Report
Report
OUT AT
POWERGRID CORPORATION OF INDIA LIMITED
GURUGRAM, HARYANA
SUBMITTED BY:
SHREYANSH SINGH
B.TECH (Electrical Engineering)
Manipal University Jaipur,Jaipur
CONTENTS:-
1.1.4 Thyristors
Since 1977, new HVDC systems have used only solid-state devices, in most
cases thyristor valves. Like mercury arc valves, thyristors require connection to an external AC
circuit in HVDC applications to turn them on and off. HVDC using thyristor valves is also
known as Line-Commutated Converter (LCC) HVDC.
Development of thyristor valves for HVDC began in the late 1960s. The first complete HVDC
scheme based on thyristor valves was the Eel River scheme in Canada, which was built
by General Electric and went into service in 1972.
On March 15, 1979, a 1920 MW thyristor based direct current connection between Cabora
Bassa and Johannesburg (1,410 km) was energized. The conversion equipment was built in 1974
by Allgemeine Elektricitäts-Gesellschaft AG (AEG), and Brown, Boveri & Cie (BBC)
and Siemens were partners in the project. Service interruptions of several years were a result of
a civil war in Mozambique.The transmission voltage of ±533 kV was the highest in the world at
the time.
There are several configurations to browse when planning and arranging of HVDC system and
the most normally and commonly used HVDC configurations are:
a. Back-to-back system configuration
b. Monopolar system configuration
c. Bipolar system configuration
An HVDC converter converts electric power from high voltage alternating current (AC) to high-
voltage direct current (HVDC), or vice versa. HVDC is used as an alternative to AC for
transmitting electrical energy over long distances or between AC power systems of different
frequencies. HVDC converters capable of converting up to two gigawatts (GW) and with voltage
ratings of up to 1,100 kilovolts (kV) have been built, and even higher ratings are technically
feasible. A complete converter station may contain several such converters in series and/or
parallel.
Most of the HVDC systems in operation today are based on line-commutated converters. The
basic LCC configuration uses a three-phase bridge rectifier or six-pulse bridge, containing six
electronic switches, each connecting one of the three phases to one of the two DC rails. A
complete switching element is usually referred to as a valve, irrespective of its construction.
However, with a phase change only every 60°, considerable harmonic distortion is produced at
both the DC and AC terminals when this arrangement is used.
Fig.4 Thyristor valve stacks for Mono-Pole of the HVDC Inter-Island between the North
and South Islands of New Zealand. The man at the bottom gives scale to the size of the
valves.
Each thyristor valve will typically contain tens or hundreds of thyristor levels, each operating at a
different (high) potential with respect to earth. The command information to turn on the
thyristors therefore cannot simply be sent using a wire connection – it needs to be isolated. The
isolation method can be magnetic but is usually optical. Two optical methods are used: indirect
and direct optical triggering. In the indirect optical triggering method, low-voltage control
electronics send light pulses along optical fibres to the high-side control electronics, which
derives its power from the voltage across each thyristor. The alternative direct optical triggering
method dispenses with most of the high-side electronics, instead using light pulses from the
control electronics to switch light-triggered thyristors (LTTs), although a small monitoring
electronics unit may still be required for protection of the valve.
In a line-commutated converter, the DC current (usually) cannot change direction; it flows
through a large inductance and can be considered almost constant. On the AC side, the converter
behaves approximately as a current source, injecting both grid-frequency and harmonic currents
into the AC network. For this reason, a line commutated converter for HVDC is also considered
as a current-source inverter.
The controllability of a current-flow through HVDC rectifiers and inverters, their application in
connecting unsynchronized networks, and their applications in efficient submarine cables mean
that HVDC interconnections are often used at national or regional boundaries for the exchange of
power (in North America, HVDC connections divide much of Canada and the United States into
several electrical regions that cross national borders, although the purpose of these connections is
still to connect unsynchronized AC grids to each other). Offshore windfarms also require
undersea cables, and their turbines are unsynchronized. In very long distance connections
between two locations, such as power transmission from a large hydroelectric power plant at a
remote site to an urban area, HVDC transmission systems may appropriately be used; several
schemes of these kind have been built. For interconnections to Siberia, Canada, India, and
the Scandinavian North, the decreased line-costs of HVDC also make it applicable.
It is mainly concerned with the production of electrical power and its transmission from the
sending end to receiving end as per requirements, incurring a minimum amount of losses. The
power often changes due to the variation of load or due to disturbances.
For these reasons, the term power system stability is of utmost importance in this field. It is
used to define the ability of the system to bring back its operation to steady state condition within
a minimum possible time after having undergone any transience or disturbance. Ever since the
20th century, till the recent times, all major power generating stations over the globe has mainly
relied on AC system as the most effective and economical option for generation and transmission
of electrical power.
In power plants, several synchronous generators are connected to the bus having the same
frequency and phase sequence as the generators. Therefore, for a stable operation, we have to
synchronize the bus with the generators over the entire duration of generation and transmission.
For this reason, the power system stability is also referred to as synchronous stability and is
defined as the ability of the system to return to synchronism after having undergone some
disturbance due to switching on and off of load or due to line transience. To understand, stability
well, another factor needs to be considered, and that is the stability limit of the system. The
stability limit defines the maximum power permissible to flow through a particular part of the
system for which it is subjected to line disturbances or faulty flow of power.
The power transfer capability of long AC transmission lines is generally limited by large signal
stability. The development of effective ways to utilize transmission system close to its thermal
limit has attracted much attention recently.
The central purpose of conventional HVDC transmission is to transfer a specific amount of
electric power in one node to another and to offer the fast controllability of real power transfer. If
the HVDC link is operated in parallel with a crucial AC line the load-flow of the AC line could
be controlled directly. The HVDC link can therefore be employed for improving stability.
HVDC links, under traditional controls, don't provide synchronizing or damping effects in a
reaction to disturbance on AC side. However, the capacity of an HVDC connect to rapidly
modulate the power flow, in response to manage signals, has been utilized for some time to
enhance the stability of AC-DC systems.
Because HVDC allows power transmission between unsynchronized AC distribution systems, it
can help increase system stability, by preventing cascading failures from propagating from one
part of a wider power transmission grid to another. Changes in load that would cause portions of
an AC network to become unsynchronized and to separate, would not similarly affect a DC link,
and the power flow through the DC link would tend to stabilize the AC network. The magnitude
and direction of power flow through a DC link can be directly controlled, and changed as needed
to support the AC networks at either end of the DC link. This has caused many power system
operators to contemplate wider use of HVDC technology for its stability benefits alone.
Stability in a power system refers to the ability of a power system to maintain a connected
generator in synchronism after the system has been subjected to a major disturbance such as
transmission system faults. The stability control strategy is based on fast balancing of the
accelerating energy. The driving mechanical power must be balanced by the electrical power to
keep the system in synchronism. This is performed by controlling the power through the HVDC.
The equal area criteria for stability study may be adopted to assess the stability limit of the
system.We know that the system becomes unstable for high value of pre-fault power i.e;
Ptotal(=Pm), which is equal to the mechanical power input. If the fault clearing time is not very
fast then the corresponding angle becomes larger than the critical angle and the system becomes
unstable. HVDC links, under traditional controls, do not provide synchronizing or damping
effects in response to disturbance on AC side. However, the controllability of an HVDC link is
inherently fast and this can be used to modulate the power flow after the fault clearance for
producing sufficient decelerating energy to improve the stability.
Fig.8 showing how HVDC improves system stability.
(Blue line in the fig indicates when HVDC is not connected whereas red line shows when
HVDC is connected to the system)
The power system is dependent of a stable and reliable control of active and reactive power to
keep its integrity. Loosing this control may lead to a system collapse. Voltage Source Converter
transmission system technology such as HVDC has the advantage of being able to almost
instantly change its working point within its capability curve. This can be used to support the
grid with the best mixture of active and reactive power during stressed conditions. In many cases
is a mix of active and reactive power the best solution compared to active or reactive power only.
VSC transmission systems can therefore give added support to the grid. For asynchronous in-
feed, active power modulation damp ~4 times better than reactive power modulation and that
local load ability can increase with ~2 times installed converter MVA size. In a parallel case
where the VSC transmission system is connected in parallel with the AC system, the VSC
transmission system can damp ~2-3 times better than reactive shunt compensation and increase
loading ability ~1.5 times installed MVA converter size. The benefits with a VSC transmission
system during a grid restoration can be considerable since it can control voltage and stabilize
frequency when active power is available in the remote end. The frequency control is then not
limited in the same way as a conventional power plant where boiler dynamics may limit the
operation during a grid restoration.
The transmission capacity and converter sizes of a VSC transmission system are becoming large
enough to also play a role in system stability improvement. Different applications will make
good use of the high controllability of active and reactive power considerably improving system
stability. In case of asynchronous infeed of power where the two ends of a VSC transmission
system do not have any mutual coupling the control of the VSC transmission can improve
stability further in the connection point. Criterions like (N-1) or similar are used to establish the
maximum amount of load that a critical grid section can transfer. If a large generator or
transmission line trips, the VSC transmission can change its operating mode and temporary
strengthen the grid until other remedial actions restore grid security. Many HVDC links are
connected between asynchronous grids operating with different frequency. In the connection
point where active power is fed into the AC grid VSC transmission can add improved
performance.
Fig.9 showing how VSC improves system stability with Q control, P control and Mixed
control.
3.4 Conclusion
The power through the HVDC helps to make the system more stable during disturbances. In case
of LCC (Line Commutated Converters) the power flow in the HVDC link is modulated by the
addition of an auxiliary signal to the current reference of the rectifier firing angle controller to
enhance the stability in power system.
In case of VSC (Voltage Source Converters) the best support from a VSC transmission system is
provided for various stability problems using a mixture of active and reactive power control. A
VSC DC transmission system is able to support the AC grid with a suitable power factor and
modulation of power transfer through VSC HVDC and hence thus improves stability.
Therefore, from above discussion we can clearly see how HVDC helps to improve
power system stability.