LT Contactor Ranges PDF
LT Contactor Ranges PDF
www.LNTEBG.com
POWER CONTACTORS
www.LNTEBG.com
CONTROL CONTACTORS
www.LNTEBG.com
SALIENT FEATURES OF MNX CONTACTORS
✦ Suitable for tropical conditions, ensures reliable performance in high ambient temperature, humidity etc.
✦ Enclosed construction ensures protection of contact & magnet pole faces from dust and foreign particles.
✦ Front ON/OFF mechanical indication provides visual inspection of the state of the contactor.
✦ Main terminals are suitable for aluminium busbars & lugs so as to give higher terminal capacity.
www.LNTEBG.com 6/1
CONTACTORS - TYPE MNX
POWER CONTACTORS
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1
AC operation
MNX 95/110/140
MNX 185/225
DC operation
✦ Suitable for applications where wide fluctuations in control supply voltage are observed.
✦ Wide band operation 55-110%
AC operation
9 25 4 1 — 10 0.37 SS94771….
9 25 4 — 1 10 0.37 SS94772….
12 30 5.5 1 — 10 0.37 SS94773…. 6
12 30 5.5 — 1 10 0.37 SS94774….
MN 9/12/16W 16 30 7.5 1 — 10 0.37 SS94679….
16 30 7.5 — 1 10 0.37 SS94680….
25 45 11 1 1 10 0.60 SS94655….
MN 25W
* For Voltage suffix refer page 6/7
CONTACTORS - TYPE MN
CONTACTORS FOR CAPACITOR SWITCHING
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1
✦ Suitable for capacitor switching of single capacitor as well as auto-switching of a bank of capacitors.
✦ Increases the life of capacitors by reducing the switching surge.
✦ 2-auxillary contacts built-in.
AC operation
10 25 1 1 1 0.62 SS94624….
MN 16C
1 — 10 0.03 CS9412OOOO0
— 1 10 CS94121OOOO
4 10 2 — 10 CS94117OOOO
1 1 10 CS94118OOOO
— 2 10 CS94119OOOO
MN A1 4 — 10 0.03 CS94112OOOO
3 1 10 CS94113OOOO
4 10 2 2 10 CS94114OOOO
1 3 10 CS94115OOOO
6 — 4 10 CS94116OOOO
4 — 10 0.03 0.05 CS9412OOOO0
— 1 10 CS94121OOOO
4 10 2 — 10 CS94117OOOO
MNX-A12T-2 MNX-A12T-4 1 1 10 CS94118OOOO
— 2 10 0.03 CS94119OOOO
4 — 10 CS94112OOOO
3 1 10 CS94113OOOO
4 10 2 2 10 CS94114OOOO
1 3 10 CS94115OOOO
— 4 10 CS94116OOOO
4 10 1 1 1 0.05 SS94201OOOO1)
MNX-A33S-2 SS94202OOOO1)
1 1 SS94203OOOO2)
SS94204OOOO2)
4 10 1 1 1 0.05 CS94205OOOO1)
1 1 CS94206OOOO1)
1 1 CS94207OOOO2)
1 1 CS94208OOOO2)
MNX-A46S-2
Surge Suppressor For Contactor type Rated control voltage Qty Wt Catalogue No.
Us [No.] [Kg]
[No.] [Kg]
MNX-M12S-0
MN 16dc 1 — SS94766OOOO
MN-M1
MNX-M33B-0
1 2.90 CS94193OOOO
MN 95 / MNX 95
MN 110 / MNX 110
MN 140 / MNX 140
MNX-M44B-0
MNX-M55B-0
www.LNTEBG.com 6/5
SPARES
AC operation
MNX 9, 12, 18, 25, 32
MNX 9, MNX 12, MNX 18, MNX 25, MNX32 10 0.09 CS94105….
6 MN 25W, MN 32C
MNX 70, MNX 80
DC operation
MN16dc 1 —7 SS94651….
MNX 550
ORDERING INFORMATION:
Example for Contactor : MNX 9 Contactor - 240V, 50Hz, 1No Example for Spare Coil : MNX 18 Spare Coil - 360V, 50Hz
Ordering Information - CS94106BOOO Ordering Information - CS94105COOO
24 4OOO
42 6OOO
48 5OOO
110 1OOO
220 2OOO
www.LNTEBG.com 6/7
POWER CONTACTORS - TYPE ML
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1
AC operation
ML0/1/1.5
25 25 11 2 2 10 0.50 SS91851….
32 40 15 2 2 10 0.95 SS90701….
ML10/12
4 10 1 1 10 0.10 SS91494OOOO
4 10 1 1 10 0.10 SS91474OOOO
✦ ML4/6/10/12 contactors are available with built in 2NO+2NC auxiliary contact block. Additional 1NO+1NC block
can be fitted on either side ,providing 4NO+4NC auxiliary contacts.
www.LNTEBG.com 6/9
SPARES
AC operation
ML1
ML1.5
ML1-1.5
ML3
6
ML4 1 0.31 SS91258….
ML2-3
ML6
ML12
ML4-6
ML1-1.5
ML2 50sets 0.05 SS90544OOOO
ORDERING INFORMATION:
Example for Contactor : ML2 Contactor - 240V, 50Hz Example for Spare Coil : ML4 Spare Coil - 110V, 50Hz
Ordering Information - SS90701BOOO Ordering Information - SS91258AOOO
Coils at 50 Hz
12 FOOO — — —
24 GOOO — — —
42 HOOO HOOO — —
110 AOOO AOOO AOOO AOOO 6
220 — KOOO KOOO KOOO
220/230 KOOO — — —
240 — BOOO BOOO BOOO
240/250 BOOO — — —
320 ROOO ROOO — —
360 COOO COOO — —
380 LOOO LOOO — —
415 — — DOOO DOOO
415/440 POOO POOO — —
525 MOOO MOOO MOOO MOOO
www.LNTEBG.com 6/11
CONTROL CONTACTORS - TYPE MN
Conformance to IS 13947 (Part 5/Sec.1) and IEC:60947-5-1
AC operation
10 4 4 — 10 0.39 SS94660….
3 1 SS94661….
2 2 SS94662….
1 3 SS94663….
MN0 AC — 4 SS94664….
6 DC operation
10 4 4 — 10 0.68 SS94665….
3 1 SS94666….
2 2 SS94667….
1 3 SS94668….
— 4 SS94669….
MN0 DC
* For Voltage suffix refer page 6/15
AC operation
DC operation
— 10 4 2 2 10 0.65 SS92007….
— 10 4 8 — 10 0.65 SS92820….
7 1 SS92821….
6 2 SS92822….
5 3 SS92823….
MM00/01 DC 4 4 SS92824….
1 — 10 0.10 SS94715OOOO
— 1 10 SS94716OOOO
4 10 2 — 10 SS94080OOOO
1 1 10 SS94081OOOO
— 2 10 SS94082OOOO
4 — 10 SS94083OOOO
MNA1 3 1 10 SS94084OOOO
For contactor type 2 2 10 SS94085OOOO
MN0ac,MN0dc 1 3 10 SS94086OOOO
(Top mounted)
— 4 10 SS94087OOOO
6
Surge Suppressor For Contactor Rated control voltage Qty Wt Catalogue No.
type per approx. per
Packing accessory
Us [No.] [Kg]
MN0 ac 24 - 48V 5 0.022 SS94623 JOOO
110 - 240V SS94623 BOOO
360 - 415V SS94623 DOOO
MN0 dc 24 - 48Vdc SS947815OOO
MNS1/S2 110 - 220Vdc SS947812OOO
Mechanical Interlock For Contactor type Qty Wt Catalogue No.
per approx. per
Packing accessory
[No.] [Kg]
MN0dc 1 — SS94766OOOO
Auxillary Contact Block Ie Auxiliary contact Qty Wt Catalogue No.
AC-15 combinations per approx.per
415V,50Hz Packing accessory
4 1 10 0.005 SS92020OOO
[No.] [Kg]
www.LNTEBG.com 6/13
SPARES
AC operation
6 DC operation
MN0 10 — SS94651….
MN0DC
MN0 1)
MN0 DC 1)
Coils at 50 Hz
www.LNTEBG.com 6/15
CONTACTORS - TYPE MR
SINGLE POLE CONTACTORS
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1
AC operation
6
25 40 3.7 — — — ---- 1 0.25 CS 94052....
MR1
CONTACTORS - TYPE MU
RUGGED POWER CONTACTORS
Conformance to IS 13947 (Part 4/Sec.1) and IEC:60947-4-1
AC operation
6/16 www.LNTEBG.com
SPARES
AC operation
MU1/MU2
AC operation
MC 01/02/03
25 50 30 1 1 1 0.84 CS94047….
1) 1)
35 63 40 1 1 1 0.84 CS94048….
MC 11/12
45 80 50 1 1 1 1.24 SS94977….
1) 1)
65 100 62.5 1 1 1 1.24 SS94978….
MC 21/22
MC 31/32/33
MC 88/99
1 — 10 0.03 SS94715OOOO
— 1 10 SS94716OOOO
4 10 2 — 10 SS94080OOOO
1 1 10 SS94081OOOO
— 2 10 SS94082OOOO
000000
4 — 10 0.03 SS94083OOOO
3 1 10 SS94084OOOO
4 10 2 2 10 SS94085OOOO
1 3 10 SS94086OOOO
— 4 10 SS94087OOOO 6
1 1 1 0.05 SS94072OOOO
4 10 1 1 1 SS94073OOOO
1 1 1 SS94090OOOO
MC 01, MC02, MC03 1 1 1 SS94092OOOO
4 10 1 1 1 0.01 SS94072OOOO
SS94073OOOO
1 1
_
4 10 1 1 0.01 SS94074OOOO
_
1 SS94075OOOO
MU - A1
6
Mechanical For Contactor type Qty Wt Catalogue No.
Interlock per approx. per
Packing accessory
MU 1, MU 2 MU 1, MU 2 1 0.45 CS94197OOOO
AC operation
MC 01/02/03
6
MC 11/12
MC 21/22
MC 31/32/33
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -20 to +55 -20 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 — —
Hold-on VA 11 11 11 15 15
6/22 www.LNTEBG.com
TECHNICAL DATA - TYPE MNX
MNX 45/50/70/80 CONTACTORS
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -20 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 2x2.5
www.LNTEBG.com 6/23
TECHNICAL DATA - TYPE MNX
MNX 95/110/140 CONTACTORS
o
Service temperature C -20 to +55 -20 to +55 -20 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5
6/24 www.LNTEBG.com
TECHNICAL DATA - TYPE MNX
MNX 185/225 CONTACTORS
60%
60%
Aux.terminal capacity
Wires(mm2) 2 x 2.5 2 x 2.5
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -5 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 2x2.5
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -20 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 2x2.5
www.LNTEBG.com 6/27
TECHNICAL DATA - TYPE MN (CAPACITOR DUTY)
MN 16C/32C CONTACTORS
MN 16C MN 32C
o
Service temperature C -20 to +55 -20 to +55
6/28 www.LNTEBG.com
TECHNICAL DATA - TYPE ML
ML0/1/1.5/2/3 CONTACTORS
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -20 to +55 -20 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 2x2.5 2x2.5
www.LNTEBG.com 6/29
TECHNICAL DATA - TYPE ML
ML4/6/10/12 CONTACTORS
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -20 to +55
Aux.terminal capacity
Wires(mm2) 2x2.5 2x2.5 2x2.5 2x2.5
6/30 www.LNTEBG.com
TECHNICAL DATA - TYPE MM
MM CONTACTORS
o
Service temperature C -20 to +55 -20 to +55 -20 to +55 -20 to +55
www.LNTEBG.com 6/31
TECHNICAL DATA - TYPE MN
MN 0 CONTACTORS
MN0 ac MN0 dc
o
Service temperature C -20 to +55 -20 to +55
6/32 www.LNTEBG.com
TECHNICAL DATA - TYPE MU
MU1/2 CONTACTORS
MU1 MU2
o
Service temperature C -5 to + 55 -5 to + 55
Aux.terminal capacity
Wires(mm2) — —
Hold-on VA 22 22
www.LNTEBG.com 6/33
TECHNICAL DATA - TYPE MC
MC 01/02/03/11/12 CONTACTORS
o
Service temperature C -20o to 55o -20o to 55o -20o to 55o -20o to 55o -20o to 55o
Aux.terminal capacity _ _ _ _ _
Wires(mm2)
Hold-on VA 11 11 22 22 22
o
Service temperature C -20o to 55o -20o to 55o -20o to 55o -20o to 55o -20o to 55o
Aux.terminal capacity _ _ _ _ _
Wires(mm2)
Hold-on VA 22 22 36 36 36
MR1
o
Service temperature C -5 to 55
Aux.terminal capacity —
Wires(mm2)
Hold-on VA 9
6/36 www.LNTEBG.com
ELECTRICAL LIFE CURVES - TYPE MNX
MNX CONTACTORS
www.LNTEBG.com 6/37
ELECTRICAL LIFE CURVES - TYPE MNX
MNX CONTACTORS
6/38 www.LNTEBG.com
ELECTRICAL LIFE CURVES - TYPE ML
ML CONTACTORS
www.LNTEBG.com 6/39
ELECTRICAL LIFE CURVES - TYPE ML
ML CONTACTORS
6/40 www.LNTEBG.com
TERMINAL ARRANGEMENTS - TYPE MNX
POWER CONTACTORS
Note: For ML, MC, MU and MR contactors the terminal arrangements available on request.
www.LNTEBG.com 6/41
TERMINAL ARRANGEMENTS - TYPE MN
CAPACITOR CONTACTORS
Note: For MNX-A33S-2 and MNX-A46S-2 auxiliary contact block terminal arrangements refer page 6/31 shown adjacent to contactor terminal
adjustments.
i.e. for 1NO+1NC left - 13, 21, 22, 14
1NO+1NC right - 43, 31, 32, 44
1NO+1NC second left - 53, 61, 62, 54
1NO+1NC second right- 83, 71, 72, 84
6/42 www.LNTEBG.com
TERMINAL ARRANGEMENTS
CONTROL CONTACTORS
MN0/MN0DC-40E
MN0/MN0DC-22E
Note: For control contactors MM00 and MM01 (AC/DC) terminal arrangements available on request.
www.LNTEBG.com 6/43
OVERALL DIMENSIONS
MNX 9, 12, 18 CONTACTORS
MN 32C CONTACTORS
50
147
136
120
99.7
6
10
2
35
60-70 45
81
POSIBILITY OF MOUNTING ON
TH35-7.5 RAIL AS PER IS : 11039
MN 0 ac CONTACTORS
52
113
102
86
65
6
65-70 35
2
81 45
ML6 CONTACTORS
MM00 CONTACTORS
MC 11, MC 12 CONTACTORS
MN 25W CONTACTORS