The SPM33 is an economical multifunction power meter that can measure voltages up to 650kV. It records active energy from grid and generator supply separately and can analyze 31st harmonics and total harmonic distortion. The meter has RS485 communication and optional relay outputs. It has basic metering functions like voltage, current, power, and energy measurement as well as maximum demand recording.

Uploaded by

Vu Son
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
926 views2 pages

SPM33 Data Sheet V2

The SPM33 is an economical multifunction power meter that can measure voltages up to 650kV. It records active energy from grid and generator supply separately and can analyze 31st harmonics and total harmonic distortion. The meter has RS485 communication and optional relay outputs. It has basic metering functions like voltage, current, power, and energy measurement as well as maximum demand recording.

Uploaded by

Vu Son
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SPM33 Multifunction Power Meter

Feature
Economical multifunction power meter

Suit for voltage distribution system up to 650kV

Dual Source kWh phasetrac record seperately grid &


generator supply

31st Harmonic analysis, THD

One RS485, support MODBUS-RTU protocol

Phase sequence adjustment

2 status input (standard) Generator

Alarm setpoint (optional)


Grid

Basic Function
SPM33 measure and display real-time parameters:

Voltage—Ua, Ub, Uc, Uab, Ubc, Uca, Frequency--F

Voltage unbalance rate – UL-L unbal, UL-N unbal Active energy—kWh

Reactive energy– kvarh


Current—Ia, Ib, Ic, In
Apparent energy - kVAh
Current unbalance rate –I unbal
Dual source kWh record seperately grid & generator supply
Active power – Pa, Pb, Pc, ∑P (Import & export kWh)

Reactive power –Qa, Qb, Qc, ∑Q Demand and Max. record for I, P, Q, S

Apparent power—Sa, Sb,Sc, ∑S 31st harmonic, THD

Power factor—PFa, PFb, PFc, ∑PF 2 DI, One RS485,

Optional Function
2 Relay output

Technical Specification
Connection Mode 3 phase 3 wires, 3 phase 4 wires Power Supply AC 85~265V or DC 100~300V

Metering True RMS, 1 sec refresh time Power loss <5VA

Input Rated current: 5A or 1A Communication RS485 serial, support Modbus-RTU


Rated voltage: 220/380V, 35Hz~65Hz Baudrate: 4800, 9600, 19200bps
Address: 1~247
Current:
120% of rated, continuously Dimension Panel: 96 x 96 x 18 mm
Instantaneous current: 10 times/ (L x W x H) Cut-out: 89.5 x 89.5 x 69.8 mm (+0.5mm)
Overload
Low voltage system: IP index IP54 (front panel) and IP20 (case)
Up to 400V(L-N) / 650V (L-L)
Weight Approx. 500gr.
High voltage system:
Up to 650kV Normal operating temperature: -10℃ +55℃~

Operating temperature: -25℃ +55℃
Status input
voltage
2 channel active status input,less than 60V
is open,more than 140V is closed,the
Environment ~
Storage temperature: -40℃ +70℃
maximum input is 300V Humidity: 5%~95% non-condensing

Relay output 2 channels, Electrostatic discharge immunity test


(optional) IEC 61000-4-2,Level 4
Node capacity: 250Vac/5A
Radiated immunity test
Power frequency withstand voltage AC 2KV/minute IEC 61000-4-3,Level 4
Standard (EMC) Electrical fast transient/burst immunity test
Insulation resistance ≥ 100MΩ IEC 61000-4-4,Level 4
Impulse withstand voltage 5kV (peak), 1.2/50uS

Surge immunity test (1, 2/50µs 8/20µs)
IEC 61000-4-5,Level 4
Parameter Accuracy Measuring Range


Line - line 0 ~ 650V

Line - Neutral 0 ~ 400V
Voltage 0.5%
PT primary side: up to 650KV
PT secondary side: 100 - 400V (L-N) (Settable)


Each phase 0 ~ 65,000A
Current 0.5%

Zero sequence 0 ~ 65,000A

Power factor 0.5% -1~1

Active power 0.5% 0~ 99,999,999.9 W

Reactive power 1.0% 0~ 99,999,999.9W

Active energy 1.0% 0~ 99,999,999.9 kWh

Reactive energy 2.0% 0~ 99,999,999.9 kVarh

Three-phase voltage unbalance class B 0%~100%

Three-phase current unbalance class B 0%~100%

THD class B 0%~100%

Dimension & Installation


Unit: mm

Order Information
SPM33--①---②

R Two relay alarm output

V1 ×
3 230/398V, 5A (support Hight voltage system up to 650KV, PT secondary settable )
V2 ×
3 230/ 398V,1A

Example: Model No. SPM33-R-V1 indicates the device provide basic function, two relay alarm output, rated input 220/ 380V, 5A

E-Power Technology Ltd. Representative:


Add: 32-7488 Salisbury Ave. Burnaby, BC, Canada VITECT Electric Automation Solution Co.,Ltd.
Tel: 1-604-3396315 Add: No 8/3/1, Bui Huy Bich, Hoang Liet, Hoang Mai,
Email: [email protected] Ha Noi.
http://www.e-powertech.ca Tel: +84.978.158.141 / +84.902.105.226
Email: [email protected]
http://www.vitect.com.vn