Transductor de Corriente
Transductor de Corriente
APPLICATIONS
• Ideal for use in enclosures with dimensional constraints.
• Designed for industrial environments.
• OEM measurement systems.
• Designed for use with OSI current transformers. Transducer output is derived from the average absolute value of
• Easily integrated into control systems. the input and calibrated as the RMS value of a sine wave input.
* Models are self-powered from measured AC input line with ORDERING INFORMATION
DIP-switch-selectable 0-1mA, 0-5Vdc, or 0-10Vdc output.
** Denotes 4-20mA loop-powered unit, requires 15-40Vdc instrument Example: 0-5A Input with 4-20mA Output.
power. MCT5-005E
Standard 4-20mA models require 85-135 Vac instrument power.
Specifications
INPUT INSTRUMENT POWER
Current.........................................................See Table “E” models..... (4-20mA)....... 85-135Vac, 50-60Hz, 3VA
Frequency Range.................... 48 to 65Hz; 60Hz Nom. “E2” models... (Loop-Powered 4-20mA)....... 15-40Vdc
Burden........................ 1-Amp models................0.05VA “A” models.............................................. Self-Powered
................................ 5-Amp models..............0.175VA
Current Overload ACCURACY
Continuous......................................... 2 X F.S. rating Accuracy......................................±0.25% F.S.@ 60Hz
10s/hr............................................... 10 X F.S. rating .................. Includes effects of linearity and setpoint.
Output Ripple..............................................<1.0% F.S.
Dielectric Test
Input/Output...................................................1500Vac Temperature
OUTPUT Effect
Response..........(to 99%)................................... 400ms “A” & “E2” models...(-20ºC to +65ºC)...............±1.0%
Field-Adjustable Span...........................................±5% “E” models.............. (-20ºC to +40ºC)..............±1.0%
Loading
“A” models set for 0-1mA output...................0-10KΩ PHYSICAL
“A” models set for 0-5Vdc output.................... >5MΩ Termination...................... wire size 22AWG to 12AWG
“A” models set for 0-10Vdc output................ >10MΩ Net Weight........................................................... 0.4 lb
“E” models......(4-20mA)................................0-500Ω
“E2” models....(Loop Powered 4-20mA)........ 0-600Ω
- + - +
OUTPUT OUTPUT
+ + + +
OUTPUT RL 15-40Vdc OUTPUT RL 15-40Vdc
- - - -
- + - +
OUTPUT INST OUTPUT INST
POWER POWER
ZERO
3.37
3.56
2. Make sure electrical service is disconnected before making any electrical connections.
3. Branch circuit protection is required to be provided in accordance with the National and Local codes of
the inspection authority.
4. Route wires as required and secure to terminals per connection diagram on this sheet and on the unit.
OPERATING INSTRUCTIONS
2. Transient overvoltages according to Installation Category (overvoltage category) II, pollution Degree 2.
3. The output signal is intended to be "Not accessible to the user." To prevent contact with live circuits, the
transducer is required to be mounted in an enclosure that requires the use of a tool for access.
4. If cleaning of the exterior surface is necessary, de-energize all services of supply (both measuring and
instrument power circuits) and brush with a soft brush or blow off with low-pressure air. Use appropriate
eye protection. Not suitable for hose-down cleaning.
5. Maximum relative humidity 80 percent for temperatures up to 31ºC decreasing linearly to 50 percent
relative humidity at 40ºC.
6. Maximum operating temperature range is -20ºC to 65ºC (-20ºC to 40ºC for "E" suffix models).
WARRANTY STATEMENT
Ohio Semitronics Inc. warrants this unit to be free of defects in material and workmanship for a period of five
years from date of shipment. This unit must not be used in any manner other than as specified in this document.