Xinje Hmi Manual
Xinje Hmi Manual
Xinje Hmi Manual
manual【Hardware】
I
1 TP series HMI
1-1 Features
Xinje TP series HMI have strong functions. It supports multi-language, any font and size of
characters. The basic functions include data display and monitoring, alarm, recipe. It can
communicate with most brands of PLC, two ports can communicate individually. The
programming software Touchwin has friendly interface and easy to operate. The software
can simulate online and offline (SCADA function).
□□○○○—□
1 2 3
1:Series name TP
2:LCD size 460:4.7’’
760:7.0’’
3:LCD display L:Monochrome LCD
T:256 colors TFT LCD
1
1-1-3 Product models
TP series HMI can connect to PLC, inverter, meters and other devices. As the interface of
machine and user, it can monitor data, control the machine operation. It is fit for small and
medium control systems.
HMI specifications
Electric specifications
2
Environment
10%RH-90%RH(no condensation)
humidity
Withstand oscillation 10-25HZ(X,Y,Z each direction 30 minutes 2G)
Anti-jamming Voltage noise:1500Vp-p,pulse 1us,1 minute
Surrounding air No corrosive gas
Protection
IP65
construction
Cooling method Natural air cooling
Exterior dimension
173.2*121.4*45.1 200.0*148.0*45.0
Construction (mm)
Mounting dimension
165.2*113.4 182.4*134.4
(mm)
PLC port Support RS232/RS485/RS422
Ports
Download port Support RS232/RS485
1-3 Hardware
Nameplate
Power supply
3
1. Download communication port
The main functions of the port:
Download: Connect with PC to download program;
Communication: Connect with PLC, printer, frequency converter etc, as a
communication port.
Pins of download port:
Pin Name Meaning
1 NC Unused terminal
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 communication “+” signal
5 GND Signal ground
6 BUSY Busy signal
7 B RS485 communication “-” signal
8 NC Unused terminal
9 NC Unused terminal
(1)Download function
When you use download function of TP series, please use Xinje special download cable:
Before user download a program, please make sure your PC has installed multiport serial
card or USB-RS232 convertor, and connect cable correctly, click “ ” button in Touchwin
software, then you could download data successfully, below are the pin definitions:
PC serial Port(COM) Download Port(TP series)
If the connection between PC and HMI is correct, but still can’t download, user
can try “Forced Download” function. The connection diagram of this function as
4
below shows:
Download Port (TP series)
pin5&8 shorted forced download mode
Steps: Pin Name
a. Cut the power of TP, shorted the Pin 5 and 8; 1 NC
2 RXD
b. Power on, move away the shorted line;
3 TXD
c. Start to download the program with special download cable. 4 A
5 GND
6 BUSY
7 B
8 NC
9 NC
(2)Communication function
The download port of TP series not only has the download function, but also has the
powerful communication function.
PLC
TP Series HMI
Send data
Receive data
Printer
When use the communication function of download port, please shorted the pin 5 and pin
6, select the corresponding communication equipment in software settings.
PIN Name
1 NC
2 RXD
3 TXD
4 A
5 GND
6 BUSY
7 B
8 NC
9 NC
Download port communication mode transformation Select communication device of download port
5
2. Communication interface of PLC
The PLC communication port of TP series has below function:
Connect and communication with industrial control equipments: PLC, inverter,
meter etc.
The pins definition of PLC communication port:
Pin Definition Description
1 TD+ RS422 send “+”
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 “+”
5 GND Signal ground
6 TD- RS422 send “—”
7 B RS485 “—”
8 RDD- RS422 receive “—”
9 RDD+ RS422 receive “+”
(1)Communicate with PLC
TP series HMI can communicate with most of popular PLCs
SIEMENS PLC
Data transfer
TP Series
Panasonic PLC
6
(2)Communicate with inverter
TP can communicate with various brands of frequency inverters. For the brands which are
not in the list, user can select Modbus protocol or user-defined protocol.
TP series
Mitsubishi FR series inverter
45.1 163.2
40.6 +0.5
173.2 165.0 0.0 +0.5
0.0
111.4
121.4
113.0
TP760-T(Unit:mm)
148.0
7
1-4-2 Installation and using environment
Install requirements:
TP has four ferric mounting racks when out of factory, there are two square holes on the
top, bottom side of TP, use mounting rack to fix the TP with control cabinet.
In order to avoid TP temperature too high after long time working, please keep 10cm
space on the up/down and 5cm on the left/right side of the TP when installing.
Install panel
Fixed bracket
Install steps:
1. Refer to the dimension in the former chapter to open a rectangle mounting hole in
the control cabinet
2. Add airproof circles in the airproof slot when installing
3. Insert the bottom of TP into the mounting hole of control cabinet
4. Insert the install rack into the fix hole of TP then tighten the screw
5. Connect TP and PLC with communication cable
Notice: The communication cable can be offered by the supplier or made by user
according to the connection diagram, input +24V DC power to start working.
Environment:
Please use TP series touch screen indoor.
+24V 0 V +24V 0 V
+DC- +DC-
Terminal type Pin type
8
Besides, if connect high voltage or AC power supply with TP, the TP may be damaged and
cause electric shock to human body.
NOTE: if use the DC +24V output of PLC to drive the TP, make sure the PLC
has enough current to drive the TP.
9
2 TH series HMI
2-1 Features
Xinje new touch screen TH series are based on TP series products. It not only has the
language, characters editing, data display, monitor and alarm functions but also has
65536 true color LCD which can bring you brand-new vision enjoyment. It has the
advantage of large capability for data duplication and friendly user interface. It provides
perfect humanized solution for industrial system; make it easy to control the system.
3D Two ports
Series Font Adjust the USB data USB data
Color picture Animation Password communication
setting touch area download duplication
library independently
TP 256 √ × × √ √ √ × ×
TH 65536 √ √ √ √ √ √ √ √
10
Communication
Two ports communication independently, can connect two different devices at the
same time
Drive the panel printer directly, economical and flexible
Support free format communication, user edits the driver program
□□○○○—□□
1 2 3
1:Series name TH
2:LCD size 465:4.3”
765:7.0”
865:8.0”
A62:10.1”
A65:10.4”
3:Port type MT/NT:USB-B, TFT-LCD
UT/NU:USB-B, USB-A, TFT-LCD
Special model:
TH465-MT2/ UT2:Increase a com port(RS232) base on the TH465-MT/UT.
TH765-NT3/NU3:Increase a com port(RS485) base on TH765-NT/ NU.
(1)About the hardware configuration of each model, please refer to below “TH
series HMI configuration form”;
(2)The difference between TH765-N and TH765-M: Use different LCD module, but
the function, parameters and specifications are the same;
11
TH series HMI configuration form
PORT1 PORT3
LCD Resolution PORT2 USB-A Download
Series Model Screen Download EXT
size (pixel) PLC port port way
port port
TH465-MT -
-
TH465-UT 1
TH465-MT 232/485/42
TH465 4.3″ 480*272 8MB - -
2 2
232
TH465-UT
1
2
TH765-MT 128M 232/485/42 -
TH765-M 7.0″ 800*480 232/485 -
TH765-UT B 2 1
TH765-NT -
-
TH765-NU 1
USB-B
TH765-NT 128M 232/485/42
TH765-N 7.0″ 800*480 232/485 485 -
3 B 2
(1A6B
TH765-NU
) 1
3
TH865-MT 128M 232/485/42 -
TH865 8.0″ 800*600 232/485 -
TH865-UT B 2 1
THA62-MT 128M 232/485/42 -
THA62 10.1″ 800*480 232/485 -
THA62-UT B 2 2
THA65-MT 128M 232/485/42 -
THA65 10.4″ 800*600 232/485 -
THA65-UT B 2 2
TH series add two kind of power-off retentive registers: PHW (520 thousand
registers) and PRW (1 thousand registers), so if user need the PHW register, user
should mark it, and TH465 doesn’t have PHW, it only has PRW.
HMI specifications
Item TH465 TH765 TH865 THA62 THA65
12
panel
More than 50000 hours, 24 hours running when surrounding
Use life
temperature is 25 ℃
Character Chinese, English, Korean, Japanese…
Character
Any size and font
size
Memory Screen 8MB 128MB
Electrical specifications
Item TH465 TH765 TH865 THA62 THA65
Input DC24V(Range:DC22V-DC26V)
voltage
Consumptio 130mA 250mA 260mA 230mA 630mA
n current
Electrical
Momentary
power off Less than 10ms (Actual power off less than 1s)
allowance
Withstand
AC1000V,10mA,less than 1 minute(signal and ground)
voltage
Insulated
DC500V,above 10MΩ(signal and ground)
impedance
Operation
0-50℃
temperature
Reserve
-20-60℃
temperature
Humidity 10%RH-90%RH (no condensation)
Environment
Withstand
10-25Hz ( X, Y, Z each direction 30 minutes 2G )
oscillation
Anti-jammin
Voltage noise: 1500Vp-p, pulse 1us, 1 minute
g
Surrounding
No corrosive gas
air
Protection
IP65
construction
Cooling
Natural air cooling
method
Construction
13
COM1 RS232/RS485/RS422
Interface
COM2 RS232 RS232/RS485
Expand port - RS485 -
USB 1 USB-A (accord with USB2.0)
USB 2 USB-B (accord with USB2.0)
2-3 Hardware
USB-A
Nameplate
USB-B
Power supply
RS232/RS485/RS422
COM 2
PLC communication
14
1. DIP switch
TH series has 4-bit DIP switch at the back side; they can set the function of COM1 port.
If the screen cannot show normally after downloading the program, please use
force-download to update the system.
Steps:
(1)Cut off the power of TH, turn ON DIP switch 2;
(2)Power on TH, connect the download cable to PC to download the program;
(3)Turn OFF DIP switch 2 after finishing the download, repower on the TH.
1 2 3 4
ON
OFF
2. Communication interface
The COM1 and COM2 port of TH series has below function:
Communication function: Connect to PLC, printer, inverter, meter, etc, used as
communication port.
The pins definition of COM1:
Pin Name Description
1 NC Unused terminal
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 + signal
5 GND Signal ground
6 NC Unused terminal
7 B RS485 — signal
8 NC Unused signal
9 NC Unused signal
15
The pins definition of COM2:
Pin Name Description
1 TD+ RS422 send +
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 + signal
5 GND Signal ground
6 TD- RS422 send -
7 B RS485 -
8 RDD- RS422 receive -
9 RDD+ RS422 receive +
PLC
TH Series HMI
Send data
Receive data
Inverter
Other devices
COM port
16
(1)Communication with PLC
TH series HMI can communicate with most of popular PLCs:
SIEMENS
PLC
Data transfer
TH series
Panasonic PLC
Please select correct PLC port (COM2) device and communication parameters:
Select the correct download port (COM1) device and communication parameters:
17
(2)Communication with inverter
TH can communicate with various brands of frequency inverters. For the brands which are
not in the list, user can select Modbus protocol or user-defined protocol.
TH
Mitsubishi FR series inverter
3. USB-A port
TH series USB-A port has below functions: (accord with USB2.0)
Backup management, data export/import, the speed can up to 480 Mbps.
USB-A
4. USB-B port
TH has one USB-B port (accord with USB2.0), located at the back side of TH, the
functions are shown as below:
18
To download the data, the speed can up to 480Mbps.
TH back side
USB cable
PC
(2)Please install USB driver before using. Download the driver from www.xinje.com.
program.
19
2-4 Dimensions and installation
92.0
24V 0V FG
1 2 3 4
1 2 3 4
PLC
+0.5
144.0 0.0
41.8 152.0
0.0
+0.5
102.0
94.0
TH765-M/TH765-N(Unit: mm)
+0.5
190.0 192.0 0.0
+0.5
138.5 0.0
136.5
THINGET
MODE: TW760T
S/ N: N20081028028
1 2 3 4
20
TH865(Unit: mm)
45.5
38.0 224.4
170.8
+0.5
209.4 211.4 0.0
+0.5
157.8 0.0
155.8
12 34
24V 0V FG
1 2 3 4
Download PLC
THA62(Unit: mm)
272.2 51.2
191.7
+1.0
258.2 260.2 0.0
+1.0
179.7 0.0
177.7
24V 0V FG
1 2 3 4
Download PLC
21
THA65(Unit: mm)
1 2 34
48.0 +24V 0V FG
43.1 300.0
+1.0
302.0 0.0
+1.0
225.0 0.0
223.0
234.0
311.0
Install panel
Fixed bracket
Install steps:
1. Refer to the dimension in the former chapter to open a rectangle mounting hole in
the control cabinet;
2. Add airproof circles in the airproof slot when installing;
3. Insert the bottom of TH into the mounting hole of control cabinet;
4. Insert the install rack into the fix hole of TH then tighten the screw;
5. Connect TH and PLC with communication cable.
Notice: The communication cable can be offered by the supplier or made by user
according to the connection diagram, input +24V DC power to start working
22
Environment:
Please use TH series touch screen indoor.
+24V 0 V
+DC-
Besides, if connect high voltage or AC power supply with TH, the TH may be
damaged and cause electric shock to human body.
If use the DC +24V output of PLC, makes sure the PLC has enough current to
drive the TH.
23
3 TG series HMI
3-1 Features
Xinje TG series HMI have high quality display: 16 million true color TFT-LCD, support
BMP and JPG format, have rich 3D photo gallery, has the flexible components choice
space, user-defined animation, convenient mode setting switch, precise touch calibration
function, data acquisition save function, curve shows, and other forms of data
management ways, offers two USB interfaces, perform high speed data download, high
speed loading and high-speed operation, can communication with several PLC
simultaneously, support Ethernet communication.
□□○○○—□□
1 2 3 4
1:Series name TG
2:Display size 865: 8.0”
A62: 10.1”
3:Interface type E:USB-B, USB-A, Ethernet port
U:USB-B, USB-A
4:Display type T:TFT-LCD
Display
Model LCD Size Interface
material
TG865-ET 8” TFT-LCD
USB-B, USB-A, Ethernet port
TGA62-ET 10.1” TFT-LCD
HMI specifications
Item TG865 TGA62
Size 8.0″ 10.1″
Type 16 million colors
Resolution 800*600 800*480
Brightness Adjust by potentiometer
Screen
Touch panel 4-wire resistance mode
Using life More than 50000 hours, temperature 25℃,running for 24 hours
Language Chinese, English, Japanese, Korean, German, French, Arabic…
Character Any font and size
Memory Capacity 128MB
25
Electric specifications
Item TG865 TGA62
Input voltage DC24V(Range: DC22V-DC26V)
Consumption 190mA 240mA
current
Allowable
momentary Below 10ms (Actual power failure<1s)
Electric
power failure
Withstand
AC1000V,10mA,less than 1 minute(signal and ground)
voltage
Insulated
DC500V,above 10MΩ(signal and ground)
impedance
Operation
0-50℃
temperature
Reserve
-20-60℃
temperature
Environment
10%RH-90%RH(no condensation)
humidity
Environment Withstand
10-25HZ(X,Y,Z each direction 30 minutes 2G)
oscillation
Anti-jamming Voltage noise:1500Vp-p,pulse 1us,1 minute
Surrounding
No corrosive gas
air
Protection
IP65
construction
Cooling
Natural air cooling
method
Exterior
dimension 224.4*170.8*45.5 272.2*191.7*51.2
Construction
(mm)
Mounting
dimension 211.4*157.8 260.2*179.7
(mm)
COM1 RS232/RS485/RS422
COM2 RS232/RS485
Interface Ethernet port RJ45(Only for ET series)
USB1 USB-A (accord with USB2.0), USB flash drive port
USB2 USB-B (accord with USB2.0), USB download port
26
3-3 Hardware
Nameplate
USB-A
USB-B
RJ45
Power supply
12 34
24V 0V FG
1 2 3 4
Download PLC
1 2 3 4
DIP switch Force-download, touch area adjustment
1 2 3 4
27
HMI remote assistance, networking function,
Ethernet port
change data between HMI and HMI…
1. DIP switch
TG series has 4-bit DIP switch at the back side; they can set the function of COM1 port.
Switch DIP1 DIP2 DIP3 DIP4 Function
OFF OFF OFF ON Interior check mode ( not recommended to users)
OFF ON OFF OFF Force-download mode
State System menu: Adjust clock and touch panel,
OFF OFF ON OFF
Import program of USB flash drive
ON OFF OFF OFF Undefined
If the screen cannot show normally after downloading the program, please use
force-download to update the system.
Step:
(1)Cut off the power of TG, turn ON DIP switch 2;
(2)Power on TG, connect the download cable to PC to download the program;
(3)Turn OFF DIP switch 2 after finishing the download, repower on the TG.
1 2 3 4
ON
OFF
2. Communication interface
The Pins definition of COM1:
Pin Name Description
1 NC Unused terminal
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 + signal
5 GND Signal ground
6 NC Unused terminal
7 B RS485 - signal
8 NC Unused terminal
9 NC Unused terminal
28
The Pins definition of COM2:
Pin Name Description
1 TD+ RS422 send +
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 + signal
5 GND Signal ground
6 TD- RS422 send -
7 B RS485 - signal
8 RDD- RS422 receive -
9 RDD+ RS422 receive +
3. USB-A port
USB-A(accord with USB2.0) of TG series HMI has below function:
Backup management, data export/import, the speed can up to 480 Mbps.
4. USB-B port
TG has one USB-B port (accord with USB2.0), located at the back side of TG, the
functions are shown as below:
To download the data, the speed can up to 480Mbps.
USB-B port definition
(2)Please install USB driver before using. Download the driver from www.xinje.com.
29
(3)Connect TH with PC, open Touchwin software, click “ or ” to download the
program.
5. RJ45 port
The pins definition of RJ45 port
Pin Name Description
1 TD+ RS422 send +
2 RXD RS232 receive
3 TXD RS232 send
4 A RS485 + signal
5 GND Signal ground
6 TD- RS422 send -
7 B RS485 - signal
8 RDD- RS422 receive -
9 RDD+ RS422 receive +
30
TGA62(Unit: mm)
Install panel
Fixed bracket
Install steps:
1. Refer to the dimension in the former chapter to open a rectangle mounting hole in
the control cabinet;
2. Add airproof circles in the airproof slot when installing;
3. Insert the bottom of TH into the mounting hole of control cabinet;
4. Insert the install rack into the fix hole of TH then tighten the screw;
5. Connect TH and PLC with communication cable.
Notice: The communication cable can be offered by the supplier or made by user
according to the connection diagram, input +24V DC power to start working
Environment:
31
Please use TG series touch screen indoor.
+24V 0 V
+DC-
Besides, if connect high voltage or AC power supply with TG, the TG may be
damaged and cause electric shock to human body.
If use the DC +24V output of PLC , make sure the PLC has enough current to
drive the TG.
32
Xinje Electronic Co., Ltd.
214072