would like to connect and click the Ethernet port of the displayed device (see
Figure 6-3).
² Enter the IP address, subnet mask and optionally the IP address of a router (standard gateway).
² In the project tree of your DIGSI 5 project, double-click the Load configuration in devices menu item.
Execute this in the corresponding offline configuration of the device.
DIGSI 5 recognizes automatically that the device is connected via Ethernet. The loading of the configuration
from the DIGSI 5 project to the device is then initiated.
NOTE
i If you wish to use another Ethernet interface port other than port J, in Device information select the inter-
face with which DIGSI 5 should communicate with your SIPROTEC 5 device.
7.1 General
Apart from the use of an engineering tool such as DIGSI 5 or SICAM TOOLBOX II for configuration and mainte-
nance, SIPROTEC 5 devices provide a Web front end that can be used with a standard Web browser. The
browser-based user interface is a comprehensive commissioning and monitoring tool that provides an easy-
to-understand display of the most important measured data. You can operate the device remotely or locally
using the browser-based user interface and a Web browser.
The browser-based user interface can be used via a communication network:
• During commissioning
• During an inspection
• During operation with the devices at all ends of the object to be protected
The browser-based user interface is especially optimized for the protection system and provides comprehen-
sive support during testing and commissioning from the PC or laptop computer.
All relevant device information and setting options are displayed graphically on the screen.
7.2 Operation
If you are familiar with the structure of the settings in DIGSI 5 and the on-site operation, you will be able to
navigate through the same structure (for example, function groups, function blocks, and display on the on-site
operation panel).
The PC that you want to use to operate the SIPROTEC 5 device must be connected to the device via a network
cable. Both the PC and the SIPROTEC 5 device must be switched on.
Before operating the device via a Web browser, you first have to check the security settings. With the security
settings, you can restrict the access rights for the Web access (Port J and Ethernet communication module).
You can define the security settings in DIGSI in the project tree under Security → Restricted access.
You can assign the following access rights:
• Read access only:
This interface only allows read access to the device.
[sc_webaccess, 1, en_US]
To operate the device via a Web browser, perform the following steps:
• Connect the SIPROTEC 5 device (for example, Port J) to your PC using a network cable.
If the device has an Ethernet communication module, you can also use Port E, Port F, Port N, or Port P.
• Enter the IP addresses of the device in the address line of the Web browser followed by the port number
4443 (for example, https://172.16.60.60:4443). Confirm the entry using the ENTER key.
NOTE
i You can operate the SIPROTEC 5 device via DIGSI 5 and via the browser-based user interface in parallel.
The following logon dialogs are available, depending on the security configuration of the SIPROTEC 5 device:
• Variant 1:
If you have entered a connection password in DIGSI 5 under Operations safety and access control, the
dialog starts with the user name Siprotec 5. This user name cannot be changed. You must use the
connection password configured in DIGSI.
• Variant 2:
If you have configured the role-based access control (RBAC) in DIGSI 5 under Operations safety and
access control, the dialog starts with the request of the user name and password that were configured
on the RADIUS server.
• Variant 3:
If you have not configured the role-based access control (RBAC) or the connection password, the dialog
starts with the user name Siprotec 5. This user name cannot be changed. The entry field for the pass-
word must be left empty.
Once the Web browser is successfully connected to the device, the following dialog (RBAC) appears:
[scwebmonitor, 1, en_US]
• Select a language.
NOTE
i If the role-based access control (RBAC) is active, access is possible only after a successful user name and
password authentication check.
You can find more information on this in chapter 11.9 Operational Security and Access Control.
NOTE
i The language selection depends on the language set for the user interface of the device.
[scwebmonitor1, 2, en_US]
You can view the appropriate settings by selecting the individual entries.
NOTE
i If you do not undertake any action in the browser-based user interface within a defined time lapse, the
Web browser disconnects from the device. The following messages appear. After a certain time lapses, you
must log on to the device again using the Web browser (see Figure 7-4).
[scwebmonitor14, 1, en_US]
Button Meaning
Use this button to log off.
Button Meaning
Use this button to control an LED reset.
Use this button to start an export (for example, for operational indications).
Use this button to access the home screen and the list box.
Use these buttons to switch the measured and statistical values to primary,
secondary, or percentage values.
You can also navigate via the list box. You can directly open settings and information that you would like to
view.
[scnaviwebmon, 2, en_US]
The additional buttons of the browser-based user interface are described in the following:
• Device:
Information such as the product code or the firmware version of the device are displayed using the
SIPROTEC 5 button.
[scwebmonitor2, 2, en_US]
• Monitoring:
The following logs are displayed using the Logs button.
You can display the contents of a log by clicking the desired log. Depending on the device the following
logs are available:
– Operational log
– Fault log
– Ground-fault log
– User log 1, User log 2
– Setting-history log
– Motor-starting log
– Com supervision log
[scwebmonitor3, 2, en_US]
• Measured values:
3 buttons are available.
– Operational measured values:
An overview of the function groups is displayed via the Operational measured values button. The
measured values can be displayed by clicking the desired function group.
[scwebmonitor15, 2, en_US]
[scwebmonitor16, 2, en_US]
[scwebmonitor18, 2, en_US]
• Terminal assignment:
3 buttons are available.
– Binary inputs:
An overview of the connected binary inputs is displayed via the Binary inputs button. You can
display the assignment of the binary inputs for this module by clicking a button in the left section
(for example, base module).
[scwebmonitor10BI, 1, en_US]
[scwebmonitor10BO, 1, en_US]
– LEDs:
An overview of the connected LEDs is displayed via the LEDs button. You can display the assignment
of the LEDs for this module by clicking a button in the left section (for example, base module).
[scwebmonitor10LED, 1, en_US]
• Engineering:
An overview of the function groups is displayed via the Settings button.
The settings of a function group are displayed by clicking the appropriate button.
[scwebmonitor19, 2, en_US]
7.3 Example
To illustrate working with the browser-based user interface, the procedure is shown using the following
example (reading operational indications).
There must be a communication connection between the PC and the device.
• Establish the connection between the device and the PC.
• Using the Web browser, log on to the device.
• Select the Operational log item in the list box or the Operational log button.
[scwebmonitor11, 2, en_US]
[scwebmonitor4, 2, en_US]
• Checking a setting value against a user-defined setting as to whether the setting value differs from the
default value specified by Siemens
• Querying a value to adjust a test case, for example, to preset the tripping current
• Viewing all types of measured values, for example, measured values and derived values such as the
minimum/maximum and average values
7.5 Settings
You can set the parameters for the browser-based user interface separately for the communication interface
(Port J). If the device has an Ethernet communication module, you can also use Port E, Port F, Port N, or Port P.
The important parameters are the IP address and the port number of the interface used to communicate
between the PC and the browser-based user interface.
• Make sure that the 12-digit IP address for the Web browser has been correctly set using the format
***.***.***.*** via DIGSI.
8.1 Overview
This chapter describes the handling of a SIPROTEC 5 device in the operating state. It contains the following
information:
• Reading information from the device
• Affecting the functions of the device in the operating state
! DANGER
Danger due to inadmissible or improper operator control actions
Noncompliance with the safety notes will result in death or severe injuries.
² Only personnel who are skilled electricians with precise knowledge of the system may operate devices
during operation.
² Please carry out all operator control actions in the indicated sequence.
NOTE
i Operator control actions are password-protected (see chapter 11 Security Settings in the Device). This
ensures that only operational crew members with access rights can use the device during operation.
8.3.1 General
The device is operated via a DIGSI 5 PC or directly on the on-site operation panel. You have the following oper-
ating options during operation:
• Readout of indications
• Readout, backup, and deletion of logs and records
• Changing device settings such as date, time, display contrast (only on site on the device) and interface
language
• Controlling equipment
NOTE
i DIGSI 5 Communication
Operation using a DIGSI 5 PC requires a functioning communication connection from the DIGSI 5 PC to the
device. For this purpose, you can use the USB interface of the on-site operation panel, the integrated or
other Ethernet interfaces.
NOTE
• Changes to device settings and the deletion of process data can be saved by entering confirmation
IDs. If no action takes place within certain times (device: 3 minutes, DIGSI 5: 10 minutes), an open
confirmation query is automatically terminated. Every action carried out within these times restarts
the time. After a confirmation query has ended you must confirm changes in device settings again by
entering confirmation IDs.
• Before modified settings or the activation of control commands is accepted, there will be additional
requests to enter the confirmation ID. You acknowledge these requests directly on the on-site opera-
tion panel by pressing the softkey buttons. You confirm the interactive dialog in DIGSI 5 by mouse
click.
During online operation, you establish a direct connection to the device to be operated. You use this method
for:
• Commissioning
• Test and diagnostics
Procedure
² First identify all devices reachable via the PC communication interfaces. You can identify your device via
the DIGSI 5 project tree.
² Establish a connection to a selected device.
² If needed, you can assign a selected device to an existing project.
[scgerinf-220211-01.tif, 1, en_US]
[scwalger-110413-01.tif, 1, en_US]
• Resource consumption
• Time Information
• Diagnostic information
² If you click Update Device Data, you can read the parameter set and the process data of the device. The
device data is loaded and the view completed.
² You can fully operate and set the connected devices under Online access in the DIGSI 5 project tree.
NOTE
i Make sure that the created device coincides with the device identified online. Otherwise, it is not accepted
into the project.
² If you have not done so yet, add the online device to the opened project (see following image) via the
context menu (right mouse-click).
[scprohin-080916-01, 1, en_US]
Offline operation offers you the ability to carry out complete configurations and extensive parameterization of
a device. Once you have finished all settings, you can load the configuration from the DIGSI 5 PC to the device.
If the loading operation was successful, the device restarts automatically.
NOTE
i For a device to be editable offline, you must first have created it in a project. After successful loading of the
configuration, the device restarts automatically.
Procedure
² From the project tree, select the project containing the device to be operated.
² Select the respective device within the project.
² Open the device in the project tree.
² You can now carry out configurations and settings in offline mode.
All the corresponding submenus are listed in the project tree under the device name.
[scproans-110413-01.tif, 1, en_US]
² To establish a connection to the device, right-click the device and from the context menu that appears
select Assign device (Figure 8-5 a).
² Select Load Configuration to Device (Figure 8-5 by right-clicking from the context menu that appears b)
and enter the confirmation ID.
The configuration is transferred and the device restarts automatically after successful transmission.
[scgerzu-070916-01, 1, en_US]
Figure 8-5 Connecting to the Device and Loading the Configuration in Offline Mode
You can operate the device directly on the on-site operation panel even without a DIGSI 5 PC. A numerical
keypad, navigation and function keys are available to you for this purpose. You have the option between a
small or large display.
LEDs allow the display of binary output signals. Key switches offer you optional additional safety for switching
operations. You will find detailed descriptions of components of the on-site operation panel and of navigation
in the device menu tree in chapter 5 Using On-Site Operation Panel.
8.4 Indications
8.4.1 General
During operation, indications deliver information about operational states. These include:
• Measured data
• Power-system data
• Device supervisions
• Device functions
NOTE
i All indications are assigned to certain device functions. The text of each indication contains the corre-
sponding function designation. You will find explanations of the meaning of indications in the corre-
sponding device functions. However, you can also define indications yourself and group them into your
own function blocks. These can be set by binary inputs or CFC logic.
Reading Indications
To read the indications of your SIPROTEC 5 device you can use the on-site operation panel of the device or a PC
on which you have installed DIGSI 5. The subsequent section describes the general procedure.
Procedure
The menus of the logs begin with a header and 2 numbers at the top right corner of the display. The number
after the slash signifies the number of indications that are available. The number before the slash indicates
how many indications have just been selected or shown. The end of the indication list is closed with the entry
***END***.
[scoprlog-090413-01.tif, 1, en_US]
To reach the desired log from the main menu, use the navigation keys of the on-site operation panel.
² Navigate inside the log using the navigation keys (top/bottom). You will find the most current indication
at the top of the list. The selected indication is shown with a dark background.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. Every indication contains date, time and its state as additional information.
You will find information about this in chapter 8.5.1 General.
In some logs you are given the option of deleting the entire indication list by softkey in the footer of the
display. To learn more about this, read chapter 8.5.12 Saving and Deleting the Logs.
NOTE
Procedure
To read the indications with DIGSI 5 your PC must be connected via the USB user interface of the on-site
operation panel or via an Ethernet interface of the device. You can establish a direct connection to your PC
via the Ethernet interfaces. It is also possible to access all connected SIPROTEC 5 devices via a data network
from your DIGSI 5 PC.
² You access the desired logs of the SIPROTEC 5 device, use the project-tree window. If you have not
created the device within a project, you can also do this via the Online access menu item.
After selecting the desired log, you are shown the last state of the log loaded from the device. To update, it is
necessary to synchronize with the log in the device.
² Synchronize the log. For this purpose, click the appropriate button in the headline of the log (see the
ground-fault indications example in Figure 8-7 a)).
[scgrflmd-191012-01, 1, en_US]
You will find additional information about deleting and saving logs in chapter 8.5.12 Saving and Deleting the
Logs.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. You will find information about this in chapter 8.5.1 General.
Displayed indications in DIGSI 5 and on the on-site operation panel are supplemented with the following infor-
mation:
Indication Columns
The following table shows the meaning of the individual columns in the log:
Indication Column Meaning
Time stamp Time stamp of the indication in device time using the local time
zone of the device or the query time for the motor log
Relative time Relative time to a reference entry
Error number Number of the error that occurred in the device. This number incre-
ments continuously.
Entry number Entry identification of buffer entries. This identification displays the
sequence of buffer entries.
Indication number Number of the indication that occurred in the device. This number
increments continuously and is necessary for an analysis by
Siemens.
Indication Message text
Function structure Path of the signal with the signal name
Name Signal name
Value Current state of the command. Also pay attention to the value
quality to check whether the value is up to date.
Quality The quality of the value shows the source of the value and whether
the value is up to date.
Cause Additional information such as the cause and validity
Number DIGSI address of the signal
Motor startup time Time of motor starting
Starting current Current needed by the motor to start up
Starting voltage Voltage needed by the motor to start up
Start duration Time needed by the motor to start up
With DIGSI 5 you have the possibility of displaying all currently transmitted indications of the selected device
in a special indication window.
Procedure
• Call up the spontaneous indications of your selected device in the navigation window under Online
access.
• The raising indications appear immediately without you having to wait for a cyclical update or initiate the
manual update.
[scspnmld-230211-01, 2, en_US]
After a fault, the most important data of the last fault can be displayed automatically on the device display
without further operational measures. In SIPROTEC 5 devices, protected objects and even circuit breakers can
be freely created and configured depending on the application (even several instances). In DIGSI 5, several
spontaneous fault displays can be configured, depending on the application, with each individual one being
assigned a particular circuit breaker. These displays remain stored in the device until they are manually
confirmed or reset by LED reset.
• To reach the Fault-display configuration of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Display pages → Fault-display configuration
• In the main window, all configured circuit breakers are displayed. A list of a maximum of 6 configurable
display lines is offered for each circuit breaker. The activation of a spontaneous fault display occurs for
each circuit breaker by selection via checkmark in the column Display.
• With the parameter (_:139) Fault-display (under Device → Parameter → Device settings) you
determine whether spontaneous fault displays should be displayed for each pickup or only pickups with
the trip command.
For every display line the following display options can be selected:
[scstfanz-090413-01.tif, 1, en_US]
• After completion of all confirmations the last display view is showed before the faults.
Method 2: Acknowledgement via LED reset
• An LED reset (device) causes the reset of all stored LEDs and binary output contacts of the device and also
to the confirmation of all fault displays stored in the display.
You can find more details on the topic of LED reset in chapter 8.4.7 Stored Indications in the SIPROTEC 5
Device
In your SIPROTEC 5 device, you can also configure indications as stored. This type of configuration can be
used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it is
acknowledged. Acknowledgment occurs via:
• On-site operation panel
• DIGSI 5
• Binary input
• Right-click the routing field of your binary indication in the desired LED or binary output column in the
routing range of the targets.
Figure 8-12 Reset Functions on the On-Site Operation Panel (for Example, Line FG)
[scquiled-140912-01, 2, en_US]
NOTE
i As long as there are no active unstored indications present at the output contacts and configured LEDs, the
acknowledgment of stored indications leads to a reset of the LEDs and output contacts.
If the test mode of the device or of individual functions is switched on, the SIPROTEC 5 device marks indica-
tions sent to substation automation technology station control system with an additional test bit. This test bit
makes it possible to determine that an indication was set during a test. Necessary reactions in normal opera-
tion on the basis of an indication can thus be suppressed.
8.5 Logs
8.5.1 General
Indications are saved in logs inside the device and are available for later analyses. Different logs allow catego-
rization of indication logging based on operating states (for example, operational and fault logs) and based on
fields of application.
Log Logging
Operational log Operational indications
Fault log Fault indications
Ground-fault log Ground-fault indications
Setting-history log Setting changes
User-defined log User-defined indication scope
Security log Access with safety relevance
Device-diagnosis log Error of the device (software, hardware) and the connection circuits
Communication log Status of communication interfaces
Motor-startup log Information on the motor startup
Communication-supervision log Communication supervision (GOOSE)
Log Management
Logs have a ring structure and are automatically managed. If the maximum capacity of a log is exhausted, the
oldest entries disappear before the newest entries. If the maximum capacity of the fault or ground-fault log is
reached, the number of the last fault is generated via the signal Fault log is full. You can route this signal in
the information routing. If indications in the information routing of DIGSI 5 are routed to a log, then they are
also saved. During a supply-voltage failure, recorded data are securely held by means of battery buffering or
storage in the flash memory. You can read and analyze the log from the device with DIGSI 5. The device
display and the navigation allow you to read and evaluate the logs on site using keys.
Configurability of Logs
The indication capacity to be recorded in configurable logs (for example, ground-fault log) is laid down in
columns of the information routing (matrix) of DIGSI 5 specifically defined for this purpose.
Procedure
To reach the information routing of your SIPROTEC 5 device, use the project-tree window. Access is only
through the project:
• Open the information routing.
Project → Device → Information routing
[scinfpuf-191012-01, 2, en_US]
For non-configurable logs (for example, setting-history logs) scope and type of logged indications are
described separately (see following chapter about logs).
Operational indications are information that the device generates during operation. This includes information
about:
• State of device functions
• Measured data
• Power-system data
Exceeding or dropping below limiting values is output as an operational indication. Short circuits in the
network are indicated as an operational indication Fault with sequential fault number. For detailed informa-
tion about the recording of system incidents, please refer to the description of the fault log (chapter
8.5.3 Fault Log). Up to 2000 indications can be stored in the log.
• To reach the operational log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → Operational log
• The status of the operational log last loaded from the device is shown to you. To update (synchronization
with the device), click the button Read log entries in the headline of the indication list (Figure 8-15 a)).
[scbetrmd-030211-01, 1, en_US]
• To reach the operational log via the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Operational log
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
• Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.
[scoperlog1-081217-01, 1, en_US]
Deletability
The operational log of your SIPROTEC 5 device can be deleted. This is done usually after testing or commis-
sioning the device. To know more about this, read chapter 8.5.12 Saving and Deleting the Logs.
Configurability
The indication scope of the operational log is configured in a specifically defined column of the information
routing (matrix) of DIGSI 5:
Target → Log → Operational log column
Selected application templates and functions from the library bring with them a predefined set of operational
indications which you can adjust individually at any time.
Fault indications are events which arise during a fault. They are logged in the fault log with real-time stamp
and relative-time stamp (reference point: fault occurrence) . Faults are numbered consecutively in rising order.
With fault recording engaged, a corresponding fault record with the same number exists for every fault logged
in the fault log. A maximum of 128 fault logs can be stored. A maximum of 1000 indications can be recorded
in each fault log.
Fault Definition
In general, a fault is started by the raising pickup of a protection function and ends with the cleared pickup
after the trip command.
When using an automatic reclosing function, the complete reclosing cycle (successful or unsuccessful) is pref-
erably integrated into the fault. If evolving faults appear within reclosing cycles, the entire clearing process is
logged under one fault number even in multiple pickup cycles. Without automatic reclosing function every
pickup is also recorded as its own fault.
User-defined configuration of a fault is also possible.
NOTE
i The definition of the fault is done through settings of the fault recording (see Device manual). Events are
logged in the fault log even when fault recording is switched off.
Apart from the recording of fault indications in the fault log, spontaneous display of fault indications of the
last fault on the device display is also done. You will find details about this in chapter 8.4.6 Spontaneous Fault
Display on the On-Site Operation Panel.
Deletability
The fault log of your SIPROTEC 5 device can be deleted. You will find details about this in chapter
8.5.12 Saving and Deleting the Logs.
• To reach the fault log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Fault logs
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[scfaullg-090413-01.tif, 1, en_US]
Figure 8-17 Reading the Fault Log on the On-Site Operation Panel of the Device
Configurability
The indication scope of the fault log is configured in a specifically defined column of the information routing
(matrix) of DIGSI 5:
Target → Log → Fault log column
Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.
The operational measured values and the measured values of the fundamental components and symmetrical
components (see Equipment Manual) are calculated every 9 cycles (at 50 Hz, this is every 180 ms). However,
this can mean that the data are not synchronized with the sampled values of the analog channels. The
recording of these measured values can be used to analyze the slowly changing processes.
Ground-fault indications are events which arise during a ground fault. They are logged in the ground-fault log
with real-time stamp and relative-time stamp (reference point: ground-fault occurrence) . Ground faults are
numbered consecutively in rising order. A maximum of 10 ground-fault logs are stored and for each ground-
fault log it is guaranteed that at least 100 indications are recorded.
The following functions can start the logging of a ground fault with the raising ground-fault indication:
• Directional sensitive ground-fault protection for deleted and isolated systems (67Ns)
• Sensitive ground current protection with I0 (50Ns/51Ns)
• To reach the ground-fault log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Ground-fault log
The status of the device-diagnosis log last loaded from the ground-fault log is shown to you.
• To update (synchronization with the device) click the button Read log entries in the headline of the indi-
cation list (Figure 8-18 a)).
[scgrflmd-191012-01, 1, en_US]
• To reach the ground-fault log from the main menu, use the navigation keys of the on-site operation
panel.
Main Menu → Indications → Ground-fault indication
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[scgfllg1-191012-01.tif, 1, en_US]
Figure 8-19 Reading the Ground-Fault Log on the On-Site Operation Panel of the Device
Deletability
The ground-fault log of your SIPROTEC 5 device can be deleted. Read details about this in chapter
8.5.12 Saving and Deleting the Logs.
Configurability
The indication scope of the ground-fault log is configured in a specifically defined column of the information
routing (matrix) of DIGSI 5:
Target → Log → Column Ground-fault log
Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.
All individual setting changes and the downloaded files of entire parameter sets are recorded in the log for
parameter changes. This enables you to determine setting changes made are associated with events logged
(for example, faults). On the other hand, it is possible to prove with fault analyses, for example, that the
current status of all settings truly corresponds to their status at the time of the fault. Up to 200 indications can
be stored in the setting-history log.
• To reach the log for setting changes of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → Setting changes
The status of the setting-history log last loaded from the device is shown to you.
• To update (synchronization with the device), click the Read log entries button in the headline of the
indication list (Figure 8-20).
[scparamd-030211-01, 1, en_US]
• To reach the setting-history log from the main menu, use the navigation keys of the on-site operation
panel.
Main menu → Indications → Setting changes
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[schislog-090413-01.tif, 1, en_US]
Figure 8-21 Reading the Setting-History Log on the On-Site Operation Panel of the Device
NOTE
• The log, which is organized as a ring buffer, cannot be deleted by the user!
• If you want to archive security-relevant information without loss of information, you must regularly
read this log.
With the user-defined log (up to 2), you have the possibility of individual indication logging parallel to the
operational log. This is helpful, for example, in special monitoring tasks but also in the classification into
different areas of responsibility of the logs. Up to 200 indications can be stored in the user-defined log.
• To reach the user-defined log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → User log 1/2
The status of the user-defined log last loaded from the device is shown to you.
• To update (synchronization with the device) click the button Read log entries in the headline of the indi-
cation list (Figure 8-22 a)).
[scanwnmd-030211-01, 2, en_US]
• To reach user-specific logs from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → User-defined log 1/2
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
• Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.
[scuserrlog1-081217-01, 1, en_US]
Figure 8-23 Reading the User-Defined Log on the On-Site Operation Panel of the Device
Deletability
The user-defined log of your SIPROTEC 5 device can be deleted. You will find details about this in chapter
8.5.12 Saving and Deleting the Logs.
[scdiu1u2-280415-01, 1, en_US]
Access to areas of the device with restricted access rights is recorded in the security log. Unsuccessful and
unauthorized access attempts are also recorded. Up to 2048 indications can be stored in the security log.
• To access the security log of your SIPROTEC 5 device use the project tree window . The device must be in
Online access.
Project → Online access → Device → Device Information → Log tab → Security logs
The state of the security log last loaded from the device is displayed.
• Before this, refresh the contents by clicking the update arrows in the headline.
[scsecmld-180816-01, 1, en_US]
• To access the security log from the main menu, use the navigation keys on the on-site operation panel.
Main Menu → Test & Diagnosis → Logs → Security indications
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[scseclog-090413-01.tif, 1, en_US]
Figure 8-26 Reading the Security Log on the On-Site Operation Panel of the Device
NOTE
• This log, which is organized as a ring buffer. cannot be deleted by the user!
• If you want to archive security-relevant information without loss of information, you must regularly
read this log.
Concrete take-action instructions are logged and displayed in the device-diagnosis log for the following items:
• Compatibility problems
Up to 500 indications can be stored in the device-diagnosis log. In normal operation of the device, it is suffi-
cient for diagnostic purposes to follow the entries of the operational log. This specific significance is assumed
by the device-diagnosis log when the device is no longer ready for operation due to hardware defect or
compatibility problems and the fallback system is active.
• To reach the device-diagnosis log of your SIPROTEC 5 device, use the project-tree window.
Project → Online access → Device → Device information → Logs tab → Device-diagnosis log
The status of the device-diagnosis log last loaded from the device is shown to you.
• Before this, refresh the contents by clicking the update arrows in the headline.
[scdevdia-180816-01, 1, en_US]
Reading on the Device through the On-Site Operation Panel in Normal Operation
• To reach the diagnosis log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Test & Diagnosis → Logs → Device diagnosis
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[scdevdia-090413-01.tif, 1, en_US]
Figure 8-28 Reading the Device-Diagnosis Log on the On-Site Operation Panel of the Device
NOTE
The logging of the respective status such as ensuing faults, test and diagnosis operation, and communication
capacity utilizations is done for all hardware-based configured communication interfaces. Up to 500 indica-
tions can be stored in the communication log. Logging occurs separately for each communication port of the
configured communication modules.
• Use the project-tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → Device → Test suite → Communication module
• Then select:
J:Onboard Ethernet → Communication log
The communication log is shown to you in the state last loaded from the device.
• Before this, refresh the contents by clicking the update arrows in the headline.
[sccompuf-140912-01, 2, en_US]
• To reach the communication log from the main menu, use the navigation keys on the on-site operation
panel.
Main Menu → Test & Diagnosis → Log → Communication log
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[sccommlg-090413-01.tif, 1, en_US]
Figure 8-30 Reading the Communication Log on the On-Site Operation Panel of the Device
Deletability
The communication logs of your SIPROTEC 5 device can be deleted. Read details about this in chapter
8.5.12 Saving and Deleting the Logs.
Configurability
The communication logs are not freely configurable. The entries are preconfigured.
• To reach the communication-supervision log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Com Supervision log
The status of the communication-supervision log last loaded from the device is shown to you.
• To update (synchronization with the device), click the button Read log entries in the headline of the
indication list.
[sc_comsuperv, 1, en_US]
• To reach the operational log via the main menu, use the navigation keys of the on-site operation panel.
Main menu → Indications → Com Supervision log
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
Deletability
The communication-supervision log of your SIPROTEC 5 device can be deleted. Read details about this in
chapter 8.5.12 Saving and Deleting the Logs.
Configurability
The communication-supervision log is not freely configurable. The entries are preconfigured.
The motor-starting log records the starting current, starting voltage and the start duration each time a motor
starts. The motor-starting current and the motor-starting voltage are displayed as primary values. Up to 200
indications can be stored in the motor-starting log.
Measurement of the motor statistics starts when the motor state changes to Start. Measurement of the
motor starting time ends as soon as the motor state changes to Standstill or Running. The motor state is
obtained from the Motor-state detection function.
No entry is recorded in the motor-starting log if the motor state changes to Start and the current drops
below the motor starting current within 500 ms.
• Use the project-tree window to reach the motor-starting log of your SIPROTEC 5 device.
Project → Device → Device Information → Log → Motor-starting log
The state of the motor-starting log last loaded from the device is shown to you.
• To update (synchronization with the device) click the button Update in the headline of the indication list
(Figure 8-32 a)).
[scmotmlp-160713-01, 1, en_US]
• To reach the motor-starting log from the main menu, use the navigation keys of the on-site operation
panel.
Main Menu → Indications → Motor-starting log
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[scmotlog-160713-01.tif, 1, en_US]
Figure 8-33 Reading the Motor-Starting Log on the On-Site Operation Panel of the Device
Deletability
The motor-starting log of your SIPROTEC 5 device can be deleted. Read details about this in chapter
8.5.12 Saving and Deleting the Logs.
Configurability
The motor-starting log is only present in the Motor function group. There is no column for the motor-starting
log in the DIGSI information routing. The entries in the motor-starting log are preconfigured and cannot be
changed.
Deleting the logs of the device in the operating state is unnecessary. If storage capacity is no longer sufficient
for new indications, the oldest indications are automatically overwritten with new incoming events. In order
for the memory to contain information about the new faults in the future, for example, after an inspection of
the system, a deletion of the log makes sense. Resetting the logs is done separately for the various logs.
NOTE
i Before you delete the content of a log on your SIPROTEC 5 device, save the log with DIGSI 5 on the hard
disk drive of your PC.
NOTE
i Not all logs of your SIPROTEC 5 device can be deleted. These limitations apply especially to logs with rele-
vance for security and after-sales (security log, device-diagnosis log, setting-history log).
NOTE
i Upon deletion of the fault log, the associated fault records are also deleted. In addition, the meters for fault
number and fault-record number are reset to 0. In contrast, if you delete fault records, the content of the
fault log, including the allocated fault numbers, remains.
NOTE
i If the device executes an initial start, for example, after an update of the device software, the following
logs are automatically deleted:
• Operational log
• Fault log
• Ground-fault log
• Setting-history log
• User log
• Motor-startup log
Back up the deletable logs using DIGSI 5.
NOTE
• To reach the selected log from the main menu, use the navigation keys of the on-site operation panel
(example operational log):
Main Menu → Indications → Operational log
[scoprlog-090413-01.tif, 1, en_US]
Figure 8-34 Deleting the Operational Log on the On-Site Operation Panel
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
• The option to delete the entire log is offered to you in the footer of the display at the bottom left. Use the
softkeys below under the display to activate the command prompts. Confirm the request to Delete.
• After being prompted, enter the password and confirm with Enter.
• After being prompted, confirm the Deletion of all entries with Ok.
• To reach the selected log of your SIPROTEC 5 device, use the project-tree window (for example, opera-
tional log).
Project → Device → Process data → Logs → Operational log
The SIPROTEC 5 devices have numerous measured and metered values. The following Table 8-9 gives you an
overview of the scope and sequencing principle. Measured and metered values will be referred to hereafter as
measured values.
Please refer to the Device manual of your SIPROTEC 5 device for detailed information and setting instructions.
You can read measured and metered values on the device display or with DIGSI 5. You can find these values in
the respective function groups such as the Line function group. Take note that the scope of measured values
is determined by the type and number of assigned measuring points. If only one measuring point, for example
3-phase current, is assigned to the function group, then all measured values linked to the voltage (voltage,
power, energy) are omitted. These measured values are hidden automatically.
In the following, you will find an example how to reach the individual measured or metered values.
You can read the measured values in the function group Circuit Breaker 1 as follows:
• In the main menu of the device display, switch to
Main menu → Measured values → Circuit breaker 1
The following measured-value group is displayed for you, and you can find the available measured and
metered values in Table 8-9.
– Fundamental component/symmetrical components
– Functional measured values (protection-specific measured values)
– Statistics
– User-defined measured values
• Double-click the respective function group and the measured value view appears in the working area.
[scmswesi-080413-01.tif, 1, en_US]
Figure 8-35 Example of the Measured-Value View for the Function Group Line 1
² Enter the desired value in the Current value column. The input value is converted to the data format
according to IEC 61850. Because of the associated quantization, the resulting display value can differ
from the input. In addition, the input value is rounded to 6 digits. The display is limited to 6 digits. There-
fore please note that, in case of small pulse weighting, minor changes to large metered values can not be
reflected in the display.
² To transfer the value to the device, click the Set button.
[scnrgwer-080413-01.tif, 1, en_US]
² Enter the desired value in the Current value column. The input value is converted to the data format
according to IEC 61850. Because of the associated quantization, the resulting display value can differ
from the input. In addition, the input value is rounded to 6 digits. The display is limited to 6 digits. There-
fore please note that, in case of small pulse weighting, minor changes to large metered values can not be
reflected in the display.
² To transfer the value to the device, click the Set button.
² Enter the desired value in the Current value column. The input value is converted to the data format
according to IEC 61850. In addition, the input value is rounded to 6 digits. The display is limited to 6
digits. Therefore please note that, in case of small pulse weighting, minor changes to large metered
values can not be reflected in the display.
² To transfer the value to the device, click the Set button.
[scubstwe-080413-01.tif, 1, en_US]
8.7.1 General
Fault data relates to events or records that are recorded during a device fault. Sampled values of analog meas-
urement inputs and calculated measured values of the device are recorded in the fault recording. A fault
record can also used for recording binary events as traces. Fault events are logged with time stamp in the fault
log. A corresponding fault exists in the fault log for each recorded fault record. The unique assignment is
formed by the time stamp and the fault defined with an automatically incrementing number.
After a fault the most important data of the fault is spontaneously shown on your device display. You can
select whether the spontaneous fault display is updated with each fault or only in case of faults with tripping
(no Trip – no Flag). Spontaneous fault displays such as LEDs fall back again in case of pickup without tripping.
NOTE
The control settings of the fault recording are described in the Device manual. The starting condition,
recording length, and the storage criterion are selected with these parameters.
You can rename the signals in the DIGSI information routing matrix. You can change the order of the binary
signals and measured-value channels to be recorded in DIGSI under Signal sequence. For further information,
you will find help in DIGSI 5 version V07.50 and higher (ordering number: C53000-D5000-C001-D). The
following chapter describes the readout and editing of fault records.
Fault Definition
A fault is started by the incoming pickup of a protection function and ends after the trip command with the
cleared pickup.
When using an automatic reclosing function, the full reclosing cycle (successful or not) is integrated in the
fault. If evolving faults appear within reclosing cycles, the entire clearing process is logged under one fault
number even in multiple pickup cycles. Without automatic reclosing function every pickup is also recorded as
its own fault.
User-defined fault configuration and initiation by an external starting signal are also possible.
NOTE
i • Define the extent of the fault recordings using the control settings of the Fault recording function.
You can read out the fault record recorded in the device via the communication interfaces. You can do this
from a PC with DIGSI 5 or by way of standard (IEC 61850, IEC 60870-5-103) from a central controller upon
request. The fault records read out via DIGSI 5 are saved on the PC in the COMTRADE format. You can analyze
the fault records with the analytical software SIGRA.
Procedure
• Use the project-tree window to reach the fault records of your SIPROTEC 5 device.
Project → Device → Records
The fault records that have been loaded from the device to date are displayed with time stamps and fault
numbers.
• To read all fault records stored in the device, click the Read records button in the headline of the indica-
tion list.
NOTE
i • Take note that when accessing via online access points the fault records read replace all fault records
previously shown in the window. If you wish to save special fault records, then export the fault
records (see chapter 8.5.12 Saving and Deleting the Logs).
• When accessing via a device created in the project, older fault records no longer in the device remain
kept. If you wish to delete no longer needed fault records, read chapter 8.5.12 Saving and Deleting
the Logs).
[scaslstr-080413-01.tif, 1, en_US]
Procedure
• To be able to display and analyze a fault record, you must open the fault record of your choice in the list
of read fault records by double-clicking.
After opening, the fault record is automatically displayed on the COMTRADE Viewer. You can select between
primary and secondary values. If you wish to do expanded analyses of fault records using the options of the
COMTRADE viewer, you can optionally press the Open record with SIGRA button to start the analytical soft-
ware SIGRA. You must have the analytical software SIGRA installed on your PC.
[scttrecd-080211-01.tif, 2, en_US]
For the analysis of important fault records you can save them as files on your DIGSI 5 PC. You have 2 export
options available in DIGSI 5.
Procedure
• Start the standard export of the fault record in COMTRADE format (CFG file) by pressing the Export
button in the headline of the display window (Figure 8-39 a)). The fault record is now available to SIGRA
and other analytical tools.
• Start the export of the fault record as a CSV file in tabular form by pressing the CSV button in the head-
line of the display window (Figure 8-39 b)). You can, for example, open this file with Excel and individu-
ally edit or analyze it.
The recorded fault records are managed in a ring buffer in the device. So that new records can always be
created securely, the oldest records are deleted automatically when the maximum storage capacity is reached.
However, you can also delete targeted fault records. This differentiates whether you wish to delete the fault
records stored or selected in the device in a DIGSI 5 project.
• To delete the fault records stored in the device, click the Delete fault records button in the headline of
the display window (Figure 8-39 c)).
• You can delete selected fault records within a DIGSI 5 project. To do this, tag the respective fault records
and right-click with the mouse. Complete the delete action with the offered Delete option.
NOTE
i Recorded events of corresponding faults in the fault log are also deleted with the fault records.
For test purposes, SIPROTEC 5 devices can record fault records of fixed length. You must manually initiate this
recording from the PC via DIGSI 5. The recording length of the test fault records is independent and is set to 1
second.
Procedure
• To start a test fault record, click the Start fault record button in the headline of the display window
(Figure 8-39 d)). Then read the current fault records to view and analyze them from your SIPROTEC 5
device.
While the Fault Recording function contains the control settings for recording data, you must configure the
channels to be recorded with DIGSI 5 in the configuration matrix. Every application template contains a preset
configuration of channels to be recorded that you can adjust individually.
Fault-Record Channels
The following values are available for fault-record channels:
• Sampled values of analog measuring inputs (currents and voltages)
• Internal measured values of measured value preprocessing
[sccnfrec-080413-01.tif, 1, en_US]
NOTE
i The sampled values of analog measuring inputs (currents and voltages) are not freely configurable in the
fault record. The values are specified automatically by the routing of measuring points to the analog input
modules of the device.
NOTE
i The maximum recording length of an individual fault record and the sum of fault records stored in the
device are affected by the following factors:
• Sampling rate setting
• Number of fault-record channels
The start criterion for recording a fault record and the duration of a fault record are determined by the control
settings in the Fault Recording function. Read the Fault Recording chapter in the Device manual of your
SIPROTEC 5 device.
Start Criterion
A start criterion is the fault which is formed by the pickups of protection functions and which also takes
account of a reclosing cycle duration during the respective parameter setting.
• You can configure the start criterion for each parameter setting using your own user definitions. A
Recorder column especially provided for this purpose is then displayed in the information routing of
DIGSI 5 (matrix).
[scusrrec-051016-01, 1, en_US]
Figure 8-41 User-Defined Configuration of the Start Criterion for Fault Recording
• You can also set parameters for the start criterion via an external start signal in the Fault recorder func-
tion. >External start). With this you can, for example, initiate recording of a fault record using an
external protection device without internal fault recording in case of pickup.
• A test fault record can also be initiated manually and directly via the on-site operation panel of the device
(for example, via function key) or via DIGSI 5. For this, a freely configurable starting signal (>Manual
start) is available.
[scmnstrt-051016-01, 1, en_US]
Fault recording can also be initiated via communication. This can happen via the standards IEC 61850 and
IEC 60870-5-103 through a connected substation automation technology system.
The integrated date and time synchronization of your SIPROTEC 5 device allows you to assign the precise time
of events to an internally maintained device time. Events in the logs are stamped with the device time. These
time stamps are also transmitted during transmission to substation automation technology or via a protection
interface. You can synchronize the device time using external time sources. You can also take local time zones
and daylight-saving time arrangements into consideration.
You can set the date and time of your SIPROTEC 5 device through the on-site operation panel as well as the
DIGSI 5.
[scztinfo-030311-01.tif, 1, en_US]
• After finishing the input, press the Set time button to transfer it to the device.
• The display for modified values for date, time, and their cyclical updates will confirm the successful
transfer.
NOTE
i The Edit time button is inactive until data have been queried from the online device for the first time.
[scdttime-080413-01.tif, 1, en_US]
• Enter the change and then confirm the entry by selecting the Ok softkey.
The Date and Time menu items show you the current values with ongoing update.
• To change Date or Time, select the desired menu item and press the Change softkey.
• Enter the changes and then confirm the entry by selecting the Ok softkey.
Input the time keeping settings of your SIPROTEC 5 device preferably using DIGSI 5. You have access here to
all possible settings. You can only access some of the settings using the on-site operation panel while the
device is being operated.
• Configure up to 2 external timers (time source, latency, time zone) and the time by which failures should
be logged.
First decide whether your PC settings should be accepted or whether you wish to enter the settings manually.
• Enter the settings for your local time zone and daylight saving time. The settings include the local time
zone (relative to GMT) as well as the daylight saving time options (activation, start, end, and offset of
daylight saving time).
You will find application and setting information in the System Functions Device manual.
[scztkonf-030311-01.tif, 1, en_US]
[sctimsyc-080413-01.tif, 1, en_US]
• Configure up to 2 external time sources. There are port and channel numbers in communication inter-
faces for every configured time source. This depends on the configured hardware of your SIPROTEC 5
device.
• Select the time-zone arrangement (UTC or local) for each time source.
NOTE
i Make sure that the settings for the time sources coincide with the actual hardware configuration of your
SIPROTEC 5 device. In any event, incorrect settings cause the status indications of time sources to pick up.
[scztinfo-030311-01.tif, 1, en_US]
• Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.
NOTE
i All indicated times (even of time sources) take account of settings for local time (zone and daylight saving
time of the device) in the form of a numeric offset to UTC (world time).
[scdttime-080413-01.tif, 1, en_US]
The Date & Time menu items show you the current values, which are continually updated. You can also
change entries here.
NOTE
i In case of a missing or discharged battery, the device starts without active external time synchronization
with the device time 2011-01-01 00:00:00 (UTC).
You can enter the contrast setting only on the device via the navigation keys on the on-site operation panel.
Procedure
• Open the contrast menu by pressing the Left + Right navigation keys simultaneously.
• If prompted, change the contrast intensity +/- using the Right/Left navigation keys.
• You can restore the basic setting by simultaneously pressing the Up + Down navigation keys.
[sckontra-080413-01.tif, 1, en_US]
If the Language of the operation panel was configured in DIGSI 5, you can select between the national
language and US English on the device at any time.
• To reach the setting dialog for the language selection, press the function key <F9>.
• Use the up/down navigation keys to select the languages.
• To reach the settings dialog for selecting the units, select the Localization menu in Device functions.
[scchgun1-050413-01.tif, 1, en_US]
[scchgun2-050413-01.tif, 1, en_US]
• To reach device information of your SIPROTEC 5 device in the menu, use the project-tree window. You
can reach the device optionally via online access or via the project in which it must be created:
Online access → Interface → Device → Device settings
Project → Device → Settings→ Device settings
[scsprums-040613-01.tif, 1, en_US]
Authorization for security-relevant operations on the device directly via the on-site operation panel or DIGSI 5
is assured by the assignment of confirmation IDs. These are assigned exclusively using DIGSI 5 (see also
11.6 Authentication, Connection Password, and Confirmation ID During Operation).
• Enter the new confirmation ID (comprising 6 digits between 0 and 9) twice, and then confirm it with OK.
The confirmation IDs are set ex factory as default (see table Table 8-13).
[scaktvor-210311-01.tif, 1, en_US]
[scbstcod-210311-01.tif, 1, en_US]
Enter the function settings of your SIPROTEC 5 device preferably using the DIGSI 5. You have access here to all
possible settings. Using the on-site operation panel you can make individual setting changes while the device
is in operation.
• For decimal parameters, you can change the setting value incrementally using the setting arrows, or
enter the setting value directly via your PC keyboard. Setting values that are not permitted are indicated
by a red background color and red exclamation marks in the affected areas of the project-tree window.
DIGSI 5 cannot load invalid setting values into the device.
2 Thisconfirmation ID is automatically used internally for read operations; user details are not required for this non-modifiable confirma-
tion ID.
[scstfugr-030311-01.tif, 1, en_US]
• When you are finished changing your settings, load the entire device configuration into the device.
• To load the setting changes for multiple devices via the system, press the project-specific Load configu-
ration in devices button in the project-tree window.
[scladknf-040613-01.tif, 1, en_US]
[scaswfnk-080413-02.tif, 1, en_US]
Figure 8-57 Changing and Selecting Function Settings on the On-Site Operation Panel
• If you are not yet authorized for access via LOGIN, you will be requested to input the confirmation ID.
• Use the number keys to enter the confirmation ID and confirm with Ok.
• For the selection of settings, use the navigation keys to select a value from the displayed list of possible
settings.
• For decimal parameters, you can enter the setting value directly using the number keys within the
displayed setting range.
• Confirm your settings with Ok or Enter. Setting values that are not permitted are declined.
• To activate all changes made, press the left navigation key until you are prompted in the base bar to
confirm or cancel the changes.
[scbstubn-080413-01.tif, 1, en_US]
Figure 8-58 Confirming Acceptance of Function Settings on the On-Site Operation Panel
For different applications you can save the respective function settings in so-called Settings groups, and if
necessary enable them quickly.
You can save up to 8 different settings groups in the device. In the process, only one settings group is active at
any given time. During operation, you can switch between settings groups. The source of the switchover can
be selected via a parameter.
You can switchover the settings groups via the following alternatives:
• Via the on-site operation panel directly on the device
• Via an online DIGSI connection to the device
NOTE
i Bear in mind that the settings group in the project is switched by loading the DCF into the device. This
causes an automatic device restart (reset). If you make other functional changes at the same time, a device
restart may also occur in online mode or at the on-site operation panel. Switching without interrupting
device operation may be performed only with online access.
Settings Group Switching at the Device Using the On-Site Operation Panel
Use the navigation keys of the on-site operation panel to initiate settings group switching on your SIPROTEC 5
device.
• Select Main menu → Settings → General → Settings group switching
• Using the navigation keys, go to the Settings group activation setting and click Change in the base bar
dialog.
• If you are not yet authorized for access via LOGIN, you will be requested to input the confirmation ID.
• Use the number keys to enter the confirmation ID and confirm with Ok.
[scesakpa-080413-01.tif, 1, en_US]
Figure 8-59 Setting the Active Settings Group on the On-Site Operation Panel
• Use the navigation keys to select the settings group to be activated from the displayed list of possible
settings.
• To activate settings group switching, press the left navigation key until you are requested to confirm or
cancel in the base bar.
[scbstubn-080413-01.tif, 1, en_US]
Table 8-11 Binary Codes of the Signal Inputs and Associated Settings Groups
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC 61850, DNP or Modbus TCP can be used
for switching the settings groups via a communication connection.
In order to use a CFC chart for switching, you must create a new CFC chart in DIGSI 5. Create the CFC chart in
the DIGSI 5 project tree under Name of the device → Charts → Add new chart. Link the signals that control
settings group switching in the CFC chart.
NOTE
i The device starts in this mode after a DCF upload (offline mode) with active settings group 1. The device is
only informed of a settings group change via the substation automation technology. As long as the substa-
tion automation technology command is pending, protection runs using the settings from active settings
group 1.
If the Control mode is changed in online mode (settings changes via DIGSI 5 or the on-site operation
panel), the device continues to run with the last active settings group. If a substation automation tech-
nology command for a settings group change is sent or the mode for settings group switching is changed,
this state ends. In the case of a device warm start, the device starts in the mode of the most recently active
settings group.
8.9.1 General
You can execute switching device control via a connected substation automation system and through DIGSI 5.
You can also control the device directly via the keyboard. The large graphic display is best suited for this
purpose but control is also possible with the small display.
Operation of switching devices is subject to different safety tests such as switching authority and switchgear
interlocking protection-function test. You will find a detailed description of these functions in the Device
manual in the chapter Control Functions. To facilitate access to on-site control only for authorized persons,
you can set parameters of a confirmation ID using DIGSI 5.
If you go to the main menu of the device and select the Control menu item, you get the following submenu:
[scstemen-090413-01.tif, 1, en_US]
The switching authority ensures that simultaneous control can be done only from one command source. For
example, you must prevent a switching command from being executed by the control center during field
work. To do this, you must set the switching authority to Local. SIPROTEC 5 recognizes the following
switching authorities:
• Local
• Remote/station
• Remote/control center
The Remote/station switching authority level was redefined in IEC 61850. You can deactivate the switching
authority in the device. Full support for this level is ensured only in devices with the IEC 61850 protocol.
The Remote/control center switching authority is normally used as the remote switching authority. You can
change the switching authority from Local to Remote Using the top key switch. You can also set this switch-
over in devices without the key switch after entering the confirmation ID.
! DANGER
Danger due to hazardous voltages during the operation of electric devices
Noncompliance with the safety notes will result in death or severe injuries.
² Only electrically qualified personnel may work on these devices. The electrically qualified personnel
must be thoroughly familiar with pertinent safety regulations and precautionary measures as well as
the warnings in this manual.
If you perform non-interlocked switching, for example, in the commissioning phase, you can change the
switching mode during operation.
You can set the switching mode using the key switch. Non-interlocked switching is permitted in the horizontal
key position (Interlocking OFF). Only interlocked switching is allowed in the vertical key position.
Proceed as follows for devices without a key switch:
² Select the menu item Commands in the main menu.
Devices with a graphic display can depict a single-line diagram of the field in the control display, see
Figure 8-62. You can create the control display with the display editor of DIGSI 5. The display becomes active
directly after activation. You can reach the display at any time by pressing the yellow <Ctrl> key.
[scabzstb-280211-01.tif, 1, en_US]
Initiating command
• Then enter the new target position ON or OFF with the corresponding control key (green <I> for ON, red
<O> for OFF).
[scauswqa-090413-01.tif, 1, en_US]
You can also initiate a control action via the navigation keys after selecting a switching device.
To do so, select Open or Close in the menu and confirm with Ok.
[scsteuvo-090413-01.tif, 1, en_US]
For devices with the small display, you can control from the switching device list, in the same way as for
devices with the large display. A single-line representation of the feeder is impossible here.
• Select the list of all switching devices in Commands/Equipment and then the switching device to be
controlled in the Control menu item.
The currently recorded position is shown to you.
• You now control via the right context-sensitive key (labeled Switch).
• Then select the target position (off or on).
[scklndis-090413-01.tif, 1, en_US]
During commissioning, maintenance, or testing, a brief interruption of the connection between the logical
signals and binary inputs may be useful. It allows you to manually update the status of a switching device that
is not providing feedback correctly. Before this can take place, you must first set acquisition blocking.
To set the acquisition blocking, proceed as follows:
• Using the navigation keys, move in the main menu of the device display to
Commands→Equipment→Aq.blkman. update.
• Select the appropriate device (for example, a circuit breaker) from among the several switching devices
using the navigation keys.
• Enter the confirmation ID (not relevant for active role-based access control (RBAC) in the device).
[scerfass-310816-01, 1, en_US]
Manual updating of the switching device is possible from within the same menu.
• Select Manual update (Figure 8-67) using the navigation keys.
• Select the switching device setting to be updated manually using the navigation keys (for example, off,
Figure 8-68).
[scstatus-310816-01, 1, en_US]
[scstatu2-310816-01, 1, en_US]
[scstatu3-310816-01, 1, en_US]
NOTE
i For security reasons, manual updating is possible only directly through the on-site operation panel of the
device and not through DIGSI 5.
NOTE
i Setting acquisition blocking and the subsequent manual updating are also possible via the IEC 61850
system interface.
You can also set acquisition blocking via a binary input. If you want to put the feeder or the switching device
in revision, you can set the acquisition blocking for an individual or several switching devices with an external
toggle switch. For this purpose, every switching device in the Switch function block (circuit breaker or discon-
nector switch) has the input signal >Acquisition blocking. This signal can also be set from the CFC.
[scbeerfa-190215, 1, en_US]
Figure 8-70 Input Signals >Acquisition Block and >Release Acquisition Block & Manual
Updating on the Switching Device
NOTE
i Interlockings are carried out with the status changes of the switching device. Remove acquisition blocking
again manually. Otherwise, position changes of the switching device are not detected and interlockings are
ineffective.
If the acquisition blocking and the manually updated position are set using the operation panel of the device
or the system interface IEC 61850, these are retained until the acquisition blocking is manually deactivated.
When you initially start the device, the acquisition blocking is deactivated.
Except for a restart, the acquisition blocking and the manually updated position are retained.
If the acquisition blocking is activated via the input signal >Acquisition blocking, it is retained as long as
the binary input is active.
To set the acquisition blocking of a switching device, the following sources are possible:
• Operation panel of the device
• System interface IEC 61850
NOTE
i When the acquisition blocking is activated or the switching device updated manually while the entire
device or the switching device is in test mode, these states are not saved. The acquisition blocking and the
manual updating are not retained after a restart.
The acquisition blocking and the manual update for the circuit breaker, the disconnector, and the tap changer
are reset by way of the >Reset AcqBlk&Subst binary input. Setting acquisition blocking and manual
update is blocked with the input activated.
You reach the following display through the Status menu item:
[scstatus-090413-01.tif, 1, en_US]
In order to be able to set a marker manually with a device operation, you must activate a cross in the Control
Menu column in the DIGSI 5 information matrix (see Figure 8-72).
[scrangma-090413-01.tif, 1, en_US]
NOTE
i To change the state of a marker (from On to Off or vice versa), you need to enter the confirmation ID for
control.
Authorization for sensitive operations in the on-site operation panel is done by the assignment of confirmation
IDs (see also chapter 11.4 Confirmation ID).
Figure 8-73 shows an example of a device without a key switch. For devices with key switches, the confirma-
tion IDs are not required for non-interlocked switching and for the switching authority. These are replaced by
the corresponding key switches for non-interlocked control and for local switching authority.
[scaktvor-210311-01.tif, 1, en_US]
Name Description
Seting/operate Authorization to change settings on the device display and DIGSI 5
Switching (operation) To prevent unintentional switching of combined protection and control
devices, this general authorization for switching on site is available.
Release for manual setting of markers
Switching (non-interlocked) Only in devices without key switch authorization for non-interlocked
switching (only effective in devices with parameterized switchgear inter-
locking protection conditions)
Switching Authority Only in devices without the key switch release of On-site switching
authority and hence of control on the device display
Switching (without synchro- Authorization for unsynchronized switching of a circuit breaker (only in
check) devices with activated synchrocheck)
8 of 9 function keys can also be used for control. Function key <F9> is hardcoded for language switching.
Using a function key you can initiate a switching sequence, for example, to switch on a feeder.
• You reach the function keys by pressing the blue <Fn> key and the corresponding digit from <1> to <9>
in the numerical keypad.
• Link a single command (type SPC) in the information routing matrix with the desired function key.
• Connect this single command with a SPC_INFO block that starts the switching sequence.
9.1 Overview
This chapter contains information about the commissioning of the SIPROTEC 5 device. Test functions inte-
grated in the device support you during testing, simplify testing processes and reduce testing times. You will
get an overview of the numerous possibilities of initial startup in chapter 9.3 Initial Startup.
The secondary test described in chapter 9.4 Secondary Tests is used for checking:
• Correct setting of functions
• Routing of logical signals to the binary inputs and outputs
After you complete the initial startup (see chapter 9.3 Initial Startup), you can access the test functions inte-
grated in the device. To do this, establish connection to the online device. In the project tree, open the Folder
Test Suite. Underneath you will find the individual test points that are explained to you in the following chap-
ters. The following figure shows the project tree.
[scproans-110413-01.tif, 1, en_US]
If you have activated a connection password for the device, you must enter it in the corresponding dialog.
After correct password entry, the connection between DIGSI 5 and device is established. In case of wrong
entry, the connection is not established.
If you have configured a confirmation ID with DIGSI 5, this is queried when you access the individual test func-
tions. Enter here the corresponding 6-digit number.
You will find details for configuring the password and the confirmation ID in chapter 11.6 Authentication,
Connection Password, and Confirmation ID During Operation of this manual.
If the connection between DIGSI 5 and the device is interrupted during a test function, re-establish the
connection to the device. Then do a reset on the device with DIGSI 5. If no connection can be established,
then do the reset directly on the device through the on-site operation panel. After successful reset, the device
is now in a normal operating state 9.3.3 Initializing Device and Verifying Basic Status.
NOTE
i The device must be set in another mode for most tests. If the tests occur in a system in operation, ensure
that the running operation is interrupted.
After successful tests, bring the device back to the previous mode in the following manner:
• Confirm the link Show device mode in the upper right of the work window.
[scgemoaz-210611-01.tif, 1, en_US]
• Select the previous mode in the working area Device information under Device mode.
If you click in the project tree according to Figure 9-1 on the menu item Analog inputs , a representation visu-
alizing for you the current values of the measuring points existing in the device appears in an editor. On the
left side you will see the phasor diagram for 3-phase analog inputs (absolute value and phase). To the right
the measured values are displayed as numerical values. The primarily measured values for voltage and current
are shown as indicators of absolute value and phase. The reference is the voltage in phase A of measuring
point 1. If no voltage is connected, the current in phase A of measuring point 1 is the reference. All indicated
phasor values refer to the reference quantities.
You can identify and verify the following errors with measured-value control:
• Turner in the analog wiring
• Vector group
[sctstane-140211-01.tif, 1, en_US]
Test procedure:
• Feed the test quantities to the terminals (for example, exchange terminals in the control cabinet) using
multiphase test equipment. Siemens recommends a test with the rated values and the infeed of current
and voltage in phase. The test functions from 10 % of the rated quantity.
• Check the measuring result in the DIGSI 5 operating program (absolute value and phase). Make use of
the phasor diagram as well as the indicated measured values. Check phase displacement between
voltage and current as well.
• In the event of implausibility, first check the proper connection of the test equipment and the angle
between voltage and current set in it. Then check the wiring to the device as well as the settings (for
examle, under Power-system data).
Figure 9-3 shows you the result of a successful test on a device which has 4 voltage and current inputs.
NOTE
i To check the wiring between device and connected transformers, Siemens recommends that this test be
done on the system with primary measured signals. This allows you to check the correct connection of
secondary circuit completely.
NOTE
i The device remains in commissioning mode until you set the device in the process mode consciously or
until the internal monitoring time (statement of time) has expired. You reach the process mode by clicking
the link in the upper right of the working area. The settings sheet Device information opens. Go to Device
mode to set the device in process mode.
You can execute more tests in this mode.
The purpose of this test is to verify the correct setting of protection functions and the routing of signals. To do
this, you can feed the test signals with test equipment. Digital test equipment offers you multiple test
programs and test sequences.
NOTE
i Simulation mode is indicated by flashing of the top line of the device display.
NOTE
i If you only want to select a graphical representation of a protection function, all available and active
protection functions of your SIPROTEC 5 device are checked.
Simple tests can also be done via simulation mode on the device and DIGSI 5 interaction. To do this, use
DIGSI 5 to generate test sequences which are then executed in the device without the need for external test
equipment and which simulate the change in values on the inputs.
• Click the Test sequences folder in the project tree.
• Open this folder by double-clicking.
Under the Create test sequence menu item create your test sequence which, for example, consists of 3 steps:
the pre-fault, the short circuit and the post-fault. You can save the created sequence and use it for other tests.
You will also find the stored sequence under the Test sequences folder. Sequences can be copied between
devices that have the same measuring points.
Figure 9-4 shows you the editor for creating test sequences. You can enter a name (for example, pre-fault,
post-fault) for every test step. You can set the duration of the current test sequence, as well as the duration of
a ramp. You can define amount and phase angle for each phase of a measuring point. You can select the
frequency in 3 phases for each measuring point.
Additionally you can define a ramp for each phase via amplitude, phase or frequency via the ramp functions.
You can still define 3 various harmonic superimpositions per phase. This allows the setting of ramps within
one test step. If additional binary inputs are effective, you can adjust that in the section below. Using a hook
tag which binary input is active during the test step. If a voltage (corresponds logically to 1) is present, the
binary input is active.
[scprfsqu-150211-01.tif, 1, en_US]
You can a use created test sequence, for example, for a protection function test. Start a test sequence in the
protection function test editor in DIGSI 5. You can also start a test sequence through a binary input of the
device. By starting through a binary input you can play back test sequences in several devices simultaneously.
You lay down the start criterion for the device using DIGSI 5 Figure 9-5. The test quantities are fed as sampled
values directly into the functions of the device by bypassing the analog and binary inputs. Before starting a
sequence DIGSI 5 switches the device to a simulation mode that activates the internal signal generator.
To check a protection function systematically, click again in the project tree the Test button and open the
Protection function test menu item. You are offered the existing protection functions and you can select
which protection function is tested. The characteristic curve of the protection function appears in the oper-
ating range (see Figure 9-5). The measured values are displayed in color in the characteristic curve and the list
of spontaneous indications is updated simultaneously. Feeding through a test sequence is done in this simula-
tion mode where the protection functions work with the calculated sampled values of the sequence.
Switching to an internal sequence is done in DIGSI 5. The designated sequence is selected (it must first have
been configured offline), loaded into the device and its progress activated.
A SIPROTEC 5 device has numerous protection and supervision functions that work in parallel. For the tests
switch some or only the function to be tested. For this purpose, a test aid that greatly simplifies the test for
you was set up in SIPROTEC 5.
The protection functions have indirectly the same setting as when you switch the mode to Test in the func-
tion. In this state, the protection function is active. In addition, a test bit is generated and transmitted with
every indication. In the Test setting the routed relay in the device is not activated and the circuit breaker is
thereby not actuated.
Upon exiting of the test mode, the execution of an authorized test period or the conscious switching to the
normal operating state (Process mode) leads to the deactivation of the temporary settings. The original
setting then becomes active. You can also make us of this test menu to have a quick overview of available and
enabled protection functions.
[scprscfk-160413-01.tif, 1, en_US]
NOTE
i The device remains in commissioning mode until you set the device in the process mode consciously or
until the internal monitoring time (statement of time) has expired. You reach the process mode by clicking
the link in the upper right of the working area. The settings sheet Device information opens. Go to Device
mode to set the device in process mode.
You can execute more tests in this mode.
The test editor serves to set signals or states in the device that are then output via the communication inter-
faces.
During a primary test the device in combination with DIGSI 5 offers the possibility of checking switching
devices. Click again the Test button and open the Control functions menu item. The existing switching
devices appear in the operating range. You can set the switching state and read in the status again. To do this,
activate the respective switching device and execute the desired actions. The spontaneous indications log the
behavior of the switching device (see Figure 9-6). You can verify the interlocking conditions by opening or
closing disconnectors or grounding switches. This takes place via the binary feedbacks on the device. Induce
unauthorized circuit states and check whether the interlocking logic stored in a CFC plan works correctly in the
device.
! WARNING
Warning of danger due to unauthorized switching states
Noncompliance with safety notes means that death, serious injuries, or considerable material
damage can occur.
² Primary tests may be done only by personnel who are skilled electricians and who are familiar with the
startup of protection systems, with the operation of the system and with safety regulations and provi-
sions (switching, grounding, etc.).
Apart from circuit breakers and disconnectors, you can also increment transformer tap switch higher or lower
and check arc-suppression coils.
NOTE
i This switching function is used exclusively for testing. Operational switching operations are performed with
the on-site device control or with a connected substation automation technology.
[scschver-150211-01.tif, 1, en_US]
² If special confirmation IDs are activated for this test, these must be entered prior to the test. This applies,
in particular, to non-interlocked switching. For this purpose, the switching authority must be on Remote
and DIGSI 5 must be authorized to carry out switching operations.
NOTE
i The device remains in commissioning mode until you set the device in the process mode consciously or
until the internal monitoring time (statement of time) has expired. You reach the process mode by clicking
the link in the upper right of the working area. The settings sheet Device information opens. Go to Device
mode to set the device in process mode.
You can execute more tests in this mode.
² To test circuit breakers, go to Test suite and open the Circuit-breaker test menu item. The existing
circuit breakers then appear in the operating range (see Figure 9-7).
² You can bypass the interlock of the circuit breaker. You can activate the circuit breaker 3-pole or every
circuit-breaker pole separately depending on the type of the circuit breaker. The feedbacks from the
circuit breaker are shown to you in the bottom part of the window. DIGSI 5 shows you the available test
sequences. Before execution of the test, a confirmation ID is queried.
[sclsscpr-110413-01.tif, 1, en_US]
NOTE
i The device remains in commissioning mode until you set the device in the process mode consciously or
until the internal monitoring time (statement of time) has expired. You reach the process mode by clicking
the link in the upper right of the working area. The settings sheet Device information opens. Go to Device
mode to set the device in process mode.
You can execute more tests in this mode.
In online operation, if you open the Device information table in the project tree, you get a lot of information
about the device. The table appearing in the operating range shows different tabs with corresponding infor-
mation about the device. Figure 9-8 gives you an overview of the numerous possibilities.
[scgerinf-100413-01.tif, 1, en_US]
• Device information:
General information about the device such as device name, product code and serial number is indicated
here. If the device uses Ethernet, you can select at this point the IP address of the device through which
DIGSI 5 communicates with the device (port J, this setting only available in offline mode). You can
furthermore set the device language here, as well as the operating modes (process mode, commissioning
mode).
• Resource consumption:
The first area shows you the state of the device load offline. If it is green, the parameterization can be
loaded into the device and real-time behavior ensured. If the lamp is red, functionality must be reduced.
The number of used function points is shown to you in the second area. If the allowed number is
exceeded, replacements must be bought for device-related function points. To reorder, use the configu-
rator and follow the menu instructions there.
In the 3rd area you are shown the capacity utilization of the operational diagram (Continuous function
chart, or CFC in short).
• Log
– Device diagnosis log:
Monitoring indications are entered in this buffer. If, for example, a device fault is present, the
required information is entered in plain text. Every result is time-stamped. Plain text means that you
receive the necessary information about, say, erroneous modules and the type of error. At the same
time, an operation recommendation such as replacement of the expansion module is given.
– Safety indications:
In this buffer logs, entries are time-stamped when access was carried out on the device using
DIGSI 5. Rejected access, for example, if you entered the password incorrectly 3 times, is registered.
You cannot delete this buffer. This buffer is organized as a ring buffer. Selected indications can be
transmitted to a systems control and can be archived there. This guarantees a long-term buffer for
accessing the device as it is required in cyber-security recommendations such as NERC-CIP (see
chapter11.1 Security Design).
• Time information:
In this setting sheet you can open diagnoses for the first and second clock and query their synchroniza-
tion status. In addition, it gives information about the internal device time. This can also be set via this
menu for test purposes. If a high-precision second pulse is available, its status is also shown here
8.8.3 Setting Time Keeping Parameters .
• Diagnostic information:
Here detailed information on the individual hardware and software components are stored.
NOTE
i The device remains in commissioning mode until you set the device in the process mode consciously or
until the internal monitoring time (statement of time) has expired. You reach the process mode by clicking
the link in the upper right of the working area. The settings sheet Device information opens. Go to Device
mode to set the device in process mode.
You can execute more tests in this mode.
It is assumed that you have gone through steps in chapters 1 to 4. Check the connection of the auxiliary
power supply. SIPROTEC 5 devices have 2 power-supply unit designs (type 1: DC 24 V to DC 48 V and type 2:
DC 60 V to DC 250 V as well as AC 110 V to AC 250 V). You can also read the rated voltage range from the
name plate. After successful testing of your voltage source, switch it on. The device is now in startup mode.
The LEDs RUN (green) and ERROR (red) light up simultaneously. In addition, some LEDs on the base module
start flashing. When the RUN LED is permanently On and the ERROR LED is permanently Off the device has
started up. Figure 9-9 and Figure 9-10 show the basic status of the device display using the example of trans-
former differential protection.
Afterwards you can initialize the device by loading the parameterization. Before going to the
chapter 9.3.3 Initializing Device and Verifying Basic Status , read the information in the chapter 9.3.2 Using a
Project with DIGSI 5.
NOTE
i If you find another default display after device startup, then someone before you has initialized the device.
You can now load your parameterization to the device. In the DIGSI 5 project tree, use the Load Configura-
tion in Device menu item.
All settings of the device are created with the DIGSI 5 operating program. The engineering department is
responsible for editing. In the respective project (see chapter 6 Using DIGSI 5) you will find the devices with
the project-specific settings. Familiarize yourself with the project and the device settings before you execute
the next steps.
Take the following procedure as your guide:
² Install the DIGSI 5 operating program on your PC/laptop. For commissioning, Siemens recommends the
DIGSI 5 variant Premium.
² Accept the project from the engineering department and save it.
² Open the project and the devices in it.
² Check whether inconsistencies are shown. DIGSI 5 constantly performs a consistency check. If inconsis-
tencies are detected, the corresponding position in the operating program is marked. If this is the case,
clarify the cause.
² Look into device-specific parameterization. Use the sequence described below as your guide.
SIPROTEC 5 devices are initialized via the front USB interface. Alternatively, you can initialize the devices via
port J. If you connect port J to a system, you must change the previous IP address.
² Connect the device to the corresponding USB interface of your computer.
² In the DIGSI 5 operating program right-click the device to be initialized.
² Click the Load Configuration in Device menu item.
DIGSI 5 then accepts the connection to the device and loads the complete parameterization into the device.
This process takes some time.
[scstartsc-270814-01, 1, --_--]
Once the transfer is completed, the device executes a reset and is in the startup mode. Once this status is
finished, the display image appears and the green LED (Run) lights up. The red LED (Error) must be off.
The display image contains information about the basic device type, for example, transformer protection, the
firmware version (FW), and the loaded parameterization version. In SIPROTEC 5, this is called Configuration
(CFG).
If a display image is adjusted in the parameterization, then the device switches to this display state after
several seconds. The set display image, for example, the measured-value display, should appear.
If you wish verify the loaded parameterization randomly, you can execute a check through the on-site opera-
tion panel. Log in and follow the menu. Read the user instructions in chapter 5 Using On-Site Operation Panel.
Alternatively, you can also verify the parameterization with DIGSI 5. To do this, activate the online mode and
establish connection to the device. Then open the settings comparison between the online device and the
offline device in the project.
During the initialization, the serial number of the device is transferred to the offline project. Alternatively you
can also enter the serial number by hand in the offline device.
By carrying out the points in chapter 9.3.3 Initializing Device and Verifying Basic Status, the device is ready for
operation. If devices are built into cabinets, additional wiring and communication connections are necessary.
Subsequent checks can be made in preparation for the secondary test. To do this, you can make use of
numerous test aids available in the device, which are described in chapter 9.2 Test Suite Integrated in the
Device.
Siemens recommends the following procedure in this order:
² Testing binary inputs and outputs
Check that the connection from the transmission terminal to the device is correct and the binary inputs
and outputs as well.
² Testing voltage and current inputs
Using multi-phase test equipment, apply the corresponding test quantities and check the results. To do
this, make use of the testing options in the device (see chapter 9.2.2 Testing Current and Voltage Inputs.)
You can also check the measured values directly on the device by calling up the operational measured
values in the respective function group.
You can also read the operating measured values in the operating software DIGSI 5. Under Online Access
Points, open the assigned device. Under the menu item Measurement, you will find a clear presentation
of the operational measured values in the respective function group.
² Checking communication interfaces
You can also set the state of signals transferred via communication interfaces. This action allows you to
check, for example, the connection to the systems control. In the communication diagnosis, you will find
helpful information, for example, about data traffic on a communication interface.
² Checking time synchronization
The device is synchronized by a maximum of 2 independent time sources. In online mode, first click in
the project tree on Device information then on the tab Time information. The delivered specific values
(UTC) of the 1st and 2nd time source (if available) are shown. The internal time of the device which
results from the time information of the active time source is likewise shown.
• Checking the routing of signals to the most varied targets (binary inputs (BI), binary outputs (BO), LEDs,
and interfaces)
• Checking the interactions between devices, for example, exchange of information or measured values via
interface
• Checking the correct setting of protection functions and the interaction of protection functions (for
example, circuit-breaker failure protection, automatic reclosing)
! WARNING
Warning of danger from secondary tests
Noncompliance with safety notes can result in death, serious injuries, or considerable material
damage.
² Secondary tests must only be carried out by personnel who are qualified electricians and are familiar
with the commissioning of protection systems, the operation of the system, and with safety regula-
tions and provisions (switching, grounding, etc.).
² Make sure that there are no connections to the primary system during the secondary test.
In the secondary test it is assumed that there are still no connections to the primary system. But if you do this
in the primary system, special safety conditions must be followed.
² Consider that no other measurands are locked in, unless otherwise indicated.
² Consider that the trip and close commands to the circuit breakers are interrupted, unless otherwise indi-
cated.
² Take note of the general instructions in chapter 9.5 Primary Tests.
Only general recommendations are given in this manual. Please refer to the respective Device manual for the
function-specific instructions to be followed. Remember also that a deviation from the expected functionality
can have its cause in an erroneous test sequence.
• Before checking, familiarize yourself first with the measuring principle of the protection function in the
Device manual and consider the test recommendations given in the Device manual.
• Perform the tests using multi-phase test equipment since numerous protection functions require a 3-
phase system.
• You can test most protection functions using stationary signals. Some protection functions require tran-
sient signals. Typical examples are the testing of protection reaction on power swings (power-swing
blocking in distance protection and out-of-step protection) and the transient effect on transformers. They
generate transient test files with a dynamic network calculation program or these test files are provided
by special test programs.
• If setting values are offered only in percent or per unit, remember that the setting values refer only to
rated quantities of the protected object. Secondary test quantities must be converted using the trans-
former ratio.
• Perform the tests successively. Activate only the function that you wish to test. Make use of DIGSI 5
support (see chapter 9.2.3 Testing Protection Functions).
• Since protection functions can be assigned to different protection function groups, check the interaction
between function groups as well. If you have created your own application template or modified the
delivered template, Siemens recommends that you check the interaction. The application templates
provided with the device have been tested.
• Check the reaction of the protection functions via the indications in the corresponding logs. The indica-
tions in the spontaneous indication log (available in online mode), which are shown at the moment of
occurrence, are a good tool. Testing using the fault record (binary signal traces in relation to the input
variables) is also advisable for transient processes.
• Check individual protection functions in the test editor using signals from test equipment or the internal
signal generator (sequences). Examine the test sequence in the characteristic curve of the protection
function and its spontaneous indications.
• Created logics (function charts) must be tested. A working relationship with the engineering department
is necessary for this purpose. Familiarize yourself first with the objective of the function chart. DIGSI 5
offers you a tracing function during offline operation. This allows you to verify the correct logical
sequence by loading the function chart with test sequences and following the reaction in the function
chart. Switchgear interlockings and other logic can be tested easily with it.
• If the logic reacts to transient changes, you must perform dynamic tests. To do this, generate the neces-
sary test sequences and load them into the device. You can then provide inputs or outputs for tracing in
the function chart. The exact temporal sequence of signals is then logged in a fault record during the
progress of the test sequence. This can be analyzed, for example, using SIGRA and the runtimes and time
differences analyzed. This is a very good way of checking and simultaneously documenting behavior over
time (file export in PDF format).
• Switching of switching devices requires that the switchgear interlockings are properly executed and that
the correct signals are fed to the logic. Perform the corresponding tests. Check the switchgear inter-
locking by simulating the corresponding input variables and checking the reaction on the output.
• If you perform on-site control with the device, check the on-site control diagram in devices with large
display. Select the respective switching device and check the different switching operations. Check the
reaction on the outputs.
• In devices with small display, select the switching device (selection via text) and execute the switching
operation as well.
• Since measured values are also displayed apart from switching devices in the display diagram, check the
proper assignment of measured values by feeding and changing the test quantities.
• Tap changer position commands and control commands for arc-suppression coils can be checked via
DIGSI 5. Check the corresponding relay outputs and feedbacks via binary inputs or communication inter-
faces.
Besides binary inputs and outputs, communication between devices occurs via serial communication inter-
faces. Test instructions are hereinafter given for the following applications:
A requirement for the primary test is that prior tests (chapter 9.3 Initial Startup and 9.4 Secondary Tests) have
been completed successfully. Take note of the following before starting the test:
General Notes
! DANGER
Danger due to hazardous voltages during the operation of electric devices
Noncompliance with the safety notes will result in death or severe injuries.
² Only electrically qualified personnel may work on these devices. The electrically qualified personnel
must be thoroughly familiar with pertinent safety regulations and precautionary measures as well as
the warnings in this manual.
! WARNING
Warning of hazards due to improper primary tests
Noncompliance with the safety notes can result in death, serious injuries, or considerable material
damage.
² Primary trials may be performed only by qualified electricians who are familiar with the commis-
sioning of protection systems, the operation of the system and safety regulations and provisions
(switching, grounding, etc.).
You must perform switching operations for the commissioning. The described tests require that they can be
done without danger. They have not been conceived for operational checks.
You must follow pertinent safety regulations (VDE 105-100/A1, BGV A3/VBG 4).
Before starting work you must take note of the 5 safety regulations:
• Isolate from the power supply
• Safeguard against reclosing
! CAUTION
You must ground the device at the protective grounding terminal before making the connections. There
may be hazardous voltages in all switching components linked to the power supply and to measurand or
test quantities. There may be hazardous voltages in the device (capacitor storage of the current supply)
even after disconnecting the supply voltage.
Noncompliance with the safety notes will result in death or severe injuries.
² To reach the defined initial conditions after switching off the auxiliary voltage, wait at least 10 s
before restarting the auxiliary voltage.
² Do not exceed the limiting values indicated under Technical Data of the Device manuals, even during
testing and commissioning.
! DANGER
Hazardous voltages during breaks in secondary circuits of current transformers
Noncompliance with the safety notes will result in death or severe injuries.
² Short-circuit the secondary connections of the current transformer before the electrical lines to the
device are disconnected.
² If there is a test switch which short-circuits the current-transformer secondary line automatically, it is
sufficient to set this switch to the Test position, provided you checked the short-circuiting device
beforehand.
NOTICE
Pay attention when wiring the safety cabinet to the system
Noncompliance with the safety notes will result in material damage.
² Before the 1st test, wire the safety cabinet to the system. You must check the wiring of the connec-
tions to the primary system.
² Test all connections, including the polarity of transformers. In voltage transformers with broken-delta
winding make sure that they are not short-circuited.
NOTE
i Before you perform this test, make sure that the respective system part is isolated and a switching opera-
tion can be executed safely.
² Check the feedback once you have activated the switching device.
² In the menu, go to Test-suite → Analog inputs and check the voltage and current inputs. The relevant
measurands must have the value 0 in the de-energized switch position.
² Using test equipment parallel to the transformers, feed stationary test quantities.
² Check the measured values. Take note of the absolute value and phase as well as the correct phase
sequence.
NOTE
i If additional signals such as from a substation automation technology are coupled, perform the corre-
sponding tests (see chapter 9.4 Secondary Tests).
The scope of primary tests depends on the type of system. To check proper system integration, various
primary tests are performed in power plant systems. The generator delivers the necessary test quantities
based on the operating mode. Refer to the Device manual for generator protection for details.
The scope of inspection is much smaller in power system protection applications. It boils down to a direction
check in the broadest sense. Differential protection tends towards overfunction if there is a sensitive setting
and a wiring error. Each function can be switched to a special mode to avoid unnecessary activation of the
circuit breakers. It is ready to function but the trip command is not switched further (see Function descriptions
in the Device manual). In the desired function, switch the Mode parameter to Test. The trip signal is supplied
with a test bit. The tripping contacts in the device are not activated so the circuit breaker is not actuated by the
protection.
If you enter this setting for the differential protection, make sure that at least one overcurrent protection is
active as backup protection. Once all preparatory measures are complete, you can begin with the actual
primary test.
² First check that you can produce a non-critical switch position and that you have a specific power flow.
The possible load current must be greater than 10 % of the rated load. Avoid a maximum load.
² Activate the circuit breaker (for example, with a synchrocheck).
² Check the measured values.
² In online mode, open the Editor Test suite → Analog inputs.
² Check the phasor values of the measuring points in terms of plausibility (amount, phase and phase
sequence).
² Check the phase displacement of the current and voltage phasors with each other.
² Check the operational measured values per function group.
² Check the direction indirectly via the measured values for active and reactive power (Operational indica-
tions tab.) If the power flow is to the protected object (for example, line) and an ohmic inductive load is
assumed, the active and reactive power must assume positive values. The size of the measured values
determines the current load. If 2 protection devices are connected, both must show the same value.
² Click the Fund. comp./sym. comp. tab.
² You can verify the direction of rotation using positive-sequence and negative-sequence system quanti-
ties. The negative-sequence system quantities must be 0.
² If deviations arise during the tests, check the selected settings (for example, current transformer neutral
point, phase sequence, etc.) and the interface in a 2nd step.
NOTE
i Using wiring modifications, switch the primary system to the de-energized state.
You can do tests specific to protection functions via the operational measured values.
² To do this, click the Functional meas. values tab. In a differential protection function, the differential
currents must be 0 and the corresponding restraint current available.
² Click Test suite → Protection functions.
² In the function group, select the protection function and you will get a graphic display. Apart from the set
characteristics, you see the functions relevant to protection.
To be 100 % sure about the direction setting in a directional overcurrent protection, make use of the test func-
tionality integrated in the protection function.
² Activate the binary input signal >Direction test, and the protection function switches to test mode.
² Analyze the indication behavior of the protection function according to the selected setting.
² Deactivate the test mode by terminating the binary input signal again.
With active protection you can continue the testing of the switching devices.
² Check the on and off switching of the circuit breaker.
² With the circuit breaker switched off, check the activation of disconnectors and the corresponding inter-
locking mechanisms.
Checking the operational measured values for plausibility is a simplified test of components of the primary
system (transformer, wiring) and of secondary equipment (measured-value acquisition including measured-
value processing). You can set a default display in the device display that also contains the measured values.
Several measured-value windows are preadjustable and can be further switched if needed. Check these meas-
ured values for plausibility.
² If you wish to check measured values more precisely, follow the device menu and navigate to the corre-
sponding measured values.
² Alternatively, you can set parameters for a function key so that directly jumping to the desired menu is
possible.
Online operation with DIGSI 5 provides a good complete overview. You will find the relevant measured values
in Measurements for the respective function group. If there is a communication connection to systems
control, measured values that the operational crew can verify are also transmitted here.
No special maintenance is required for SIPROTEC 5 devices. The only maintenance measure is to replace
batteries.
NOTE
i To avoid data loss, Siemens recommends replacing the device battery with the device supply voltage
switched on.
All measurement- and signal-processing circuits are designed full-static. All input modules are also static, and
the binary outputs are equipped with protective covers.
Since the device is mainly self-monitoring, hardware and software errors are automatically forwarded. This
action minimizes any downtime of the device. It also eliminates the need for frequent maintenance inspec-
tions.
Repeat Test
A routine test of characteristics or pickup values is unnecessary since this is part of the continuously monitored
firmware programs. As long as you make no changes in the pickup values or characteristics, a test is not
necessary.
Use the specified maintenance intervals to check and maintain the system and check the protection and
control equipment. The primary purpose of maintenance is to check the interfaces of the SIPROTEC 5 device,
that is, the coupling to the system.
If you discover a failure, follow the instructions in the corresponding chapters for failure search or call the
Siemens hotline.
General
NOTE
i When performing a protection-function test, make sure that it does not lead to any undesired tripping.
Likewise no information must be transmitted to a higher-level systems control where the operator may
incorrectly interpret it.
² Make sure that the green RUN LED on the front cover lights up and not the red ERROR LED. This is how
the device indicates that it is properly functioning and that no failures have been observed during self-
monitoring.
² Make sure that the LEDs on the front cover present a plausible image of the actual state of the device. If,
for example, the tripping of a protection function is saved as an LED display, the device has fault indica-
tions and a fault record for this purpose.
² Press the LED test key. All LEDs apart from the red ERROR LED light up. Stored LED displays are reset and
only those states currently indicated by the device are shown.
² Read the operational measured values and compare them to the actual measurands to control the analog
inputs. To do this, enter a reference quantity into the device using secondary test equipment. This is how
you check the proper operation of the analog section of devices.
² Read the operational indications. You can do this directly on the device or following a clearly arranged
procedure using the DIGSI 5. Make sure that they do not contain inputs about failures of the device, of
measurands or other implausible information.
² If the protection equipment has picked up or disabled an error, you can verify this through the fault
record and the fault log. This is how the protection equipment demonstrates its correct operation in the
operating state. Additional protection-function tests can be omitted.
NOTE
i The system operator is responsible for further protection-function tests within maintenance intervals.
Check protection functions using secondary test equipment or the integrated test sequencer (see chapter
9 Commissioning).
10.2.1 Troubleshooting
Procedure
If the device indicated an error, then Siemens recommends that you proceed as follows:
If no LED on the operation panel of the device lights up, then verify as follows:
² Check whether the auxiliary voltage on the corresponding connections has an adequate amount and
correct polarity. You will find information about this in the overview plans in the appendix of the Device
manual.
² If the device shows a fault via the red ErrorLED, look for the cause of the fault in the operational log. You
can do this directly on the device or with DIGSI 5.
² If the Fallback Mode display appears in the device display, then reinitialize the device through DIGSI 5.
Look for the cause in the device-diagnosis log first. If a connection to the system cannot be established,
initialization takes place via the USB interface on the device together with DIGSI 5.
² If the confirmation ID is queried, enter it for the device initialization.
The display first disappears in the device display. After successful initialization, the LEDs again indicate normal
operation and the default display goes back into the display. If the device-specific setting values were saved in
the PC during commissioning, they are again loaded into the device.
The device is ready for operation.
Additional Support
If these measures do not lead to the desired result, the Support team will help you.
² Keep the device serial number to hand for the Support team.
² Read out the version of the installed firmware.
² Read the device-diagnosis log of your SIPROTEC 5 device with DIGSI 5 so that the Support employee has
all the necessary information.
If a Support employee is on site, he has the option of configuring the device with special software for further
analysis of an existing problem. A signed start-up file is loaded onto the device by the employee. For this, a
firmware version of the device, version V07.50 and higher, is required. When correction of defects is
complete, the correct configuration is established and the device continues to run normally.
[scdevinf-080413-01.tif, 1, en_US]
[scgerdia-230816-01, 1, en_US]
NOTE
i Defective modules can be replaced only by experienced persons. Never open modules yourself.
NOTE
i If these measures do not lead to the desired result, avoid further measures during operation.
If an error is detected in the device that cannot automatically be cleared (hardware components, software or
parameters), the device switches automatically into fallback mode. This can appear in system start or during
operation of the device. The fallback mode allows you a minimum procedure with error diagnosis and error
correction.
NOTE
i Ensure that the protection and control functions are deactivated in fallback mode.
Fallback mode is evident from the termination of the life contact, the Error LED, and the Fallback mode
header in the device display. In this mode the outputs of the device are brought to their initial state. Access to
the hardware is impossible. A limited operating menu is available for further actions.
Fallback Mode
You can select various information areas and have them displayed in the Fallback mode. The reason for the
fallback are shown in the lower part of the display as an indication (1 in Figure 10-3). When selecting the
softkey <More> on the right-hand side, a list of entries is displayed that was generated during the diagnosis of
the device (2 in Figure 10-3). Use the navigation keys to select the relevant entry or use the softkey <Details>
to open the currently selected entry. Precise information about the fallback will be displayed (3 in
Figure 10-3).
[scfbmenudet-030914-01, 1, en_US]
[scmbfb5ein-030914-01, 1, en_US]
• Device information
The menu item Device information provides data about the SIPROTEC 5 device, for example, device
name, serial number, device type, and product key.
• Hardware/software information
The HW/SW information menu item offers you additional information about the hardware and software
of the device (see Structure of the HW/SW Information Menu Item, Page 217).
• Log
Information about the entries in the logs is available via the Logs menu item. This entry provides you
with all the information from the diagnostics, security and system start memory and you can display the
history.
• Actions
By selecting the menu item Actions and clicking Restart Device, you can restart the device.
• IP configuration
During operation or commissioning, the IP Configuration menu offers you system information, for
example the MAC or IP address of the device.
[schwswfb-020914-01, 3, en_US]
• Mainboard
This menu item informs you about the board type and the details concerning the version of the main-
board.
• Communication
The menu item Communication displays information about the assignment of the communication ports
and their hardware information, for example, slot, version, and board type.
• I/O modules
A list of the input/output modules being used can be found under the menu item I/O Modules. You can
select each individual printed circuit board assembly and, for example, have the slot or the terminal posi-
tion displayed.
• Transformer modules
If using transformer modules, this menu item displays all available information about these modules (for
example, slot, board type or serial number)
Group-Warning Indication
Pickup of the following supervisions with entry of the device into the fallback mode does not allow output of
normal supervision indications. The entry of the device into the fallback mode thus also does not lead to the
activation of the group warning indication.
If the SIPROTEC 5 device is outside a normal operating mode (for example, device is in commissioning mode or
in simulation mode), this is shown by an indication. By default this indication is prerouted to LED 16 and
makes the red LED flash.
If you have exited one of the modes incorrectly (for example, by pulling out the DIGSI 5 PC), the red LED
flashes and after 4 hours the Device Ready indication will go.
This function is realized in the SIPROTEC 5 device via a predefined CFC chart. This means that you can change
this behavior in case of doubt. To do this, change or delete the CFC chart.
Overview of Errors
For each error indication on the on-site operation panel, a specific error code is issued additionally (see
Figure 10-3 (2)). This error code is helpful for further analysis by the repair service.
Device-Diagnostic Log
Memory failure (recoverable): Reset initiated.
PCB link failure (non recoverable):
• Check the module configuration and interconnection.
• If the failure remains, contact the repair service.
Binary-output failure at module 1-12:
Contact the repair service.
Hardware failure at module 1-12:
Contact the repair service.
Wrong module 1-12 detected:
Synchronize the hardware configuration of the device with DIGSI.
Wrong plug-in module detected at position E/F/M/N/P:
Synchronize the hardware configuration of the device with DIGSI.
Device-Diagnostic Log
Hardware failure at measuring-transducer module position E/F/M/N/P:
Contact the repair service.
A faulty display configuration was detected:
Synchronize the hardware configuration of the device with DIGSI.
Offset failure at a measuring input:
• Check for the affected module in the operational log.
• If the failure remains, contact the repair service.
A wrong display type was detected.
Contact the repair service.
CPU failure at base module:
Contact the repair service.
Communication-configuration failure:
• Reload the DIGSI device configuration.
• Update the device firmware or the DIGSI device configuration.
Port E/F/M/N/P: Communication module with incompatible firmware version detected.
Firmware update required.
Clock failure:
• Check time setting first.
• Change the battery if necessary.
• If the failure remains, contact the repair service.
A current terminal is missing.
Check your hardware and the connections!
FPGA hardware failure at the base module:
Contact the repair service.
The device is low on memory. Reduce the number of allocated functions, stages, and/or setting groups in the
configuration.
Configuration error:
The version of one or more functions is incompatible to the used firmware. Load a suitable DIGSI device
configuration.
Failed reading significant feature
Unknown significant feature
Failed reading bay type
Wrong hardware configuration:
Synchronize the hardware configuration of the device with DIGSI.
Unknown bay type
Failed reading disconnector type
Unknown disconnector type
Maximum number of feeder bays exceeded
Maximum number of coupler bays exceeded
Maximum number of coupler bays with 1 CT exceeded
Maximum number of coupler bays with 2 CT exceeded
Maximum number of coupler bays without CT exceeded
Maximum number of bus section bays exceeded
Maximum number of bus zones exceeded
Maximum number of bus zones without measuring system exceeded
Maximum number of disconnectors exceeded
Maximum number of busbar disconnectors exceeded
Maximum number of line disconnectors to busbar exceeded
Device-Diagnostic Log
Maximum number of line disconnectors exceeded
Maximum number of transfer bus disconnectors exceeded
Maximum number of sectionalizing disconnectors exceeded
Maximum number of level 2 disconnectors exceeded
Maximum number of load breaking switches exceeded
Maximum number of bays exceeded
Auxiliary power-supply failure:
Check the external power supply.
Either 1 busbar disconnector or 1 line disconnector allowed
Maximum number of Busbar DC & Transferbus DC exceeded
Undefined bay type
Undefined disconnector type
At least one Feeder is necessary
Failure of device configuration:
Check the logs for reasons and upload valid configuration into device.
The voltage measured values indicate a failure.
There is no CFC logic available or a negative ID of measuring point is selected for Function block Voltage
measuring-point selection (1ph).
The voltage measured values indicate a failure.
There is no CFC logic available or a negative ID of measuring point is selected for Function block Voltage
measuring-point selection (3ph).
A non-existing voltage measuring point ID is selected for Function block Voltage measuring-point selection
(1ph). Please check your CFC logic.
A non-existing voltage measuring point ID is selected for Function block Voltage measuring-point selection
(3ph). Please check your CFC logic.
Failure in data structure:
Contact the repair service.
Firmware-version failure:
• Update the device firmware.
• If the failure remains, contact the repair service.
Bus link failure:
• Check the connection of the modules.
• Update the device firmware.
• If the failure remains, contact the repair service.
The IEC 61850 protocol could not be started up successfully. Too many protection functions might be config-
ured leading to a memory leakage problem for protocol data. Protocol health set to alarm. Reduce the
amount of configured protection functions.
Error instantiating a GOOSE control block for subscription. Too many protection functions might be config-
ured leading to a memory leakage problem for protocol data. Protocol health set to alarm. Reduce the
amount of configured protection functions.
Internal power supply failure:
Contact the repair service.
Module update failure:
• Check the module interconnection and carry out the update again.
• If the failure remains, contact the repair service.
Hardware failure:
Contact the repair service.
A failure could not be solved automatically:
• Check the previous entries of device-diagnosis log.
• If the failure remains, contact the repair service.
Device-Diagnostic Log
Signature failure:
Contact the repair service.
A failure occurred during the device startup:
• Check the previous entries of device-diagnosis log.
• If the failure remains, contact the repair service.
The device firmware could not be started:
• Carry out the update again.
• If the failure remains, contact the repair service.
Internal memory failure: .
• Stored data may be lost.
• Upload the firmware and the configuration again.
• If the failure remains, contact the repair service.
Data transfer time-out:
• Check the connections and repeat the upload.
• If the failure remains, contact the repair service.
Forced Fallback mode by local user.
Arc protection:
• The device hardware does not fit to the DIGSI configuration.
• Correct the configuration in DIGSI 5 and transfer a valid configuration to the device.
The maximum number of sampled measured value channels (SAV) is exceeded.
PQ Flicker does not support more than one Meas. point V-3ph. Route only one Meas. point V-3ph to function
group or remove PQ Flicker
PQ Flicker does not support the selected rated frequency. Use 50 Hz or 60 Hz.
PQ Flicker does not support selected connection type. Change the connection type of the voltage trans-
former.
Device-configuration failure:
The number of signals in a GOOSE dataset/application is too big. Reduce the number of signals in the related
dataset and upload a valid configuration.
Battery failure:
Change the device battery. To avoid data loss, Siemens recommends replacing the device battery with the
device supply voltage switched on.
Function-point violation:
No adequate number of function points. Upload a valid configuration or contact your local sales organization.
Measurement calibration failure:
• Check the affected module in the operational log.
• If the failure remains, contact the repair service.
CPU program-sequence failure:
If the failure remains, contact the repair service.
Time-synchronization masters failed:
• Check the external master clocks first.
• Check the external wiring.
• If the failure remains, contact the repair service.
CPU overload failure:
If the failure remains, contact the repair service.
CFC failure:
Check your CFC chart in DIGSI for reasons and reload the configuration.
PCB link failure (sporadic):
• Check the module configuration and interconnection.
• If the failure remains, contact the repair service.
The connection to the detached operation panel is disturbed. Check the connection.
If you cannot correct a defect reported by the device, you can replace this device with a backup device. If the
error is on the base module, only the base module is replaced. Expansion modules belonging to the device
remain at the installation location and are connected to the backup base module. If the error is on an expan-
sion module, only this expansion module is exchanged.
The backup module must be of the same type as the defective module to be replaced. If you replace the defec-
tive base module, the backup base module is configured with available project data from DIGSI.
NOTE
i If the device comprises a base module and expansion modules, you can exchange the base module as well
as the expansion modules individually for the respective replacement modules.
• Remove the wired terminal blocks from the module to be exchanged or alternatively all lines from the
device.
• If needed, remove the defective base module from the expansion modules.
• If needed, assemble the replacement base module with the expansion modules.
• Put the device back into operation (see chapter 9.3.1 Establishing Readiness for Operation State.)
NOTE
i If the wired terminals of the defective base module are to remain in the system, fit the defective base
module with the terminals of the replacement module or order replacement terminals.
• Ensure that the devices are either shipped with the original current and voltage terminals or, alternatively
– if the wired terminals are to remain in the system – with the designated transport safety devices.
If there are green single-row voltage terminals, it is irrelevant in terms of transport whether or not they
are plugged in. They do not require any alternative transport safety device.
• Protect the optical interfaces on the communication or arc-protection modules against the ingress of
dust. Use, for example, the protective caps provided in the delivery condition.
• Pack the defective module (base module and expansion module) or the complete device (see chapter
1.1 Unpacking, Repacking, Returning, and Storing).
NOTE
i If the base module is incomplete, for example if terminals are missing, it cannot be taken back.
10.4.1 General
You can use DIGSI 5 for updating both the configuration and the firmware. No additional tool is necessary for
updating the firmware of the device or the firmware of the communication module. In order to carry out an
update, you must first import the new DIGSI device driver (DDD) into DIGSI 5. You can then update the device
firmware and the configuration. When updating the firmware, use a connection with at least 1 Mbit/s.
If you wish to use new functions or if the manufacturer provides an improved version of the firmware, a firm-
ware update is necessary. The files for the firmware update are digitally signed. This prevents you from
loading the device with any faulty files or firmware that is not suitable for the device.
If you have installed new communication modules in the SIPROTEC 5 device, check the firmware version of the
individual components. You can find up-to-date device drivers and communication protocols (*.DDD, DIGSI
Device Driver) in the Siemens download area.
DIGSI 5 device drivers contain both the firmware and the configuration data.
Siemens recommends performing the firmware update on the device locally. If you wish to start the firmware
update remotely, use a data circuit with a transmission rate of at least 1 Mbit/s.
Step 1
• Download the device drivers or protocol drivers necessary for updating your SIPROTEC 5 device from the
Siemens download area.
http://www.siemens.com/siprotec
• Open the overview of download products with the > Enter link.
Step 2
• In the SIPROTEC 5 and DIGSI 5 Downloads download area, select the device (for example: 7SL87).
• Save the file to any location on your DIGSI 5 PC, for example, C:\temp.
• Save the file to any location on your DIGSI 5 PC, for example, C:\temp.
Step 3
• Select the previously saved device driver file (DDD for device and protocol) in DIGSI 5 via the menu item
Tools → Import device drivers.
[scdddcom-260716-01, 1, en_US]
If the process has been completed without errors, the following dialog will appear:
[scsucddd-260716-01, 1, en_US]
[scgetrvw-250716-01, 1, en_US]
NOTE
i Before doing a firmware update of your SIPROTEC 5 device or the communication modules, back up the
data and the configuration of the device using DIGSI 5 via Connect device and retrieve data!
NOTE
i The device will not carry out any functions during the update.
The update can take several minutes and the device can reboot several times. Do not shut off the device
under any conditions during the update.
[scausfiw-011116-01, 1, en_US]
As an alternative, you can update the firmware for all the devices on the network at the same time.
• To do this, double-click in the project tree the menu item Load firmware to devices.
[scmulaus-260716-01, 1, en_US]
The following dialog allows you to select the devices to be updated and their firmware components.
[scfwupsd-280716-01, 2, en_US]
• Confirm the subsequent dialog with Yes if you would like to continue with the firmware update.
[sc_fw_req, 1, en_US]
[sc_transferfw, 1, en_US]
After the data has been transmitted successfully to the device, the firmware update starts automatically on the
SIPROTEC 5 device.
[scfwdvlo-280716-01, 1, en_US]
After the firmware update of the device and the communication modules, all firmware components of the
device have been updated.
You can find more information on this in Structure of the HW/SW Information Menu Item, Page 217.
The firmware for the communication modules consists of the basic firmware and all available protocols. The
communication drivers depend on the device firmware and must be updated together with this firmware.
When you set parameters for a protocol in DIGSI 5 and when you load the configuration into the device, the
protocol firmware is loaded automatically in the device if necessary.
To be able to use the extended functionality after a firmware update, you must perform an upgrade of the
configuration. Proceed as follows:
NOTE
i Before doing an update, back up the configuration of your SIPROTEC 5 device using DIGSI 5 via Connect to
device and retrieve data!
[scupgpar-041016-01, 1, en_US]
• Select the desired device configuration and the corresponding communication configuration by selecting
the available version:
[scupgcnf-290716-01, 1, en_US]
[scaktolf-290716-01, 1, en_US]
[scupginf-260716-01, 1, en_US]
The 2nd tab shows information, possible errors and warnings regarding the upgrade procedure.
[scupgwrn-260716-01, 1, en_US]
[scupgpa2-130913-01, 2, en_US]
• Click Ok to confirm.
If the data was successfully transmitted, the device is restarted.
Safety Instructions
! DANGER
Danger due to the execution of test functions
Noncompliance with safety instructions will result in death, serious physical injury, or considerable
material damage.
² The execution of test functions requires a high degree of qualification and precise know-how of
system conditions.
Procedure
DIGSI 5 offers the possibility to start different test and diagnostic functions for a SIPROTEC 5 device in the
Online operating mode. In chapter 9.2.1 Test Functions you will find the description of the test functions that
the device and DIGSI 5 offer you.
Activate the test functions via the menu bar and via different functions that you reach via the list view of the
device.
² Open the device in the Online operating mode.
² Open Test suite in the project tree.
[sctstsut-140211-01.tif, 1, en_US]
All subordinate test options appear in the data window. Select the desired test editor and start the test. If
configured, enter the confirmation ID. In some test functions the device switches to an operating mode that
first requires a system start of the device. Confirm this with DIGSI 5. The selected test function then becomes
available.
NOTE
i Depending on the device layout, not all test functions are always available. The execution of test functions
is protected by a confirmation ID.
Procedure
If the test mode is switched on, indications transmitted via communication interfaces are labeled with an addi-
tional test bit, provided this is supported by the protocol. With this test bit you can determine whether an indi-
cation is generated in a test and all or individual functions of the device are in the test mode. In this manner
the reactions that are necessary in the normal mode due to an indication can be suppressed in other devices
that receive these indications.
• You can activate the test mode via a binary input. All functions in the device are hence in the test mode.
• You can activate the test mode via a GOOSE indication from another device. This allows you, for example,
to bring several devices into the test state virtually simultaneously.
• If you have activated a confirmation ID, this is queried by DIGSI 5 or the integrated control before start of
the test mode.
• You can switch on the test mode via the integrated control.
• You can activate the test mode via DIGSI 5. All functions go into the test mode.
• You can bring selected functions into the test state. DIGSI 5 offers a test editor for this purpose.
The test editor shows you all protection functions in the device with the current states. The state of a
function is set systematically there to Test. An activated test mode is marked with a check mark in the
menu item.
[scsetsfk-160413-01.tif, 1, en_US]
Procedure
If block monitoring direction is switched on, no indications are output via the system interface(s) of a
SIPROTEC 5 device. Block monitoring direction can be switched on or off depending on the current state.
• Select block monitoring direction via the on-site operation panel.
• Enter the confirmation ID so that block monitoring direction can be activated.
[scblkdir-080413-01.tif, 1, en_US]
[scmemspr-081015, 1, en_US]
When switching block monitoring direction on or off, an indication is output in the left area of the status bar.
Bar segments inform you as well about the progress of the process.
NOTE
i The settings via the on-site operation, like the binary inputs, have no effect for the DNP3 protocol.
The >Block monitoring dir. signal is only provided for the IEC 60870-5-103 protocol.
[scproest-230311-01.tif, 1, en_US]
NOTE
i The confirmation IDs are only needed if the role-based access control (RBAC) is not activated in the
SIPROTEC 5 device.
The 3-level security concept consists of secure authentication, the connection password, and other confirma-
tion IDs. This concept provides the highest possible degree of access protection during operation. Even remote
access to devices is protected. You can also use an Ethernet module exclusively for the communication with
DIGSI 5. Access by a substation control network with the unsecured IEC 61850 protocol and remote access
with DIGSI 5 are then carried out via completely separate networks. Even though the SIPROTEC 5 device
communicates with DIGSI 5 via an Ethernet module, communication between DIGSI 5 and the device is
encrypted using tap-proof technology.
Wrong password entries are identified and logged. An alarm can be triggered via remote link. Safety-critical
operations are also logged and cannot be deleted in the device. If files on the PC were manipulated by
malware (for example viruses), they cannot be loaded into the device.
• Communication interface
The confirmation IDs then apply for on-site operation and for operation with DIGSI 5.
You can deactivate or reset the connection password at the on-site operation panel. You can change the
connection password with DIGSI 5 by entering the old connection password and then assigning a new pass-
word.
You can change the confirmation ID via the Ethernet network. Communication is encrypted and tamper-
resistant.
Proceed as follows for the security settings:
• Establish a direct connection from DIGSI 5 to the USB interface of the device.
• Set and initialize the connection password.
NOTE
i If the battery of the device no longer functions or has been taken out, the connection password will be
deactivated after restarting the device. You can find more information in chapter 11.7 Using Connection
Passwords and Confirmation IDs.
11.4 Confirmation ID
NOTE
i If you have not activated access protection with a confirmation code and connection password, the device
operates using role-based access control (see chapter 11.9 Operational Security and Access Control).
The confirmation ID consists of 6 digits, see Table 8-10. If DIGSI 5 is online with the device and you execute
safety-critical actions, the query also protects against undesirable actions during operation. Use only DIGSI 5 to
set the confirmation IDs. After initialization of the confirmation ID with DIGSI 5, the query is saved in the
device.
Change the confirmation ID as follows.
• Double-click the Security menu item in the project tree.
• Click the Change... button in the action column (see Figure 11-3).
[scbstcod-021116-01, 1, en_US]
NOTE
Enter the setting of the confirmation ID with DIGSI 5. For devices with a key switch, non-interlocked switching
is possible by selecting the Interlocking Off position. If no key switch is present, there is a confirmation ID in
the on-site operation panel or in DIGSI 5 before non-interlocked switching is possible. If you have entered the
correct confirmation ID, non-interlocked switching is possible.
• Resetting meters
• Executing other safety-critical operations that carry out a write access to the device, for example, deleting
of fault records and logs
NOTE
i Deactivation of the connection password means that a user has access to the device through DIGSI 5. If you
wish to hinder this, set the connection password in the device.
[scaktvor-210311-01.tif, 1, en_US]
Figure 11-3 Setting Window for the Connection Password and the Confirmation ID
After entering a new connection password, the password is automatically transferred to the device (an empty
text box will not be accepted). Initialization of the connection password is possible only via the front USB inter-
face or via an Ethernet interface.
Further access to the device after connection is possible only if you have entered the connection password in
the DIGSI 5 dialog and communication with the device has been established. This procedure prevents unau-
thorized access. Siemens recommends that the connection password be checked after initialization.
A connection password is not copied from one device to another device. You must enter the password in
offline mode from DIGSI 5 for every individual device of a project.
You can change the connection password online via an Ethernet connection. After entering the previous pass-
word and entering and repeating the new password, the device accepts the change. This change is always
encrypted and tamper-resistant.
NOTE
NOTE
i If the battery of the device no longer functions or has been taken out, the connection password will be
deactivated after restarting the device.
Using DIGSI 5 reset the confirmation ID for the offline configuration of the device as well (see 11.4 Confirma-
tion ID).
² For this purpose, use the DIGSI 5 dialog Have you forgotten one of the confirmation IDs or the
connection password?
The device must now be initialized with the project data that was saved with DIGSI 5 for this device.
Because the connection password was deleted and the confirmation ID reset, the project data for this device
can be transferred easily.
• Module port
You can find additional information on the security log in chapter 8.5.7 Security Log.
Figure 11-4 shows an example of the setting options for the port and IP addresses in DIGSI for 2 syslog servers.
[sccenlog1-130417-01, 2, en_US]
With the adjustable Security log cap. warn. threshold, you can determine from which utilization of the
security log on a warning indication is issued. A warning threshold of 80 % means that the set capacity limit
has been reached after approx. 1600 entries in the security log. Further warning indications are issued when
the capacity limits of 85 %, 90 %, 95 %, and 98 % are reached.
If the log organized as a ring buffer exceeds the 100 % capacity limit, the oldest entries are automatically over-
written and the capacity utilization is reset to 0 %.
When you read the security log using DIGSI 5, the capacity utilization is reset to 0 %. The indications remain in
the device. You must apply all settings with DIGSI 5.
NOTE
i If you downgrade the firmware to a version <V07.50, the device-internal log size is decreased from the
current value of 2048 entries to 500 entries. The older firmware supports only 500 entries in another
format. In this case, the most recent 500 entries are taken from the current/syslog-capable device status
and format and applied to the older firmware-appropriate format. The rest of the entries is lost.
After the downgrade, the contents of the internal log with its 2048 entries is deleted. A message that a
firmware downgrade has taken place is logged as the most recent entry in the ported log after the down-
grade.
[sc_centrlog, 1, en_US]
Recordings
The following items are logged in the security log and forwarded to a connected syslog server:
• Actions
– Successful log off of a user, even after a certain period of time
– Successful log on of a user
– Change or delete the connection password
– Update or restore the firmware version in the device
– Update the configuration in the device
– Change the operating mode of the device
– Change the date and time
– Change or overwrite state value entries by the logged-on user
– Switching operations by the registered user
• Potential errors
– Number of entries with correct or incorrect passwords
– Unsuccessful login attempt by typing 3 wrong passwords
– Reboot or restart the device
• Other entries
– Capacity warning of the security log
The following table shows when which type of message (including format) and which action is expected.
Event/Alarm Summary Syslog Message Event Information
Severity
Successful remote and local WARNING The content of the events for the successful logon
logon depends on whether RBAC is active or not and on the
location from which the logon is made: Remotely (for
example, DIGSI) or locally (on-site operation).
Manual logoff WARNING The events for the manual logoff are logged in the Audit-
Trail and transmitted using syslog UDP. The content of
the indication depends on whether RBAC is active or not.
Logoff determined by time WARNING The content of the indication depends on whether RBAC
is active or not.
Forcing control operations WARNING Events for control operations initiated locally or
remotely. For example:
• Changing the position of the poles
• Tripping/closing operations in relation to the
primary equipment
• Command operations in relation to the primary
equipment
• Mode-change operations in relation to the primary
equipment
• Start/cancellation of the switching sequence
• Change in coil position
• Control of sequential voltages/target voltages
• Control of the switching authority
• Controlling the winding selection
Downloading the configura- WARNING Events relating to downloading the protection configura-
tion tion to a PC
Uploading the configuration WARNING Events relating to uploading the protection configura-
tion from a PC to a device
NOTE
i The use of a confirmation ID is not logged. Only cyber security-related events are logged.
• IEC 61850
• IEC 60870-5-103
All warning indications or alarms are available as temporary indications.
• Commissioning mode
• Fallback mode
[scsolradius, 1, en_US]
During a user logon, the SIPROTEC 5 device sends the user name and password to a RADIUS authentication
server. This server checks the user data and, in case of successful authentication, sends the assigned roles of
the specific user back to the SIPROTEC 5 device.
SIPROTEC 5 devices have an advanced role-based access control with predefined roles. Users are assigned
roles; roles receive rights according to their functions. The assignment between users and roles is defined in
the configuration for a RADIUS server. The assignment of rights to roles is defined in the security configuration
for the SIPROTEC 5 device.
The following requirements are supported by SIPROTEC 5 devices:
• Minimum roles, role and right assignment from the IEC 62351-8 and IEEE 1686 standards
• Minimum roles and rights recommended in the BDEW white paper
NOTE
i If you have not activated the role-based access control, the device operates with a confirmation ID and
connection password (see chapter 11.7 Using Connection Passwords and Confirmation IDs).
RADIUS Server
The main tasks of the RADIUS server are the authentication and control of user access rights. During authenti-
cation, the service determines who the connecting user is. Unique user names and passwords are used to
check whether the user is actually who they claim.
If the user is clearly identified, the authorization handles assignment of the access rights. The user receives
specific access rights to data or services of the SIPROTEC 5 device. Furthermore, the data is recorded for later
analysis (audit trail).
The following data is recorded, for example:
• Connection attempts
• User name
• Time of logon
[dw_use_RADIUS-server, 1, en_US]
• Open the Safety and security menu item in the project tree.
[sc_rbacacccontr, 1, en_US]
First, establish the connection between the SIPROTEC 5 device and a RADIUS server as the authentication
server.
• Activate the access control.
[sc_rbacselect, 1, en_US]
NOTE
i Note that no emergency account exists after starting the access control (see 11.10 Emergency Restore).
NOTE
i Note that a connection password set before the activation of RBAC must be deactivated.
Logon Attempts
You can change the parameters for logon attempts in the following menu:
• Change the following 3 parameters if necessary.
[sc_passwsec, 1, en_US]
• Time lapse
– With this parameter, you set the time range after which the number of login attempts is set back to
0 after the last unsuccessful attempt.
• Blocked duration
– With this parameter, you set the time during which the device remains blocked after the maximum
number of login attempts is reached.
If you log on with the correspond references, the login attempts are counted. Once the maximum number of
login attempts has been reached, logging on is not possible for the set Blocked duration. If this Blocked
duration has elapsed, logon can proceed once again.
[sc_rbacacc, 1, en_US]
The following figure shows an example of the settings for the RADIUS server in DIGSI 5.
[sc_radserv, 1, en_US]
• For server B, enter an IP address that is different from the one for server A.
• Follow the same steps as for the settings for the 1st server.
NOTE
i Note that no security settings can be changed locally on the SIPROTEC 5 device regardless of the access
rights of the user.
INSTALLER
ENGINEER
SECADM
SECAUD
VIEWER
Administrator
RBACMGMT
OPERATOR
INSTALLER
ENGINEER
SECADM
SECAUD
VIEWER
Change CFG Changing/downloading/uploading the
X4 – X X – – – X
configuration
Change FW Changing the firmware – – – X – – – X
RBAC Mgmt RBAC management – – – – X – X X
Audit Trail Audit Trail – – – – X X – X
Security Mgmt Managing and performing security
– – – – X – – –
functions
User Management
A role is a combination of rights defined for the SIPROTEC 5 device. You can assign a role to users in various
contexts. The role(s) a user has in specific contexts determines what the user is or is not allowed to do in the
SIPROTEC 5 device.
You can find more information on the RADIUS server in the download area under → Cyber Security
Products and Solutions → Cyber Security General Downloads.
• Interlocking_Mode
4 Only downloading
[sc_logdevrbac, 1, en_US]
NOTE
i Store the SCRF file at a secure location because any user is able to use this file.
Load and back up the SCRF file when commissioning the device.
To do this, proceed as follows:
• Connect the SIPROTEC 5 device to a PC using a network cable.
• Start DIGSI 5.
• Log on as security-administrator.
• Select Security.
[sc_scrf_dl, 1, en_US]
NOTE
i Note that no emergency account exists after starting the access control.
You can activate the emergency accounts only via DIGSI 5.
• Switch to the Safety and security menu item in the project tree.
[sc_emaccset, 1, en_US]
• For on-site operation of the device, enter an emergency password that is at least 6 numbers long.
• For operation via DIGSI, enter an emergency password with at least 8 characters, which must consist of
upper-case letters, lower-case letters, numbers, and special characters.
[sc_emapasswset, 1, en_US]
NOTE
i Note that the emergency password for on-site operation can be entered only directly on the device and
that the emergency password for DIGSI access can be entered only via DIGSI.
If the centralized user management (RADIUS server) cannot be accessed and you cannot log on as a user, you
can also access the device via DIGSI 5. You need the emergency password for DIGSI access for this.
NOTE
i You can use this emergency access only if you do not have access to the centralized user management of
the used server (for example, RADIUS).
• Start DIGSI 5.
NOTE
i Every user can reset the device security settings by uploading this signed SCRF file.
NOTE
i Store the SCRF file at a secure location because any user is able to use this file.
NOTE
i Note that this file can always be used to reset the security settings and it must be effectively deleted from
the PC for this reason after resetting.
11.11 Decommissioning
Secure Reset to Factory Default Settings
To return the device to its factory default state, the signed SFRF file (Secure Factory Reset File) must be loaded
from the SIPROTEC 5 device first. Siemens recommends storing the SFRF file in a secure location. The security
administrator role is required for configuring the factory default state.
Load and back up the SFRF file when commissioning the device.
To do this, proceed as follows:
• Connect the SIPROTEC 5 device to a PC using a network cable.
• Start DIGSI 5.
• Select Security.
[sc_sfrf_dl, 1, en_US]
• Start DIGSI 5.
• Select Security.
NOTE
i Note that all of the data on the device as well as the security and protection settings are cleared upon
loading the SFRF file.
NOTE
i Store the SFRF file in a secure location because any user is able to use this file.
NOTE
i Note that this file can always be used again for decommissioning and must be effectively deleted from the
PC for this reason after decommissioning.
Chatter blocking
A rapidly intermittent input (for example, owing to a relay contact fault) is disconnected after a parameteriz-
able monitoring time and therefore cannot generate any more signal changes. The function prevents the
system from overloading in the event of an error.
Control display
The control display becomes visible for devices with a large display after pressing the Control key. The diagram
contains the switching devices to be controlled in the feeder. The control display serves for implementing
switching operations. Specification of this diagram forms part of configuring.
Data window
The right area of the project window visualizes the content of the area selected in the navigation window. The
data window contains for example, indications or measured values of the information lists or the function
selection for parameterization of the device.
DIGSI
Configuration software for SIPROTEC
Double command
Double commands (DPC – Double Point Control) are process outputs which visualize 4 process states at 2
outputs: 2 defined states (for example, On/Off) and 2 undefined states (for example, disturbed positions).
DPC
IEC 61850 data type: Double Point Control
Folder
This object type helps when structuring a project hierarchically.
Function group
Functions are brought together into function groups (FG). The assignment of functions to current and/or
voltage transformers (assignment of functions to measuring points), the information exchange between the
function groups via interfaces as well as the generation of group indications are important for this bringing
together.
General interrogation
The state of all process inputs, of the status, and of the error image are scanned on system startup. This infor-
mation is used to update the system-side process image. Likewise, the current process state can be interro-
gated after data loss with a general interrogation (GI).
GOOSE
Generic Object-Oriented Substation Event
Ground
The conductive ground whose electric potential can be set equal to 0 at every point. In the area of grounding
conductors, the ground can have a potential diverging from 0. The term reference ground is also used for
this situation.
Grounding
The grounding is the entirety of all means and measuring for grounding.
IEC
International Electrotechnical Commission - International electrotechnical standardization body
IP
Internet Protocol
List view
The right area of the project window displays the names and symbols of the objects which are within a
container selected in the tree view. As the visualization is in the form of a list, this area is also referred to as list
view.
Metered value
Metered values are a processing function, used to determine the total number of discrete similar events
(counting pulses), for example, as integral over a time span. In the power supply utility field, electrical energy
is often recorded as a metered value (energy import/delivery, energy transport).
Navigation window
Left area of the project window, which visualizes the names and symbols of all containers of a project in the
form of a hierarchical tree structure.
Offline
If there is no communication connection between a PC program (for example, configuration program) and a
runtime application (for example, a PC application), the PC program is offline. The PC program executes in
Offline mode.
Online
If there is a communication connection between a PC program (for example, configuration program) and a
runtime application (for example, a PC application), the PC program is online. The PC program executes in
Online mode.
Parameterization
Comprehensive term for all setting work on the device. You can parameterize the protection functions with
DIGSI 5 or sometimes also directly on the device.
Parameter set
The parameter set is the entirety of all parameters that can be set for a SIPROTEC device.
PLC
Programmable Logic Controller
Project
In terms of content, a project is the replication of a real energy supply system. In graphic terms, a project is
represented as a number of objects which are incorporated in a hierarchical structure. Physically, a project
consists of a series of directories and files containing project data.
Protection device
A protection device detects erroneous states in distribution networks, taking into account various criteria, such
as error distance, error direction or fault direction, triggering a disconnection of the defective network section.
RSTP
Rapid Spanning Tree Protocol
SCD
Ssubstation Configuration Description
Single command
Single commands (SPC – Single Point Control) are process outputs which visualize 2 process states (for
example, On/Off) at an output.
SIPROTEC
The registered trademark SIPROTEC designates the product family of protection devices and fault recorders.
SIPROTEC 5 device
This object type represents a real SIPROTEC device with all the contained setting values and process data.
SPC
IEC 61850 data type: Single Point Control
SPS
IEC 61850 data type: Single Point Status
TCP
Transmission Control Protocol
Time stamp
A time stamp is a value in a defined format. The time stamp assigns a time point to an event, for example, in a
log file. Time stamps ensure that events can be found again.
UTC
Universal Time Coordinated
F
L
Factory default settings 263
Fallback Mode 215 Language Selection 171
Fault definition 161 Lockout 133
Fault log 139 Log 136
Fault recording 161 Configuring 136
Fault records Deleting 152
Displaying 162 Logs 152
recording 164 Management 136
retrieving 100 Logon Attempts 256
Fault Records
deleting 164
reading 161
saving and exporting 163 M
Fault-record channels
Configuration 164 Maintenance 212
Start criterion 165 Manual updating 184
Firmware update 224 Measured values 154
Flush-mounting device Menu dialogs 82
Expanding 22 Menu structure 79
fitting 40 Menu Tree 80
Function settings 174 Metered Values 154
Min./Max./Mean Average
resetting 159
Motor-starting log 150
G
GOOSE communication 205
Ground-fault log 140 N
Grounding a Device 41
Notification windows 82
H
O
Hardware/software information 217
Offline area 94, 94
Offline operation 122
On-site operation panel 68
I Installing 57
Online area 94
Importing and managing device drivers 224 Online mode 94
Incident display Online operation 120
Configuration 131 Operating Concept 68
Spontaneous 131 Operational log 137