CPC 100 User Manual v1.43
CPC 100 User Manual v1.43
CPC 100 User Manual v1.43
Asia, Pacific
OMICRON electronics Asia Ltd.
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 2634 0377
E-Mail: [email protected]
This manual is a publication of OMICRON electronics GmbH. Web: www.omicron.at
All rights including translation reserved. Reproduction of any kind, for example, photocopying, North and South America
microfilming, optical character recognition and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON electronics. Reprinting, wholly or in part, is not OMICRON electronics Corp. USA
permitted. 12 Greenway Plaza, Suite 1510
Houston, TX 77046, USA
The product information, specifications, and technical data embodied in this manual represent
the technical status at the time of writing and are subject to change without prior notice. Phone: +1 713 830-4660 or 1 800 OMICRON
We have done our best to ensure that the information given in this manual is useful, accurate E-Mail: [email protected]
and entirely reliable. However, OMICRON electronics does not assume responsibility for any Web: www.omicronusa.com
inaccuracies which may be present.
The user is responsible for every application that makes use of an OMICRON product. For addresses of OMICRON offices with customer service centers, regional sales offices or
OMICRON electronics translates this manual from the source language English into a number offices for training, consulting and commissioning, please see our website.
of other languages. Any translation of this manual is done for local requirements, and in the
event of a dispute between the English and a non-English version, the English version of this
manual shall govern.
Preface Introduction Quick Current Voltage Transformer Resistance Others Common Technical Data CP TD1 CP CU1 CP SB1 CP CB2
Transformer Transformer Functions
Preface
CPC 100 V 1.43
About this User Manual Safety Instructions for the CPC 100 and its Accessories
The purpose of this User Manual is to get you started quickly. It guides you directly to the various Orderly Measures
Caution: The CPC 100 must be used in observance of all existing safety require-
CPC 100 application fields, shows the typical test setup, the corresponding CPC 100 test card,
ments from national standards for accident prevention and environmental protec- • This User Manual only complements the CPC 100 Reference Manual available in PDF
and outlines the parameters used for this test in a compact form.
tion. format on the CPC 100 Toolsets and the CPC 100 Start Page. However, it does not replace
Since the scope of this User Manual is confined to the most important information about a it.
specific subject, the CPC 100 User Manual complements the CPC 100 Reference Manual, Before operating the CPC 100, read the following safety instructions carefully. It is not • Either this User Manual or the CPC 100 Reference Manual should always be available on
however, it does not replace it. The CPC 100 Reference Manual is available in PDF format on recommended that the CPC 100 be used (or even turned on) without understanding the the site where the CPC 100 is being used.
the CPC 100 Toolsets and the CPC 100 Start Page. information in this manual. If some points of the safety instructions are unclear, contact • Personnel assigned to use the CPC 100 should carefully read the CPC 100 User Manual/
OMICRON electronics. Reference Manual - in particular the section on safety instructions - before beginning to work
Reading the CPC 100 User Manual alone does not release the user from the duty of complying
with all national and international safety regulations relevant for working with the CPC 100, for with it. On principle, this also applies to personnel who only occasionally work with the
example, the regulation EN50191 "Erection and Operation of Electrical Test Equipment" as well Principle Use According to Regulations CPC 100.
as the applicable regulations for accident prevention in the country and at the site of operation. • The CPC 100 should only be used in a safe manner, mindful of the dangers while paying • Do not undertake any modifications, extensions, or adaptations to the CPC 100.
attention to the User Manual, and when it is in a technically sound condition and when its • Use the CPC 100 in conjunction with original accessories only.
Conventions and Symbols Used use is in accordance with the regulations. In particular, avoid disruptions that could in turn
affect safety. Operator Qualifications and Primary Responsibilities
In this manual, the following symbols indicate paragraphs with special safety relevant meaning:
• DANGER: If you have a cardiac pacemaker, do not use the CPC 100! Before operating the
Symbol Description CPC 100, make sure there is no person with a cardiac pacemaker in the immediate vicinity. Warning: Testing with the CPC 100 should only be performed by authorized and
• The CPC 100 is exclusively intended for the application fields specified in detail in qualified personnel. Clearly establish the responsibilities.
Equipment damage or loss of data possible.
”Designated Use” on page Preface-4. Any other use is deemed not to be according to the
regulations. The manufacturer/distributor is not liable for damage resulting from improper Personnel receiving training, instruction, direction, or education on the CPC 100 should remain
usage. The user alone assumes all responsibility and risk. under the constant supervision of an experienced operator while working with the equipment.
Personal injury or severe damage to objects possible. • Following the instructions provided in this User Manual and in the CPC 100 Reference
Manual available in PDF format on the CPC 100 Toolsets and the CPC 100 Start Page is Safe Operation
also considered part of being in accordance with the regulations. When putting the CPC 100 into operation, follow the instructions in section "Putting CPC 100
• Do not open the CPC 100 housing. into Operation" in the CPC 100 Reference Manual (available in PDF format on the
• If you do not use the CPC 100 anymore, turn the safety key to "lock" (vertical) and remove CPC 100 Toolsets or the CPC 100 Start Page).
the key to avoid anybody accidentally turning on the CPC 100.
• Store key and the CPC 100 separately to prevent unauthorized personnel from using the Note: Never use the CPC 100, any accessory or the CP TD1 equipment trolley without a solid
CPC 100. connection to earth with at least 6 mm². Use a ground point as close as possible to the test
object.
Preface - 1
CPC 100 V 1.43
Preface - 2
Preface
CPC 100 V 1.43
If a test object with a big inductance was connected to the CPC 100, short-out the test object
additionally before disconnecting it from the CPC 100.
Warning: Use separate clamps for current and voltage connections on both sides
of the test object to avoid hazards in case one clamp falls off during the test.
Preface - 3
CPC 100 V 1.43
Designated Use
Changing Fuses CPC 100 in Combination with the CP TD1 The CPC 100, in conjunction with its accessories or as a stand-alone unit, is a multi-
• Turn off the CPC 100, unplug the power cord and/or press the Emergency Stop button. purpose primary test set for commissioning and maintaining substation equipment. It
The CP TD1 is an optionally available high-precision test system for on-site insulation tests of
• We recommend to wait for about 30 seconds. This time is necessary for the internal performs current transformer (CT), voltage transformer (VT) and power transformer (TR)
high-voltage systems like power and measuring transformers, circuit breakers, capacitors and
electrolytic capacitors to fully discharge. tests. Furthermore, it is used for contact and winding resistance testing, polarity checks as
isolators. The CP TD1 works as an add-on device to the CPC 100 and is described in chapter
• Ground the test object, and disconnect it from the CPC 100. By disconnecting it, you prevent ”CP TD1” of this User Manual. well as primary and secondary protection relay testing.
a possibly faulty test object feeding power back into the CPC 100.
On principle, the safety instructions that apply to the CPC 100 and its accessories also apply to The various, partly automated tests are defined and parameterized via the front panel control of
• Locate the blown fuse on the front panel of the CPC 100, and replace it.
the CP TD1. However, the CP TD1 requires some additional precautions and measures. They a built-in embedded PC.
Note: Replace with identical fuse type only (refer to the chapter "Changing Fuses" of the are listed in chapter ”CP TD1” on page CP TD1-1. The functionality scope of the CPC 100 is described in detail in the chapter "Designated Use" of
CPC 100 Reference Manual available in PDF format on the CPC 100 Toolsets or the CPC 100
the CPC 100 Reference Manual available in PDF format on the CPC 100 Toolset CD-ROM or
Start Page).
Different Symbols for PE the CPC 100 Start Page.
The CPC 100 and CP TD1 use different symbols for protective earth (PE): Note: Any other use of the CPC 100 but the one mentioned above is considered improper use,
and will not only invalidate all customer warranty claims but also exempt the manufacturer from
its liability to recourse.
This is due to a new standard and does not symbolize any functional difference.
Note: Both symbols mean exactly the same, i.e., protective earth (PE) or equipotential ground.
Preface - 4
Preface
Introduction
CPC 100 V 1.43
Fuse 6.3A T (slow-acting wire fuse 5x20 mm) Test Procedure Overview: Provides an
for 3A AC, 6A AC, 130V AC and 6A DC enhanced overview of all test cards of the currently
active test procedure. Defines the test procedure
AC OUTPUT default.
6A, 3A or 130V output
File Operations: Lets you save, load, delete, copy
Fuse 3.15A (slow-acting wire fuse 5x20 mm) and rename test procedures.
for 3A AC and 130V AC Options: To specify general parameters.
V1 AC input V2 AC input
300V AC input 3V AC input Context-dependent menu keys
Directly invoke specific commands associated with the
DC OUTPUT currently selected control of the test card and view.
6A DC output (fuse-protected with a 6A fuse)
Introduction - 1
CPC 100 V 1.43
Introduction - 2
Introduction
CPC 100 V 1.43
CPC 100 Block Diagram Principles of Test Cards and Test Procedures The Components of a Test Card
Ext. Test Cards Focus on the data entry field for AC current.
Booster
The CPC 100 software comprises a number of test cards. A test card carries out one specific The term "focus" designates the currently selected (active) part of the test card. The selected
Rectifier
& power test, e.g., measuring a CT excitation curve, or testing the ratio of a voltage transformer. component is highlighted or inverted.
factor +
corrector
500V A test card holds a number of user-definable test settings and - after the test was run - test The actual function of the context-dependent
R
500V results. menu keys depends on the selected view, test
2kV mode, test card and selected test card
500V 500V 4A
Switched 1kV 2A
R
Test Procedure component (i.e., the focus).
2kV 1A
mode 500V
amplifier A test procedure contains multiple test cards.
Temperature and power consumption
L
Mains The composition of such a test procedure and the settings of all single test cards can be freely monitoring.
100-240V Filter defined by the user. Within a test procedure, each test card and its associated test is executed If an output is activated, both the CPC 100’s
50/60Hz I individually in a user-defined order. power consumption and the current emitted at
65V 130V / 6A AC
N 2kV
U O the high-current outputs is monitored and,
65V
PE I 800A u Report together with the temperature, displayed by this
3.15A t temperature gauge.
ADC U
p For archiving or reporting purposes, or later processing, a test procedure with all of its test cards, Status of test assessment. The test
6.3A The temperature gauge’s bar therewith
U 65V / 6A DC
u specific settings and - after the test was run - test results and assessments can be saved. It is assessment is a manual procedure carried represents an indicator for the remaining time
DSP I t then considered a report. out by the user. After the test, set the focus
(Digital the CPC 100 can output power.
Signal
U
s Such a report can later be opened any time in the CPC 100’s File Operations menu. on the assessment symbol. Use the context-
Processor)
dependent menu key OK or Failed to assess plenty of spare
6V / 800A AC Note: For detailed information about test cards, test procedures and templates, refer to section
the test. no more spare
"How to Use The CPC 100 Software" of chapter "Introduction" in the CPC 100 Reference
For a few seconds, the status line also
Manual available in PDF format on the CPC 100 Toolsets or CPC 100 Start Page.
+ displays general operation information, e.g.
Ethernet
5V / 400A DC "Emergency key pressed".
-
to 300V AC
RS 232 Built-in
ext.
ePC 3V AC I Pressing the Settings menu key opens the Settings page (see page Quick-1) allowing you to
PC optional 10A AC/DC
n
10V DC set the test cards individually. As a rule, do not set the test cards on the Settings page but set
BIN IN p.
all test cards of a test procedure using the Device Setup tab in the Options view (see page
optional analog or digital interfaces Introduction-5).
(plug-in boards)
Introduction - 3
CPC 100 V 1.43
The Menus
The Test Procedure Overview lists all test cards of the currently active test procedure in a list
Opens the submenu Edit (refer to “Submenu Edit” on page 5)
box showing the card’s name, its creation date and time, whether test results are available and
the test card’s assessment status.
The CPC 100 file system differentiates two file types: Saves the currently open test, i.e., the test card(s) previously opened in the Test
Card View (refer to Note below).
With Save As Default, Test Procedure Overview provides a function to save the
current test procedure as the test procedure default, i.e., that default the CPC 100 name.xml A test procedure with all of its test cards and specific settings. An .xml file Opens the String Editor. You can save the currently open test under a new name
software will start with in future. may also contain test results and assessments that were stored together of your choice (15 characters max.).
with the settings as report in the CPC 100 file system for archiving
Note: For detailed information refer to section "Test Procedure Overview" of chapter purposes. Use the handwheel or the Up / Down keys to select a test, and press Open to open
"Introduction" in the CPC 100 Reference Manual available in PDF format on the it. Changes to Test Card View.
name.xmt Test procedure template, i.e., a user-defined template containing one or
CPC 100 Toolsets or CPC 100 Start Page.
more test cards with all of their specific test settings but without test Closes the current test card(s), changes to Test Card View and opens the test
results. procedure default.
Introduction - 4
Introduction
CPC 100 V 1.43
Move to the destination folder of your choice. Press Paste to insert the contents of Select the check box if the
Opens the String Editor. You can create a new folder with any name of your choice.
the CPC 100 clipboard to this folder. PE connection is intact and
an error message (313)
Appends the contents of a test file (.xml) or template (.xmt) of your choice to the Press Paste As Templ. to make the contents of the CPC 100 clipboard a test
appears.
currently open test. procedure template.
Operating the CPC 100
(for future use) with the check box
Deletes the currently selected test or folder from the CPC 100’s disk space. selected can cause injury
or possibly death of the
Closes the Edit submenu and returns to the main File Operations menu. operating staff! Resets all user-specific settings made in the
Opens the String Editor that enables you to rename the current test to any new CPC 100 software to factory-defined defaults
name of your choice. including:
Set the default frequency.
(for future use) Note: If a folder is cut or copied to the Clipboard, the selection is recursive, i.e., all of its This value will be used for all • the test card defaults
subfolders will also be put to the Clipboard. test cards. • the test procedure default
Cutting or copying a test or folder, and trying to paste it in the same location, opens the String • all settings made at the Device Setup tab
Closes the submenu and returns to the main File Operations menu. (Sets external booster to CB2, sets CT and
Editor. Auto save automatically
Since a test or folder cannot exist twice under the same name at the same location, determine saves the current test VT to "OFF" and sets the default frequency
a new name for it using the String Editor. settings in fixed intervals to 50 Hz.)
specified to a file named • the String Editor’s template strings
lastmeas.xml.
Introduction - 5
CPC 100 V 1.43
Introduction - 6
Introduction
CPC 100 V 1.43
The command Restore Defaults at the Options tab Device Setup resets all
user-specific settings made in the CPC 100 software to factory-defined defaults.
This includes the test card defaults and the test procedure default.
Introduction - 7
CPC 100 V 1.43
Introduction - 8
Introduction
Quick
CPC 100 V 1.43
Quick - 1
CPC 100 V 1.43
Note that some of the trigger events offered in the Trigger on: combo box depend on the
measured quantity settings below (trigger on measurement).
Trigger on "Overload": the occurrence or the clearing of an output overload condition (clearing
is delayed by 100 ms to debounce).
Quick - 2
Quick
Current Transformer
CPC 100 V 1.43
CTRatio (and Burden) CTRatio (with Burden) - The Option Measure Burden
Use the CTRatio test card to measure a current transformer’s ratio and burden with injection on Select the check box Measure Burden to measure the burden in VA.
the CT’s primary side with up to 800 A from AC OUTPUT. Nominal primary current
Note: This option is only useful as long as the injected current I test is about of the magnitude
Primary Output range Select to stop test automatically when measurement is of the nominal current I prim.
injection current done.
Nominal secondary current
Use current clamp
Actual current rather than IAC
injected into CT’s input*)
primary side
Burden
CT
Burden
CT
Phase angle
relative to Iprim
*) Due to cross-talk between the measuring inputs V1 AC and V2 AC, we suggest not to connect
a current clamp to the input V2 AC. Therefore, use a current clamp with current output. See also
“Device Setup” on page Introduction-5.
Current Transformer - 1
CPC 100 V 1.43
Burden
Output frequency
CT
Actual injection
Burden in VA: I sec nom × current
(V sec act × I sec nom/I sec act) measured via Select to enter
input I AC secondary voltage
cos : cosine of angle between I sec and V sec instead of
measuring it
Secondary
voltage at the
Note: For the meaning of the other test card components, refer to page Current Transformer-1.
burden,
measured at
Cosinus of phase
input V1 AC,
angle
and phase angle Burden in VA: I sec nom ×
relative to Isec (V sec act × I sec nom/I sec act)
Current Transformer - 2
Current
Transformer
CPC 100 V 1.43
Burden
CT graph does not Demagnetization can also be done without recording an excitation curve by
work in Auto pressing the button Demag.
Actual current mode.
To make the context-dependent menu key Demag. visible put the focus onto the test card’s tab.
IEC/BS According to IEC 60044-1, the knee point is defined as the point on the
curve where a voltage increment of 10% increases the current by 50%.
ANSI 45° According to IEEE C57.13, the knee point is the point where, with a double
logarithmic representation, the tangent line to the curve forms a 45° angle.
Applies to current transformer cores without an air gap.
ANSI 30° Like ANSI 45° but forming a 30° angle.
Applies to current transformer cores with an air gap.
Current Transformer - 3
CPC 100 V 1.43
Burden
CT
Burden
CT
Transformer’s
winding
Total elapsed time
resistance
Enable/disable
temperature T meas: Actual ambient temperature
compensation
Off before disconnecting for the result T ref: Temperature for which the result is calculated
device under test R ref: Calculated resistance.
In Centigrade:
Rref = (V DC / I DC) x (235° C + T ref) / (235° C + T meas)
In Fahrenheit:
Rref = (VDC / IDC) x (391°F + Tref F) / (391°F + Tmeas F)
Note: Formula according to IEC 60076-1
Off before disconnecting device under test Note: If n/a appears in the V DC or R meas box, the V DC input is overloaded.
Current Transformer - 4
Current
Transformer
CPC 100 V 1.43
+ If the capacity of the CPOL’s battery gets low, the LEDs start flashing. As long as
Terminates test when testing
the LEDs are flashing, the CPOL’s battery provides sufficient power to continue
time has elapsed flashing working. However, the battery should be changed as soon as possible.
Warning: If you detect a wrong polarity in the current path, turn off the CPC 100
Actual test voltage first, and only then disconnect the terminals.
Actual test current green LED red LED Never operate the CPOL with an open battery compartment. A life-hazardous
The CPC 100 injects a
voltage level may occur in the battery compartment if the CPOL’s probe touches a
special polarity check
signal test point with high-voltage potential!
Highest measured current
polarity polarity checker
checker CPOL CPOL
Time span Vtest is applied to
the output
During the test, the test voltage increases in a ramp characteristic from 0 V to V test. V test is
then applied to the output for the specified time span. The measurements are continuously
taken. Afterwards, V test decreases in a ramp characteristic.
Current Transformer - 5
CPC 100 V 1.43
2. define a pulse duty cycle for the output signal: The preferred method for CT ratio measurement is current injection using the CTRatio test card.
However, on some GIS CTs or bushing CTs on power transformers where the primary current
path is not accessible, the method described in this section is the only solution.
T on: time span the signal is applied to the output To measure the CT ratio using the CTRatioV test card, connect the 2kV AC output to the CT’s
T off: time span the signal output is paused secondary winding and the V2 AC input to the main conductors, e.g. on a power transformer to
the transformer’s bushings of different phases.
Burden
CT
Select output
range
Amplitude
Enter results
manually
Current Transformer - 6
Current
Transformer
CPC 100 V 1.43
Ratio error
Polarity: Ratio Iprim. / Isec.:
Isec act x (Iprim nom/Iprim act)
OK = phase I sec - phase I prim
= - 45 ° < 0 ° < + 45 ° and deviation in %
((Kn x Isec - Iprim)/Iprim) x 100%
NOTOK = all other cases
Note: If the transformer’s knee point voltage is approximated or exceeded, due to the
transformer’s saturation the measurement results are not correct anymore. If the knee point is
extensively exceeded, the transformer can even be damaged.
Therefore, the knee point voltage should be known or measured beforehand.
Current Transformer - 7
CPC 100 V 1.43
*) Note that the current I sec does not really exist in the system. It is a calculated current only.
Current Transformer - 8
Current
Transformer
Voltage Transformer
CPC 100 V 1.43
VTRatio VTBurden
Use the VTRatio test card to measure a voltage transformer’s ratio with injection on the VT’s Use the VTBurden test card to measure a voltage transformer’s secondary burden with voltage
primary side with up to 2 kV from AC OUTPUT. Correction factor Nominal primary voltage injection on the VT’s secondary side with up to 130 V from AC OUTPUT.
for V prim 1/3 and 1/3: Correction factors for V sec To do so, open the circuit as shown in the figure below, and inject the AC voltage from the
CPC 100’s 130V AC output into the burden. Input I AC measures the current that flows into the
Nominal secondary voltage burden, and input V1 AC the voltage at the burden.
A Primary
a injection A
voltage a
Select to stop test
Output automatically
when
Burden
VT frequency
Burden
measurement is VT
done
Measured
n primary voltage
N Select to enter n
secondary voltage N
instead of
Secondary measuring it
voltage
measured at
V1 AC, and its
phase angle Ratio and deviation in %
relative to the
measured Vprim Polarity:
OK = phase I sec - phase I prim
= - 45 ° < 0 ° < + 45 °
NOTOK = all other cases
Voltage Transformer - 1
CPC 100 V 1.43
Burden
VT
*) Due to cross-talk between the measuring inputs V1 AC and V2 AC, we suggest not to connect
a current clamp to the input V2 AC. Therefore, use a current clamp with current output.
Voltage Transformer - 2
Voltage
Transformer
CPC 100 V 1.43
VTElectronics TanDelta
Use the VTElectronics test card to test the ratio of non-conventional electronic voltage The TanDelta test card was especially developed for the CP TD1.
transformers with a very low-level secondary voltage. Correction factor The CP TD1 is an optionally available high-precision test system for on-site insulation tests of
Nominal primary voltage
for V prim high-voltage systems like power and measuring transformers, circuit breakers, capacitors and
Electronic protection relay
1/3 and 1/3: Correction factors for V sec isolators. The CP TD1 works as an add-on device to the CPC 100 and is described in chapter
Electronic voltage transformer with low-voltage input Primary ”CP TD1” of this User Manual.
injection Nominal secondary voltage
Since the TanDelta test card exclusively belongs to the CP TD1, it is also described in the
voltage
Select to stop test CP TD1 Reference Manual.
automatically
The TanDelta test card can be accessed from CT, VT, Transformer and Others test card
Output when
groups.
frequency measurement is
Shielded cable with done
twisted wires
Measured
primary voltage Select to enter
secondary voltage
instead of
Secondary measuring it
voltage
measured at
V1 AC, and its
phase angle
relative to the
Ratio and deviation in %
measured Vprim
Polarity:
OK = phase I sec - phase I prim
= - 45 ° < 0 ° < + 45 °
NOTOK = all other cases
Voltage Transformer - 3
CPC 100 V 1.43
Voltage Transformer - 4
Voltage
Transformer
Transformer
CPC 100 V 1.43
Transformer tap
identifier and tap V sec Actual voltage measured at V1 AC
number for the ° Phase angle of the primary current relative to Vprim
measurements nominal.
in the respective
line of the table :1 Calculated ratio value from the measured values
Vprim / Vsec
% Deviation of the actual ratio from the nominal ratio
Transformer - 1
CPC 100 V 1.43
Transformer - 2
Transformer
CPC 100 V 1.43
B V-W / H2-H3 w-v / X3-X2 B V-(U+W) / H2- v-u / X2-X1 Warning: Connect the CP SA1 discharge box to the CPC 100's V DC input sock-
(H1+H3)
ets to protect yourself and the CPC 100 from high-voltage hazards.
C W-U / H3-H1 u-w / X1-X3
C W-(U+V) / H3- w-v / X3-X2
Dz6 V/H2 w/X3 u/X1 A U-V / H1-H2 v-u / X2-X1 1 (H1+H2)
Transformer - 3
CPC 100 V 1.43
Warning: Never open the measuring circuit while current flows. Dangerous volt- Slope Samples and holds the biggest measured steepness of the falling edge of the
age may occur. actual test current.
Transformer - 4
Transformer
CPC 100 V 1.43
When testing a tap changer, we recommend: After pressing the Auto Keep Result menu key, the CPC 100 waits until stable
• To inject the same current value for each phase. results with a deviation less than the defined tolerance (in %) within the defined
• To perform tests of each phase, start with the lowest tap through to the highest and continue settling time ( t) are achieved. After then, a new result line is added and the next
backwards down to the lowest tap again. Taps may show quite different results depending measurement starts.
on the direction of the tap movement and defects can behave differently. An interruption
caused by a defective tap changer results in comparatively high measured values for ripple Note: If the CPC 100 is in Auto Keep Result status, the user can end the process by either
and slope. pressing Keep Result or by changing to the Tolerance setting and changing the value. The soft
key Set Current Deviation resumes the value of the current deviation in the Tolerance field.
Example: Results of a tap changer and winding resistance test
For the tap changer test, the last two columns of the table are relevant. Performing a Tap Changer Test
High ripple because inductance is 1. Press the I/O (test start/stop) push-button to start the test.
charged
2. Press Keep Result to save the resistance value of this tap or press Auto Keep
Result. In this case, the CPC 100 waits until stable results within the set
Tolerance and t are achieved. After then, a new result line is added showing
Values okay because always in the
the number of the next measured tap.
same range
3. Move to the next position on the tap changer.
4. Repeat steps 2 and 3 for all taps you want to measure.
5. Press the I/O (test start/stop) push-button to stop the test and wait until the
transformer windings are discharged.
Tap defective: significantly higher values for ripple and slope. Compared to the properly
functioning tap change of line 5, for the defective tap in line 7 the ripple is about 30 times and
the slope about 15 times higher. Warning: Before disconnecting the transformer under test, ground all transformer
connections.
Transformer - 5
CPC 100 V 1.43
Transformer - 6
Transformer
Resistance
CPC 100 V 1.43
µ Measurement
The Resistance test card provides a total of three output ranges. The test setup depends on 10 m to 10 10 to 20 k
the selected range.
Setup for a m measurement in the 6A DC range: Setup for an to kmeasurement in the V DC (2 wire) range:
1 µ to 10 m
Setup for a µ measurement in the 400A DC range:
Inject current from the 6A DC output to both sides of the test object. To measure this current,
route it via the I AC/DC input as shown in the figure above. Input V DC measures the voltage
drop, the software calculates the test object’s resistance. At this range, the DC input V DC outputs the current needed to measure the resistance.
Resistance - 1
CPC 100 V 1.43
Burden
Highest possible CT
Smallest resistance
possible
resistance
Select to enter
VDC manually
instead of
measuring it
Actual test
current that is
injected into the
test object
Measured voltage Calculated resistance of test object,
drop at the test object R = V DC / I DC
Resistance - 2
Resistance
CPC 100 V 1.43
RGround
Use the RGround test card to determine earth resistance between a substation’s ground Measuring the Ground Resistance of Small Ground Systems Measuring the Ground Resistance of Large Ground Systems
system and a remote auxiliary electrode. To measure the earth resistance, the CPC 100 injects
AC current between the substation’s ground system and a temporary remote auxiliary electrode.
A second auxiliary electrode is used to measure the voltage potential across the substation’s
earth resistance.
Note: Make sure not to position the auxiliary electrode U too close to the substation’s ground
system. If you do so, you measure in a range where the earth resistance may not be linear (see
figure below).
We suggest to test several points using a longer distance to the substation ground. That way
you get a better understanding of where the linear range of the earth resistance lies, and where
the measurements are reliable.
Theoretical resistance characteristic of an earth electrode: Auxiliary
electrode U 90º
Earth resistance in m
(Bird’s-eye view) > 1km
600 U
500 3...5 x a
Auxiliary
400 linear range of earth resistance electrode I
300
10xa
Auxiliary
200 electrode U
Resistance - 3
CPC 100 V 1.43
RGround
Measuring the Soil Resistivity Calculating the soil resistivity:
=2dR Nominal test current
Legend:
= soil resistivity
Frequency of test current. Select a
d = distance between auxiliary electrodes (identical between all electrodes)
frequency other than the 50 or
R = calculated resistance as indicated at the RGround test card (R(f)) 60Hz mains frequency to prevent
With the spacing of "d", the test measures the average soil resistivity between the U auxiliary interferences by stray earth
electrodes down to a depth of "d". Therefore, varying "d" also varies the depth of the volume for currents.
which the soil resistivity is to be measured.
Caution: The 6A AC output can carry a life-threatening voltage level at high loop
impedances or open measuring circuits.
Note: To learn how to measure the resistance of a single ground rod in an earthing system, refer Actual test current (rms value)
to the CPC 100 Reference Manual, section "RGround" of chapter "Resistance". The CPC 100
Reference Manual is available in PDF format on the CPC 100 Toolsets or the
CPC 100 Start Page.
Auxiliary Auxiliary Auxiliary Auxiliary Measured voltage between
electrode I electrode U electrode U electrode I
U substation ground and the
auxiliary electrode U (rms value, Calculated ohmic part Calculated inductive
non-selective frequency) and of earth impedance part of earth
d d d phase shift between VRMS and (frequency-selective impedance
IRMS. measurement) (frequency-selective
d= distance measurement)
Resistance - 4
Resistance
Others: Sequencer
CPC 100 V 1.43
Others: Sequencer - 1
Others:
Sequencer
CPC 100 V 1.43
100ms 100ms
State 4: "wait for the CB to close"
Long dead time. Set to output 50A*) until the "Overload" trigger
State 2: "wait for the CB to close" t
condition that started state 4 clears.
Short dead time. Set to output 50A until the "Overload" trigger The measurement table shows for state 4 that the long dead time + *) *)
State 1 State 2 State 3 State 4
condition that started state 2 clears. the CB closing time lasted 3.191 s. This time also includes the short long dead time
The measurement table shows for state 2 that the short dead time + additional time to compensate for the debounce (see note). dead time
the CB closing time lasted 477 ms. This time also includes the The actual value for CB close equals 3.191 s - 100 ms = 3.091 s.
additional time to compensate for the debounce (see note). *)Current values < 50A do not initiate an "Overload" when the current
The actual value for CB close equals 477 ms - 100 ms = 377 ms. circuit opens. For this reason, a nominal current value of 50A was chosen
*) State 2 and 4 incl. the additional 100 ms the CPC 100 adds to compensate for the debounce
here, even though the CB is open. (see note above).
Note that the r.m.s. measurement of IOut reacts slow and therefore
the measurement table does not show the full current.
Others: Sequencer - 2
Others:
Sequencer
Others: Ramping
CPC 100 V 1.43
General
Use the Ramping test card to define a series of ramps to be applied to a connected test object.
The feature Manual Trigger provides a possibility to manually initiate a trigger
A series of up to 5 ramps can be defined. The ramps within that series execute sequentially, and signal (i.e., a premature termination) of the current ramp at any time. This manual I
run from a start to an end value within a set period of time. Ramp 2
trigger has the same function as an automatic trigger signal.
200A
It is possible to specify a trigger signal that prematurely terminates either Press the Add Ramp button to define additional ramps. Note that the maximum
• the entire series of ramps possible number of ramps is 5.
• or the actual ramp only, and then continues with the next one (if any).
Ra
mp
Example of a series of ramps
mp
Start value of ramp
Ra
3
Switch off on trigger, i.e., when a trigger condition becomes true
Ramp 1
Ramp 2
Output range selection & actual
Ramp 3
output value
Ramped quantity & fixed quantity The three ramps defined in the ramps table shown above result in an output signal like this: 1A t
0s 5s 15s 20s
Ramps table (ramp-specific
settings):
• output quantity settings
• ramp duration if no trigger Ramp 1 Ramp 2 Ramp 3
occurs • from 1 A • from 200 A • from 200 A
• trigger specification (set at "Start val:") (end value of ramp 1) (end value of ramp 2)
• to end value 200 A • to end value 200 A • to end value 0 A
(set in line 1 column "A") (set in line 2 column "A") (set in line 3 column "A")
• in 5 s • for 10 seconds • in 5 seconds
(set in line 1 column "s") (set in line 2 column "s") (set in line 3 column "s")
Others: Ramping - 3
Others:
Ramping
CPC 100 V 1.43
Others: Ramping - 4
Others:
Ramping
Others: Amplifier
CPC 100 V 1.43
General
Use the Amplifier test card to set the CPC 100 to an "amplifier-like" mode. In this mode, an Starting a high-current output
input signal fed into a synchronization input drives the high-current output’s magnitude, Display of the measured high-current
frequency and phase angle. output signal
Caution: Depending on the measured input signal, setting the amplification factor
Set range
Select between I AC, V1 AC and V2 AC as synchronization inputs. can result in unintentionally high currents. If the magnitude of the input signal is
unknown or uncertain, it is strongly recommended to set the amplification factor to
To prevent saturation, the output signal follows sudden magnitude changes at the
"0" before starting the test.
synchronization input slowly. This smoothening effect delays the follow-up of the output current
up to 250 ms. Measured phase
Set phase angle
Both the "amplification" factor and the phase angle between input and output are set by the user angle between
between input • Set an amplification factor of "0".
in the Amplifier test card. input and output
and output signal • Press I/O (test start / stop) to start the measurement.
signal
Note: Changes in frequency and phase angle may result in unwanted effects. Both frequency
and phase must be held stable. Now the display field shows the measured input value.
Note: The input frequency is limited to a range of 48 ... 62 Hz.
Select • With the measured input value in mind, enter the amplification factor now.
synchronization Value measured • Acknowledge this entry by pressing the handwheel or the Enter key to start the
at output.
synchronization
input (refer
to ”Starting a
high-current
output” in the
Measured input frequency (48 ... 62 Hz) next column).
Set the amplification factor to determine the ratio between input and output signal.
Note: The synchronization input is not automatically range-switching, it is fixed to its maximum
value.
Others: Amplifier - 5
Others:
Amplifier
CPC 100 V 1.43
Test set
CMC 256-3
GPS
synchronization
unit CMGPS
CT 1 CT 2 CT 3
Protection
relay
Others: Amplifier - 6
Others:
Amplifier
Others: Comment
CPC 100 V 1.43
Others: Comment - 7
Others:
Comment
Others: TanDelta
CPC 100 V 1.43
General
The TanDelta test card was especially developed for the CP TD1.
The CP TD1 is an optionally available high-precision test system for on-site insulation tests of
high-voltage systems like power and measuring transformers, circuit breakers, capacitors and
isolators. The CP TD1 works as an add-on device to the CPC 100 and is described in chapter
”CP TD1” of this User Manual.
Since the TanDelta test card exclusively belongs to the CP TD1, it is also described in the
CP TD1 Reference Manual.
The TanDelta test card can be accessed from CT, VT, Transformer and Others test card
groups.
Others: TanDelta - 8
Others:
TanDelta
Common Functions
CPC 100 V 1.43
Test Assessment
The test assessment is a manual procedure carried out by the user. The String Editor is used to name or rename test cards, tests and templates as well as to fill out Important special characters
The example below shows an assessment made at a VTRatio test card. However, the the Comment card.
assessment procedure is carried out in the same fashion on all test cards. Any time such an operation becomes necessary, the String Editor starts automatically. carriage return (line feed)
Change case tab (special function in Form Editor mode; refer to page Others-7).
Available Move right • enter the new test or folder name by consecutively selecting the characters of your
Assessment choice from the "on-screen keyboard" with the Up / Down keys or by navigating
characters
symbol to it with the handwheel
Finish editing
• acknowledge every selected character by pressing the handwheel or Enter
Template Abort editing,
phrases discard changes
• After the test, set the focus on the assessment symbol by turning the handwheel.
Test not assessed. The number of available characters to choose from depends on the String Editor’s use. If, for
example, a user-defined comment is to be entered in the Comment card, the number of
available characters is bigger than if a test is to be renamed. This difference are special
characters, such as !, ?, _, [ ], etc.
• Use the context-dependent menu keys to assess the test.
Test OK
Test failed
Common Functions - 1
CPC 100 V 1.43
Common Functions - 2
Common
Functions
CPC 100 Technical Data
CPC 100 V 1.43
Generator / Output Section - Current Outputs Generator / Output Section - Voltage Outputs Internal Measurement of Outputs
Note: For detailed information refer to the section “Technical Data” in the CPC 100 Reference
Manual available in pdf format on the CPC 100 Toolsets or the CPC 100 Start Page.
Range Amplitude5 tmax Imax Powermax5 f Guaranteed accuracy Typical accuracy6
0 … 2 kV 1 min 1.25 A 2500 VA 15 … 400 Hz Output Range Amplitude Phase Amplitude Phase
The output is either voltage or current, and is automatically selected by the software or manually 2kV AC3
by the user. Current and voltage outputs are overload and short-circuit proof and protected 0 … 2 kV >2h 0.5 A 1000 VA 15 … 400 Hz Reading Full Full Reading Full Full
against over-temperature. error scale scale error scale scale
1kV AC 3 0 … 1 kV 1 min 2.5 A 2500 VA 15 … 400 Hz
error error error error
Range Amplitude tmax1 Vmax2 Powermax2 f 0 … 1 kV >2h 1.0 A 1000 VA 15 … 400 Hz
800A AC - 0.20% 0.20% 0.20° 0.10% 0.10% 0.10°
0 … 800 A 25 s 6.0 V 4800 VA 15 … 400 Hz 500V AC3 0 … 500 V 1 min 5.0 A 2500 VA 15 … 400 Hz
400A DC - 0.40% 0.10% - 0.20% 0.05% -
0 … 400 A 8 min 6.4 V 2560 VA 15 … 400 Hz 0 … 500 V >2h 2.0 A 1000 VA 15 … 400 Hz
800A AC3 2000 V 0.10% 0.10% 0.20° 0.05% 0.05% 0.10°
0 … 200 A >2h 6.5 V 1300 VA 15 … 400 Hz 130V AC10 0 … 130 V >2h 3.0 A 390 VA 15 … 400 Hz
1000 V 0.10% 0.10% 0.30° 0.05% 0.05% 0.15°
6A AC 10 0 …6A >2h 55 V 330 VA 15 … 400 Hz 2kV AC 500 V 0.10% 0.10% 0.40° 0.05% 0.05% 0.20°
Output transient characteristics
3A AC10 0 …3A >2h 110 V 330 VA 15 … 400 Hz 5A 0.40% 0.10% 0.20° 0.20% 0.05% 0.10°
0 … 400 A 2 min 6.5 V 2600 VA DC Changes from “off” or a low Changes from a high magnitude to 500 mA 0.10% 0.10% 0.20° 0.05% 0.05% 0.10°
magnitude to a higher magnitude a lower magnitude or “off”
400A DC 0 … 300 A 3 min 6.5 V 1950 VA DC
AC current within one period 300 ms maximum; accordingly less Note: For the individual notes, see “Notes regarding Inputs and Outputs” below.
0 … 200 A >2h 6.5 V 1300 VA DC
for smaller magnitudes
6A DC4, 10 0 …6A >2h 60 V 360 VA DC
AC voltage 1200 ms maximum; accordingly less 300 ms maximum; accordingly less
3
2000A AC with an optional current booster. For more details, refer to page CP CB2-1. for smaller magnitudes for smaller magnitudes
Measuring Inputs Output to Input Synchronization Notes Related to Inputs and Outputs
All input/output values are guaranteed over one year within an ambient temperature of 23° C ±
Guaranteed accuracy Typical accuracy6 Test cards Quick, Test card Amplifier
5° (73 F ± 10 F), a warm-up time longer than 25 min and in a frequency range of 45 … 60 Hz
Sequencer, Ramping
Amplitude Phase Amplitude Phase or DC. Accuracy values indicate that the error is smaller than ± (value read x reading error + full
Input Imped. Range Frequency range 48 … 62 Hz scale of the range x full scale error).
Reading Full Full Reading Full Full
error scale scale error scale scale Synchronization inputs V1 AC V1 AC, V2 AC, I AC 1. With a mains voltage of 230 V using a 2 x 6 m high-current cable at an ambient temperature
error error error error (automatic range switching) (fixed to maximum range) of 23° C ± 5° (73 F ± 10 F)
10A AC 0.10% 0.10% 0.20° 0.05% 0.05% 0.10° 2. Signals below 50 Hz or above 60 Hz with reduced values possible.
Input magnitude 10% of input range full scale
1A AC 0.10% 0.10% 0.30° 0.05% 0.05% 0.15° 3. Output can be synchronized with V1 AC in Quick, Sequencer, Ramping and Amplifier.
Output magnitude 5% of output range full scale
IAC/DC4, 7 < 0.1 4. The input / output is protected with lightning arrestors between the connector and against
10A DC 0.05% 0.15% - 0.03% 0.08% - Settling time 100 ms after 5% of output 1000 ms after 5% of output protective earth. In case of energy above a few hundred Joule the lightning arrestors apply
1A DC 0.05% 0.15% - 0.03% 0.08% - magnitude is reached magnitude is reached a permanent short-circuit to the input / output.
300 V 0.10% 0.10% 0.20° 0.05% 0.05% 0.10° Signal changes All quantities must be ramped No changes of frequency and 5. Signals below 50 Hz or above 200 Hz with reduced values possible.
within 20 signal periods phase. Magnitude changes
30 V 0.10% 0.10% 0.20° 0.05% 0.05% 0.10° 6. 98% of all units have an accuracy better than specified as typical.
without limitation. Output
V1 AC8 500 k
3V 0.20% 0.10% 0.20° 0.10% 0.05% 0.10° follows within 250 ms. 7. Input is galvanically separated from all other inputs
300 mV 0.30% 0.10% 0.20° 0.15% 0.05% 0.10° Phase tolerance 0.5° within the limits as specified above 8. V1 and V2 are galvanically coupled but separated from all other inputs.
3V 0.05% 0.15% 0.20° 0.03% 0.08% 0.10° 9. There are power restrictions for mains voltages below 190V AC.
V2 AC 8, 11 10 M 10. Fuse-protected
300 mV 0.15% 0.15% 0.20° 0.08% 0.08% 0.10°
11. When using the CTRogowski test card, the 3V V2 AC input uses an additional software
30 mV 0.20% 0.50% 0.30° 0.10% 0.25% 0.15°
based integration method. In the range of 50 Hz < f < 60 Hz, this results in a phase shift of
10 V 0.05% 0.15% - 0.03% 0.08% - 90° as well as an additional phase error of +/- 0.1° and an additional amplitude error of +/-
1V 0.05% 0.15% - 0.03% 0.08% - 0.01%. For frequencies in the range of 15 Hz < f < 400 Hz, the phase error is not specified,
V DC4, 7 and the amplitude error can be up to +/- 0.50% higher.
100 mV 0.10% 0.20% - 0.05% 0.10% -
10 mV 0.10% 0.30% - 0.05% 0.15% -
CPC 100
Technical Data
CPC 100 V 1.43
General
Weight and Dimensions
Weight 29 kg (64 lbs), robust case with cover
Dimensions W x H x D: 468 x 394 x 233 mm (18.4 x 15.5 x 9.2"), cover,
without handles.
CPC 100
Technical Data
CP TD1
CP TD1
• Never remove any cables from the CP TD1 or the test object during a test.
• Keep clear from zones in which high voltages may occur. Set up a barrier or establish similar
adequate means.
CP TD1 - 1
CP TD1
CP TD1 - 2
CP TD1
CP TD1
CP TD1 Connected to a Power Transformer CP TD1 Connected to CP CAL1 Putting the CP TD1 into Operation
CP TD1 CP TD1 CP CAL1 As the first step, before you set a CPC 100 / CP TD1 measurement setup into
12 kV 12 kV operation, link the CPC 100, CP TD1 and, if applicable, the equipment trolley with
IN a min. 6 mm² grounding cable as displayed on page CP TD1-2.
Never use the CPC 100 / CP TD1 measurement setup without a solid connection
C1 to ground.
IN A IN A
C2 1. Switch off the CPC 100 at the main power switch.
Ix IN B IN B
Ix 2. With trolley:
C3 Properly connect the CPC 100 and CP TD1 grounding terminals to the trolley’s ground bar.
Connect the ground bar to earth. All cables minimum 6 mm².
Measurement Measurement Without trolley:
PE PE Properly connect the CPC 100 and CP TD1 grounding terminals to earth. Both cables
minimum 6 mm².
Booster Serial Booster Serial 3. Connect the CP TD1’s "BOOSTER IN" to the CPC 100’s "EXT. BOOSTER" with the
OMICRON electronics supplied booster cable.
Equipotential
CPC 100 ground 4. Connect the CP TD1’s "SERIAL" to the CPC 100’s "SERIAL" with the OMICRON electronics
CPC 100
supplied data cable. This cable also provides the power supply for the CP TD1.
Power transformer 5. Pull out the measuring cables from the cable drum and connect the test object to the
CP TD1’s measuring inputs IN A and IN B.
6. Pull out the high-voltage cables from the cable drum and connect the test object to the
When using the CP CAL1 for calibration, we recommend to take C1 as reference and to select CP TD1’s high-voltage output.
Equipotential ground the calibration frequency in a range between 50 … 200 Hz. 7. Switch on the CPC 100.
8. Selecting the TanDelta test card from any of the CPC 100’s CT, VT, Transformer or Others
test card groups automatically turns on the CP TD1. If no CP TD1 is connected to the
CPC 100, an error message appears.
9. Set up your measurement in the TanDelta test card (see page CP TD1-5).
10. Press the CPC 100’s I/O (test start / stop) push-button.
CP TD1 - 3
CP TD1
Calibrate the CP TD1 Using a Reference Capacitor Option TH 3631 Application and Test Templates
By connecting a reference capacitor (e.g., optional device CP CAL1) with known values of Use the optional device TH 3631 to measure ambient temperature, the test object temperature For detailed information on the CP TD1 applications, refer to the CP TD1 Reference Manual
capacity Cref and dissipation factor DFref, in mode UST-A the values Cx and DFx can be and humidity. Once these values were measured, enter them into the respective entry fields of delivered with the CP TD1 or available in pdf format on the CPC 100 Start Page.
measured and then compared to the known reference values. the TanDelta test card’s Settings page at "Compensations" (see page CP TD1-6).
If you experience substantial deviations, re-calibrate the CP TD1: Test Templates
• Cx = Cref / Cmeas and The test procedures for designated applications are controlled by templates available on the
• DF / PF + = DFref - DFmeas CPC 100 Toolsets shipped with your CP TD1 or on the CPC 100 Start Page.
as described on page CP TD1-6. Test templates are available for the following areas:
A re-calibration of the CP TD1 is also shown in the test report (.xml file). • power transformers
• instrument transformers
Note: If you change the factory-made calibration, the responsibility for the accuracy of the
• rotating machines
CP TD1 will be in your hands.
• cables and transmission lines
• grounding systems
Calibration tips: • others
• For calibration, set the averaging factor to maximum and the filter bandwidth to ± 5 Hz (refer
to page CP TD1-5).
• To reset to the factory settings, select "DF/PF+" to 0.0 ppm and "Cx" to 1.000 (refer to page
CP TD1-6).
CP TD1 - 4
CP TD1
CP TD1
CP TD1 - 5
CP TD1
TanDelta Test Card - Main Page TanDelta Test Card - Settings Page
Compound measurement setting Pressing the Settings button on the TanDelta main page opens the Settings page allowing you Selecting “Compensations" converts the actually measured dissipation or power factor to
to set additional measurement options. normalized values corresponding to an ambient temperature of 25° C. In doing so, the values
Cp, DF (tan) = parallel capacitance & dissipation factor
Cp, PF (cos) = parallel capacitance & power factor The CP TD1 leaves OMICRON entered at "Compensations" represent the existing ambient condition.
Cp, Ptest = parallel capacitance & power
At "Assessment Limits", set the tolerance of the
Cp, P@10kV = parallel capacitance & power; linearly interpolated to 10 kV test voltage
electronics factory-calibrated. If a main page’s nominal values for the assessment. • Enter oil temperature, ambient temperature (at bushing) and relative humidity first.
Qtest, Stest = reactive & apparent power component needs to be exchanged by a For the capacitance, the tolerance is entered in • Then place the cursor on "k".
Z = impedance with phase angle spare part, the CP TD1 must be re- percent, for the dissipation factor it’s a multiplier.
Cp, Rp = parallel capacitance & parallel resistance The medium the measurement takes place in, oil or air, determines the k-factor.
Ls, Rs = serial inductance & serial resistance
calibrated.
To re-calibrate, set the focus onto the Note: Availability and naming of the entry fields • ANSI C57.12
Cp, QF = parallel capacitance & quality factor
Ls, QF = series inductance & quality factor test card tab designation TanDelta and depend on the measuring mode, e.g., DF and PF The oil temperature is the determining medium for the k-factor.
press Edit Calib to enable the entry are the same entry field. • Bushings
fields: The air temperature at the respective bushing is the determining medium for the k-factor.
Bushings provides three bushing types to select from: RBP (Resin Bonded Paper), RIP
• Cx = correction factor for Cmeas
The averaging factor determines the (Resin Impregnated Paper) and OIP (Oil Impregnated Paper). The k-factor changes
(multiplier)
number of measurements. A factor of 3 accordingly.
• DF/PF + = corrective value added
means: the CP TD1 carries out 3 to dissipation or power factor (can
measurements whose results are then be + or -)
averaged. The higher the factor, the
Note: You must enter your name and Select if you use an external CT.
more accurate the measurement but
the longer the measuring time. press Update Calib to complete the re- The entered ratio is used to calculate
calibration. the measured current accordingly.
See also figure CP TD1 CP CAL1 on
Note: "Use ext. CT" can only be
page CP TD1-3.
selected if there are no measurement
Filter bandwidth of measurement. If selected, the beeper sounds during
results yet.
the entire test. If cleared, the beeper
Note: If the test frequency equals the default frequency (as set at Options | Device Setup),
sounds at the beginning and the end of
the filter bandwidth is always ± 5 Hz, regardless of the set value. This even applies if the option
the test only.
"use default frequency of xx.xx Hz" is not specifically selected.
± 5 Hz means that interferences at frequencies with an offset of ± 5 Hz from the measuring If selected, the CPC 100 checks whether the shield of the high-voltage cable is connected. For
frequency will not affect the results. some large inductive loads, the CPC 100 can accidentally report shield check error even when
The smaller the filter bandwidth, the longer the measuring time. the shield is connected. If this is the case, it makes sense to clear the check box.
Returns to TanDelta’s main page
CP TD1 - 6
CP TD1
CP TD1
Conditions: Signals below 45 Hz with reduced values possible. Capacitive linear loads. Conditions: f0 = 15 … 400 Hz
Range Resolution Typical accuracy Conditions
Terminal U/f THD I S tmax Filter bandwidth Meas. time Stop band specification (attenuation) error < 0.05% of reading Ix < 8 mA,
f0 ± 5 Hz 2.2 s > 110 dB at fx = f0 ± (5 Hz or more) 1 pF … 3 F 6 digits + 0.1 pF Vtest = 300 V … 10 kV
High-voltage 10 … 12 kV AC < 2% 300 mA 3600 VA > 2 min
output f0 ± 10 Hz 1.2 s > 110 dB at fx = f0 ± (10 Hz or more) error < 0.2% of reading Ix > 8 mA,
15 … 400 Hz 100 mA 1200 VA > 60 min Vtest = 300 V … 10 kV
f0 ± 20 Hz 0.9 s > 110 dB at fx = f0 ± (20 Hz or more)
Measurements Dissipation factor DF (tan)
Test current (RMS, selective)
Test frequencies
Range Resolution Typical accuracy Conditions
Terminal Range Resolution Typical accuracy Conditions
Range Resolution Typical accuracy 0 … 10% 5 digits error < 0.1% of reading f = 45 … 70 Hz,
IN A or IN Ba 0 …5A AC 5 digits error < 0.3% of reading + Ix < 8 mA (capacitive) I < 8 mA,
15 … 400 Hz 0.01 Hz error < 0.005% of reading + 0.005%a
100 nA Vtest = 300 V … 10 kV
error < 0.5% of reading Ix > 8 mA 0 … 100 5 digits error < 0.5% of reading Vtest = 300 V … 10 kV
TanDelta test card: Column “Hz” of the results table
(0 … 10000%) + 0.02%
Special displays in the frequency column “Hz” and their meanings: a
) IN A (red) or IN B (blue), depending on the mode.
*50 Hz (*60 Hz) Measurement mode suppressing the mains frequency Test voltage (RMS, selective) Power factor PF (cos)
interferences; doubles the measurement time.
Range Resolution Typical accuracy Range Resolution Typical accuracy Conditions
!30 Hz The selected test voltage is not available in Automatic
measurement (applies to frequencies below 45 Hz only). 0 … 12000V AC 1V error < 0.3% of reading + 1 V 0 … 10% 5 digits error < 0.1% of reading f = 45 … 70 Hz,
(capacitive) + 0.005%a I < 8 mA,
?xx Hz Results with reduced accuracy, e.g., in case of a low testing Vtest = 300 V … 10 kV
voltage, influences of partial discharge etc.
0 … 100% 5 digits error < 0.5% of reading Vtest = 300 V … 10 kV
+ 0.02%
a
) Reduced accuracy of DF and PF at mains frequency or its harmonics. Mains frequency suppression
available by precisely selecting a mains frequency of *50 Hz or *60 Hz in the “Hz” column.
CP TD1 - 7
CP TD1
Shock IEC68-2-27 (operating), 15 g/11 ms, half-sinusoid equipment and 26.6 kg 680 x 450 x 420 mm
Quality factor QF
casea (58.7 lbs) (26.8 x 17.7 x 16.5”)
Vibration IEC68-2-6 (operating), 10 … 150 Hz, acceleration 2 g
Range Resolution Typical accuracy continuous (20 m/s²); 5 cycles per axis Equipment trolley equipment 14.5 kg
0 … 1000 5 digits error < 0.5% of reading + 0.2% (32 lbs)
EMC EN 50081-2, EN 55011, EN 61000-3-2, FCC Subpart B of Part
> 1000 5 digits error < 5% of reading 15 Class A, EN 50082-2, IEC 61000-4-2/3/4/8, CE conform equipment & carton 18.9 kg 590 x 750 x 370 mm
(89/336/EEC) (41.7 lbs) (23.2 x 29.2 x 14.6”)
Safety EN 61010-1, EN 60950, IEC 61010-1, produced and tested in CP TD1, CPC 100, equipment 85 kg 750 x 1050 x 600 mm
an EN ISO 9001 certified company. equipment & trolley (187.5 lbs) (29.5 x 41.3 x 23.6”)
(without CP CAL1) equipment & packing 125 kg
Prepared for IEEE 510, EN 50191, VDE 104
(275.8 lbs)
a
) Case = robust case, IP22
CP TD1 - 8
CP TD1
CP CU1
CP CU1
CP CU1 - 1
CP CU1
To CP CU1
To test object
Surge arrestor
Fuse 30 A Voltmeter
Ground connection
Current range switch I OUT output
BOOSTER input
CT 100 A : 2.5 A
CP CU1 - 2
CP CU1
CP CU1
Measurement Setup Configuring the CPC 100 Connecting the CPC 100 and CP CU1 to Power Lines
The CPC 100 must be configured for the CP CU1. To configure the CPC 100: Safety Instructions
1. Press the Options view selector button to open the Options window.
Warning: A lightning discharge to the line under test can cause injury or possibly
death of the operating staff. Do not connect the measurement setup to overhead
lines if there is a possibility of a thunderstorm over any part of the lines to be mea-
sured.
Warning: Connecting the measurement setup to overhead lines with a life paral-
lel system brings about high-voltage hazards. It is strongly recommended to take
all parallel lines out of service before proceeding
Dangerous zone
Warning: During the grounding switch at the near end of the power line is open,
I AC V1 AC the area around the CP GB1 in the range of 5 m/15 ft and around the CP CU1 in
V1 AC I AC
the range of 2 m/5 ft is a dangerous zone due to high-voltage and mechanical
CP CU1 V SENSE Test object
CPC 100
CP GB1 hazards. Do not enter the dangerous zone. Keep the grounding switch open for a
EXT. BOOSTER BOOSTER I OUT time as short as possible.
(optional)
2. In the External booster combo box, select CU 1. Warning: If you see or hear anything uncommon in the test equipment, e.g. noise
The CT and VT settings are set according to the built-in current and voltage transformers of electrical discharge or lightening of surge arrestors, close the grounding switch
automatically. before touching the measurement setup.
3. Set the current range of the CP CU1 using the current range switch (see page CP CU1-2)
to the value configured by the CPC 100 software.
Warning: Set the current range switch on the CP CU1 front panel only when the
CPC 100 is turned off and the test object is connected to ground with closed
grounding switch near the measurement setup.
Note: Current range settings on the test card and on the CP CU1 front panel must be the same.
CP CU1 - 3
Yes
Yes
Yes
CP CU1 - 4
10 km/6 mi?
2 km/1.5 mi?
Use the 10 A
50 km/30 mi?
current range.
current range.
Start with the 100 A
Set 10 A
Set 20 A
Set 50 A
No
No
No
Connect a grounding set in parallel to the closed
grounding disconnector to each phase. Connect it first to
the ground and then to the line. Open the grounding
disconnector and measure the currents in all three
grounding sets. Use the highest measured value of IGS in
the following formula. Close the grounding disconnector
after the measurement is done.
Connecting the CPC 100 and CP CU1 to Power Lines
Yes
Yes
Yes
Yes
Is
Is
Is
Is
greater than 50 V?
Set 10 A
Set 50 A
Set 20 A
No
No
No
No
Yes
Yes
Yes
50 V?
500 V?
250 V?
100 V?
Set 50 A
Set 10 A
Set 20 A
No
No
No
No
Try to take parallel lines out of service or to reduce the current flow on the parallel systems.
No
No
No
CP CU1
Is 1 A possible?
Are 12 A possible?
Are 30 A possible?
Are 60 A possible?
Set 50 A
Set 10 A
Set 20 A
Yes
Yes
Yes
Yes
Applications and Test Templates Line Impedance Measurement Ground Impedance Measurement
The following application examples show the typical usage of the CP CU1. The test procedures
running on the measurement setup are controlled by templates available on the
CPC 100 Start Page.
For detailed information on the CP CU1 applications, refer to the CP CU1 Reference Manual
delivered with the CP CU1 or available in pdf format on the CPC 100 Start Page.
Far end
Far end
Overhead line
Overhead line
Near endend
Near
90°
V1
V1 AC
AC II AC
AC I AC V1 AC
CPC 100
100 CP CU1 V SENSE V1 AC I AC I AC
CPC
EXT.
EXT. BOOSTER
BOOSTER BOOSTER CP GB1 CPC 100 CP CU1
I OUT
EXT. BOOSTER BOOSTER I OUT
CP GB1
There are seven different measurement loops: A-B (shown here), A-C, B-C, A-G,
B-G, C-G and ABC in parallel to ground (similar to the next figure).
CP CU1 - 5
CP CU1
Measurement of Coupling into Signal Cables Step and Touch Voltage Measurement Technical Data
Output Ranges
Accuracy
There are four measurements with different connections. For detailed information, refer to the For the step and touch voltage measurements using the CP AL1 FFT voltmeter, refer to the
template or the CP CU1 Reference Manual. CP 0502 Application Note.
CP CU1 - 6
CP CU1
CP SB1
CP SB1
CP SB1 - 1
CP SB1
Functional Components of the CP SB1 Connecting the CPC 100 and CP SB1 to Power Transformers
The front panel of the CP SB1 provides the following functional components: Safety Instructions
Transformer High Transformer Low
Read the • Transformer High Voltage: • Position the CP SB1 in the safety area and do not enter this area during the entire
Voltage Tap Changer manual
Voltage – Outputs (Source) for the injection of current or voltage on the individual phases of the measurement.
Up Down transformer • Connect the CPC 100 and CP SB1 using the delivered grounding cable.
– Inputs (Measure) for the voltage measurement • Connect the grounding cable of the CP SB1 at a safe grounding point at the transformer.
Note: The inputs and outputs of the respective connections (U/H1, V/H2, W/H3, N/H0) are Note: Do not operate the test equipment without safe connection to ground.
connected to the transformer using Kelvin clamps. • Make sure that all high-voltage connections of the transformer are removed.
• Transformer Low Voltage: • Make sure that all terminals of the transformer are connected to ground.
• Switch off the power supply of the tap changer.
– Outputs (Source) for the injection of current or voltage on the individual phases of the • Connect the Kelvin clamps to the bushings.
transformer • Connect the cables to the Kelvin clamps. Make sure that the cables show upwards and that
– Inputs (Measure) for the voltage measurement each colour is connected to a different phase.
Note: The inputs and outputs of the respective connections (u/X1, v/x2, w/x3, n/X0) are • Connect the cables from the Kelvin clamps’ voltage sense outputs to the CP SB1’s
LEDs connected to the transformer using Kelvin clamps. transformer inputs. Observe the color code.
• Make sure to measure the voltage to ground at the terminals of the tap changer. If no voltage
• Tap Changer: Two potential-free contacts for switching the tap changer is measured, connect the flexible terminal adapters to the "up" and "down" terminals of the
• AC input for connection to the 2KV AC output of the CPC 100 tap changer.
• DC input for connection to the 6A DC output and I AC/DC input of the CPC 100 • Connect the cables ("up", "down") to the CP SB1.
• AC output for connection to the V1 AC input of the CPC 100 • Connect the CP SB1 to the CPC 100 according to ”Functional Components of the CP SB1”
• DC output for connection to the V DC input of the CPC 100 on page CP SB1-2.
• Serial interface for the CPC 100 (TRRatio and TRTapCheck test cards) to control the • Switch on the power supply of the tap changer.
CP SB1 • Remove all grounding connections of the terminals except one per winding. Use Neutral (N)
• Equipotential ground terminal for grounding the CP SB1 close to the position of the for the grounding connection if accessible.
operating staff • Start the measurement according to page Transformer-1 and page Transformer-5.
Serial Equipotential
AC Input DC Input V1 AC Output V DC Output
connection ground
terminal
CP SB1 - 2
CP SB1
CP SB1
CP SB1 - 3
CP SB1
CP SB1 - 4
CP SB1
CP CB2
CP CB2
Burden
Burden
Note: If you select the CP CB2 as external booster on the Device Setup tab in the Options
menu, it will be saved as default value for new test cards. However, it is also possible to select
the external booster individually on the test cards. The settings for already inserted test cards
will only be changed if no test results are available yet.
CP CB2 - 1
CP CB2
Technical Data
Notes regarding the CP CB2
Current outputs
1. With a mains voltage of 230 V using a 2 x 0.6 m high-current cable at an ambient
Range Amplitude tmax1 Vmax2 Powermax2 f
temperature of 23° C ± 5° (73 F ± 10 F)
1000 A AC 0 … 1000 A 25 s 4.90 V 4900 VA 15 … 400 Hz 2. Signals below 50 Hz or above 60 Hz with reduced values possible
0 … 500 A 30 min 5.00 V 2500 VA 15 … 400 Hz
Caution: Make sure to establish series or parallel connection, depending on the
2000 A AC 0 … 2000 A 25 s 2.45 V 4900 VA 15 … 400 Hz selected range on the test card.
Weight Dimensions (W x H x D)
CP CB2 test set 16 kg (35.3 lbs) 186 x 166 x 220 mm (7.3 x 6.5 x 8.7”),
without handle.
test set & case 25 kg (55.1 lbs) 700 x 450 x 360 mm (27.6 x 17.7 x
14.2”)
CP CB2 - 2
CP CB2