7.7a - Electrical Cables and Connectors

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Summary of Annotations

Page 4

#1 Highlight (Shabbir)

Electrical safety practices do not replace regulations specified by manufacturers and authorities

#2 Highlight (Shabbir)

There is a risk of electrocution if the ac or dc power stays connected to aircraft electrical circuits

#3 Highlight (Shabbir)

Do not look into the end of a fiber-optic cable

#4 Highlight (Shabbir)

Laser radiation is dangerous for eyes

#5 Highlight (Shabbir)

There is a risk of laser radiation at the end of fiber optic cable, which human cannot see

#6 Highlight (Shabbir)

Before you start work: open, safety and tag the circuit

breaker(s) related to the system/equipment to prevent the

supply of electrical power to the system/equipment during the

maintenance work
#7 Highlight (Shabbir)

Some circuit breakers (A320 family only) have a red threaded

bush

#8 Highlight (Shabbir)

a red threaded bush (in A320 family) prevents reset of the circuit breaker in flight (the crew cannot pull it)

#9 Highlight (Shabbir)

The red threaded bush can be removed using a standard wrench

Page 5

#1 Highlight (Shabbir)

Never use electric tools which deliver energy of more than 0.02 mill joule in fuel tanks or in areas where there are flammable vapors

#2 Highlight (Shabbir)

Never use heat-generating tools in the fuel tanks or in areas where there are flammable vapors

#3 Highlight (Shabbir)

Use only crimp-type contacts, terminals, splices, sleeves (nonheat shrinkable sleeves) in the fuel tanks or in areas where there are flammable vapors

#4 Highlight (Shabbir)

when you use electric tools on the aircraft because

there are risks of electrocution or explosion

#5 Highlight (Shabbir)
Some electric tools such as heat guns, soldering irons and tools without intrinsic protection are not permitted in the fuel tanks or in areas
where there are flammable vapors

Page 7

#1 Highlight (Shabbir)

A concealed break in a cable core or at a connection may be found by using a continuity tester

#2 Highlight (Shabbir)

A continuity tester normally consists of a low voltage battery (2.5 volts is satisfactory) and a test lamp or an ohmmeter

#3 Highlight (Shabbir)

To prevent damage in continuity tester, the currents should be limited to 120 milliamps

#4 Highlight (Shabbir)

Before continuity testing, the main electrical supply should be switched off or disconnected

#5 Highlight (Shabbir)

Before continuity testing, all switches and circuit breakers, as appropriate, should be closed to complete the circuit

#6 Highlight (Shabbir)

When carrying out a low voltage continuity check, it is essential to work progressively through the circuit, commencing from the relevant fuse or circuit
breaker and terminating at the equipment

#7 Highlight (Shabbir)

Large circuits will probably have several parallel paths and these should be progressed systematically, breaking down as little as possible at plug and socke
or terminal block connections

#8 Highlight (Shabbir)
While testing large circuits, it is valueless to check several low resistance paths in parallel
#9 Highlight (Shabbir)

Excessive resistance in high-current carrying circuits can be caused by loose terminal connections, poorly swaged lead ends, etc

#10 Highlight (Shabbir)

Faults due to loose terminal connections, poorly swaged lead ends, etc are indicated by low terminal voltage at the connections to the service load and by
heating at a conductor joint

#11 Highlight (Shabbir)

If faults caused by loose terminal connections, poorly swaged lead ends, etc are suspected, a millivolt drop test is recommended

#12 Highlight (Shabbir)

in case of faults caused by loose terminal connections, poorly swaged lead ends, etc, it is also acceptable to check along progressive sections of the system
accurately calibrated voltmeter

#13 Highlight (Shabbir)

In millivolt drop test, for short-rated circuits, a suitable resistance or other dummy load should be used in lieu of the normal load and the current should
be scaled down to avoid overheating

#14 Highlight (Shabbir)

The voltage drop across a joint, an approximate guide is 5 mV /10 amps flowing

Page 8

#1 Highlight (Shabbir)

After installation and where specified in the Approved Maintenance Schedule or Test Schedule, aircraft circuits should be tested by means of a 250-volt ins
tester which should have its output controlled so that the testing voltage cannot

exceed 300 volts


#2 Highlight (Shabbir)

In all systems having nominal voltages over 30 volts, cables forming circuits essential to the safety of the aircraft should be tested individually

#3 Highlight (Shabbir)

Circuits having nominal voltage less than 30V may be connected in groups for test

#4 Highlight (Shabbir)

Immediately after an insulation test, functioning checks should

be made on all the services subjected to the test

#5 Highlight (Shabbir)

Prior to insulation test, the aircraft battery and any external supply should be disconnected

#6 Highlight (Shabbir)

Prior to insulation test, all switches in the circuit concerned should be ‘ON',
dimmer-switches should be set at the minimum resistance position and micro-switches operated to the ‘ON' position

#7 Highlight (Shabbir)

Prior to insulation test, in cases where the insulation resistance with the items concerned is not less than 2 megohms, the disconnection may be made by th
earth lead, leaving the item connected to the circuit

Page 9

#1 Highlight (Shabbir)

The insulation resistance values are likely to vary with changes in the temperature and humidity of the local atmosphere

#2 Highlight (Shabbir)
If the aircraft has been in damp conditions for some time before the test, low readings (insulation resistance values) can be expected
#3 Highlight (Shabbir)

after completion of insulation tests, Results of tests and the temperature and humidity conditions at the time of the test should be recorded

#4 Highlight (Shabbir)

Whenever possible,
functioning tests should be carried out using an external supply coupled to the ground supply connector

#5 Highlight (Shabbir)

Where applicable, when one or more engines are

running, the power supply can be obtained from the associated

generators, due reference being made to the functioning of any

isolating relays

#6 Highlight (Shabbir)

For certain circuits (e.g. standby lighting), functioning tests can

only be carried out using the aircraft battery system

Page 11

#1 Highlight (Shabbir)

Bonding is the electrical interconnection of metallic aircraft parts

(normally at earth potential) for the safe distribution of electrical

charges and currents


#2 Highlight (Shabbir)

Primary conductors are those required to carry lightning strikes

#3 Highlight (Shabbir)

in bonding, The cross-sectional area of Primary Conductors made from copper shall be not less than ¼ inch by 26 s.w.g.
wire

#4 Highlight (Shabbir)

where a single primary conductor used in bonding is likely to carry the whole discharge from an isolated section, the cross-sectional area shall be not
less than ½ inch by 26 s.w.g. wire

#5 Highlight (Shabbir)

Aluminium conductors shall have a crosssectional area giving an equivalent surge carrying capacity as copper primary conductor

#6 Highlight (Shabbir)

The cross-sectional area of secondary conductors made

from copper must not be less than 44 strands of 39

s.w.g. for braided conductors

#7 Highlight (Shabbir)

Where a single secondary conductor wire is used for bonding, its size must be not less than 18 s.w.g

#8 Highlight (Shabbir)

in the case of renewal or repair, if the original conductor cannot be matched exactly, a replacement manufactured of the same type of material, but of greate
crosssectional area, should be selected

#9 Highlight (Shabbir)
Braided copper or aluminium cords fitted at each end with connecting tags or lugs (usually referred to as 'bonding jumpers'), should be used for bonding
connections between moving parts or parts subjected to vibration and these are suitable both as primary and secondary conductors
#10 Highlight (Shabbir)

The tags or lugs on bonding jumpers are generally fitted by the 'Crimping method’

#11 Highlight (Shabbir)

During assembly of the connections to aluminium cords, antioxidant (crimping) compound consisting of 50% by weight of zinc oxide in white petroleum
jelly and complying with DTD 5503 should be applied to the connections

#12 Highlight (Shabbir)

Intermittent contact is worse than no contact at all

Page 12

#1 Highlight (Shabbir)

bonding jumpers should not be excessively tight or slack

#2 Highlight (Shabbir)

The run of all primary conductors should be as straight as possible; sharp bends must be avoided

#3 Highlight (Shabbir)

where an engine is not in direct electrical contact with its mounting it should be bonded with at least two primary conductors, one on each side of the engine

#4 Highlight (Shabbir)

Where applicable, bonding jumpers for control surfaces should be as flexible and as short as possible, of as low impedance as is practicable and should no
tinned.

Page 13
#1 Highlight (Shabbir)

Flexible hose connections used for joining rigid pipes should be

bonded by fitting clips around the pipes approximately 13 mm

(0.5 inch) away from the hose and bridging with a corrugated

bonding strip or jumper

#2 Highlight (Shabbir)

The soldering of broken ends of a fractured/broken bridging strip or bonding cord is prohibited

#3 Highlight (Shabbir)

Not only must the flexible hose connection be bridged, but each

pipe run should be bonded to earth at each end, particularly

within a radius of 2.42 meters (8 feet) of any unscreened radio

equipment or aerial lead, where earthling bonds should not be

more than 1.5 meters (5 feet apart), or less distance apart, if

called for by the manufacturer

#4 Highlight (Shabbir)

High-pressure flexible pipe assemblies are usually self-bonding

#5 Highlight (Shabbir)

Metallic coatings, such as cadmium and tin, are satisfactory conductors and should not be removed for bonding purposes
#6 Highlight (Shabbir)

If a poly sulphide compound is used for sealing the earth or bonding point, it must be ensured that the anti-oxidant to be subsequently applied will not have
detrimental effect on the sealing; e.g. DTD 5503 should not be used

#7 Highlight (Shabbir)

When the connection has been made after bonding, any excess compound should be wiped off, using a rag damped in methyl ethyl ketone (MEK)

#8 Highlight (Shabbir)

A corrosion washer is plated, or manufactured of a material having a potential such that when placed between materials of widely differing potentials it redu
the risk of corrosion caused by electrolytic action

Page 15

#1 Highlight (Shabbir)

When earth terminal assemblies are also used to carry electrical supplies, a mill volt drop test, must be carried out.

#2 Highlight (Shabbir)

Leads connected to earth terminal assemblies should be

of insulated cable with terminal tags fitted by the crimping

method

#3 Highlight (Shabbir)

The maximum resistance values for the various conditions of bonding are summarized in the Table (CAA Requirements)

Table on page 13 of the book?


#4 Highlight (Shabbir)

Bonding carrying the main electrical supply should be capable of carrying the full short-circuit current which can pass, without risk of fire or damage to the
bonding system

Page 16

#1 Text (Shabbir)

IMPORTANT

Page 17

#1 Highlight (Shabbir)

A meter widely used for bond testing, consists of an ohmmeter operating on the current ratio principle and a single 1.2-volt nickel-alkaline cell housed in a w
carrying case

#2 Highlight (Shabbir)

The associated cables for this common bonding tester are 60 feet and 6 feet in length and are fitted with a single-spike probe and a double-spike probe
respectively

#3 Highlight (Shabbir)

Prior to carrying out a bonding test, a check should be made on

the state of the nickel-alkaline cell of the tester by observing:-

a) That a full-scale deflection of the meter is obtained when the two spikes of the 6-foot cable probe are shorted by a suitable conductor; and

b) That the meter reads zero when the two spikes of the 6- foot probe are shorted by the single spike of the 60-foot probe
#4 Highlight (Shabbir)

The 60-foot lead of the test equipment should be connected to the main earth (also known as the bond datum point) at the terminal points, which are
usually shown diagrammatically in the relevant Aircraft Maintenance Manual.

#5 Highlight (Shabbir)

When connecting the 60-foot lead to an earthling point,

any protective treatment (e.g. strippable lacquer) should be

removed at the point of contact

#6 Highlight (Shabbir)

The 6-foot test lead should be used to check the resistance

between selected points

#7 Highlight (Shabbir)

As an alternative to the common bonding tester, the four terminal method of resistance measurement may be adopted with the appropriate

miliohmmeter

#8 Highlight (Shabbir)

With 4 terminal method type of instrument, a test current (approximately 2 amps) is supplied by the internal batteries and passed through the resistance
via cables

Page 19

#1 Highlight (Shabbir)

Where an abrasive has been used it is


important to ensure that all traces of it are removed

#2 Highlight (Shabbir)

Corrosion tends to form at a bonding or earth

connection and is often the cause of excessive

resistance

#3 Highlight (Shabbir)

Where the required bond value cannot be obtained at a

structural joint the advice of the manufacturer should be

sought

#4 Highlight (Shabbir)

The ohmmeter (used as bonding tester)is normally sealed in its case and no attempt should be made to open it; if a fault should develop, then the complete
instrument should be withdrawn from use and overhauled

#5 Highlight (Shabbir)

Normally three standard test resistors are supplied for testing purposes regarding the accuracy of the tester and the readings obtained should be
within 10% of the standard ohmic values

Page 21

#1 Highlight (Shabbir)

Crimping ensures electrical and mechanical connection of the

wire to an item of equipment or to a connecting system by


means of the end fitting

#2 Highlight (Shabbir)

A properly crimped terminal provides a joint between the wire and the terminal as strong as the wire itself

#3 Highlight (Shabbir)

The preferred crimping tool is a ratchet-type crimper that is periodically calibrated to ensure a consistent and proper crimp

#4 Highlight (Shabbir)

Crimping tools come in different sizes indicated by the color coding on the handle

#5 Highlight (Shabbir)

Hydraulic crimping tools are often used on wire gauge sizes 0

through 0000 because of the force required to properly crimp

the wire.

Page 23

#1 Highlight (Shabbir)

Each crimping tool shall be submitted for gauging at(after) 1000 and 2000 crimps and only if successful, returned for use

#2 Highlight (Shabbir)

The checking of crimping tool at (after) 3000 crimps shall be by gauging and specimen checks

#3 Highlight (Shabbir)

All crimping tools not in regular use shall be similarly checked every 12 months to the gauging requirements
#4 Highlight (Shabbir)

Each crimping tool or die shall be tested by the insertion of GO/NO GO gauge.

Page 25

#1 Highlight (Shabbir)

After crimping, make sure crimping indents away from inspection hole

Page 26

#1 Highlight (Shabbir)

The distance between the crimping barrel and the wire insulation must be less then 1mm

#2 Highlight (Shabbir)

On completion of the crimping operation, the wire insulation must not be pushed back out of end fitting and sealing system

#3 Highlight (Shabbir)

In specific cases where, by construction, the distance between rear face of the hard insulation is less then 3mm, this value is brought to 0.3mm max.

#4 Highlight (Shabbir)

The maximum distance tolerated for the extension of the wire core out of the crimping barrel, connection side is 1.5mm

#5 Highlight (Shabbir)

It is recommended that each crimp has a gentle manual pull applied in order to establish there is no movement of conductor within the crimp

Page 27
#1 Highlight (Shabbir)

The rear-release method provides better front-end support for the contact; therefore, the contact is less likely to bend during reassembly of the connector

Page 29

#1 Highlight (Shabbir)

Antennas are connected to most of the radio receivers and transmitters with a special type of shielded wire called “Coaxial Cable”

#2 Highlight (Shabbir)

Coaxial cables contain two or more separate conductors

#3 Highlight (Shabbir)

The insulation between inner and outer conductor in a coaxial cable is usually teflon or polyethylene.

#4 Highlight (Shabbir)

The inner most conductor in a coaxial cable may be solid or stranded copper wire, and may be plain, tinned, silver plated or even gold plated

#5 Highlight (Shabbir)

The remaining/outer conductors are in the form of tubes,


usually of fine braid

#6 Highlight (Shabbir)

Outer coverings or jackets in a coaxial cable serve to weatherproof the cables and protect them from fluids, and mechanical and electrical damage.

#7 Highlight (Shabbir)

Coaxial cables are shielded against electrostatic and magnetic fields


#8 Highlight (Shabbir)

Since coaxial cables do not radiate, then likewise they will not pick up any energy or be influenced by magnetic fields

#9 Highlight (Shabbir)

Coaxial cables have specific values of; impedance, capacitance per unit length and attenuation per unit length

#10 Highlight (Shabbir)

while stripping a coaxial cable, The outer jacket must be cut off flat all round and at right angles to the longitudinal direction of the cable

Page 31

#1 Highlight (Shabbir)

If the impedance of the line does not match the load impedance, not all the energy fed down the line flows into the load

#2 Highlight (Shabbir)

To measure the VSWR (Voltage Standing-Wave Ratio),


“Time Domain Meter” (TDM) is used

#3 Highlight (Shabbir)

In a Coaxial cable, if the line importance does not match load impedance, some of the energy is reflected back to the source, forming standing waves on
the line

#4 Highlight (Shabbir)

The ratio of the voltage

across the line at the High V points to that at the Low V points is

known as the “Voltage Standing-Wave Ratio” (VSWR)


#5 Highlight (Shabbir)

Measuring the VSWR on the line will

identify the position of the damage in the Coaxial cable

Page 32

#1 Highlight (Shabbir)

Most aircraft manufacturers have adopted a method of coding wires and cables which conform to the ATA 100 specification. This method is often
referred to as ‘series coding'

#2 Highlight (Shabbir)

Construction of the series code:

example: 3135-21B20N

digit 1-4 : wire number prefix


digit 5-6: wire number (the wire number can be upto 5 digits. explained later)
digit 7: segment letter
digit 8-9: wire gauge
digit 10: ground, phase or thermocouple suffix letter

#3 Highlight (Shabbir)

Wire number prefix has the special job of determining in which system on the aircraft the wire or cable is located

#4 Highlight (Shabbir)

A dash separates the ATA number prefix/wire number prefix from the wire number

#5 Highlight (Shabbir)
A wire number consisting of a maximum of 5 digits is used to differentiate between wires, cables or co-axial cables in a particular sub system
#6 Highlight (Shabbir)

If there was a switch or relaycontact between the two wires then the wire number would change because in this case, there would not be a permanent
connection between them

#7 Highlight (Shabbir)

A different wire number is used for each

conductor not sharing a common connection

Page 33

#1 Highlight (Shabbir)

Parallel or identical systems are identified with a 5 digit wire number

#2 Highlight (Shabbir)

The first digit in a wire number indicates the specific parallel or identical system unit identification number such as Number 1 is AC generation System

#3 Highlight (Shabbir)

A different letter is used for each segment sharing a common terminal or connection and having the same 4 digit ATA number

#4 Highlight (Shabbir)

since the wire number didn't change where two wires were permanently connected, such as in a terminal block or a splice, we discriminate between
these two wires using a letter called wire segment letter

#5 Highlight (Shabbir)

practicable wire segments are lettered in alphabetical sequence and the letter A identifies the first segment starting at the signal and/or power source

#6 Highlight (Shabbir)
The letters I and 0 are not used as wire segment letters
#7 Highlight (Shabbir)

Double letters AA, AB, AC, BA,


BB, BC, etc., are used when more than 24 segments are required

#8 Highlight (Shabbir)

Segments joined by a permanent splice have different segment letters assigned to them

Page 34

#1 Highlight (Shabbir)

The wire or cable size number is used to identify the American wire gauge (AWG) size of the wire or cable

#2 Highlight (Shabbir)

For

thermocouple wires a dash is used instead of the wire size

number

#3 Highlight (Shabbir)

The wire size

number is not normally included for co-axial cables

#4 Highlight (Shabbir)

The letter N (ground or earth) is used as a suffix to the wire

identification code to identify a segment of a wire or cable that is

a part of the ground network


#5 Highlight (Shabbir)

The phase letter 'V' is used as a suffix to the

identification code to identify all segments of the high voltage

side of a single phase power circuit

#6 Highlight (Shabbir)

The phase letters 'A', 'B' and 'c' are

used as suffixes to the wire or cable identification code on all

wire segments carrying three phase a.c. power

Page 35

#1 Highlight (Shabbir)

The quantity of wires and cables required for a distribution

system depends on the size and complexity of the systems.

#2 Highlight (Shabbir)

Wiring protection methods may be grouped under three principal headings:

 Open loom

 Ducted loom

 Conduit
#3 Highlight (Shabbir)

In cable loom method, wires or cables to be routed to and from

consumer equipment in the specific zones of the aircraft are

grouped parallel to each other in a bundle and bound together

with waxed cording or p.v.c. strapping

Page 36

#1 Highlight (Shabbir)

Magnetic Field cancellation is achieved by routing the positive and earth return cables together and connecting the earth-return cable at an earthing point
located at a specific safe distance from the magnetic detector element of a compass system

#2 Highlight (Shabbir)

When wires or wire bundles are routed through the aircraft

without the mechanical protection of conduit, it is called open

wiring

#3 Highlight (Shabbir)

Most aircraft use the open wiring system

#4 Highlight (Shabbir)

Open wiring is more vulnerable to wear, abrasion, and damage

from liquids than wiring installed in conduits


#5 Highlight (Shabbir)

Shielded cable, ignition cable, and wire that is not

protected by a circuit breaker or fuse should be routed

separately

#6 Highlight (Shabbir)

The bending radius of a wire bundle should not be

less than 10 times the outer diameter of the bundle

Page 37

#1 Highlight (Shabbir)

Ducted loom method is basically the same as that of the open loom except that the bundles are supported in ducts, which are routed through the aircraft an
secured to the aircraft structure

#2 Highlight (Shabbir)

In Ducted loom method, for identification purposes, each loom is bound with appropriately colored waxed cording.

#3 Highlight (Shabbir)

Ducts used in Ducted loom method may be of aluminium alloy resin impregnated asbestos or molded fiber-glass-reinforced plastic

Page 38

#1 Highlight (Shabbir)

Electrical conduit consists of thin-walled aluminium tubing,


braided metal tubing called flexible conduit, and non-metallic tubing
#2 Highlight (Shabbir)

The purpose of conduit is to provide mechanical protection, and metal conduit is often used as a means of shielding electric wiring to prevent radio interfere

#3 Highlight (Shabbir)

Approved flexible conduit is covered by specification MIL-C-6136 for aluminium and specification MIL-C-7931 for brass

#4 Highlight (Shabbir)

The aluminium conduit is made in two types. Type I is bare, and type II is rubber-covered

#5 Highlight (Shabbir)

The size of conduit should be such that the inside diameter is about 25 percent larger than the largest diameter of the cable bundle

#6 Highlight (Shabbir)

To obtain the correct inside diameter of a conduit,


subtract twice the wall thickness from the outside diameter

#7 Highlight (Shabbir)

Typically, conduits are specified according to their outside diameter.

#8 Highlight (Shabbir)

If a fitting is not installed on the end of a conduit section, the end should be flared to prevent the edge of the tubing from rubbing and wearing the insulation
cable

#9 Highlight (Shabbir)

A clean metal-to-metal contact will assure good bonding to aid in shielding

#10 Highlight (Shabbir)

Drain holes must be provided at the lowest point in any conduit run
#11 Highlight (Shabbir)

Bends in the conduit must not be wrinkled and must not be flattened to the extent that the minor diameter is less than 75 percent of the nominal tubing diam

#12 Highlight (Shabbir)

Flexible conduit cannot be bent as sharply as rigid conduit

#13 Highlight (Shabbir)

Before a wire or cable bundle is placed in a conduit, the bundles should be liberally sprinkled with tale

Page 40

#1 Highlight (Shabbir)

Approved lacing cord complying with specification MIL-C-5649 or twine specification JAN-T-713 may be used for wire lacing

#2 Highlight (Shabbir)

If wire bundles will not be exposed to temperatures greater than 248°F [120°C], cable tie straps complying with specificationMS-17821 or MS-17822 can
be used

#3 Highlight (Shabbir)

Single-cord lacing is used for cable bundles 1 in. [2.5 cm] in diameter or less

#4 Highlight (Shabbir)

In open areas, the bundles should be laced or tied if supports for the cable are more than 12 in. [30.5 cm] apart

#5 Highlight (Shabbir)

When it is desired to use single ties to secure a wire bundle, the locked clove hitch is used
#6 Highlight (Shabbir)

When the continuous lacing is applied, the first loop is a clove hitch locked with a double overhand knot

#7 Highlight (Shabbir)

These loops are continued at suitable intervals, and the series is then terminated with another clove hitch

#8 Highlight (Shabbir)

The terminating ends of the cord are trimmed to provide a minimum length of 3/8 in [0.95 cm]

#9 Highlight (Shabbir)

When double-cord lacing is required for large cable bundles, the

first loop is made with a special type of slipknot similar to the

bowline-on-a-bight

Page 42

#1 Highlight (Shabbir)

Specification MS-21919 cable clamp meets the requirement for civil aircraft use.

#2 Highlight (Shabbir)

The cables are a tight fit in the holes of the bung

#3 Highlight (Shabbir)

The anti-friction washer prevents damage to the face of the bung when the clamping nut is turned

#4 Highlight (Shabbir)
On assembly, holes not occupied by cables are plunged with plastic plugs
Page 44

#1 Highlight (Shabbir)

Where wire bundles pass through bulkheads or other structural members, a grommet or suitable clamping device should be provided to prevent abrasion

#2 Highlight (Shabbir)

lf a wire bundle is held by a clamp in the center of a hole through a bulkhead, and the clearance between the edge of the hole and the bundle is more than
64 cm), a grommet is not required

#3 Highlight (Shabbir)

At points in an installation where electric wire may be exposed to oil, hydraulic fluid, battery acid, or some other liquid, the cable should be enclosed in a
plastic sleeve

#4 Highlight (Shabbir)

At the lowest point in the sleeve, a hole 1/8 in. [0.32 cm] in diameter should be cut to provide for drainage

#5 Highlight (Shabbir)

When separation between electrical wire and fluid lines is impractical, the electric wire should be placed above the flammable-fluid line and securely
clamped to the structure

#6 Highlight (Shabbir)

Electric wiring is insulated and protected with various types of materials, some of which can withstand temperatures as high as 392°F [200°C)

#7 Highlight (Shabbir)

In areas where a wire must be subjected to high temperatures, it is necessary to use wiring with insulation made of asbestos or some other heat-resistant m

Page 46
#1 Highlight (Shabbir)

When it is impossible to prevent cable loom contact with the

aircraft structure, then wrapping is the recommended method of

protection

Page 47

#1 Highlight (Shabbir)

When a loom has to pass through a bulkhead, cable clamps and grommets are used to keep the cables clear of the bulkhead structure

#2 Highlight (Shabbir)

The slack or droop of a loom between loom supports should be not more than 1/2 inch when moderate hand pressure is applied at the mid point between
clamps

Page 48

#1 Highlight (Shabbir)

The selection of a cable as an alternative is most readily achieved by obtaining a Declaration of Design and Performance (DPP) from the manufacturer if
that manufacturer is suitably CAA Approved

You might also like