Inversor
Inversor
Inversor
table of Contents
7.6.1 Command code: 03H Read N Words ( Word ) (Maximum continuous reading 16 Words) ... 65
A Notes
This manual has three signs definition, the following well-known icons and their meaning, and carefully read the manual, be sure to follow the standard operation
Note Ming.
Indicates a potentially dangerous, if not followed, can cause serious or fatal injury to personnel.
It represents the absolute prohibition of conduct which, if not followed, could result in product failure or even damaged beyond use.
Indicates a potentially dangerous, if not avoided, could result in moderate injury to personnel, or cause the product to malfunction, or even serious damage!
1.2 Precautions
. Installation environment without rain, water droplets, vapor, dust and oily dirt; without corrosive or flammable gases or liquids;
. Inverter is installed in the control cabinet, should ensure that the control cabinet, and smooth ventilation.
. Grounding should be reliable, motor and inverter grounding respectively, must not be connected in series to ground. .
Control loop wiring shall be separate from power loop wiring to avoid possible interference. . Signal wire should not be
. Within 5 minutes off, do not touch the internal elements. After fully discharged, just safe. . In accordance with Table 2-1 on
3
The first chapter Notes
. AC power is prohibited to output terminals U , V , W On, otherwise it will cause damage to the inverter. . Inverter running Do not load the
output terminals of the switch. . Do not touch the high-voltage terminal of the inverter to prevent electric shock. . No live work.
. Drive before powering Put on all protective cover to prevent electric shock. . Only
. Cooling fan should be cleaned periodically, and checks whether it is normal; periodically accumulated in the dust cleaner. .
Inverter input and output wiring should be checked regularly. . Check the Terminal screws are tightened. Check the wire is
aging.
4
Chapter 2 Product Introduction
On the right side of the inverter, the inverter type and affixed represents major rating nameplate, nameplate Figure 2-1 Below:
Map 2-1
5
Chapter 2 Product Introduction
ACV - I S 30075 GC
Code control
A enlightenment Abbreviations
C Vector control
Inverter Products
V V / F control
Simplex S G Universal
Three-phase T P Dedicated
Map 2-2
table 2-1
Rated output
Inverter model Input voltage rated output power Applicable Motor
rate( kW ) flow( A )
Three-phase 380V
ACV-IT30075GC 7.5 17 7.5
± 15%
ACV-IT30110GC 11.0 25 11.0
6
Chapter 2 Product Introduction
2.4 specifications
table 2-2
project specification
Start-stop control Stops the control keyboard, external terminal control, PC control
Analog given, keyboard keys given rise and fall, a given multi-speed, traverse operation, to the host computer
Frequency given
set
protection Standard Protection Overcurrent, overvoltage, overload, undervoltage, overheat, stall, the input and output phase protection
7
Chapter 2 Product Introduction
display
led display Display operating frequency, voltage, current, speed, fault codes, parameters, function code
communication
RS-485 Standard built
interface
Installation Site Room, no corrosive gas, combustible gas, dust, direct sunlight
use
Ambient temperature --10 ℃ ~ + 50 ℃
surroundings
8
Chapter III Installation Wiring
GI200 The drive should be mounted a distance adequate ventilation, as shown in 3-1 with 3-2 Below:
9
Chapter III Installation Wiring
When mounting two frequency up and down, to add the intermediate guide plate.
RST P B UVW
Three-phase AC
X1 X2 M
power input
X3 X4
X5 X6 Ground
Multifunctional RC
COM
external
RA
control
RB
terminal
output
COM
Y1
Multi-Output relay
24V Y2
power supply Y3
24V
10V
AM1 I Current output
10K
analog input
VIN
FM1 V Voltage Output
Map 3-3
10
Chapter III Installation Wiring
RST P N UVW
Three-phase AC
X1 X2 M
power input
X3 X4
X5 X6 Ground
Multifunctional RC
COM
external
RA
control
RB
terminal
output
COM
Y1
Multi-Output relay
24V Y2
power supply Y3
24V
10V
AM1 I Current output
10K
analog input
VIN
FM1 V Voltage Output
GND Jumper terminal
Map 3-4
PBRSTUVW
RST + BUVW
11
Chapter III Installation Wiring
RST + - BUVW
RST + - EUVW
Brake unit
Copper shorting
- + P1 R S T E VWU
Brake DC
unit reactor
~ 380V Electric motor
Copper shorting
- + P1 R S T VWU E
Brake DC
unit reactor
~ 380V Electric motor
table 3-1
12
Chapter III Installation Wiring
Map 3-5
table 3-2
When the current selection ( 0 ~ 20ma )Time, 20ma The corresponding voltage 5V .
simulation
enter
GND Analog Power Ground Common to the analog inputs and outputs.
10V Analog power supply Provided inside the drive 10V Power signal
X1
X2
Programmable multi
X5
X6
13
Chapter III Installation Wiring
Y2 by F6.00-F6.02 To set
Y3
RA
Fault RB with RC closure, RB with RA OFF, as shown in
RB Fault relay
3-3 Shown
RC
Relay and Y1 , Y2 , Y3
24V Provided inside the drive 24V Power signal
Power
12V 12V power supply Provided inside the drive 12V Power signal
14
Chapter 4 Operation operation
Map 4-1
Jog / fast Pressing hold, jog operation, inching back to pre-release status
In the function code edit mode, pressing the set key, enter parameter editing state, then set the button to save the
set up
Adjusted parameters return function code editing status
Menu / Back Press the Menu key to access the function code edit mode, press the Menu button again to return to the last state
When editing parameters and function code, for incrementing the selected data bit, in the course of operation, the
Increment ↑
State display frequency, the frequency is incremented
15
Chapter 4 Operation operation
When editing parameters and function codes, for decrementing the selected data bit, in the course of operation, the
Decreasing ↓
The display state frequency for decreasing the frequency
When editing parameters and function code, for selecting the data bits, you can view the operating state of the switching cycle
Displacement
And stopped in the state
table 4-1
Map 4-2
Specific operation process: pressing the enter function code edit mode, and then by pressing , Select the partition and area code
(Selected bit flashes), then press enter into parameter editing status, and displays the current value of the parameter, and then through,
, Modify the parameters (the selected blink bit, if the parameter is not flashing, indicates that the function code can not be modified), the modification is completed,
Press, save the modified parameters to the frequency converter automatically returns to the edit mode function code, if a plurality of parameters need to be modified, heavy
The above operation can be multiplexed, if you want to return to the current state, the parameter edit state, press to return.
5 LED display, can display various setting frequency, the output frequency monitoring data and alarm codes
16
Chapter 4 Operation operation
Forward / Reverse Reversing lights, forward rotation off, when the reverse light
Retention Retention
Hz Frequency Unit
A Current unit
V Voltage unit
On during the inverter power system is first initialized, led shown as"- acv- . "Etc. After the initialization is complete, the inverter is in the standby
state.
In stop state or running, it can display a variety of status parameters. By function code F7.06 ( Operating parameters), F7.07 ( Stop parameters) in binary
Bit choose whether to display the parameters, defined F7.06 with F7.07 Description function code.
During shutdown, a total of nine stop status parameters can choose whether to display, respectively: set frequency, bus voltage, an input terminal shape
State, the state of the output terminal, PID Given value, PID Feedback value, the analog input VIN Value, the analog input SIN Value, the current number of multi-speed segment, is
No displayed by the function code F7.07 Bit (binary conversion) selection key to switch the display order of the selected parameters.
In the operating state, a total of fifteen state parameter can choose whether to display, respectively: running frequency, set frequency, bus voltage, output
Voltage, output current, operating speed, output power, the output torque, PID Given value, PID Feedback value, an input terminal, the output terminal
Sub-state, the analog VIN Value, Analog SIN Value, the current number of multi-speed segment is displayed by the function code F7.06 Bit (binary conversion)
For details, please refer to the function code F0.12 The detailed description.
GI200 Series offers a variety of fault information, please refer to GI200 Series inverter faults and their countermeasures.
17
chapter Five Parameter Function
Table 5-1
Function Code Function Description Setting range and description Unit Default modify No.
F0.01 Start-stop signal selection 0: Keyboard start-stop 1: Terminal start-stop 2: Since no communication control stop 0 × 1
0: Keyboard settings
operation
F0.06 0.00Hz
The lower limit of the operating frequency ~ F0.05 hertz 0.00 √ 6
F0.10 Select the running direction 0: Forward run 1: Reverse run 2: Reverse operation is prohibited without 0 × 10
F0.13 Are Restore Defaults 0: No action 1: Restore Defaults 2: Clear fault records None 0 × 13
F0.14 AVR Feature Selection 0 :invalid 1 : Full effective 2 : Not only ineffective during deceleration 1 √ 14
18
chapter Five Parameter Function
0: Direct start
F1.06 Parking brake start frequency 0.00 ~ F0.04 hertz 0.00Hz √ twenty one
F1.07 Braking waiting time 0.0 ~ 50.0s second 0.0s √ twenty two
F1.11 The electrical terminal operation selection 0: Terminal run command invalid when power on no 0 √ 26
1: When the electrical terminals run command
F1.12 Retention 27
F2.08 Motor stator, rotor inductance 0.1 ~ 6553.5mH Millihenry Model set √ 36
F2.09 0.1 ~
The motor stator and rotor mutual inductance 6553.5mH Millihenry Model set √ 37
19
chapter Five Parameter Function
F3.07 The torque limit setting 0.0 to 200.0% ( Inverter rated current) % 150% √ 46
F3.08 Retention 47
F3.09 Retention 48
F4.02 As of torque boost 0.0 to 50.0% (Relative to motor rated frequency) % 20.0% × 51
F4.05 Retention 54
0: No function
4: Forward Jog
7: Fault reset
20
chapter Five Parameter Function
22 to 25: Retention
5: Frequency arrival
F6.04 FM1 (AM1) Select Output 4: The output voltage 5: Output Power 6: Output torque no 0 √ 78
twenty one
chapter Five Parameter Function
9-10: Retention
F6.09 Retention 83
F6.10 Retention 84
F6.11 85
Retention
F6.12 Retention 86
F6.13 Retention 87
F7.01 Retention 89
F7.02 Retention 90
0: Jog
1: Local and external keypad display simultaneously, only the outer primer button
effective
F7.05 Keyboard Display selection no 0 √ 93
2: Local and external keypad display simultaneously, only the unit key
effective
3: The machine, external keypad keys are displayed simultaneously and efficiently
0 ~ 0x7FFF
twenty two
chapter Five Parameter Function
BIT15: Retention
0 ~ 0x1FF
0: Trouble-free
twenty three
chapter Five Parameter Function
F8.03 Jog run acceleration time 0.1 ~ 3600.0s second 10.0s √ 111
F8.04 Jog operation deceleration time 0.1 ~ 3600.0s second 10.0s √ 112
F8.07 Swing frequency amplitude 0.0 to 100.0% (Set frequency) % 0.0% √ 115
F8.08 Kick frequency amplitude 0.0 to 50.0% (Relative wobble amplitude) % 0.0% √ 116
twenty four
chapter Five Parameter Function
F8.13 FDT Level detection value 0.00 ~ F0.04 hertz 50.00Hz √ 121
F8.14 FDT Lag detection value 0.0 to 100.0% ( FDT Level) % 5.0% √ 122
F8.15 Amplitude detection frequency reaches 0.0 to 100.0% (Maximum frequency) % 0.0% √ 123
F8.16 Brake voltage value 115.0 ~ 140.0% (Standard bus voltage) % 130.0% √ 124
0.1 to 999.9%
F8.17 Speed display factor 100.0% √ 125
Speed = 120 * Operating frequency * F8.17 / The number of motor poles %
0: Keyboard given
F9.00 PID Reference source selection 2: Analog channels SIN given no 0 √ 126
4: Multi-given
% ×
F9.01 Keyboard Preferences PID given 0.0% to 100.0% 0.0% 127
F9.03 PID Output characteristic selection 0: PID Output is positive characteristic no 0 √ 129
1: PID Output is negative characteristic
F9.10 Feedback disconnection detection time 0.0 ~ 3600.0s second 1.0s √ 136
25
chapter Five Parameter Function
Fb.00 Motor overload protection selection 0: Does not protect 1: Common motor (with low speed compensation) no 2 × 145
2: Inverter motor (without low speed compensation)
Fb.01 Motor overload protection current 20.0% - 120.0% (Motor rated current) % 100.0% √ 146
Fb.02 Instant power off frequency point 70.0 to 110.0% (Standard bus voltage) % 80.0% √ 147
Fb.03 Frequency instant power-off rate 0.00Hz ~ F0.04 hertz 0.00Hz √ 148
Fb.07 Frequency decrease rate when current limiting 0.00 ~ 50.00Hz / s Hz / sec 10.00Hz / s √ 152
0: 1200BPS 1:
2400BPS 2:
4800BPS 3:
FC.01 Communication baud rate settings no 3 √ 154
9600BPS 4:
19200BPS 5:
38400BPS
ASCII
26
chapter Five Parameter Function
FC.04 Communication timeout fault time 0.0 (invalid), 0.1 ~ 100.0s second 0.0s √ 157
FC.06 Transmission response processing 0: Write operation has to respond 1: Write no response no 0 √ 159
A low frequency
Fd.00 0 to 500 no 5 √ 160
oscillation suppression threshold point
Suppress oscillation
Fd.01 0 to 500 no 100 √ 161
frequency threshold point
Fd.04 Oscillation suppression 0: Effectively suppress oscillation 1: Suppress oscillation invalid no 1 √ 164
Torque limit)
Torque limit)
Fd.06 Torque setting mode selection no 0 √ 166
3: Analog VIN + SIN Set torque ( 100% With respect
Torque limit)
27
chapter Five Parameter Function
maximum frequency)
2: selected
Setting an upper limit frequency source is Analog SIN
fromSet an upper limit frequency ( 100% Corresponding to the
maximum frequency)
Fd.09 Current limiting action selection 0: Current limit remains in effect 1: Invalid constant speed limiting no 0 √ 169
0: no PG Vector control
It refers to the open-loop vector. It means not applicable to encoder PG High performance general purpose applications, such as machine tools, centrifuges, drawing machine, and injection m
Tip: When vector control mode, the motor parameters have been self-learning. Only accurate motor parameters in order to play vector
Control of the amount of advantage. Obtain better performance by adjusting the speed of the controller parameters.
1: V / F control
Suitable for the control where less precision, such as fans and pumps. It can be used for one inverter drives multiple motors.
2: Torque Control
Suitable for high precision torque control applications, such as wire, drawing and so on. In the torque control mode, the motor speed by the motor
Load decided that its acceleration and deceleration time is no longer by the inverter deceleration time decision.
F0.01 Start-stop signal selection 0: Keyboard start-stop 1: Terminal start-stop 2: Since no communication control stop 0 ×
Inverter control commands include: start, stop, forward, reverse, jog, fault reset.
28
chapter Five Parameter Function
The keyboard panel Perform running command control button. In the operating state, if pressed with
Multifunctional input terminal forward, reverse, forward jog, reverse jog operation command control like.
2: Communication Channel
Run command controlled by the host computer via the communication mode.
Keyboard and the terminal is 1: Effective, and the drive not save
F0.02 no 0 √
set up down 2: invalid
And the keyboard via the inverter and a terminal UP / DOWN (Frequency setting increment / decrement frequency setting) function is provided
Predetermined frequency, the highest authority, may be combined with any other frequency setting. Mainly to complete the fine-tuning in the commissioning process control system
0: Valid, and the inverter power-down store. Frequency command can be set, and after the drive is switched off, the setting frequency value is stored, the next
1: Valid, and the inverter not save. Frequency command can be set only in Upon power failure, the frequency setting value is not stored.
2: invalid, the terminal keyboard and increment / decrement of the frequency value of the function setting is automatically cleared, and the keyboard and the terminal increment / decrement is invalid
3: setting up and running, and the terminal UP / DOWN Function is set, and the terminal shutdown and keyboard
Note: When the user of inverter operation to restore the default value, and the terminal keyboard increment / decrement function setting frequency value is automatically cleared.
0: Keyboard settings
operation
Selecting a frequency transformer input channels. There are 7 main reference frequency channels:
0: Keyboard settings
By modifying the function code F0.07 Value "Keyboard set frequency", the purpose of the keyboard of the set frequency.
It refers to the analog input terminal of the frequency set. GI200 Series inverter provides two analog input terminals, wherein VIN for
0 ~ 10V Voltage input, SIN Can 0 ~ 10V Input voltage, may also be 0 (4) ~ 20mA Current input current, input voltage by jumper J8A
29
chapter Five Parameter Function
To switch.
Analog input settings 100.0% Corresponding to the maximum frequency (Function Code F0.04 ), - 100.0% Corresponding to the maximum reverse frequency.
Select this frequency setting mode, the inverter operating in multi-speed mode. You need to set F5 Group and FA Group "multi-speed control group" parameter
Determining the corresponding relationship between a given frequency and a given percentage.
Selecting this parameter the inverter operation mode PID Control settings. At this point, we need to set F9 group" PID Control group. "Frequency inverter operation
Was PID Frequency value role. among them PID Given source, meaning given quantitative feedback source, refer to F9 group" PID Features.
Frequency command given by the host computer via the communication mode. Please refer to 485 Protocol.
Used to set the maximum output frequency of the inverter. It is the basis of the frequency setting, the speed of deceleration is also based .
The upper limit of the operating frequency of the inverter. This value should be less than or equal to the maximum output frequency.
F0.06 The lower limit of the operating frequency 0.00Hz ~ F0.05 hertz 0.00 √
Lower limit of the operating frequency of the inverter. When the reference frequency is lower than the lower limit frequency lower limit frequency.
When a given frequency is selected for "Keyboard Settings", the digital frequency inverter function code value sets the initial value.
Acceleration means for accelerating 0Hz time to maximum output frequency ( F0.04 ) The time required.
Deceleration time from the maximum output frequency of the inverter ( F0.04 ) To decelerate 0Hz The time required.
Illustrated as follows:
30
chapter Five Parameter Function
Output frequency
f MAX
f SET
time t
Actual acceleration time The actual deceleration time
When the reference frequency is equal to the maximum frequency, the actual acceleration and deceleration time and consistent set of acceleration and deceleration time.
When the reference frequency is less than the maximum frequency, the actual acceleration time is less than the deceleration time setting.
The actual deceleration time = deceleration time setting × (set frequency / maximum frequency)
F0.10 Select the running direction 0: Forward run 1: Reverse run 2: Reverse run prohibited no 0 ×
0 : Forward run. After power inverter, in accordance with the actual running direction.
1 : Reverse run. Case can not change any other parameters changed by changing the function code of the steering motor, which acts through
Adjusting the motor line ( U , V , W ) Converting any two lines of the motor rotation direction.
Tip: After initialization parameters, the motor running direction will restore the original state. For non-system debugging good occasion to change the motor rotation Shen
use.
2 : Disable reverse operation. Reverse run prohibit inverter, suitable for use in a specific prohibition of reverse running applications.
The carrier frequency of the electromagnetic noise is noise, the leakage current heat dissipation
10kHz
15kHz
small Big Big
Carrier frequency models The highest carrier frequency kHz Lowest carrier frequency kHz Factory default kHz
31
chapter Five Parameter Function
0.75 ~ 15 kW 15 0.5 8
18.5 ~ 75 kW 8 0.5 4
90 ~ 200 kW 6 0.5 2
This function is mainly used to improve the problem of noise and inverter motor running outside interference and so on.
High carrier frequency advantages: ideal current waveform, the harmonic current is small, a small motor noise; disadvantage of using a high carrier frequency:
Switching loss is increased, the drive temperature is increased, the output capacity of the inverter is affected, at high carrier frequency, the inverter should be derated; while
The leakage current of the inverter increases, the increase of the external electromagnetic interference.
The carrier frequency is low on the contrary, too low carrier frequency will cause unstable operation, even oscillation current torque reduction
Like.
When drives leave the factory, the carrier frequency has a reasonable setting. In general, users do not need to change the parameters.
1: Motor autotuning
Before motor parameter self-learning, motor and load must be disconnected, so that the motor is unloaded, that the motor is at a standstill.
Motor parameters from the previous study, you must enter the correct motor nameplate parameters ( F2.01-F2.05 ), Otherwise the motor parameter self-learning is likely to result
Incorrect.
Motor parameter from the previous learning, should be appropriately set acceleration and deceleration time according to the inertia of the motor ( F0.08 , F0.09 ), Otherwise the motor parameters
set up F0.12 for 1 Then press the button to start the motor parameters self-learning, this time led display"- TUN- "Flashes and then key
Start autotuning, which displays " TUN-0 "After the motor running, the display" TUN-1 "," Run "LED flashes when parameter
Since the end of the study, shows "- END- "Finally, the display returns to stop status interface when." - TUN- "But the key to exit the parameter flashes
In the process parameters self-learning can also suspend a key parameter self-learning operation. Note that the parameter self-learning starting and stopping only
A keyboard control; parameter since learning is completed, the function code is automatically restored to the 0 .
When stationary motor parameter self-learning is not necessary to disengage the motor and load. Motor parameters from the previous study, you must enter the correct motor nameplate paramet
( F2.01-F2.05 ). After learning from the detected motor stator leakage inductance, the resistance and the motor rotor, and the mutual inductance and the load current of the motor
Can not be detected, the user may input appropriate values based on experience.
F0.13 Are Restore Defaults 0: No action 1: Restore Defaults 2 : Clear fault records no 0 ×
32
chapter Five Parameter Function
F0.14 AVR Feature Selection 0: invalid 1: Full effective 2: Invalid only during deceleration no 0 ×
AVR The output voltage function automatic adjustment function. when AVR When the function is disabled, the output voltage with the input voltage (or DC bus voltage)
Change change; when AVR When the function is enabled, the output voltage does not vary with changes in the input voltage (or DC bus voltage), the output
Pressure will remain substantially constant over the range of the output capability.
Note: When the motor is stopped during deceleration, the automatic voltage regulator AVR Close will shut down function in a shorter deceleration time without overpressure.
0: Direct start
1: DC braking start: DC braking (note setting parameters F1.03 , F1.04 ), And then start the motor at the starting frequency. suitable
2: Speed tracking and start: first calculates the drive speed and direction of the motor running, and then run from the current speed to the set frequency,
In order to achieve the rotating motor start smoothly without impact, the method is applicable to a large inertia load when instantaneous power off.
Suitable starting frequency setting, the starting torque can be increased. Retention time in the starting frequency ( F1.02 ), The output frequency
As starting frequency, and then at the starting frequency to the target frequency, if the target frequency (frequency command) is less than the starting frequency, the inverter will not
Operation in the standby state. The starting frequency is not the frequency lower limit.
DC braking current before starting the inverter at startup of the press is set DC braking, DC braking before starting after a set time after
The larger the DC braking current, the greater the braking force. DC braking current before starting is the percentage of the drive's rated current.
0: Deceleration to stop
After the stop command is valid, the inverter reduces the output frequency according to the deceleration mode and the defined deceleration time, reduced frequency 0 After the shutdown.
1: Free Parking
After the stop command takes effect, the inverter output is terminated immediately. Load coasts to stop by its mechanical inertia.
33
chapter Five Parameter Function
Braking start frequency stop: stop during deceleration, when the frequency reaches the start DC braking.
Braking waiting time: Before DC braking starts, the inverter output block, then the delay through the DC braking. use
DC braking current: refers to the added amount of the DC braking. The greater the current, the DC brake effect.
DC braking time: the DC braking duration. Time 0 DC braking is invalid, the deceleration time set by the inverter
Room Park.
Reversible drive set during the transition, the transition time of the output at zero frequency.
As shown below:
When the terminal control channel operation command, the inverter power-on process, the terminal automatically detects the operating state of the system.
0: Invalid on power terminal running command. Even during the power-on, the detected run command is valid, inverter will not run, based
Protection system is in operation until undo the run command terminal, and then enable the terminal, the inverter will run.
1: When the electrical terminals run command. I.e., the drive power in the process, if it detects a valid run command terminal, waiting for initialization End
34
chapter Five Parameter Function
Into the future, the system will automatically start the inverter.
Note that the user must be careful to select the function, it may cause serious consequences.
F1.12 Retention
1: P This machine applies the specified rated torque load variation parameter (fans, pumps load)
GI200 Series inverter using G / P Unity manner, i.e. for constant torque load ( G Type) Motor Power ratio for fans, pumps
Note: Please set according to the nameplate parameters of the motor. Excellent control performance vector control requires accurate motor parameters.
The inverter provides parameter self-learning function. The exact parameters self-learning the correct setting of the parameters of the motor nameplate.
In order to ensure the control performance, follow the motor as per the inverter standard motor, if the motor power standard motor gap is too large,
Note: Reset the motor rated power ( F2.01 ), You can initialize F2.02 to F2.10 Motor parameters.
F2.08 Motor stator, rotor inductance 0.1 ~ 6553.5mH Millihenry Model set √
F2.09 The motor stator and rotor mutual inductance 0.1 ~ 6553.5mH Millihenry Model set √
After the motor parameter self-learning is completed normally, F2.06 to F2.10 The set value is automatically updated. These high-performance parameter is a reference parameter vector control
35
chapter Five Parameter Function
The above parameters are only for vector control of V / F Control is invalid. In the switching frequency 1 ( F3.02 ) Or less, the speed loop PI The parameters are: F3.00
with F3.0 1. In the switching frequency 2 ( F3.05 ) Or more, the speed loop PI The parameters are: F3.03 with F3.04 . Between the switching point, PI By two sets of parameters
PI parameter
( F3.00-F3.01 )
( F3.03-F3.04 )
f
F3.02 F3.05
Proportional and integral time factor by setting the speed regulator, the speed can be adjusted to control the dynamic response characteristics of the vector. Increase the proportion of increase
Benefits, reducing the integration time, can accelerate the dynamic speed loop corresponding, but the proportional gain is too large or too small integration time systems are prone to oscillate,
Overshoot is too large. Proportional gain is too small and can lead to the steady state oscillation, and possibly static speed difference.
Speed ring PI Inertia close motor system parameters and user needs to be based on the default PI parameters for different load characteristics
Slip velocity compensation factor is used to adjust the slip frequency vector control, to improve the control accuracy of the system, appropriately adjusting the parameters, there may be
F3.07 The torque limit setting 0.0 to 200.0% (Inverter rated current) % 150.0% √
F3.08 Retention
36
chapter Five Parameter Function
F3.09 Retention
F4.00 V / F Curve setting 0: straight line V / F curve 1: 2.0 Power torque down V / F curve no 0 ×
F4.02 As of torque boost 0.0% - 50.0% (Relative to motor rated frequency) % 20.0% ×
Torque boost is mainly used in cut-off frequency ( F4.02 ) Or less, after the upgrade V / F Curve as shown, torque-up may be improved V / F of
Load size should be suitably selected according to the amount of torque, the load can be increased to enhance the large, but not the torque boost set too large, excessive torque extract
L, overexcitation operation of the motor, over temperature, and the inverter output current, reducing efficiency. When the torque boost is set to 0.0% , The inverter
Torque boost cut-off frequency: below this frequency, the effective torque boost, the frequency exceeds this setting, torque boost failure.
When this parameter can be compensated V / F When the motor speed control with load variations generated as to increase the hardness of the mechanical properties of the motor, this value
37
chapter Five Parameter Function
Motor load or light load operation of the process, by detecting the load current to adjust the output voltage, to achieve automatic saving.
F4.05 Retention
0: No function
2: Reverse operation
5: Reverse jog
6: Free parking
7: Fault reset
F5.02 X3 Terminal function selection no 7 ×
22 to 25: Retention
0: No function even if there is no signal input inverter operation. Can be set to an unused terminal nonfunctional prevent malfunction.
1: Forward running
2: Reverse operation Frequency converter is controlled by an external terminal forward and reverse.
3: Three-line operation is controlled by this operating mode terminal determines the inverter is a three-line control mode. For more information, refer to F5.07 Three-wire
38
chapter Five Parameter Function
4: Jog forward
5: Reverse jog
Jog operation frequency, jog deceleration time See F8.02 , F8.03 , F8.04 Detailed description of the function codes.
6: Coast to stop The inverter locks the output and the motor drive stop process is not controlled. For large inertia load and no time to stop
When required, the method often adopted. This way and F1.05 Freewheel the meaning is the same.
7: Fault Reset External fault reset function. The same function key on the keyboard. This function is used to implement remote fault reset.
8: When the external fault input signal to the external fault Frequency converter reports fault and stops.
9: Frequency setting increment ( UP ) 10: Decreasing frequency setting ( DOWN ) 11: Clear increase or decrease the frequency setting
Modify the frequency increment instruction given from an external frequency decrement command. Frequency source is set to be vertically adjustable set frequency digital setting.
K1
UP terminal
K2
DOWN terminal
K3 UP / DOWN
clear terminal
COM
Terminals can be used to clear the frequency value increment / decrement is set, a given frequency back to the frequency command given frequency channel.
This number may be three terminals were combined state can be achieved 8 Speed setting. Note: Multi-speed 1 Is low, multi-speed 3 It is high.
15: Deceleration time selection This terminal group selected ramp time:
16: PID Control Pause PID Temporary failure, the inverter maintains the current frequency output.
17: Swing frequency pause (stop at the current frequency) inverter pause after the current output frequency function revoked, continues to operate at the current frequency starts wobble.
18: Wobble reset (return to the center frequency) drive back to the center frequency of the output.
19: Ensure that the drive acceleration and deceleration prohibited from foreign influence signal (except stop command), to maintain current output frequency.
20: Torque control is prohibited Prohibiting the torque control drive mode, the drive mode is switched to speed control.
twenty one: Clear temporarily increase or decrease the frequency setting When the terminal is closed to clear the increment / decrement of the frequency setting value, a given frequency back to the
Frequency command given frequency channel, when the terminal is disconnected returned increased or decreased frequency value of the frequency setting.
22 to 25: Retention
39
chapter Five Parameter Function
Set up X1 ~ X6 Terminal filter time sample. Under heavy interference, this parameter should be increased in order to prevent misuse.
This parameter defines four different ways of running through the external terminal control inverter.
0: Two-wire control 1 . This mode is most commonly used two-wire mode. by FWD , REV Command to determine the positive terminal of motor reversal.
K1 K1 K2 Run command
terminal
OFF OFF stop
K2
ON OFF Forward
REV
OFF ON Reverse
ON ON stop
COM FWD
1: Two-wire control 2 . When using this mode FWD It is enabled terminal. Direction from the REV The state is determined.
K1 K1 K2 Run command
terminal
OFF OFF stop
K2
OFF ON stop
REV
ON OFF Forward
ON ON Reverse
COM FWD
2: Three-line control 1 . This mode SIn Is enabled terminal, the run command FWD Generating, by a direction command REV produce. SIn Normally closed input.
SB1
FWD K direction
SB2
SIn
K ON Reverse
REV
COM
among them: K: Reversing switch SB1: Run button SB2: Stop button
40
chapter Five Parameter Function
SIn Terminal function is defined as the corresponding 3 No. features "three-line running features'.
3: Three-line control 2 . This mode SIn Is enabled terminal, the run command SB1 or SB2 Generating and simultaneously control the direction of travel. Shutdown
SB1
FWD
SB2
SB3
SIn
COM REV
among them: SB1: Forward run button SB2: Stop button SB3: Reverse run button
SIn Terminal function is defined as the corresponding 3 No. Function "three-wire operation."
Note: For two-line operation mode, when FWD / REV When the terminal is valid, the stop command is generated by other sources stop the drive
, Even if the control terminal FWD / REV Remains valid, inverter will not run after the stop command disappears. If you want the inverter operation
Frequency adjusting terminal rise and fall when the rate of change of the set frequency.
The above function codes define the relationship between the analog input voltage and a set value corresponding to the analog input, when the analog input voltage exceeds a set
Input maximum or minimum input range, than the portion will calculate the maximum input or minimum input.
The analog input current input, 0mA ~ 20mA Current corresponding 0V ~ 10V Voltage.
In different applications, the analog setting 100.0% The corresponding value is different, specifically refer to the description of each application.
Under the legend the case of several settings: Note: VIN The lower limit value must be less than or equal to VIN The upper limit.
41
chapter Five Parameter Function
Map 5-13 Simulation of a given correspondence relation with the set amount
VIN Input filter time: to determine the sensitivity of the analog input. When the analog prevent interference and malfunction, by this parameter
Large, the enhanced anti-jamming capability, but due to the analog input sensitivity.
F5.17 -~
SIN Corresponding to the upper limit setting 100.0% 100.0% 100.0% % 100.0% √
SIN Functions and VIN Similar setting method. Analog SIN Support 0 ~ 10V or 0 ~ 20mA Input when the selected SIN 0 ~ 20mA enter
1: Motor Forward rotation It indicates that the drive is running forward, the output frequency. At this point output ON signal.
2: Said drive motor reverse run reverse operation, the output frequency. At this point output ON signal.
4: Frequency level detection FDT Refer to Output Function Code F8.13 , F8.14 The detailed description.
5: Frequency reached Please refer to function code F8.15 The detailed description.
6: Zero-speed running And inverter output frequency at a given frequency at the same time zero, the output ON signal.
7: The upper limit frequency arrival When the operating frequency reaches the upper frequency, the output ON signal.
8: When the operating frequency reaches the lower limit frequency reaches the lower limit frequency, the output ON signal.
42
chapter Five Parameter Function
Standard output of the analog output 0 ~ 20mA ( or 0 ~ 10V) , By jumper J8A Selected current or voltage output. Which represents an amount corresponding to the
The above function codes define the relationship between the output value of the analog output corresponding to the maximum output when the output exceeds a set value or the most
A small output range, calculating a maximum output will be outside the portion or minimum output.
In different applications, the output value 100% Analog output corresponding to vary, refer to the description of each application.
43
chapter Five Parameter Function
Map 5-14 The correspondence between the analog output of the quantitative and
F6.09 Retention
F6.10 Retention
F6.11 Retention
F6.12 Retention
F6.13 Retention
00000 : Clear previously set user password, and the password protection function is invalid, restore factory value can clear the password.
When a user password is set and the entry into force, if the user password is incorrect, the user can not access menu, only enter the correct user
Password, users can view the parameters and modify parameters. Keep in mind that a user password set.
Exit function code edit mode, password protection will 1 After the entry into force of minutes, when the password is activated if the button to enter the function code editing status
When displayed " 00000 "The operator must enter the correct password, otherwise it is impossible to enter.
0: Jog
Key features
F7.03 1: Forward reverse switch no 0 ×
select 2: Clear up / down setting
Key, is the multifunction key. Set function keys may be defined by the parameter keyboard.
1: Forward reverse switch. Keyboard command to achieve the switching frequency direction. Valid only when the keypad command channel.
2: Clear jog / quick settings. Keyboard jog / quick setting value removed.
The function code defines the stop / reset stop function effective option. For fault reset button is valid under any condition.
1: Local and external keypad display simultaneously, only the outer primers key is valid
F7.05 Keyboard Display selection no 0 √
2: Local and external keypad display simultaneously, only the unit key is valid
3: The machine, external keypad keys are displayed simultaneously and efficiently
This function sets the local keypad and display external keypad key role logic.
note: 3 No. function to be used with caution. Misuse could have serious consequences.
44
chapter Five Parameter Function
BIT15: Retention
The drive in the operating state, by the function code parameter display effect, namely a 16 Binary digit, if a bit = 1 , The
Parameters corresponding to the bit during operation can, by pressing key. If the bit is 0 , The bit corresponding to the parameter will not be displayed. Setup function
Code can F7.06 When you want to convert a binary number to a hexadecimal number, enter the function code.
low 8 Place BIT7 ~ BIT0 And high 8 Place BIT15 ~ BIT8 Display contents indicated in the table above.
frequency
Set this function with F7.06 The same settings. Only when the drive is shut down, the parameters displayed by the action of the function code. low 8
Place BIT7 ~ BIT0 And high 8 Place BIT15 ~ BIT8 Display contents indicated in the table above.
Rectifier module temperature: Indicates the rectifier module temperature, different models of rectifier over-temperature protection value may vary.
The inverter module temperature: display inverter module IGBT Temperature, different models of inverter module IGBT Over-temperature protection value may vary.
Accumulated running time: Displays the current total running time is to drive.
45
chapter Five Parameter Function
0: Trouble-free
F7.12 The first two types of fault 1: Inverter unit U Phase protection ( E001) 2: Inverter no
unit V Phase protection ( E002) 3: Inverter unit W Phase
Inverter record three recent fault types: 0 For trouble, 1 to 24 Different twenty four Kinds of fault (detailed functions of this table).
46
chapter Five Parameter Function
Select the ramp time See F0.08, F0.09 The instructions. The movable operating point defines a given frequency inverter and the deceleration time.
Jogging operation start and stop operation process in a direct manner and the deceleration start stop mode.
Jog acceleration time for inverter to run from 0Hz Up to maximum output frequency ( F0.04 ) The time required.
Jog operation Deceleration time from the maximum output frequency of the inverter ( F0.04 ) To decelerate 0Hz The time required.
When the set frequency hopping within the frequency range, the actual operating frequency will run from the frequency near the set frequency hopping boundary.
By setting the frequency hopping, the inverter to avoid the mechanical resonance point of the load. This inverter can be provided a hop frequency. If jumping
Set frequency f
½ * Jump size
Frequency hopping
½ * Jump size
time t
F8.08 Kick frequency amplitude 0.0 to 50.0% (Relative wobble amplitude) % 0.0% √
Traverse function suitable for textile applications, and chemical fiber industry traversing and winding functions.
The wobble function is to set the output frequency of the inverter to the center frequency swing up and down, the operating frequency of the track timeline shown below,
Wherein the oscillation amplitude F8.07 Set when F8.07 Set 0 , That swing 0 Swing frequency does not work.
47
chapter Five Parameter Function
Swing frequency amplitude: Wobble operation frequency by the lower limit frequency constraints.
Swing with respect to the center frequency: swing AW = Center frequency × swing amplitude F8.07 .
Swing kick frequency = AW × jump frequency amplitude F8.08 . Traverse operation i.e., relative to the swing kick frequency value.
Wobble rise time: running from the lowest point to the highest point of the wobble time used.
Wobble fall time: from the highest point run wobble to the lowest elapsed time.
Automatic fault reset times: when the drive select automatic fault reset is used to set the number of auto reset drive fault exceed this value.
Auto-reset interval is set to: select a time between failure to automatically reset from the operation interval.
F8.14 FDT Lag detection value 0.0 to 100.0% ( FDT Level) % 5.0% √
Set output frequency detection value and the output value of the hysteresis releasing operation. As shown below:
Output frequency f
FDT Level
FDT Hysteresis
time t
time t
48
chapter Five Parameter Function
F8.15 Amplitude detection frequency reaches 0.0 to 100.0% (Maximum frequency) % 0.0% √
When the output frequency of the inverter frequency reaches a set value, this function adjust the detection amplitude. Illustrated as follows:
Output frequency
Set frequency
Detection width
time t
Y, R0
time t
F8.16 Brake voltage value 115.0 ~ 140.0% (Standard bus voltage) % 130.0% √
The function code is a set of dynamic braking start bus voltage, appropriately adjusting the effective value of the braking load.
Speed = 120 × × operating frequency F8.17 / The number of pole motor, the rotational speed used to correct this display error, not the actual speed
influences.
PID Is a common method for controlling process control, by the ratio of the feedback signal and the difference signal is controlled quantity target amount,
Integral, differential operation, to adjust the output frequency of the inverter, form a negative feedback system, the controlled amount of the stabilizer on the target amount. Suitable for traffic
Control, pressure control and temperature control, process control. The basic principle of the control diagram is as follows:
Feedback value
0: Keyboard given
49
chapter Five Parameter Function
4: Multi-given
When the frequency source selection PID When, that is, F0.03 Selected for 5 The group function is active. This parameter determines the process PID The target amount for a given channel.
process PID The target amount is set as a relative value, set 100% Corresponding to the feedback signal of the controlled system 100% ; The system always in relative value
select F9.00 = 0 When that target given the source for the keyboard. You need to set this parameter.
Note: The reference channel and feedback channel can not be coincidence, otherwise, PID Can not effectively control.
PID Output positive characteristic: when the feedback signal is greater than PID Given, output frequency will fall, in order to make PID Achieve balance. As income
PID Output is negative characteristic: when the feedback signal is greater than PID Given, output frequency will rise to the PID Achieve balance. The discharge
Proportional Gain ( Kp ): Determines the entire PID Intensity modulating filter, F The larger, the greater the intensity adjustment. This parameter is 100 Means that when PID Feedback
And the amount of a given amount of deviation 100% Time, PID Regulator regulates the amplitude of the output frequency command is the maximum frequency (ignoring the integral and derivative
effect).
Integration time( Ti ): Decision PID Regulator for PID Integrating feedback amount and speed of adjustment to the amount of deviation. Integration time is when PID
And feedback given amount of deviation 100% , The integral regulator (ignore proportional action and derivative action) continuously adjusting the time elapsed, adjustment
The amount of the maximum frequency ( F0.04) . The greater the shorter the integration time adjustment strength.
Derivative time ( Td ): Decision PID Regulator for PID Feedback and quantitative intensity adjustment to the rate of change of the deviation. Derivative time is
If the feedback amount of change in this time 100% , Derivative controller adjustment amount is the maximum frequency ( F0.04 ) (Ignore proportional action and integral action).
PID Process control is the most common method of controlling each part of its role varies, and the following summary of the principle of adjusting the side
France briefly:
Proportional control ( P ): When the feedback given deviation, outputs the adjustment amount proportional to the deviation, if the deviation constant, a constant amount is adjusted
50
chapter Five Parameter Function
set. Proportional control can respond quickly to changes in the feedback, but can not be done simply by adjusting the ratio of the isochronous control. The greater the proportion of the gain of the system
Adjust faster, but being too oscillate. The method of adjusting first long integral time, derivation time is set to zero, the ratio of tone alone
Section running of the system, changing the size of a given amount, and to observe the stability of the feedback signal deviation amount of (static error), if the difference in a static
Quantitative changes in the direction (e.g., increasing a given amount, the system stabilizing feedback is always less than a given amount), the proportional gain continues to increase, and vice versa
Proportional gain is decreased, the above process is repeated until the force difference is small (that is difficult to do without the static error) on it.
Integration time( I ): When the feedback given deviation, adjusting the output of the continuous accumulation, if the deviation persists, the amount of adjustment continued growth
Plus, until there is no deviation. Integral controller can effectively eliminate static error. Integral regulator too strong overshoot occurs repeatedly, make the system a
Straight unstable until the oscillation. Since the oscillation characteristics caused by too strong integral action, the feedback signal in a given amount of vertical swinging pendulum
Amplitude gradually increases until the oscillation. Adjusting the integral time is generally from big to small, gradually adjust the integration time to observe the effect adjustment system
Derivative time ( D ): When the feedback with a given deviation change, rate of change of the output deviation is proportional to the amount of adjustment, the adjustment amount only with the deviation
And the size of the change in direction, regardless of the direction and magnitude of the deviation itself. Differential regulation effect when the feedback signal is changed,
Adjusted according to the change trend of the feedback signal so as to suppress variation. Differential regulator careful to use, easy to adjust because the differential amplification
The sampling period( T ): Refers to the sampling cycle of feedback amount, the regulator calculation in each sampling cycle. The larger the slower the response sampling cycle.
PID Control deviation limit: PID Output of the system with respect to a given loop value allowed maximum deviation, as shown, within the limits of the deviation, PID
Regulator stops. Setting this function code Adjustable PID Accuracy and stability of the system.
Feedback
Deviation limit
Given amount
time
Output frequency
time
Map 5-24 Corresponding to the deviation of the relationship between the output frequency limit
Feedback the break detection value: the detected value is relatively full scale ( 100% ), The system has been detected PID Feedback amount, when the feedback value is less than or
Equal to the feedback the break detection value, the system begins to detect timing. When the detection time exceeds the feedback disconnection detection time, the system will report PID Feedback o
51
chapter Five Parameter Function
Description: Multi-speed running direction of the symbol decision. If it is negative, it means the opposite direction to run. Frequency setting 100.0% Corresponding to the maximum frequency
(F0.04) .
X1 = X2 = X3 = OFF When, by the code frequency input mode F0.03 select. X1 , X2 , X3 Not all OFF When, multi-speed operation, and more
Priority segment is higher than the speed of the keyboard, analog, communication frequency input, by X1 , X2 , X3 Combination coding, selectable 8 Segment speed.
The parking channel selection multi-speed operation by the function code at the same F0.01 Determining, multi-speed control process in FIG. 5-19 Fig. X1 ,
X2 , X3 Relationship between the terminal segment and multi-segment velocity as shown in the following table.
52
chapter Five Parameter Function
Run segment 0 1 2 3 4 5 6 7
Fb.00 Motor overload protection selection 0: Does not protect 1: Common motor (with low speed compensation) no 2 ×
2: Inverter motor (without low speed compensation)
0 : No protection. No motor overload protection characteristics (with caution), the inverter has no load motor overload protection.
1 : Common motor (with low speed compensation). Since the common motor cooling effect is poor at low speed, the corresponding electronic thermal protection value is also
Make appropriate adjustments, where said low-speed compensation characteristic, the operating frequency is less than 30HZ The motor overload protection threshold lowered.
2 : Frequency motor (without low speed compensation). Since the cooling time of special motors independent of speed, and low-speed operation is not required
Fb.01 Motor overload protection current 20.0% - 120.0% (Motor rated current) % 100.0% √
Motor overload protection current = (the maximum allowed load current / rated current of the inverter) * 100% .
Generally defined maximum permissible load with a rated current load of the motor.
When the load on the motor's rated current value and the drive does not match, by setting Fb.00 ~ Fb.01 The value of the motor can be achieved
Overload protection.
Fb.02 Instant power off frequency point 70.0 to 110.0% (Standard bus voltage) % 80.0% √
Fb.03 Instant power frequency drop rate 0.00Hz ~ F0.04 hertz 0.00Hz √
When the instant power drop rate is set to the frequency 0 A momentary power failure restart function is invalid.
Instant power down point: it refers to the power grid after power failure, bus voltage instant power off frequency drop point, the inverter starts out in accordance with the instant
53
chapter Five Parameter Function
Electrical frequency rate of decline ( Fb.03 ) Reduce the operating frequency, the motor is in the power generation state, so that the feedback energy to maintain the bus voltage, to ensure the frequenc
Note: Proper adjustment of these two parameters, you can realize the power switch, without causing inverter protection resulting from production downtime.
Fb.05 Overvoltage stall protection voltage 110 ~ 150% ( 380V series) % 120% √
Inverter deceleration during operation, since the load inertia, the actual motor speed is lower than the rate of decline may occur in the output frequency
Rate of descent. At this time, feed back the power to the inverter, resulting in DC bus voltage of the inverter rises, if no measures are taken, it will cause the mother
Overvoltage protection stall during inverter operation by detecting the bus voltage, and in Fb.05 (Relative to the standard bus voltage) is defined
Comparing the stall overvoltage point, if the overvoltage exceeds the stall point, the output frequency of the inverter is stopped down again when the detected voltage is lower than the over the bus
Fb.07 Frequency decrease rate when current limiting 0.00 ~ 100.00Hz / s Hz / sec 10.00Hz / s √
The drive during operation, since the load is too large, the increase rate of the actual motor speed is lower than the increase rate of the output frequency, if not
Measures, will result in accelerated overcurrent fault caused by frequency converter trip.
The stall protection during inverter operation by detecting the output current, and with Fb.06 Limiting the definition of horizontal dots is compared,
If the level exceeds the current point, the output frequency of the inverter frequency decreasing along the flow rate through the ( Fb.07 ) Is decreased when the detected output current is low again
After the current limit level at the point, and then resume normal operation. Figure:
54
chapter Five Parameter Function
When the host in the preparation of the frame, the slave communications address set 0 When, that is, broadcast address, MODBUS All slaves are connected on the bus
By the frame, but the machine does not respond. Note that, the slave address is not set 0 .
Local communication address is unique in the communication network, which is the basis point to point communication between host computer and the drive.
0: 1200BPS 1:
2400BPS 2:
4800BPS 3:
FC.01 Communication baud rate settings no 3 √
9600BPS 4:
19200BPS 5:
38400BPS
This parameter is used to set the data transfer rate between the host and the drive. Note that the host computer and the inverter setting the baud rate must be the same,
Otherwise, communication is impossible. The larger the baud rate, the faster communications.
PC and inverter setting data format must be consistent, otherwise, communication is impossible.
Response delay: inverter means accepts data up to the intermediate end sends response data bit interval. If the response delay is less than the Department
55
chapter Five Parameter Function
System processing time, the response delay to the processing system based on the time, such as longer than the response delay time of the processing system, the system after processing the data,
To delay to wait until the response delay time to only transmit data up crew.
FC.04 Communication timeout fault time 0.0 (invalid), 0.1 ~ 100.0s second 0.0s √
When the function code is set to 0.0s When the communication timeout parameter is invalid. When the function code is set to a valid value, if the next communication time
Interval time communication beyond communications timeout, the system will alarm communication error ( E018 ).
Typically, it is set as invalid. If the continuous communication system, set time parameters, you can monitor the communication status.
control)
The drive in unusual circumstances may choose to shield communications failure alarm and shutdown, continue to maintain protection by setting the action.
FC.06 Transmission response processing 0: Write operation has to respond 1: Write no response no 0 √
When the function code is set to 0 When the drive will read and write commands PC has responded. When the function code is set to 1 , The drive for the PC
The command has only read response, no response to the write command, in this way can improve communication efficiency.
Suppress oscillation
Fd.01 no √
0 to 500 100
frequency threshold point
Most motor in certain frequency bands current runtime prone to shocks, the light can not be stable operation of the motor, in serious cases can cause the inverter over-current.
when Fd.04 = 0 When enabled suppress oscillation, Fd.00 with Fd.01 When set small, the oscillation suppressing effect is more obvious, the current increases obviously provided
By setting this parameter value may be suppressed to limit a large oscillation voltage boost value.
1: Suppress oscillation is invalid. Oscillation suppression function is for VF For control of ordinary vibration motor currents often occur at light load or no-load running
Swing phenomenon, leading to the motor is not running properly, will make a serious over-current inverter. Fd.04 = 0 Will be able to suppress the oscillation function, the drive will follow
Fd.00 ~ Fd.03 This parameter is set for the oscillation motor occurs can be suppressed.
56
chapter Five Parameter Function
0: PWM mode 1 1:
Fd.05 PWM select no 0 ×
PWM mode 2
0: PWM mode 1 This mode is normal PWM Mode, the motor noise at low frequencies is small, a large high frequency motor noise.
1: PWM mode 2 The motor runs less noise in this mode, but a higher temperature, such as selecting this function the inverter should be derated.
limit)
when F0.00 = 2 When the torque control is valid. When the torque control, the torque converter output torque command is set according to the output frequency by the upper frequency limit
System, when the load speed is greater than the set upper limit frequency, the output frequency is limited, the output torque will not be the same as the set torque. As a transfer
Torque control, Fd.06 The set torque is a torque command. When the set torque command keyboard ( Fd.06 = 0 ), The function code is provided by
Fd.07 To obtain a torque command. When the set torque is negative, the motor will be reversed. May be controlled in speed and torque control via the multifunctional input terminal
Switch between system. When the drive torque is greater than the set load torque, the output frequency will increase, when the output frequency reaches the frequency
Limit the rate has been above limit frequency inverter operation. When the drive torque is set smaller than the load torque, the output frequency will decrease, when
Inverter output frequency reaches the lower limit frequency, lower limit frequency converter has been running. Fd.07 The set 100.0% Corresponding to the upper limit of torque,
Note: When the torque control stop command, automatically switches to speed control.
Setting an upper limit frequency source2: Analog SIN Set an upper limit frequency ( 100% Corresponding
Fd.08 no 0 √
select to the maximum frequency)
by Fd.08 You can achieve a variety upper frequency reference source selection. Especially in the torque control, by changing the frequency to change the upper bound
Fd.09 Current limiting action selection 0: Current limit remains in effect 1: Invalid constant speed limiting no 0 √
Automatic current limiting function is always active in the deceleration state, when the automatic current limiting action, the output frequency may vary, so the required constant
Stable output frequency occasion speed operation, not to use the automatic current limiting function. When the automatic current limiting effective, due to the lower limiting level set
57
chapter Five Parameter Function
The group opens the set of parameters for the factory set parameters, users do not try, otherwise the inverter normal operation or damage.
58
Chapter Six Troubleshooting and exclusion
E004 Accelerate the run overcurrent 2. The low voltage grid 2. Check input power
3. Small power inverter 3. Selection of the inverter power freshman profile
E005 Deceleration overcurrent 2. Large load inertia moment 2. Suitable energy applied brake assembly
E006 Constant speed overcurrent 2. The low voltage grid 2. Check input power
3. Small power inverter 3. Selection of the inverter power freshman profile
E008 Deceleration overvoltage 2. Inertia load 2. Energy consumption increases brake assembly
E010 Bus undervoltage The low voltage grid Check the input power grid
59
Chapter Six Troubleshooting and exclusion
E017 External fault SI External fault operation input terminal Check the external input device
E021 EEPROM Failure to read and write 1. Write control parameter error service
2.EEPROM damage
2. Calling for service
No power on display:
Input power supply and the inverter rated voltage coincides with a multimeter to check the drive. If you have questions, please check the power supply and excluded. Check
Check the three-phase rectifier bridge is intact. If the rectifier bridge has been exploded, please seek services.
an examination CHARGE Whether the lamp lit. If the light is not on, the fault will be in the snubber resistor or a rectifier bridge, if this lamp is lit,
Is there a short circuit to ground or input power between the inspection, remove the problem. Check whether the rectifier bridge has broken down. If,
For service.
an examination U , V , W Is there a balance between the three-phase output. If, for the motor circuit itself or damage, or motor stall due to mechanical reasons.
Please excluded. There can be three-phase output but is not balanced, it should be damage to the inverter drive board or output module, please seek services. If there is no output voltage,
60
Chapter Six Troubleshooting and exclusion
The inverter displays the normal operation after the power switch trips open air: phase check for short circuits between the output module. if,
Please seek.
Or whether there is a short circuit between grounding motor lead wires. If yes, please excluded. If the trip is occasional and
the distance between the motor and the inverter distant, then consider raising output AC reactor.
61
Chapter VII communication protocol
GI200 Inverter, providing RS485 Communication interface, the use of international standards ModBus Main communications protocol from the communication. Users can
by PC / PLC The control PC and the like to achieve centralized control (inverter control command set, modify the operating frequency, the correlation function parameter,
Monitor the drive working status and fault information, etc.) to suit specific application requirements.
7.1 Agreement
That Modbus Serial communication protocol defines the frame contents and format of serial communication using asynchronous transfer. Which comprises: a host poll
Broadcast frame and the response frame from the machine format; content of the master frame comprising: a slave address (or a broadcast address), execute the command, data and the error
Error checking. Response from the slave is the same structure, including: operation confirmation, return data and error checking. If the slave
Motion error occurs when the received frame, or host requirements can not be completed, it will organize a fault frame as a response to the host.
GI200 Accessible drive comprising RS485 Bus "from the single master multiple" control network.
(1) Interface
Serial asynchronous, half-duplex transmission mode. At the same time master and slave transmitting only one data and the other data received. number
In the form of packets, a data transmission in a serial asynchronous communication, based on.
(3) Topology
Single master multi slave system. Range of slave address is 1 to 247 , 0 It is broadcast communication address. In each network address from the machine
They are unique. This is to ensure that ModBus Basic serial communication.
GI200 The drive is an asynchronous serial communication protocol from the master ModBus Protocol, only one network device (host)
We can build a protocol (referred to as "Inquire / Command"). Other devices (slaves) only in response to data provided by the host "Query / Command"
Or make the appropriate action based on the host "inquiry / command." This refers to the host personal computer ( PC ), Industrial control equipment, or programmable
Programmable Logic Controller ( PLC ), And the slave means GI200 Series inverter or other control devices with the same communication protocol. Both host
For a slave communication alone can release all slaves broadcast information right. For hosts "inquiry / command" individual visit, slave
It must return a message (called a response), the broadcast information sent by the host to the slave without feedback response information to the host.
GI200 Series Inverter Modbus Protocol communication data format is divided into RTU (Remote Terminal Unit) mode, and ASCII ( American
62
Chapter VII communication protocol
Coding system: 8 Bit binary, each 8 Bit frame field includes two hexadecimal characters, hexadecimal 0-9 , A ~ F .
Coding system: communication protocol is 16 Ary, ASCII Information character meaning: " 0 " ... " 9 "" A " ... " F "Every
ASCII code 0x30 0x31 0x32 0x33 0x34 0x35 0x36 0x37
ASCII code 0x38 0x39 0x41 0x42 0x43 0x44 0x45 0x46
Data format: start bit, 7/8 Data bits, stop bits, and parity. Data format is described in the following table:
Starting BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 BIT8 check stop
Starting BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 check stop
in RTU Mode, the new frame is always at least 3.5 Byte as a starting silence time transmission. In order to calculate the transmission baud rate
On the network, 3.5 Byte transmission time can easily grasp. Immediately transmitting data fields as follows: the slave address, operation command code,
Data and CRC Check words, each field is transmitted byte hexadecimal 0 ... 9 , A ... F . Network device keeps track of live communication bus
move. When receiving the first field (address information), each network device to confirm this byte. With the completion of the transmission of the last byte
Into, there are some similar 3.5 Byte transmission time interval used to identify the end of the table frame, after this, a new frame will start
Transfer.
Information of one frame must be transmitted in a continuous data stream, if there is more than before the entire frame is transmitted 1.5 Bytes or more
Interval, the receiving device will clear these incomplete information, and then the error that is a byte address field of a new part, with
Like, if the start of a new frame and a previous frame interval is less than 3.5 Byte time, the receiving device will consider it a previous frame
Continue, due to the confusion of the frame, final CRC Checksum value is incorrect, resulting in communication failure.
MODBUS Packets
63
Chapter VII communication protocol
ADDR
...
DATA ( 0 )
Low
CRC CHK
High
in ASCII Mode, the header is ":" ( 0x3A ), The default value for the end of frame " CRLF "(" 0x0D ' " 0x0A ").in ASCII square
Of the formula, in addition to the header and trailer, to all of the remaining data bytes ASCII Send code, first sending high 4 Bit bytes, and then sent
Send low 4 Nibble. ASCII Data is under way 8 Bit length. for' A '~' F 'Respective capital letters ASCII code. at this time
Using data LRC Checking, checking covers the data from the slave address to the information part. The checksum is equal to all the characters involved in the check data and (homes
MODBUS Packets
64
Chapter VII communication protocol
Address Hi mailing address: 8-bit Address by the 2 More ASCII Code group
Address Lo Close
Function Hi function code: 8-bit Address by the 2 More ASCII Code combination
Function Lo
Data Domain Data Content: nx8-bit Data from the content 2n More
... code
DATA ( 0 )
LRC CHK Hi LRC Detection code: 8-bit Check code by the 2 More ASCII
Place
7.6.1 Command code: 03H Read N Words ( Word ) (Maximum continuous reading 16 Words)
For example: the slave address 01H The drive, memory start address 0004 , Continuous reading 2 Words, the structure of the frame as described
under:
START T1-T2-T3-T4
ADDR 01H
CMD 03H
END T1-T2-T3-T4
65
Chapter VII communication protocol
START T1-T2-T3-T4
ADDR 01H
CMD 03H
END T1-T2-T3-T4
START ':'
ADDR '0'
'1'
CMD '0'
'3'
'0'
'4'
'0'
'2'
END Hi CR
END Lo LF
66
Chapter VII communication protocol
START ':'
ADDR '0'
'1'
CMD '0'
'3'
'4'
Place '3'
Place '8'
Place '3'
Place '8'
END Hi CR
END Lo LF
For example: the 5000 ( 1388H ) Writes slave address 02H Inverter 0005H Address. The frame structure is described as follows:
START T1-T2-T3-T4
ADDR 02H
CMD 06H
67
Chapter VII communication protocol
END T1-T2-T3-T4
START T1-T2-T3-T4
ADDR 02H
CMD 06H
END T1-T2-T3-T4
START ':'
ADDR '0'
'2'
CMD '0'
'6'
'0'
'5'
'3'
'8'
68
Chapter VII communication protocol
END Hi CR
END Lo LF
START ':'
ADDR '0'
'2'
CMD '0'
'6'
'0'
'5'
'3'
'8'
END Hi CR
END Lo LF
Error check parity mode frame comprises two main parts, i.e., byte parity bit (odd / even parity) check the entire data frame, and
The user may select different bit Parity required, can select no parity, which will affect the parity bit of each byte set.
Even parity meaning: before a data transmission of additional parity bits used to represent the data in the transmission " 1" The number is odd or even, of
An even number, the check position " 0 " Otherwise, set to " 1" To parity preserving data. Meaning odd parity: a data transmission before
Plus an odd parity bits used to represent data transmission " 1" It is odd or even number, an odd number, the check position " 0 " ,otherwise
It is set to " 1" To parity preserving data. For example, the need to transfer. " 11001110 " , Containing data 5 More " 1" If even parity,
It even parity bit is " 1" , If odd parity, which is odd parity bit is " 0 " When transmitting data, the parity check after calculation on the frame
69
Chapter VII communication protocol
Bit position, the device also receives parity, parity and if not received preset data found, that communications sent
use RTU Frame format, based on the frame comprises CRC The method of calculating frame error detection field. CRC Field detecting the content of a frame.
CRC Field is two bytes, comprising 16 Bit binary value. It is calculated by the transmission device is added to the frame. The receiving device recalculates received
Frame CRC And with the received CRC Compare the value of the domain, if two CRC Values are not equal, then a transmission error. CRC Yes
First deposit 0xFFFF And then calls a procedure successive frames 6 Or more bytes processed in the current register value. Each word only
The symbol 8Bit Data on CRC Active, start and stop bits and the parity are invalid. CRC Generating process, each 8 Bit word
Symbols individually and register contents or different ( XOR ), The result of moving to the least significant bit direction, with the most significant bit 0 filling. LSB Rapture
Detection taken out, if LSB for 1 , The individual registers and different preset value or, if LSB for 0 , Not made. The whole process to re
complex 8 Times. In the last (first 8 Posterior) is completed, the next 8 Single-bit byte and the current value register or different. The final register
The value, which is after all the bytes of the frame are performed CRC value. CRC This calculation method, using international standards CRC
Check rule, users edit CRC When the algorithm, can refer to the relevant standards CRC Algorithm, written in a truly meet the requirements CRC meter
Computer Program.
Checksum ( LRC Check )by Address To Data Content The results add up to the value of.
This part is defined by the address data communication, for controlling the operation of the inverter, the inverter state information acquiring functions related drive and
Parameter settings.
Function code corresponding to the parameter number register address, but converted to hexadecimal as P5.05 The serial number 61 , Then with hexadecimal
System indicates that the function code address 003DH . High and low byte range are: high byte 00 to 01 ; Low byte 00 ~ FF . note:
PE Group: setting parameters for the factory, the set of parameters is neither readable nor can change the set of parameters; some parameter in the drive is running
When, can not be changed; some argument whether the drive is in what state are final; change the function code parameters, pay attention to set parameters
70
Chapter VII communication protocol
0004H : Failure
Communication setting value of the address 2000H When the percentage of the maximum relative frequency; when W/R
R
Bright 3007H Output torque
71
Chapter VII communication protocol
300EH Retention
300FH Retention
3010H Retention
3011H Retention
72
Chapter VII communication protocol
When the response from the device, it uses the function code field to indicate the fault address is a normal response (correct) or there is some error occurred
(Referred to respond to objections). Normal response from the device to respond to the corresponding function code and subfunction codes or data addresses. Respond to objections from
A return device is different from the normal code, the code, address data 5001H .
For example: a master device to the request message from the device a set of function codes read address data, a function of the generated code and data
address:
00,000,011 (Function code, hexadecimal 03H ) 00,000,005 (Data address, hexadecimal 05H )
Normal response, respond to the same function code and the address data from the device.
Objections response, it returns: 00,000,110 (Hex 06H ) 00,000,005 (Hex 05H ) In addition to the function
Code and address data has been modified due to disagreement error, the device in response to a byte from the exception code, which defines the cause of abnormality. the Lord
After the device application gets responding to an objection, the typical process is to resend the message, a command or change for the corresponding fault.
01H wrong password Password verification and address written F7.00 Different password set by the user
02H Illegal function Is received from the host computer to the function code is not allowed to operate; slave may
03H Parity error When the frame information transmitted from the host computer in CRC Parity check bit and the next crew
The number is not the same calculation, report validation error message.
04H Illegal Data Address Requested data address is the address of the host computer is not allowed; in particular, the register
05H Illegal data value When the received data is contained in the domain of allowed values.
73