TF SYSTEM MASTER SPEC As of 28feb18
TF SYSTEM MASTER SPEC As of 28feb18
TF SYSTEM MASTER SPEC As of 28feb18
Do not scale the drawings. If a required dimension is not indicated, please request the missing
information.
These drawings are for the heavy timber superstructure only as herein defined below for the
structure or structures indicated. Architectural details such as waterproofing, flashing, roofing,
finishes, coatings; the design of the chimney and fireplace; the design of hvac, plumbing, and
electrical systems and the site work are the responsibility of others.
Timbers will shrink after installation until they reach the EMC (Equilibrium Moisture Content).
This will cause the loosening of bolts and threaded connectors. Periodic tightening of these
connections by the end user during the first several years of the structure’s service life may be
required. See technical specifications hereinbelow.
The key to the long-term survivability of the structure depends on keeping the timbers sealed,
dry and well ventilated. These design details are the responsibility of others
To resist lateral wind loads, this heavy timber framed roof system requires shear walls and the
roof diaphragm to be designed and installed by others including all connections between them
and the timber framing system and foundation to have been completed. Adequate bracing
must be installed and maintained to resist wind loads and erection loads until all of the
structural systems defined on the drawings herein have been completely installed.
The load bearing timber system as described in these documents and being supplied by this
manufacturer is designed to resist vertical, in-plane loads only, as specified above. It is the
responsibility of the engineer of record to design all supporting elements including but not
limited to roof structural decking/sheathing system (to transfer roof diaphragm shear), the
shear wall system, load bearing walls and posts, and the foundation system to resist the
lateral, uplift and gravity loads indicated.
The timber knee braces may provide some lateral stability during erection depending on wind
direction. It is the responsibility of the erector/installer of the timber frame system to provide
temporary lateral bracing and guying systems until the structural components of the exterior
wall system have been completely installed.
The exterior wall and roof framing and sheathing systems and connections between them and
the timber frame system shall be designed and installed by “others” to transfer lateral loads
due to wind or seismic forces thru the roof and timber frame system to the wall system and the
foundation.
Continuous double 2x top plates are assumed and required for anchorage of specified screws
to resist uplift. It is the responsibility of others to design and install any connections required to
transfer these loads to the foundation.
Any required spacers between the timber frame and the wall system to tuck dry wall sheathing
behind the timber frame must be structural plywood or oriented strand board. Drywall/gypsum
board spacers are not permitted for the transfer of lateral loading between the timber frame
and stud framed or SIP wall systems.
OSB or structural plywood sheathing must be designed and installed by others to be fastened
directly to the 2x6 T and G decking to resist wind uplift and develop roof diaphragm shear.
Shear walls must be balloon framed to extend to the underside of the overlaid 2x6 decking
(which shall be made to lap over the top of these walls) and fastened to transfer roof
diaphragm shear to the walls. Shear walls must “follow” all gabled profiles.
Nothing contained herein or indicated hereon shall infer or imply any responsibility on the part
of the timber frame manufacturer or supplier or their component/system engineer for such
design or for the analysis of those supporting elements which have been or are to be prepared
by others.
Temporary support of the heavy timber system including, but not limited to, lateral bracing, bridging,
blocking, strong-backs (or other devices as required) on frames and trusses shall be installed and
maintained while the remainder of construction is completed and the permanent connections from the
timber frame system to the lateral force resisting system (structural insulated panels or other
structural framing/walls) have been completed. Once all construction is completed, the temporary
support system components may be removed and returned to the supplier of that material.
________________________________________________________________________________
TIMBER FRAME SYSTEM ENGINEERING DRAWING NOTES
Other included systems (if any) are: T&G Roof Decking/OSB Diaphragm Sheathing/SIPs Wall
and/or Roof Panels/Glulam Elements (etc) SIPs Roof and Wall Enclosure are to be designed,
furnished and installed By Others. See “BOXED NOTES” elsewhere on this sheet for
installation requirements of Supplemental Roof Decking Systems included with the Timber
Frame System.
2015 International Residential/Commercial Building Code with local and state amendments,
ASCE 7-10, AF&PA NDS 2015, TFEC 1-2010 (Draft for Standard for Design of Timber Frame
Structures)
DESIGN CRITERIA
WIND LOADS:
Design Wind Speed: 115 MPH, 3-Second Gust
Exposure Category: C
Building Classification: II
Wind Importance Factor: 1.0
Enclosure Classification: Enclosed with protected openings.
SEISMIC LOADS: Not Applicable/Not Controlling
ROOF SNOW LOAD
Ground Snow Load: 35 PSF (Controls Roof Design)
Exposure Factor, Ce: 1.2 (assumed ‘sheltered’)
Thermal Factor, Ct: 1.0
Roof Slope Factor, Cs: 1.0
Importance Factor, I: 1.0
ROOF LIVE LOAD: 20 PSF (Not Controlling)
ROOF DEAD LOAD: 20 PSF Horizontal Projection Plus Weight Of Timber
FLOOR LIVE LOAD: 40 PSF
FLOOR DEAD LOAD: 20 PSF Plus Weight Of Timber
NOTE: Concentrated Loads and Construction Loads must not exceed design loads above.
TIMBER
INTERIOR: Douglas Fir, #1 and Better, WCLIB Grading Rules, “Green” at time of fabrication
and expected to be less than 19% moisture content in service, free of heart center and finished
S4S in accordance with NDS 2012 Table 1B.
Note: Douglas Fir is not a “naturally durable wood” as defined in Section 202 and as
may be required by Section 2304.11 of the International Building Code. Its use in
exposed locations requires special care in providing protective flashing, sealing or oiling
of timbers, and ongoing/active maintenance and observation to prevent premature
deterioration from rot, decay and UV degradation. The design and detailing of such
system and coatings and inspection/maintenance procedures is the responsibility of
others.
EXTERIOR: White Oak, #2, NELMA, “Green” at time of fabrication and expected to be less
than 19% moisture content in service, box-heart, S4S in accordance with NDS 2012 Table 1B.
Timbers to be cut, trial fitted, sanded and shipped F.O.B. jobsite for installation. Any special
coatings are ‘by others’ or as otherwise required by the heavy timber purchase agreement.
The use of end grain sealer is recommended for all timbers to help resist end checking.
Surface sealers to resist moisture penetration are recommended for all timber exposed to
weather.
Special Truss Fabrication Note: Parallel Chord Trusses with tension splices shall be
cambered L/180 where L is the span in inches.
Note: Some warping, twisting, checking, and splitting of timbers as they reach equilibrium
moisture content can be expected.
CONNECTORS
1. SCREWS:
a. 'RSS' (Rugged Structural Screws) high tensile/bending yield strength by GRK
FASTENERS, or equal. Screws shall be washer-headed. Shaft diameters shall be
5/16" diameter up to 7 ¼” long and 3/8" diameter from 8” long and above. Screws
shall penetrate a minimum of 4” in receiving timber. Where heads would be visible,
screws shall be installed in counter-bored holes to clear the head and allow
approximately 1/2” for plugging. See www.grkfasteners.com for additional
information.
b. “ASSY-VG-CSK all-threaded, zinc plated (electroplated with a zinc layer thickness
of 5-8 micro meters), self-countersinking screws (ICC/ESR #3178) provided by
My-Ti-Con Timber Connectors (my-ti-con.com),
c. Lag Screws: Lag screws shall be ‘galvanized’ unless otherwise noted. Drill two lead
holes: the first for the threads at 65% to 85% of the shank diameter in wood with a
specific gravity (SG) greater than 0.60; 60% to 75% for an SG between 0.50 and
0.60; and 40% to 70% for an SG equal to or less than 0.50 to insure a ‘tight grip’ into
the timber receiving the threads; and, the lead hole for the smooth shank equal to
the diameter of the shank.
2. PEGS: 1" Diameter, Structural, Straight Grained, Black Walnut, White Oak, Red Oak or
Locust treated with paraffin, linseed oil or similar sealing substance.
4. BOLTS and PINS: ASTM Grade A307 (Interior) or Grade 316 Stainless Steel (Exterior)
unless otherwise noted. (Installer Note: At least two full threads shall extend past the face of
any nuts.) Bolt holes in timber shall be drilled to yield a tight fit requiring ‘moderate’ driving
force with a mallet to seat the bolts. To compensate for the effects of cross grain shrinkage on
bolted connections in ‘green’ timber, re-tighten all bolts: a) immediately prior to occupancy;
b) six months after occupancy; and, c) 18 months after occupancy. Where the equilibrium
moisture content is equal to or less than 19%, re-tighten bolts: a) immediately prior to
occupancy; and, b) 12 months after occupancy.
6. DOWELS AND THREADED ROD TENSION TIE BOLTS: ASTM Grade A36 (Installer
Note: At least two full threads shall extend past the face of any nuts or threaded turn-buckle
sleeves.) Hi-Strength rods where noted shall be ASTM Grade A572 Gr 50.
7. CONCRETE ANCHOR SYSTEM: Cold Weather: Simpson AT-XP Acrylic Adhesive (14
degree limit); Warm Weather: Simpson SET-XP (45 degree limit) or SET-3G (40 degree limit)
All installed in strict accordance with Simpson instructions. Installer Note: Temperatures are
‘base material temperatures NOT air temperature with differences in cure time vs temperature.
10. FINISHES: All steel connections and hardware exposed to weather to be hot-dip
galvanized, electrostatically coated or stainless steel unless otherwise noted.
TF JOINERY/CONNECTIONS (As noted below and on the drawings and details)
1. Housings/Connections
a. Rafters: ¾” unless otherwise noted w/2-9” screws LogHogs or GRK-RSS Screws
b. Floor Joists: 3/4” unless otherwise noted w/2-9” screws LogHogs or GRK-RSS
Screws
c. Non-load bearing beams and connecting girts: 1” plus 3 ½” tenon as described
below (unless otherwise noted) w/ 2 pegs or connecting splines as shown plus two
(2) GRK RSS Screws from top of beam 3 ½” min. into receiving timber
d. Load bearing beams: 1 ½” plus 3 ½” tenon as described below (unless otherwise
noted) w/2 pegs or connecting splines as shown plus two (2) GRK RSS Screws from
top of beam 3 ½” min. into receiving timber
2. Rafters to Posts: 1 ½” housings with 2-Peg M&T connection or two (2) GRK RSS screws
with 3 ½” min. into receiving timber.
3. Pegs: Quantity Shown (see specs for mortise and tenon sizes and peg spacing)
________________________________________________________________________________
“SUPPLEMENTAL SYSTEM NOTES” – (add as required)
1. Material:
a. Roof Panels: 10 ¼” thick (nominal) with 7/16 OSB skins and EPS foam core, installed
where noted.
b. Wall Panels: 6 ½” thick (nominal) with 7/16” OSB skins and EPS foam core, installed
where noted.
2. Design and Installation Standards: Structural insulated panels (SIPs) shall be provided by a
firm with demonstrated experience in the fabrication and installation of that system.
Membership in SIPA (Structural Insulated Panel Association will satisfy this requirement). The
firm shall have a current code certification report (NTA or similar) with sizes, and span and
load tables.
3. The SIP system shall be designed to resist required design loads as indicated or referenced
above.
4. Where SIP systems are installed on framing by others, fastening requirements shall be
designed to resist gravity loads, wind uplift, and diaphragm shear.
5. SIP system shop drawing shall be provided with a summary of the location, thicknesses and
types of panels (type of foam core) with to-scale drawings of all supporting elements, layout of
panels, sections, and details with fastening requirements on the details on in appropriate
tables.
6. Select panel screws of sufficient length to provide full thread penetration into receiving timbers
such that threads are excluded from the shear plan to maximize shear strength.
7. Provide 15# rolled felt or synthetic vapor barrier over sheathing to provide temporary
protections from the elements prior to installation of finished roof system designed and
installed by others.
8. The SIP system shop drawings and a copy of the current code certification report shall be
submitted to the Timber Frame Specialty Engineer for review and approval prior to fabrication
and installation of the SIP system