Parallel Operation of DC Generators
Parallel Operation of DC Generators
Parallel Operation of DC Generators
• Reliability: The generators that are sources of power are primary safety items, and hence paralleled for
OF DC GENERATORS • Efficiency: The load is not uniform. It is maximum during the ON-peak hours and minimum during Off-peak
hours. The generators must operate most efficiently during full-load condition. It is preferred to use a single
Dr. S. THANGALAKSHMI • Continuity of service: Un-interrupted power supply is most important thing to satisfy the customers. If one
generator is used, it becomes impossible to deliver un-interrupted power supply during its maintenance hours
or breakdown.
of order. 3. Easy to Maintain:- The routine maintenance of generator is required time to time. But for that
supply of power cannot be obstructed. In parallel generators the routine check-up could be done one
by one.
4. Easy to Increase Plant Capacity:- The demand of electricity is increasing day by day. To meet the
requirement of power generation, additional new unit can run paralleled with the running units.
1
23-Sep-19
situations.
4. The change of voltage with the change of load must be the same character.
2
23-Sep-19
3. The circuit breaker V2 (voltmeter) connected across the open switch S2 is closed to
CONNECTION OF PARALLEL DC GENERATORS
complete the circuit. The excitation of the generator 2 is increased with the help of
field rheostat till it generates voltage equal to the voltage of bus-bars.
4. The main switch S2 is then closed and the generator 2 is ready to be paralleled with
existing generator. But at this point of time generator 2 is not taking any load as its
induced e.m.f. is equal to bus-bar voltage. The present condition is called floating, that
means ready for supply but not supplying current to the load.
5. In order to deliver current from generator 2, it is necessary that its induced e.m.f. E
should be greater than the bus-bars voltage V. By strengthening the field current, the
induced e.m.f. of generator 2 could be improved and the current supply will get
started. To maintain bus-bar voltage, the field of generator 1 is weakened so that value
remains constant.
3
23-Sep-19
It is generally desired to keep the bus bars voltage constant. This can be achieved by
The value of current output depends upon the values of E1 and E2 which could be managed by field
adjusting the field excitations of the generators operating in parallel.
rheostats to keep the bus-bars voltage constant.
4
23-Sep-19
current in the two machines will be in the direction shown in Fig. (ii). After Instead, DC series motors are arranged in parallel to operate as DC series
machine 2 changes from a generator to a motor, the current in the shunt field will generators during Electric Braking.
remain in the same direction, but the current in the armature and series field will
reverse.
5
23-Sep-19
During braking the motors continue to run due to the kinetic energy of train and act as self-
The kinetic energy is converted into heat and dissipated in the resistors. This is how DC
PARALLEL OPERATION OF SERIES GENERATOR When the induced EMFs E1 and E2 are equal they will share the equal load.
There is a problem when induced EMFs are different in the two machines. When one of the
For satisfactory parallel operation of dc series generators, it is necessary to connect the
induced emf becomes greater than another induced emf a circulating current will flow.
armatures of the two machines through a heavy copper bar, called the equalizing bar. It is
explained below :
6
23-Sep-19