Control System Engineering LABs Manual
Control System Engineering LABs Manual
Apparatus:
Theory:
This system is based upon the variable resistor known as potentiometer. The
potentiometer function is calibrating the temperature by changing the value of
resistor. This system contains resistor as well as LED when the resistor heated up to,
certain level of temperature then the LED becomes ON, and heating of the resistor
is also controlled by the fan of a speed controlled system mentioned below. In
temperature, controlled system a converter is used known as temperature-Voltage
controller used to converts the temperature into voltage, which becomes the output
of this system.
Speed controlled system is based upon the motor which works as a ventilator. The
fan helps in cooling of the heated resistor used in temperature control system. In this
system, a speed controlled sensor generates a signal known as TTL signal, this signal
is a speed dependent frequency signal. In this system, a converter is used known as
frequency-Voltage converter, which converts the frequency to the voltage, which is
shown on the output of the system.
A light control system is composed of two components known as emitter LED and
a receiver photo sensor. The input to this system is given at YL and output is taken
at the XL as shown in the figure below.
Apparatus:
Objective: The main objective of this lab is to find the operating point of
temperature controlled system with respect to the response of the system at reference
point.
Theory:
The operating point is defined as the difference between the actual value and the
reference value .The temperature control system is composed of the following parts,
Block Diagram:
Set Point
+ Value +
Disturbance
Measuring
System
+es Element/Sensor
-
+
Error
Command
Feedback Amplifier
Temperature
Output Controller
Input: The temperature control system has many inputs which are used to measure
the variable in the form of temperature.
Procedure:
1. Make the circuit according to the diagram, and initially set the potentiometer
at the end of the range, then activate the voltage source and voltmeter
accordingly.
2. Apply DC voltage in a range of 0-10V
3. Set the potentiometer to zero value by rotating its nob
4. To the input Y=1/T.
5. Find the static output voltage Y=XT at zero reference point with zero potential
difference.
6. When the potentiometer is brought to the middle point little fluctuations are
observed and the steady state graph along voltage axis is observed.
Apparatus:
Objective: The main objective of this lab is to find the static characteristics of
temperature control system. This characteristics is obtained through a graph obtained
from the ratio of steady state output to the steady state input at numerous operating
points so find the value of Kp, where Kp is the gain of the temperature controlled
system.
Procedure:
Table:
Results:
Fig-3.1
Fig-3.2
Fig-3.3
Fig-3.4
Fig-3.5
LAB 04
Theory:
“It corresponds to the relationship of the final steady state values of the output and
input variables in term of their elevations from the operating point.”
Lag Time ( 𝐓𝐮 ):
“The Lag time is measure of how long it takes for the output variable to noticeably
responds to the input step’’ .
Compensation Time ( 𝐓𝐠 ) :
‘‘Compensation Time is the measure of the time it takes for the transient response
to be essentially complete’’.
Fig-4.1
Procedure:
Fig-4.2
100
%
x 1:
0.5
y 1: 90
5
x 2: 80
9.5
y 2: 70
95
dx : 60
9
dy :
50
90
dy /dx :
40
10
30
20
10
0
010
2030
4050
6070
8090
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
t/s
Fig-4.3
Fig-4.4
LAB 05
Apparatus:
Objective:
Theory:
“Operating point is actually the difference between actual value and reference
value”. The operating point is specific point for the variable with in the operation
characteristic of a device.
Speed Controller:
“A Device used to control speed at some specific value is called a speed controller”.
The block diagram shown below is the speed controlled control system in which a
voltage is applied at the input Ys of the motor and this voltage is proportional to the
speed of the fan which is obtained at the output Xs
Circuit Diagram:
𝒚𝒔 𝑿𝑻𝑻𝑳 𝒙𝒔 RPM f
M
TTL v
This above block diagram shows the speed controlled system in which the motor is
connected with the converter where speed is converted to TTL level and then in the
second block contain another converter called frequency to voltage converter in
which the frequency is converted into voltage.
Procedure:
Fig-5.1
LAB 06
Apparatus:
Theory: Steady state of any system is defined as the response that arrives after
transient response or the response arrives when transient response is faded. Steady
state response is also known as the static state response.
Procedure:
Circuit diagram:
Fig-6.1
Results:
Fig-6.2
LAB 08
Objective: The main objective of this lab is settling and analyzing operating point
of speed control system, by setting the desired reference point and checking its
behavior.
Theory:
In this lab, we are finding the desired reference point of operation and checking its
behavior. In different fields, light is playing a vital role so to get the desired amount
of intensity of light we need a system, which is known as light control system. In
order to set the operating point of this system we need to calculate a difference
between two values known as reference value and actual value.
Procedure:
Results:
Fig-8.1
LAB 09
To study and determine the steady state characteristics of light control system
Objective: The main objective of this lab is to determine the steady state
characteristics of light control system.
Theory:
Light is the most important thing in almost every field of life. So in order to get
desirable amount of light we need a control system known as light control system.
This experiment is about to analyze and determine the static characteristics of light
control system through graph, which is, obtained from the ratio of steady state o/p
to steady state I/p at different operating points.
Procedure:
Results:
OBJECTIVES:
We find the various parameters of speed controlled system for various input steps
and then compare these parameters to each other.
THEORY:
Such a system in which the input step function is changed, then the controlled
variables will try to reach its final steady state in response.
Here the controlled variables continuously rise at full strength and reaches to a
point it which its natural limit because of some physical reasons. In this experiment
we consider the compensated system and the experiment card we are using has
model number S04201-5V. This experiment can be fully described in terms of
three basic parameters through which we can find out steps response to.
Gain(Ks/Kp):
It is a steady state value of step response when the input step change is equal to
one. It is represented by Ks or Kp. Kp/Ks shows the relationship of final steady
state value of output and input variable in terms of deviation of input and output
before step change is fed forward.
The time taken by the system for the completion of the transient response. To find
compensation time, we draw a perpendicular line from the point of the final steady
state intersected by the in section tangent line, touching at point in the time axis
and subtracting the lag time from this which was determined before.
APPARATUS:
PROCEDURE:
Fig-10.1
LAB NO. 11
THEORY: A controller that feeds forward to the plant a proportion of the error
signal is called Proportional Controller, represented by P-Controller. It is further
classified into the categories i.e. PD Controller (proportion-plus-derivative
controller), PI Controller (proportion –plus-integration controller) & PID
Controller (proportion-plus-derivative-plus-integration controller)
𝑦 = 𝐾𝑝𝑒(t)
PROCEDURE:
%
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
THEORY: A Controller used to feed to the plant a proportional of the error signal
plus it’s integral to improve the steady state error of the close loop system is called
PI-Controller.
PROCEDURE:
If the system is heated up. Then wait for the system to cool down to correctly
observe the graph otherwise it will not start from the actual position.
Result/Graph:
Fig-12.1: PI Controller for Temperature Control System
LAB NO.13
“To Analyze and Study PID Controller for Temperature Control System”
Apparatus:
THEORY:
The Controller used to feed to the plant a proportional of the error signal, it’s
integral and it’s derivative for the improvement of the steady state error and the
transient response of the close loop system is called PID-Controller.
Working Principle:
PID works on three basic controllers that are explained below. A Proportional or
P- controller’s output is proportional to the current error e (t). The Integral or I-
Controller and Differential or D-Controller. The working mechanism of PID
controller is shown in figure.
To design a Stable PID controller for a temperature control system, set the
values of the parameter as below
For Proportional controller Kp=5, factor=1.
For Integral controller Tn=5, factor=0.01.
For Differential controller Tv=5, factor=5.
Select the step function plot.
And then press the Run simulator button.
Result/ Graph:
Precaution:
If the system is heated up. Then wait for the system to cool down to correctly
observe the graph otherwise it will not start from the actual position.
LAB NO. 14
THEORY: A Controller that feeds forward to the plant a proportion of the error
signal plus its integral for the purpose of improving the steady state error of the
close loop system is called PI-Controller.
PROCEDURE:
If the system is heated up. Then wait for system to cool down to correctly observe
the graph otherwise it will not start from actual position.
Result/Graph:
100
% 90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
THEORY: A controller that feeds forward to the plant a proportion of the error
signal is called Proportional Controller, represented by P-Controller. It is further
classified into the categories i.e. PD Controller (proportion-plus-derivative
controller), PI Controller (proportion –plus-integration controller) & PID
Controller (proportion-plus-derivative-plus-integration controller)
𝑦 = 𝐾𝑝𝑒(t)
PROCEDURE:
100
%
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
THEORY: A controller that feeds forward to the plant a proportion of the error
signal is called Proportional Controller, represented by P-Controller. It is further
classified into the categories i.e. PD Controller (proportion-plus-derivative
controller), PI Controller (proportion –plus-integration controller) & PID
Controller (proportion-plus-derivative-plus-integration controller)
𝑦 = 𝐾𝑝𝑒(t)
PROCEDURE:
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
t/s
THEORY: A Controller that feeds forward to the plant a proportion of the error
signal plus its integral for the purpose of improving the steady state error of the
close loop system is called PI-Controller.
𝑦 = 𝐾𝑝𝑒(t) +𝑇𝑣𝑑/𝑑𝑡𝑒(𝑡)
PROCEDURE:
If the system is heated up. Then wait for system to cool down to correctly observe
the graph otherwise it will not start from actual position.
Result/Graph:
100
%
90
80
70
60
50
40
30
20
10
0
0 1 2 3 4 5 6 7 8 9 10
t/s