Ge Avr PDF
Ge Avr PDF
INSTRUCTIONS
STATIC EXCITER-REGULATOR
EQUIPMENT
3S7501FS141
GEK-147’72
TABLE OF CONTENTS
PAGE
INTRODUCTION ........................................................ 3
RECEIVING, HANDLING, AND STORAGE ..................................
Receiving and Handling ................................................
Storage ...............................................................
DESCRIPTION ...........................................................
Component Arrangement ............................................... i
Static Magnetic Power Components and Power Rectifiers .................. 3
Silicon Diode Fundamentals ............................................
Automatic Voltage Regulator ........................................... :
Manual Voltage Regulator .............................................. a
Control Equipment Operation ........................................... a
CT and PT Burdens ................................................... 11
INSTALLATION ......................................................... 11
Location and Mounting ................................................. 11
Connections .......................................................... 11
Polarity and Phase Rotation ............................................ 11
INITIAL OPERATION, TEST, AND ADJUSTMENT .......................... 11
Control Circuits ...................................................... 11
Static Exciter ......................................................... 11
Gain Measurements .................................................... 13
System Self -Compensation ............................................ 13
Under excited Reactive Ampere Limit ................................... 13
MAINTENANCE ......................................................... 16
PPT and SCT’s ........................................................ 16
Static Equipment ...................................................... 17
Other Equipment ...................................................... 17
RENEWAL PARTS ....................................................... 17
TROUBLESHOOTING ..................................................... ia
These instructions do not purport to cover all details or variations in equipment nor to
provide for every possible contingency to be met in connection with installation, operation
or maintenance. Should further information be desired or should particular problems
arise which are not covered sufficiently for the purchaser’s purposes. the matter should
be referred to the General Electric Company.
GEK-14772
STATIC EXCITER-REGULATOR EQUIPMENT
FOR GAS TURBINE PACKAGE POWER PLANT
INTRODUCTION STORAGE
The silicon-controlled rectifier @CR) Static Exciter - If the equipment is not to be used as soon as it is un-
Regulator equipment performs its regulation and ex- packed, it should be stored in a clean dry place and
citation function by monitoring AC machine line volt - protected from accidental damage. Particular care
age and current and producing the proper excitation should be exercised to avoid storing the equipment
conditions required by the machine. in locations where construction wtrk is in progress.
The power potential transformer (PPT) and saturable
current transformers (XT’s) are the main source of DESCRIPTION
power for the AC machine field; at no load all field
power is obtained from the PPT while both supply power COMPONENT ARRANGEMENT
at full load with the SCT’s supplying most of the power.
The power from these two units is rectified by the three- The static exciter-regulator consists of the following:
phase full-wave bridge rectifier and then applied to the
field of the AC machine. The currents in the primaries A. Equipment mounted in the exciter compartment:
of the SCT’s provide some inherent self-regulation.
Theorectically, this self -regulation should completely 1. 3S7501FS Rectifier assembly consisting
compensate for load changes, however, AC machine of a three:-&-&: full-wave bridge rectifier,
saturation, field heating, and other secondary effects shunt, shaft voltage suppressor circuit and
make it necessary to add more compensation. This Thyrite* resistors. This welded angle-fram?
extra compensation is obtained by saturating the SCT’s assembly is floor mounted.
with a DC control winding current. The amount of DC
required is obtained from the automatic regulator whose 2. Three 44A------ Resistor assembleies (one
input continuously monitors line current and voltage resistor in parallel with y SCT control
when in the automatic mode operation. Also, a manual winding and one resistor in parallel with the
control of the DC control winding is provided. SCT suppression winding for each assembly.)
oVOLTAGE
REFERENCE
SCR AMPLIF.
AND
STABILIZING
’ COMPONENTS
P Q
P?
SECONDARIES
PRIMARP
” / \ I i * /
SC T’S LINEAR REACTORS PPT
neutral side. The secondary of each satuarable cur- The control windings of the SCT ‘s are connected in
rent transformer is connected from line to line of the series. A resistor is connected across each control
bridge rectifier . When the AC machine is oper sting winding to reduce the magnitude of the AC voltage
at no-load, the power potential transformer supplies appearing across the control winding.
voltage to the three-phase full-wave bridge rectifier
so that a unidirectional voltage, VSE, is applied to the When the machine is supplying current to a load, the
field of the AC machine. Field voltage is controlled SCT primaries carry the load current. This primary
by means of the saturable current trausformers. The current helps the secondary current excite the iron
exciting current of the saturable current transformers core. Therefore, an increase in primary current
is virtually proportional to the DC current, I , flowing causes a decrease in secondary exciting current for
in their control windings. This exciting curr&t flows a given value of I . A decrease in secondary exciting
from the PPT secondary through the linear reactors in- current decreased the voltage drop across the linear
to the SCT secondaries. When I is increased, the reactors with the result that bridge rectifier input
increased exciting current cause% increased voltage voltage and field voltage are increased. The turns
drop across the linear reactors so that the input voltage ratios of the SCT’s and the PPT end the reactance of
to the bridge rectifier and, consequently, the field the linear reactors are selected so that this increase
voltage is decreased. Thus, no-load terminal voltage in field voltage which accompanies an increase in load
of the AC machine is controlled by the value of Ice current is approximately the increase necessary to
hold terminal voltage constant.
Static Exciter -Regula or Equipment GEK-14772
It is an object of the design to maintain required ter- state, regardless of the lead or power factor, without
mmal voltage on the machine without requiring a change a change III regulator output.
in control current Ic.
If - field current (on the AC side of the rectifier). Figure 2. Equivalent Circuit of Saturable C. T. Type
Static Exciter
I m - is the magnetizing current of the saturable
current transformer (referred to SCT secondary).
magnetizing reactance of the SCT (referred to
xm - the secondary). This reactance decreases
with an increase in direct current from the
regulator.
5
GEK-14772 Static Exciter -Regulator Equipment
Due to various factors, such as AC machine field Certain precautions must be taken when dealing with
heating and field saturation, and other minor effects, circuits containing silicon rectifiers. Brazing or
it is necessary to trim this action of the PPT and SCT’s welding should not be attempted. If soldering is
to provide the exact compensation for load changes. necessary, something must be done to prevent the
This is accomplished by the automatic regulator or by heat from being conducted to the junction. Hipotting
manually controlling the current in the saturating should not be done without first shorting out the diodes,
windings by means of the manualregulator voltage Diodes being replaced must be screwed in with the
adjuster. proper amount of torque.
The suppression windings of the SCT’s are connected
in series with a resistor across each winding. This I One Cycle Of Line Voltage I
resistor, like the control winding resistor, reduces
the magnitude of the AC voltage appearing across the
suppression winding.
When relay 415 is de-energized its power contact
closes, applying power (usually 125 volts DC obtained
from the station battery) to the suppression windings.
The sequence of events that follows is the same as
that produced by the maximum current flowing through
the control windings, i.e., the exciting current in-
creases causing and increased voltage drop across Figure 5. Wave-form Across One Diode
the linear reactors, therefore reducing the input vol- When Oper sting Properly
tage to the bridge rectifier and consequently the field
voltage essentially to zero. AUTOMATIC VOLTAGE REGULATOR
The three-phase bridge rectifier contains twelve cast Automatic Regulator Component Fundamentals
aluminum finned heat sinks with two diodes mounted
on each heat sink (one diode is the reverse polarity Zener Diode
type, i.e., the stud is the anode). The bridge is
convection air cooled. To insure adequate current The current-voltage characteristic of a zener diode
carrying capability, two parallel rectifier bridges are is shown in Figure 6. A zener diode conducts current
furnished. No provisions for isolating one of the at a constant voltage which is nearly independent of
bridges have been made. the value of current. It is an open circuit for all
voltages less than its break-down voltage.
Each rectifier “leg” consists of two diodes in series
to provide sufficient margin for the peak inverse vol-
tages which may appear. The potted block assembly
(PBA) connected across each diode will cause equal
division of the peak inverse voltages which may occur
due to power line transients.
Saturable Reactor As a Firing Element the reset windings in only one direction because of the
diode in series with these windings. To digress to the
Figure 7 shows a simplified version of the SCR old days, a “buck” signal decreases the reset current,
circuit used in this regulator with its associated and “boost” signal increases the reset current.
firing reactor. The gate winding is connected be-
tween the sate and cathode of the SCR. while the re- The saturable reactors are used to provide the neces-
set wind& is connected to a DC source. During sary gate pulses to fire the SCR’s. Refer to Figure
the time that point A is positive with respect to B, 13 in following this discussion. The SCR supply voltage
the gate winding accumulates enough volt-seconds is obtained from one phase of the PPT secondary; it
to saturate the reactor and fire the SCR. When A is this voltage that is applied across the SCR’s and
is negative with respect to B. the flux in the react- their associated firing networks. The firing network
or is reset to a value dictated by the amount of DC for the ABCD SCR consists of a series combination of
current in the reset winding. Increasing and de- A5R, A2SX1, and A6D with the gate of A2CD connected
creasing the reset current causes the SCR to fire between A9R and A2SXl. As the supply voltage in-
Iater or earlier in the positive half cycle of the creases in the positive direction APSXl accumulates
supply voltage. In this way the amount of current enough volt-seconds to saturate its core, and once the
through the load is dependent upon the amount of core saturates, the voltage across all coils wound on
reset or error signal current in the reset windings. the A2SX core becomes zero. When this occurs, the
voltage across A2SXI becomes zero, therefore, caus-
The saturable reactors not only fire the SCR’s but ing the voltage across A9R to increase rapidly and fire
they also provide stabilization and positive feedback the ASCD SCR. When the supply voltage goes negative
for the system. the same sequence of events occurs for the AlCD SCR.
During the time A2CD is conducting, current flows
Operation from A14 through the control windings to AU, through
the A2CD SCR and to the AlT supply transformer, from
The signal PT monitors line voltage and feeds the the AlT supply transformer it then goes through A2D
single-phase bridge whose output delivers a DC and back to A14. The circuitry is so arranged that the
signal which is proportional to the line voltage to current flows through the control windings in the same
the comparison circuit. This signal, applied to a direction when either SCR fires. The average of these
voltage divider and reference zener diode branch current pulses is the DC that the SCT control windings
connected in parallel through the reset windings of see.
the saturable reactors, controls the firing signals for
the SCR’s. The voltage divider is preset in the fact- The error signal current flowing through AlSX2 and
ory such that approximately 13 ma (this may vary A2SX2 in the comparison circuit resets each core for
from 10 ma to 18 ma.) will flow through the reset the next operation and dictates how many volt-seconds
windings when the machine is working at its proper will be needed to fire the SCR’s. If the error signal
voltage. If the line voltage increases, the reset cur- increases, the amount of reset for each SCR is great-
rent decreases, and likewise if the line voltage de- er, therefore, more volt-seconds are needed to saturate
creases the reset current increases. It must be em- AlSX and A2SX. Since more volt-seconds are needed,
phasized at this point that current will flow through the SCR’s fire later in each half cycle, allowing current
to flow through the control windings for a shorter period
of time; hence, less DC current flows inthe control
N
windings. To become more familiar with this operation
lets take the case in which the generator line voltage in-
creases. The sequence of events at no-load is as
gate wdg. follows:
c:2
1. PT output increases
2. DC output of bridge increases
R 3. Error signal current through AlSX2 and
A25X2 decreases (less reset flux in each core)
4. SCR’s fire earlier in each half-cycle of the
supply voltage and conducts longer
5. DC current through the SCT control windings
increases
6. Current through SCT secondary increases
7. Drop across reactor increases
8. Excitation decreases
9. Generator line voltage decreases
Figure 7. Simplified Version of SCR Circuit
GEK-14’772 Static Exciter -Regulator Equipment
Other windings on the saturable firing reactor are more thsn 5-e will cause excessive voltage droop at
AlSX3, A2SX3, AlSX4, and A2SX4. The AlSX3 and the high voltage bus. For generators tied directly at
A2SX3 windings are wired in series with a linear their buses, Er should be approximately 6.9 volts.
reactor and potentiometer; together these items make
up the positive feedback network used to increase the Since the signal current transformer and the signal
gain. Remaining are the AlSE4 and A2SX4 windings potential transformer have a common electrical con-
used for rate feedback stabilization end AlSX5 and nection, only one of the transformers or the common
A2SX5 used with the URAL panel. All windings are connection may be grounded.
wound on the two saturable reactors AlS2S and A2SX.
MANUALVOLTAGEREGULATOR
During the time that each SCR is not conducting,
diodes A5D and A2D along with resistors A8R and A7R The manual voltage regulator consists of two rheostats
protect the SCR’s from reverse voltages. The diodes of which either rheostat, but not both, is in series
appear as very high impedances when their associated with the SCT control windings when operating under
SCR’s are not conducting, Thus, most of the reverse manual control. One rheostat is for “on-line” con-
voltage is across the diode and not the SCR’s. trol and the other for “off-line” control.
Before each unit is shipped for the factory, gain Operation
curves are taken, and potentiometers are checked
and set. The series combination of rheostat and SCT control
windings is supplied from the exciter voltage. If the
Figures 8a and 8b indicate typical curves obtained DC exciter voltage rises above normal, the SCT con-
from the SCR units prior to smpment. trol current will increase. This acts to return the
DC exciter voltage to normal. If the DC exciter
Reactive Current Compensator (RCC) voltage decreases below normal, the SCT control
current will decrease, thereby, raising the exciter
Although the RCC potentiometer is always furnished, voltage toward normal.
the signal CT may not be present. Any reference to
the RCC assumes the signal CT is present. The “on-line” rheostat will be set to give a safe value
of control current to prevent the machine from pulling
The RCC is used to apportion reactive kva and to pre- out of step if there should be an automatic transfer
vent circulating reactive current between AC machines from automatic regulator to manual regulator. This
when two or more machines with individual regulators setting will vary, depending upon customers needs
are operating in parallel. As shown in Figure 9, a or preference and is capable of controlling the voltage
potentiometer is connected in series with the secondary from no-load to ‘I& of full-load. The “off -line”
of the signal potential transformer feeding the reg- rheostat will be set to give a value of control current
ulator averaging circuit. The potentiometer wiper which will reduce the AC machine terminal voltage
is connected to one side of a signal current trans- when the AC machine is tripped off the line to a safe
former, the current transformer located in phase C. value, which is usually line voltage, although there
may again be a customer preferred value other than
The compensator will vary the regulator signal volt- line voltage. These two rheostats are adjusted at
age mainly as a function of the machine reactive cur- initial start-up and require no further adjustments
rent. As the machine overexcited reactive current in subsequent start-ups. They are manually operated
increases, the voltage will be increased. As a re- and are mounted on the DC Control Panel.
sult, the average single-phase signal voltage supplied
to the regulator will rise. Due to this higher voltage CONTROL EQUIPMENT OPERATION
signal, the regulator will act to reduce excitation,
thereby reducing the overexcited reactive current, In the following paragraphs the components designated
with a double asterisk (**) indicates they are not fur-
If the AC machine is operating in the underexcited nished by the Communication and Control Devices
region, the compensator will decrease the average Department of General Electric Company. Some of
single-phase voltage signal presented to the regulator the components serve functions in other circuits of the
so that the regulator will act to increase the excitation generating system but their functions discussed here
and decrease the underexcited reactive current. The will only be in conjunction with the static exciter-
effect of the compensator can be increased by turning regulator. Refer to Figure 13 for the following para-
the knob clockwise (in the direction of the arrow). graphs .
With five amps flowing in the signal CT secondary 59** is the overvoltage relay. Its contact is in series
and with all the resistance in, the total drop is ten with time delay relay 2E** to automatically transfer
volts. It has been experimentally determined that the regulator from automatic to manual mode. When
for proper VAR sharing, i.e. satisfactory apportion- the excitation increases above a safe value, 59E** is
ment of reactive EVA with a minimum number of ad- energized, closing its contact and energizing 2E**.
justments, there should be 5-60/oimpedance between If the excitation remains at this unsafe value for more
the generator and the paralleling bus. Less than than 30 seconds, 2E** seals itself m. Another 2E**
5-a will require more frequent adjustments and contact ~11 de-energize relay 83SR**, transferring
8
Static Exciter-Regulator Equipment GEK-14772
Signal Volts
from PT’s 115
VAC
Output
Amps
Nominal _ _ - - - .-- - - -
Control
Current
9
GEK-14772 Static Exciter -Regulator Equipment
8
c
SIGNAL
CT
1
-
---%
‘Eo *
SIGNAL
PT
1 TO LOAO
+ ”
w.1 N
0 N N AVERAGING
IA CIRCUIT
I 1
TO REFERENCE a
COMPARlSON CIRCUIT
the regulator from automatic to manual mode. To re- 4Y**, 94**, 52GX?* and 14HSY**. The 94** contact,
turn the regulator from automatic mode, momentarily as in the flashing circuit, is normally closed. When the
depress the regulator reset pushbutton 43% de- AC machine exceeds 95% speed, speed relay 14HsT**
energizing 2E**. closes its contact, energizing the 83SR** circuit, there-
by, putting the automatic regulator in service. The
Field flashing is automatic and occurs when relay 41F 52GX** in parallel with the 94** contact prevents the
is energized, This energization results from the follow- regulator from being transferred to the manual mode
ing sequence of contact action. 4Y is a time delay if the shutdown relay 94** is energized before the AC
master control auxiliary relay and is energized on machine line breaker is tripped.
turbine start-up closing its contacts. Relay 94** is
only energized on normal shutdown of the system; 41s is the field suppression relay. When de-energized,
therefore, its contact remains in the normally closed its power contact closes, applying power to the SCT
condition. Speed relay 14HSX** is not energized until suppression windings. With maximum current flowing
the AC machlne attains 95% speed; therefore, its con- through the suppression windings, a large voltage drop
tact remains closed. As the AC machine mcresses exists across the linear reactors such that the input
speed, speed relay 14HAX** is energized at 49% speed voltage to the bridge rectifier and consequently the AC
closing its contact. At this time all the contacts in machine field is essentially zero. 41s is controlled by
series are closed energizing 41F and flashing the field. speed relay 14HMX**, AC machine differential relay
When the AC machine exceeds 95% speed, 14HSX** 86G** end transformer differential relay 86T**. When
is energized, opening the contact, de-energizing 4lF. the speed is above 29%, 86G** and 86T** contacts
The start-up circuit resistance values are chosen to control 41s; i.e., if either or both contacts should open
allow a maximum of 15% of the no-load field current. end lockout because of an AC machine or transformer
The panel is shipped with total circuit resistance which unbalance, 41s will be de-energized. The 14HMX**
will allow approximately 10% of no-load field current. contact’s function is to Bnerglze 41s below 2% speed to
Resistor C3R may be adjusted for the 15% value, if remove power from the SCT suppression winding. 41s
required. has two auxiliary contacts whxh aid in controlling the
close and trip circuits of the AC machine line breaker. ’
The 83SR** transfer relay’s operation is controlled,
in addition to that by relays 59E** and 2E, by relays
10
Static Exciter -Regulator Equipment GEK-14772
11
GEK-14772 Static Exciter -Regulator Equipment
When finally adjusted, the values of C4R and C5R will When proper regulator operation has been secured,
be such that maximum desired AC machine output will optimum stability should be checked by the following
occur with 90R6 at its maximum resistance position. test and the necessary additional adjustments made,
With the regulator in control of the AC machine, ad-
To accomplish this, we must start with the total re- just 9OR4 (9ORl if Manual adjust used) to hold AC
sistance of the on-line circuit equal to the total re- machine volts at approximately 9% or greater. De-
sistance of the off-line circuit when 9OR5 is in its energize 83SR**, putting manual regulator back in
proper start-up position. control of the AC machine.
With some active load on the AC machine, adjust When the AC machine is back at rated voltage and
90R6 until the AC machine is carrying the desired steady, energize 83SR**. The AC machinevoltmeter
reactive load. should overshoot only slightly before returning to
the new steady state value.
If this is impossible to attain, shut down the equip-
ment and increase the effective resistance of C4R
and C5R. Too much resistance will make it impos-
sible to operate as low as might be desired. Before making any adjustments
in the stabilizer circuit, it is
Voltage Level necessary to transfer to manual
control when adjusting A2P or to
The automatic regulator is designed and transformer shut down the unit to adjust A2C.
ratios are selected to give a nominal signal voltage
of approximately 115 volts to the single-phase bridge The on line auto-regulator should be set to cause the
consisting of diodes A7D through AlOD. 90Rl (“off - generator to go on line at a voltage higher than line
line”) end 90R2 (“on-line”) should provide adjustment voltage in order to supply reactive power to the sys-
of at least 10% above and below nominal signal volt- tem. With the motor operated set point adjuster,
age. It is usually preferable to delay the final voltage this is accomplished by setting 9ORl to some small
level adjustment until the reactive current compen- value to give a step change in voltage. With the man-
sator is adjusted, as it may appreciably alter the ual set point adjuster, 9ORl should be set to hold rated
signal voltage. line voltage and 9OR2 to hold a voltage slightly higher
than rated.
Automatic Control
If the signal PT voltage is other than 115 volts, it will
The reactive current compensator (A6P) control knob be necessary to adjust rheostat A3P and/or A4P to
should be turned fully counterclockwise (minimum bring the regulator back to a good operating range.
affect). The URAL amplifier should be removed from Failure to do this may result in the voltage adjuster
service by disconnecting the wire from terminal E8, not having enough range.
Figure 13.
When smooth control and the desired operation has
With the AC machine operating at rated voltage, rated been obtained, the reactive current compensator po-
speed, and disconnected from the line, and with 9OR4 tentiometer A6P can now be adjusted (turning clock-
(90Rl if Manual adjust used) in its midposition, take wise) for the desired compensation for reactive cur-
whatever steps are necessary to energize 83SR**, rent. Refer to the reactive current compensator cir-
thereby causing the AC machine to be under the con- cuit description under the section titled “Automatic
trol of the automatic regulator. Watch carefully for Voltage Regulator” as a guide for the setting of A6P
signs of instability since the system will be most un- for optimum performance.
stable under these conditions. If the system is un-
stable, immediately de-energize 83SR**. Final adjustment of the compensator can only be made
after consider able experience with the machine oper -
Attempt to obtain stable operation by adjusting rhe- ating under control of the automatic regulator. It is
ostat A2P in series with capacitor AX (A2C actually desirable to keep the amount of resistance used to the
consists of five separate capacitors A2CA-A2CE. minimum required for proper division of reactive kva
Refer to the regulator panel connection diagram). Re- between machines to avoid excessive voltage regulation.
duce the resistance to a value that is about 1% less Adjustments may be made with the compensator cur-
than the original value and again place the regulator rent transformer energized. When making adjust-
in control of the AC machine excitation. If the stability ments, the AC machine power factor should swing
still has not improved, repeat the preceding adjustment toward unity as A6P resistance is increased.
using larger and smaller values of resistance. It
should be possible to stabilize the regulator by gradual Regulator Sensitivity and Voltage Regulation
adjustment of this rheostat. However, if the regulator
1s still unstable after the full range of resistance has Determination of AC machine voltage regulation witi.
been tried, the exciter stabilizer capacitors (AZCA- the regulator in sermce is a difficult procedure under
h2CE) should be adjusted in the same manner as pre- usual operating conditions and one which will produce
vlouslg described. only qualitative results. Since the regulator is ad-
justed at the factory to provide adequate sensitivity
Static Exciter -Regulator Equipment GEK-147’72
for close regulation, this measurement is usually With the machine carrying power load and some safe
unnecessary at the time of installation, and for this value of underexcited reactive current, slowly turn the
reason no special test procedure is given, After the REACTIVE AMPERE LIMIT START dial toward 0. At
equipment has been placed in service, it is possible same setting of the dial, the limit detector meter read-
to obtain data which will provide a measure of volt- ing will go to 0 and increase in the opposite direction.
age regulation, but results must be carefully inter- Limit signal-current will increase from 0 and the reg-
preted to gain a reliable estimate of performance. ulator output will decrease. If the limit-detector
current does not reverse before the dial has been turned
If the machine is connected to a system, the regula- to zero, return the dial to the highest numbered po-
tion will depend to a great extent upon the character- sition. Decrease the AC machine excitation to further
istics of this system. Regulation will also be con- increase the underexcited current being careful not to
siderably affected by the use and adjustment of com- exceed the safe operating limit for the machine.
pensators. Furthermore, the sensitivity of the reg-
ulator itself will be a malor factor affecting voltage Again turn the REACTIVE AMPERE LIMIT START
regulation. dial towards zero until the limit detector current is
10 ma. If the signal cannot be increased from zero by
GAIN MEASUREMENTS turning the REACTIVE AMPERE LIMIT START dial to
zero, the limit polarity may be reversed. Reverse the
The automatic regulator gain should be checked only primary connections of transformer E3T (Figure 13).
when it is thought that the system is not operating Repeat the test previously described to determine if
properly. If the gain is to be checked, it will be nec- reverse limit-detector current can be obtained by
essary to use a laboratory type meter to measure turning the REACTIVE AMPERE LIMIT START dial
the change in voltage on the secondary of the PT; the towards zero. THIS TEST MUST GIVE PROPER RE-
ratio of change in voltage across points Al4 and Al3 SULTS BEFORE FURTHER TESTS ARE CONDUCTED.
(See Figure 13) to the voltage change at the P’l! sec- If the limit signal-current had en initial value that
ondary is the gain of the SCR circuit. The voltage went to zero as the REACTIVE AMPERE LIMIT START
across Al4 and A13 is the output of the SCR circuit. dial setting was reduced, the input to the limit amplifier
must be reversed. If the regulator output increased,
SYSTEM SELF-COMPENSATION the limit DC output is reversed. Reverse the con-
nections between the limit amplifier and the first stage
It is necessary to determine the degree of self-compen- amplifier of the automatic regulator. Repeat the pre-
sation of this system to be certain that the linear reac- viously described tests to obtain proper results.
tors are set at the best taps. This can be done by meas-
uring the value of current through the SCT control wind- With the REACTIVE AMPERE LIMIT START dial so set
ing at no-load and at full load, rated power factor. The that the regulator output has been reduced slightly,
degree-of-correction (DOC) is the change in control cur- turn the POWER RECALIBRATION switch from point 0
rent divided by the no-load value of control current. If toward point 9. If the AC machine is delivering power,
the control current decreases from no-load to full load regulator output should decrease as the POWER RE-
the system is under-compounded. If the current in- CALIBRATION switch is turned toward point 9.
creases, the system is over -compounded. Changing
the linear reactors to a higher reactance tap causes in- Turn the POWER RECALIBRATION switch to 0. Re-
creased compensation, i. e., it tends to over-compound adjust the regulator output to 60 volts with the RE-
the system. CHANGE TAPS ON ALL THREE RE- ACTIVE AMPERE LIMIT START dial. Before pro-
ACTORS. ceeding further with the test on the underexcited re-
active limit circuit, it is necessary to check the po-
UNDEREXCITED REACTIVE AMPERE LIMIT (If larity of the LIMIT stabilizing circuit. Carefully dis-
Furmshed) connect one of the exciter voltage stabilizing leads from
the LIMIT amplifier and short the stabilizing input
Limit Polarity terminals on the LIMIT amplifier. This should cause
the regulator output to decrease. Replacing the pri-
After satisfactory operation of the regulator has been mary lead should cause the regulator output to increase.
obtained, the reactive-ampere limit should be tested. Do not proceed with the underexcrted reactive-ampere
Reconnect the limit amplifier to the regulator, set limit tests until the polarity of the limit stabilizer is
the REACTIVE AMPERE LIMIT POWER RECALIBRA- correct.
TION switch at zero and the REACTIVE AMPERE
LIMIT START dial at its highest numbered position. Turn the REACTIVE AMPERE LIMIT START dial to
its highest reading. Readjust the regulator output to
83SR** should be disabled so that the regulator re- 60 volts with 90R4 (or 90R2). Operate the AC machine
mains in Manual. Connect the test resistor furnished at normal voltage and with underexcited reactive cur-
loose with the URAL panel to terminals Al3 and Al4 rent. Remove the test resistor and then energize
of the automatic regulator. This resistor 1s necessary 83SR** so that the regulator transfers to automatic.
in order for the regulator to supply enough current for With 90R4 (or 90R2) readjust the output for the same
the SCR’s to conduct properly. Connect a voltmeter normal voltage and underexcited current. Slowly turn
across Al3 and Al4 and adjust the automatic regulator the REACTIVE AMPERE LIMIT START dial toward
output for about 60 volts. zero. The regulator output should decrease end the
13
GEX-14772 Static Exciter -Regulator Equipment
exciter voltage should increase causing the under- should be impossible to raise the underexcited re-
excited reactive current to decrease. The dial setting active current appreciably above the previously re-
at which the uuderexcited reactive current starts to corded value no matter how far the automatic-regula-
decrease is the limit-start point. If the operation is tor voltage adjuster is turned in the direction to lower
not as described, immediately remove the regulator voltage.
from control of the AC machine excitation by dis-
abling 83SR**. Repeat the limit polarity tests. Do This completes the preliminary adjustment of the
not proceed further until satisfactory operation is LIMIT. Final adjustment can be made at any time.
obtained.
Final Adjustment of The Underexcited Reactive-Am-
With 83SR** energized, the test resistor disconnected, pere Limit
and the REACTIVE AMPERE LIMIT START dial at
the limit start point, observe the exciter voltmeter The final adjustment of the LIMIT may be made by use
and the AC machine ammeter for signs of oscillation. of Figure 10 and 11, unless special calibration data
If oscillations of the reactive current appear, remove are supplied with the equipment.
the automatic-regulator from control of the machine
excitation. Adjust the resistance in series with the The limit-start adjustment is determined from Fig-
exciter LIMIT stabilizing capacitors in 15 percent ure 10. This graph shows the value of the machine
steps, first in the direction to decrease resistance current-transformer secondary underexcited reactive
and then in the direction to increase resistance. After current which will cause the LIMIT to operate as a
each of these adjustments repeat the procedure for function of dial setting and normal AC machine po-
putting the LIMIT in service as previously described, tential-transformer secondary voltage. Values of
being very careful to observe exciter voltage oscillation voltages differing from those shown on the graph may
and reactive-current oscillations. However, if the be easily interpolated. The Power-Recalibrating
LIMIT still is unstable after the full range of re- Reactor adjustment is shown in Figure 11. This curve
sistance has been tried, the exciter stabilizer cap- shows the amount by which the limit-start point will be
acitors on the LIMIT amplifier should be added and reduced below the limit-start adjustment ae a function
disconnected one at a time, After each change the of machine current-transformer secondary active
resistance should be adjusted in the same manner as Current for various values of the tap-switch (EISW
previously described. Capacitors should be changed 9etting .
only when the machine has no voltage on it. The two following examples are given to Illustrate the
method of setting the LIMIT.
14
Static Exciter -Regulator Equipment GEK-147’72
0 ID 20 30 40 so 60 70 60
LIMIT-STMT DIK SLttlNQ
Figure 10. Calibration Curves For Reactive Ampere Limit Start Dial
Figure 10 indicates, that for an underexcited reactive In Figure 10, use the dial setting and the proper AC
current of four amperes, the REACTIVE AMPERE voltage curve to determine the value of underexcited
LIMIT START dial should be set at approximately 47. reactive current for which the LIhlIT is set. From
This satisfies the requirement at zero active amperes. this value, subtract the reactive smperes recali-
Now, the number of reactive amperes necessary to bration. The result should be essentially equal to the
start the limit at four active amperes must be reduced reactive amperes delivered to the limit if the test
by one reactive ampere to obtain the desired power has been carefully conducted.
recalibration. Therefore, in Figure 11, a value of
one reactive -ampere recalibration of the LIMIT and Set the LIMIT adjustments to the points which sre
four active amperes to the LIMIT, indicates that tap desired for final operation. If it is desired to check
switch EISW should set at tap 4. the adjustments, the following procedure may be
followed.
If desired, before making the final adjustment of the
LIMIT the calibration curves (Figure 10 and 11 may Place the automatic regulator in control of the AC
be checked in the following manner. machine excitation. Operate the machine at the
desired power load and at a reactive load which should
Place Power - Recalibrating Reactor tap switch RISW not cause LIMIT operation. Turn the automatic re-
on tap 8. Place the REACTIVE AMPERE LIMIT gulator voltage adjuster in the direction to lower volt-
START dial at its highest scale position. Put the auto- age until the LIMIT prevents further reduction in ma-
matic regulator in control of the AC machine excita- chine overexcited reactive current, or increase in
tion. With the AC machine carrying some convenient under excited reactive current. Deter mine the value of
power load at about unity power factor, move the reactive current and active current supplied by the
REACTIVE AMPERE LIMIT START dial slowly toward machine current transformer to the LIMIT.
zero. At some position of the dial, the LIMIT will
start to operate. This position ~11 be that which Knowing the AC machine voltage and the setting of
will just start to decrease the machine under-excited the REACTIVE AMPERE LIMIT START dial, deter-
reactive-current, or increase the overexcited re- mine the underexcited reactive current setting from
active current. Figure 10. Determine the underexcited reactive am-
pere recalibration from Figure 11. The result of
Determine the active and reactive amperes delivered subtracting the value of underexcited reactive am-
by the machme current transformer to the LIMIT. peres read in Figtie 11 from the value of underexcited
Draw a vertical line from the active-ampere scale reactive amperes read in Figure 10 will be essentially
point in Figure 11 to the curve for tap 8. Read the equal to the value of underexcited reactive current to
corresponding reactive amperes recalibration of the the LIMIT at the limit-start point.
LIMIT. and the setting of the REACTIVE AMPERE
LIMIT START dial.
15
GEK-14772 Static Exciter -Regulator Equipment
POWER
rp (61 ACTIVE OJRRENT (AMPERES - SECONDARY OF Cl)
SWITCH POSItlOW
NO.9
2.3 NO.6
NO.7
2 /! ! -V! I
NO.6
I
NO.3
t i i ii i i
NO.2
17
GEK-147’72 Static Exciter-Regulator Equipment
TROUBlESHOOTiNG
.
SYMPTOM POSSIBLE CAUSE POSSIBLE CURE
18
ua
-
c
(X3)
I----- -e------J
Figure 13 - Typical Elementary Diagrams of 3S7501FS141
Static Exciter Regulator Equipment
(Sheet 1 of 4)
Figure 13 - Typical Elementary Diagrams of 3S75OlFS141
Static Exciter Regulator Equipment
(Sheet 2 of 4)
I-4
N
I I ! 1
GEK- 14172 Static Exciter -Regulator Equipment
22
NOTES
ALABAZUA LoulSlMA OKLAHOMA
t Blrminghpm 35205 . . 2151 Hlghlwd Aw. + BaWn ROU@ 7OaO5. . a312 Flortda Blvd. .t OWckoms. CLN 13106. . 2000 C&se,, Blvd.
*t : Mobtle 38808. . 1111 S.Beltlhe HIghway *t t Sew Orle#.“s 70125. . 4147 Euharr BLvd. + l-ulna 74 105 P 0. Box 7646, Soutkaldr St&
.r Shreveport 71104 . 2620 Cente”u’y Btvd.
ALASKA + Mmroe 11201 . . . . . 1028 Sortk 6th St.
t OREGON
Anckwpse 99601. . . . . 115 Whttnay Rd.
E”g*rl* 91401 . . . . . . . . 1170 PewI St.
MARYLAND
* : t Portland 97216 . . . . . , . a929 NW 29th Ave.
ZIZONA *t t BUtmore Zl201 . . . . 1 N. Chu’laa St.
PkcmnlX 85012 . . 3550 N. Central Ave.
t Tucmn BS718. . . . . : : .151 S.Tuc~n Bl”d. htAS3ACliUSETTS
PENNSYLVANlA
. Ahntom 18102 . . . . . . 1444 Hamilton St.
*t t Welmlay 021s 1 . . . . 1 Wa~ktqtrm St.
*tt Phllad~lpkla 19102 . . . 3 PI”” Cmur Plus
ARKANSAS
+ *+ Ptttabvrgk 15222 , .300 Etk Avenue Bldy.
Jorti Llttla Rack 72119. . . . .lZO MaIn St.
cAL1FatNIA
F*T” Dbtroit la202 . . . . . 100 AntoLnltte
JOCkSOn 49201 . . . . . . a10 W. FrMtln
St
St. SOUTH CAROLETA
‘t t LOI Ax&es 90054 . . . . , .211 N. VLE,,., St. : S#nprW Pm307 t t Columbln 29204 . . . 2100 MLddlcbvrg Dr.
t Palo Alto 91303 . . . . . 960 EM Anwnto Rd. t Greentill. 299001. . 41 No. Plwr,r,tkurS Dr.
,.... . 1908 Second National Bnak Bl@.
t sacrnmenm 95808.. . . . . . 2407 J St.
t 98,. DleSo 92105 . . . . . . . . 2560 First AM. TENNEXiEE
. f San mnct8cO Mll9. . . . 53 mtinrne St. MDWESOTA
Duluth 55802 . . 300 W. Sup&or S,. *t cmttaMoSn31411
. Vernon 90068. . . . . . . 3055 E. 44tk St. Tf
*tt Mtrmeq.dL~ 55416 1500 Ltl?c Drtw So. +
. ..*...*. 5800 Bldg, Eugata C~nt.r
Xemphia 39130. . . . .a385 Air-y, Blvd.
COLORADD
MIsSCUR
*t Denwr 80200. . . . . . 201 Unlverslty Blvd. ?!xxAs
*t Kansas cuy e4199. . . . . . . 911 &Ml St.
*+ 'T Amullto 79101 . . . . , . . , .303 Polk St.
CONNECTICUT SL LO”,S 83101 . . . . . .lOlJ LLxUst St
*tr Be~uxmnt 71704 . . . . . 1385 Catd.r Am
-+ Marlden 06450. . . . . . . 1 Prestige Dr.
MONTANA : t t Corpus Ckrtltl76401. . 205 N. Chaparral St.
t Butte 59701 . . . . . . . 103 N.wyombg St. Dalm 75222 . . a101 stammon. Rdway
FLORIDA *t El Pam TO945 . . . . . . . 215 N.StPnton
tr Jacksontitle 32203 . . . 4WO W.,Od”,c.k Dr.
NEBRASU t Fort Word, 76102 . . . 406 w. SS”wdk St.
+t Yiami 33134 . . . . . 4100 W. FL%gler St.
-t Omaha 49102 . . . . . 409S.17tkSt. *tt Hou8tm 7’7027 . . . . 4219 Rlckmond Ave.
‘T r Tampa 33609.. . . . . 2100 9. Lo,8 Ave.
t San Antnnm 78204 . . . . 434 S. Man St
GEORGIA
Lltttkurn 07O41. . . . . . . . 25 E.Wtllow St. UTAH
*t t Atlanta 30309. . .1860 PePcktrea Rd., NW
tt Sam31405 . . . . .5092 Paulaen St. t Salt L&e City 84111 . . 431 S. Tklrd East St.
NEW YORK
HAWAII tt Albany 12205. . . 15 computer Drive. west
Buffalo 14209 . . . . d25 Delaware Ave. VIRGINIA
*+ t HoMlulu 96813 . . . . . 440 Coral Sk *tt
- t I x New York 10022 . . 641 Lemn@~n A”& - r Nervport NeurS 23501 . . . . 311 MIln St.
ILLINOIS . Rockester 14404 , . . . . . . 89 East Ave. Rtckmond 23230 1508 wulc.w Lawn Dr.
640 s. cnnal St. * * * 8yracuse 13206 . . .3532 k&mea St :* Roanoke 24015 . 2018 Colonml Ave.
* t f X CklcaSo SO880 . . .
2-72 17501
DRIVE SYSTEMS PRODUCT DEPARTMENT
GENERAL ELECTRIC COMPANY, WAYNESBORO, VIRGINIA 22980