100% found this document useful (1 vote)
576 views3 pages

Electrical Cables, DB Method Statements

The document provides instructions for performing megger testing of power cables and branch circuit wiring. It describes the necessary equipment, which includes a megger instrument calibrated to 500V or 1000V depending on the item being tested. The document outlines the pre-test preparation, electrical continuity testing procedure, and short circuit/insulation resistance testing procedure for both wires and cables. It specifies checking for open circuits or shorts, and that test results should be recorded in an approved format for the engineer's reference.

Uploaded by

Babu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
576 views3 pages

Electrical Cables, DB Method Statements

The document provides instructions for performing megger testing of power cables and branch circuit wiring. It describes the necessary equipment, which includes a megger instrument calibrated to 500V or 1000V depending on the item being tested. The document outlines the pre-test preparation, electrical continuity testing procedure, and short circuit/insulation resistance testing procedure for both wires and cables. It specifies checking for open circuits or shorts, and that test results should be recorded in an approved format for the engineer's reference.

Uploaded by

Babu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Method statement megger testing for power cables

&branch circuit wiring, Megger Equipment, Cable Megger


Testing Procedure.

EQUIPMENT AND TOOLS megger testing: -


1. Megger Instrument shall be having valid calibration.

2. Megger-with range 500V/1000V shall be used for conducting the test.

Megger range 500 V shall be used for Wire testing

Megger range 1000 V shall be used for Cable testing

Method statement megger testing


PRE – TEST PREPARATION megger testing: -
1. The leads used for connecting megger testing with the circuit should be fault free and the two
connecting leads should have electrical continuity. It is checked by touching the free ends of the
leads together while the megger button is pressed ON to check for zero resistance.

2. Check for PVC adopters are provided for cables and male adapter for all PVC conduits
terminating in the panel board.

3. Check the dressing is complete for all the wires in the panel boards

4. Confirm all the connections are completed before the testing.


ELECTRICAL CONTINUITY TEST megger testing; -
1. Connect the free megger test probes to any two conductors required to be tested.

2. With all the appliance connected or the two ends of the conductors shorted and all Switches
switched ON the reading shown on the megger should be zero. If the reading shows infinity then
there is an open circuit. The fault should be traced and rectified.

3. For cables, the extreme ends of any two phase is shorted and when the test is conducted the
reading should be zero if the meter reads infinity or some value of mega ohms then there is a
fault in the cable and it should be rectified. Same procedure shall be repeated for other 3
conductors of the cable.

SHORT CIRCUIT TEST / INSULATION RESISTANCE TEST;-

FOR WIRES;

1. For wires the circuit is tested, Megger range should be 500V

I. Between phase and neutral.

II. Between phase to earth

III. Between neutral to earth

With the other ends of the circuit conductor open the value should be infinity for all the test. If
the value is zero there is short circuit or the insulation of the wire is damaged and the wire is
changed accordingly.

FOR CABLES: -

For Cables the Megger range should be 1000V, and both the ends of the cable shall be kept open
and test shall be conducted between phases and neutrals as follows:

neutrals as follows:

i.RtoY

ii.RtoB

iii.YtoB

iv.RtoN

V.YtoN

vi.BtoN
all these reading should be infinity, if otherwise the cable ^ores/phases are faulty and should be
rectified.

The test results shall be recorded in a format for Engineers reference and record. The format
shall be submitted to Consultant for approval in advance prior to perform the megger test
operation.

You might also like