Chiller - An Overview
Chiller - An Overview
Chiller - An Overview
Chiller
A chiller is operating with a condensing temperature of 105°F and an evaporating
temperature of 35°F. How much does theoretical chiller efficiency increase if leaving
chiller water temperature is increased from 45°F to 48°F and entering condensing
water temperature is decreased from 85°F to 75°F?
From: Energy, Management, Principles, 1981
Related terms:
Heat Exchanger, Cooling Tower, Compressors, Absorption Chiller, Condenser,
Refrigerants, Chilled Water
38.1 Chillers
Chillers are used to control the feed throat temperature and barrel temperature for water-cooled extruders.
Downstream cooling associated with vacuum sizing tanks for profiles, pipes, and tubing, and other cooling processes
can use chillers. Chillers provide a closed-loop water system to cool either the equipment or the product. Advantages
of chillers versus once-through water are as follows:
• Constant water temperature
• Reduced water cost
• Reduced water waste
• Lower water temperature control point possible
In a large extrusion facility with many extruders and water cooling systems, it is common to have a cooling tower. If
no cooling tower is available, a chiller provides an efficient way to recirculate treated water through the feed throat
and extruder barrels if water cooling is being used. One chiller can cool a number of feed throats if that is all the
cooling that is required. The chiller has to be properly sized to match the heat load
https://www.sciencedirect.com/topics/engineering/chiller 1/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
The most important factor to consider when selecting a chiller is to choose the proper size. The extruder
manufacturer can supply the flow rate through the feed throat and the approximate flow rate to control the barrel in
a water-cooled extruder. Using Eqn (38.1), the heat load can be calculated and the chiller can be properly sized:
(38.1)
where
Recognizing that the cooling fluid density changes with temperature, let us assume 60 °F (15.6 °C) where the water
density is 8.33 lb/gal (1.0 kg/l). Assume that the feed throat flow rate is 1 gal/min at 100 °F. Also assume the water
temperature entering and exiting the feed throat has a 10°F ΔT and maintains the feed throat at 100°F. The heat
load (Q) calculation is given by Eqn (38.2):
(38.2)
Therefore, a chiller capable of removing 1.47 kW or 4998 Btu/h is needed to keep the cooling throat at the proper
temperature. Cooling is given in British thermal units per hour (kilocalories per hour) or tons. To convert from
British thermal units per hour to tons, use the conversion 1 ton of refrigeration = minute/200 Btu. Eqn (38.3)
converts the results from Eqn (38.2) into tons:
(38.3)
In chillers, the heat load is described in British thermal units (BTU/hr), kilowatts (kW), or tons capacity. Table 38.1
gives common guidelines for basic chiller tonnages [1].
Gear box 1
HDPE, high-density polyethylene; LDPE, low-density polyethylene; PP, polypropylene; PS, polystyrene; PVC, polyvinyl
chloride.
Obviously, the calculated load depends on whether the chiller is required to cool just the feed throat or the feed
throat plus barrel zones. If the barrel zones are water cooled, factors affecting the barrel temperatures are as follows:
• How much heat supplied by viscous shear heating has to be removed
https://www.sciencedirect.com/topics/engineering/chiller 2/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
• Extruder size
• Processing temperature window size
The more the cooling required, the greater the chiller cooling capacity and the larger the chiller must be. If the
extruder manufacturer can supply an appropriate heat load for different resin systems, these data can be used to
properly size the chiller.
In sizing chillers for extrusion, the following information is required:
• Extruder diameter and length
• Number of zones
• Extruder horsepower
• Connection sizes
• Throughput
• Materials being processed
• Melt temperature
• Cooling required if it is known in either British thermal units per hour or tons
The second issue in selecting a chiller is the choice between an air-cooled or water-cooled unit. Cooling is required
to dissipate the heat removed from the process. Water-cooled units are generally used in applications where tower
water or some other inexpensive water source is available to take away the heat. Air-cooled units are used where
water is contaminated, an inexpensive water source is not available, or the heat being dissipated is part of a heat
recovery system for heating the plant. Water-cooled models use condensers, whereas air-cooled models have fins
with an air-circulating blower to remove the heat. Water-cooled units are 10–15% more efficient than air-cooled
units are. The advantage of the air-cooled model is that it becomes more portable because a water source and drain
or return are not required at each location. Portable chillers in extrusion operations are generally used when cooling
tower water is not available. If cooling tower water is available to remove the heat from a chiller, it is also available to
hook directly to the extruder. In this scenario, a portable chiller may still be required for cooling water in a vacuum
tank or other downstream equipment to a temperature below that of the cooling tower water.
The third selection criterion is the control system, with a choice between a digital temperature controller and a fully
programmable, self-diagnostic microprocessor controller. A digital controller is inexpensive and provides continuous
operating temperature readings, with a single button for starting and stopping, easy entry of the process
temperature set point, low-liquid mode signal, and status indicators for on/off, compressor, alarm, and low flow. The
microprocessor controller supplies some of the same information available with the digital controller plus additional
information and more details. Microprocessor controls can provide the following:
• Set point and actual return temperatures
• Percent load or tons
• Process flow rate in gallons per minute (GPM) or liters per minute (LPM)
• Refrigerant pressures
• Run status
• Diagnostic information
• Adjustable alarm limits to display low level, high temperature, and low temperature
• Password entry to prevent accidental or unauthorized changes in settings
https://www.sciencedirect.com/topics/engineering/chiller 3/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
• Automatic fine tuning of proportional and integral and derivative (PID) temperature control parameters to
provide a uniform temperature
• Set points in degrees Fahrenheit and Celsius
The options available include communications ports for RS232, RS485, or RS422 with remote control switches and
sensors.
Figure 38.1 shows one fluid flow design for a chiller. Hot water return from the extruder enters a hold tank. The hold
tank has a vent system and refill valve to maintain the water level in the hold tank. A chilled water bypass can be used
if the hold tank gets too hot. The return water is then pumped through the refrigerant heat exchanger and then to
the extruder.
The pump size is critical for good heat transfer characteristics. Turbulent flow through the process system is required
for good heat transfer. The pump size and flow rate are just as critical as the circulating water temperature. Higher
flow rates result in higher heat transfer rates
Some options available in chillers include the following:
• Nonferrous materials in contact with the water to prevent rust
• Pump motor overload protection
• Stainless steel tanks
• Brass shut-off valves
• Brass pump
• Audible and visual alarms
• Water filtration
One advantage of using a chiller versus once-through water is the water savings and the cost associated with the
water. Using 1 gal of water per minute for 24 h a day, 5 days per week, for 50 weeks consumes 360,000 gal/year. With
https://www.sciencedirect.com/topics/engineering/chiller 4/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
many water-cooled extruders, the consumption significantly exceeds 1 gal/min. Payback for chillers based on water
savings alone is relatively short.
Chillers are also used to control the water bath temperature in profiles and vacuum sizing tanks and to control the
cooling air temperature in blown film operations.
https://www.sciencedirect.com/topics/engineering/chiller 5/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
For a series counter flow chiller, there are a lead chiller and a lag chiller that share the load at about 50/50. Using the
same system temperature differentials as the parallel system, the lead chiller would have a lift of 95 minus 50 °F, or
45 °F (35 minus 10 °C, or 25 °C), and the lag chiller would have a lift of 90 minus 40 °F, or 50 °F (32.2 minus 4.4 °C,
or 27.8 °C). Therefore, the average lift for series chillers would be 47.5 °F (26.4 °C), which is substantially lower than
the 55 °F (30.6 °C) in the parallel configuration and would, therefore, use less energy.
condenser. Table 8.2 summarizes typical chiller efficiency ranges for different chiller technologies.
Electric centrifugal (standard single compressor) 0.52–0.7 kW/ton (COP 4.7–6.75) 500 to > 1500
Electric centrifugal (standard dual compressor) 0.52–0.7 kW/ton (COP 4.7–6.75) 1500 to > 4000
Electric centrifugal (single compressor industrial – field erected) 0.52–0.7 kW/ton (COP 4.7–6.75) 2500 to > 5500
Direct fired (double effect) absorption chiller (COP 0.85–1.30) < 100 to > 3250
The overall efficiency (normally measured in kW/ton, a measure of energy consumption per unit of cooling) of a
chilled water system is truly dependent upon the summation of the efficiencies of all components (chillers, pumps,
heat rejection, etc.) within the system and not necessarily a single component. While the chiller is the largest
electrical load in the chilled water system, the most efficient chiller selection may not lead to the lowest system
kW/ton. As stated earlier, equipment efficiencies are heavily impacted by the design temperatures of the chiller. This
is best illustrated in Table 8.3, which breaks down the energy used by each system component for a sample chilled
water system. Example 3 has the highest overall system efficiency but does not have the highest efficiency chiller.
Table 8.3. Typical overall efficiency of chilled water system at various temperature differentials
Example 1 14 °F CHW Example 2 14 °F CHW Example 3 18 °F CHW Example 4 18 °F CHW
ΔT and 10 °F CW ΔT ΔT and 15 °F CW ΔT ΔT and 10 °F CW ΔT ΔT and 15 °F CW ΔT
https://www.sciencedirect.com/topics/engineering/chiller 7/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
Note that both chillers selected with 15 °F (8.3 °C) ΔT condenser water systems (Examples 2 and 4) had lower
efficiencies due to increased compressor lift (i.e. work) requirements. While the 15 °F (8.3 °C) ΔT condenser water
pumps used less energy than the 10 °F (5.6 °C) ΔT examples, both Examples 2 and 4 had lower overall system
efficiencies, at least for this example, compared with the 10 °F (5.6 °C) ΔT examples. This may not always be the case,
so the DCS designer is encouraged to perform this calculation for their specific project to achieve the optimum
selection of equipment and operating temperatures.
stably operate at about 30% of peak load, therefore, having a smaller ‘pony’ chiller will meet the lowest part loads
and provide optimal plant performance.
● Provide a high quality control system—this includes temperature, pressure and flow measurements, since the
more accurate information the operator has at their fingertips, the better they can optimize the operations.
Highly accurate instrumentation at the customer end is also recommended, since the energy meter is the ‘cash
register’ of the entire DCS, and the less confrontation over billing invoices, the happier the customers are.
● Third party optimization software—often, aftermarket software that enhances the sequence of operation of chiller
plants pays back very quickly and should be considered.
https://www.sciencedirect.com/topics/engineering/chiller 9/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
Evaporative coolers, also called as swamp coolers, are packaged units that cool the air by humidifying it and then
evaporating the moisture. The equipment is most effective in dry climates. It can significantly reduce the peak
electric demand when compared to electric chillers
Typical full-load operating efficiencies for chillers are noted below:
• Small air-cooled electric chillers have 1.1–1.6 kW t- 1 (COP of 2.2 to3.2).
• Large and medium-sized air-cooled electric chillers have 0.95−0.85 kW t −1 (COP of 3.7 to 4.1).
• Similar water-cooled electric chillers have 0.8−0.7 kW t- 1 (COP of 4.4 to 5.0). Lower values such as 0.6−0.5 kW t- 1
chillers (COP of 5.9 to 7.0) may indicate energy efficient equipment, but part-load performance should also be
examined.
• The COP of absorption units is in the range of 0.4−0.6 for single-effect chillers, and 0.8−1.05 for double-effect
chillers.
• Engine-driven chillers attain COP of 1.2−2.0.
2. Condensers are heat exchangers that are required for chillers to reject heat that has been removed from the
conditioned spaces. They can be either air-cooled or water-cooled. Water-cooled condensers often rely on rooftop
cooling towers for rejecting heat into the environment; however, it is possible to reject the to the ground or river
water.
Air-cooled condensers are offered on smaller, packaged systems (typically from less than one ton to 120 tons). They are
initially less costly than water-cooled condensers, but do not allow the chiller to operate as efficiently.
Water-cooled condensers use water that is cooled directly from the evaporative condenser or indirectly via a cooling
tower. The lower temperature achieved by evaporating water allows chillers to operate more efficiently.
A waterside economiser consists of controls and a heat exchanger installed between the cooling tower water loop and
the chilled water loop. When the outdoor air temperature is low and/or the air is very dry, the temperature of the
cooling tower water may be low enough to directly cool the chilled water loop without use of the chiller, resulting in
significant energy savings.
Chillers
Chillers, or air conditioners, utilize heat exchanges and circulate fluid or gas to cool the air that is passed through the
unit. Chillers are often located in a mechanical area at ground level, or in a central plant in a campus environment.
Chill l i b i h t i th fi ti i l ( l k th
https://www.sciencedirect.com/topics/engineering/chiller 10/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
Chillers cool air by removing heat using the refrigeration or vapor-compression cycle (also known as the reverse-
Rankine cycle), which consists of compression, condensation, expansion, and evaporation (Fig. 3.2).
A refrigerant in vapor form is initially compressed in a compressor, reducing its volume and increasing its
temperature. It is then pumped to a condensing unit, where the refrigerant is cooled and condensed into a liquid.
This liquid is then pumped to the indoor evaporator unit, where it is passed through evaporator coils that remove
heat from the building. The hot air in the building is passed over the evaporator coils, adding heat to the refrigerant
and removing heat from the air, which is recirculated back into the building. The added heat turns the refrigerant to
vapor, which is sent back to the compressor, completing the cycle.
Chiller condensers remove heat from the system via cooling air, cooling water, and evaporation. Air-cooled systems
are typically found in residential homes and commercial buildings where the cooling load is less than 100 tons (Fig.
3.3). The air-cooled condenser is comprised of coils that house the flowing refrigerant and maximize convective
surface area (the area for the transfer of heat), and a forced air source (typically a fan) that uses convection to extract
heat from the refrigerant and remove it from the system altogether.
https://www.sciencedirect.com/topics/engineering/chiller 11/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
Water-cooled systems are used for buildings that require large cooling loads, and typically have higher efficiencies
than air-cooled systems. (Fig. 3.4). Instead of using air to remove the heat from the refrigerant, water is used to
extract heat. Once the heat is extracted the water is then pumped to a cooling tower, where the heat is rejected back
into the atmosphere and the water is then pumped back to the condenser (Fig. 3.5). Cooling towers reject heat by
using an air stream to evaporate a portion of the incoming water, thereby cooling the rest of the incoming water.
The heat transferred to the air causes it to rise, flowing out of the top of the tower and into the atmosphere.
https://www.sciencedirect.com/topics/engineering/chiller 12/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
Water-cooled chillers have higher efficiencies than air-cooled chillers because they reject heat at the wet-bulb
temperature (which takes into account humidity and radiation), rather than the dry-bulb temperature at which air-
cooled chillers reject heat. They are also smaller than air-cooled chillers for the same cooling output because its
condenser requires less surface area and does not use fans, which also significantly reduces noise levels (Fig. 3.6).
Evaporative condensed chillers operate essentially as a smaller and more efficient version of a water-cooled system;
they use the same evaporative cooling provided by a cooling tower. The cooling is achieved using a recirculating
water system, which continuously wets the condenser tubes while fans blow air over them, evaporating the water and
thereby moving (rejecting) the heat to the atmosphere.
Although this also uses air to move heat out of the condenser just as an air-cooled system would, an air-cooled
condenser is less efficient because it draws ambient air over the condensing surface and rejects heat at the dry-bulb
temperature. Evaporative condensed chillers use considerably less water than water-cooled chillers, thus reducing
the operational costs.
For each type of chiller there are four compressor subcategories: reciprocating, centrifugal, screw driven, and
absorption. Reciprocating, centrifugal, and screw-driven chillers are powered mechanically by electric motors, steam,
or gas turbines while an absorption chiller is powered by heat and uses no moving parts. Reciprocating compressors
use pistons driven by a crankshaft and are typically used for delivering small amounts of refrigerant at high pressure.
Centrifugal compressors use centrifugal force to compress air and are used for delivering large volumes of
https://www.sciencedirect.com/topics/engineering/chiller 13/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
g p g p g g
refrigerant at low pressure. They are widely used in industry because they are energy efficient and have few moving
parts. Screw-driven compressors use two opposing rotating screws to compress the air between them.
Summer operation
During the summer the chiller is automatically put into operation as soon as the temperature in the hot water
storage exceeds 78°C. The chiller stops when the storage temperature drops below 76°C. The chiller stops also when
the evaporator inlet temperature drops below 10°C. Normally the chiller cools the cold water storage, which, in turn,
provides the space cooling to the building. The chiller can be directly connected to the building in the case that the
temperature of the cold storage is too high to cool the building, but the chiller can operate with heat from the hot
storage. When both the hot and cold storage are exhausted, an auxiliary heater runs the chiller. In this case the
chiller is directly connected to the thermoconvectors.
The primary loop (chillers and pumps) provides the “header” with a constant flow of chilled water. The secondary
loop, via its secondary distribution pumping system, takes water from the primary loop as needed for the hydronic
systems it serves. The secondary pumps may be controlled in order to provide adequate flow to the secondary piping
loop, using a water pressure or flow sensor. They can be constant speed pumps with a bypass arrangement, or the
motor speed can be controlled by a variable speed drive, less energy waste. Control valves are typically two-way when
variable flow secondary control systems are used.
Secondary pumps, as with any dual equipment scenarios, shall be rotated from lead to lag typically on a daily basis.
When a failure is sensed, the lag (or redundant backup) pump can automatically take over.
A flow meter and appropriate temperature sensors, in the secondary loop, can be used to monitor its flow readings
and calculate energy usage. Flow meters can be used to monitor make-up water flows in order to trend water usage
and identify potential leaks.
When the outside air temperature is above/below an appropriate temperature (adjustable), the chiller/boiler plant
may be disabled/enabled. An override feature that will override this outside temperature shutdown should be
installed and available
https://www.sciencedirect.com/topics/engineering/chiller 15/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
installed and available.
For maintenance or out-of-service times, the control system will sense the abnormal off and/or alarm condition of a
chiller, boiler, fan or pump and bring on its next in series in order to maintain its set points. All alarms should be
monitored by an alarm providing visible or audible alarm.
Chiller optimisation
When a chiller operates at its design load and the cooling tower operates at maximum summer design
temperatures, standard catalogue data provides a close approximation to power consumption. However, in a typical
system, design conditions occur infrequently. At all other times, capacity and efficiency vary as a function of
condenser water and chilled water supply temperatures. The total power consumed by a chiller plant also includes
auxiliary equipment such as the cooling tower fans, condenser water and chilled water supply pumps. Power
required for these auxiliaries varies according to the number of chillers operating, chilled water flow and
environmental conditions. The situation becomes even more complex when chillers of different sizes or types are
utilised. Continual chiller operating efficiency cannot be maintained if a plant operator must recalculate the best
operating strategy each time load conditions change. A microprocessor is able to overview the plant and performs
calculations with speed, enabling continuous monitoring and decision processing. Chiller optimisation software
enables the microprocessor to continuously perform energy–efficient calculations, select the most favourable chiller
combination, and adjust both chilled water and condenser water supply temperatures. Overall system power
consumption is then kept to an optimum minimum level.
Gas Sweetening
Maurice I. StewartJr. PhD, PE, in Surface Production Operations (Third Edition), Volume 2, 2014
9.9.3.4.1 Chiller
A chiller may be included to reduce the dew point of the gas and the heavy hydrocarbon content. Because chilling
does not completely remove all heavy hydrocarbons, an adsorbent guard bed is still required. If deep chilling is
necessary, steps must be taken to prevent hydrates from forming, either by dehydrating the gas upstream or by
adding hydrate inhibitors. If inhibitors are added, they may need to be removed downstream of the chiller because
some inhibitors may damage the membrane.
9.9.3.4.2 Turbo-expander
The turbo-expander serves the same purpose as a chiller, but has the benefit of being a dry system. It is smaller and
lighter than the refrigeration system. A disadvantage is the net pressure loss, which must be taken up by the export
compressor
9 9 3 4 3 Glycol Unit
https://www.sciencedirect.com/topics/engineering/chiller 16/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
9.9.3.4.3 Glycol Unit
The glycol unit is added upstream of the chiller to prevent hydrate formation or freeze-up. An adsorbent guard bed is
still required to remove heavy hydrocarbons but must be larger than it would normally be because it must also
remove glycol carried over from the adsorber vessels.
The energy savings attributed to switching from a single-chiller plant to a multichiller cooling plant depend on the
load profile and climatic conditions. Table 8.5 shows the number of hours of operating one-chiller system at various
part-load ratios for a load profile associated to office buildings located in four US climates. The potential savings in
total electrical energy use as a function of the number of chillers in a multichiller cooling plant is provided in Fig.
8.13.
Climate 0–10 10–20 20–30 30–40 40–50 50–60 60–70 70–80 80–90 90–100 100+
https://www.sciencedirect.com/topics/engineering/chiller 17/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
Figure 8.13. Energy use reduction as a function of number of chillers for office buildings located in four US climates.
Fig. 8.14 illustrates the potential savings associated with the annual building electrical energy savings when using a
two-chiller central cooling plant with various chiller sizing ratios. The chiller size ratio, SR, is defined as the ratio
between the sizes of the small chiller to that of the larger chiller in a two-chiller cooling plant. The analysis was
carried out by letting the SR vary from 0 (single chiller configuration) to 1 (two equal chiller).
Figure 8.14. Energy use savings as a function of chiller size ratio in a two-chiller central cooling plant for office buildings located in four US
locations.
Process Control
William A. Poe, Saeid Mokhatab, in Modeling, Control, and Optimization of Natural Gas Processing Plants, 2017
3.6.6 Chillers
A chiller is a machine that removes heat from a liquid via a vapor-compression or absorption refrigeration cycle. A
vapor-compression chiller uses a refrigerant internally as its working fluid. Many refrigerant options are available;
when selecting a chiller, the application, cooling temperature requirements, and refrigerant's cooling characteristics
need to match. Important parameters to consider are the operating temperatures and pressures. Natural gas
processing employs a number of refrigerants. Among some of the refrigerants used are:
• sodium brine
• ammonia
• freon (phased out)
• propane
th l ( ft d d ith ) d
https://www.sciencedirect.com/topics/engineering/chiller 18/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
• ethylene (often cascaded with propane), and
• mixed light hydrocarbon refrigerants.
In some processing schemes, the refrigerant is delivered directly to chillers and in other schemes chilled water or
other medium is delivered to the process.
The typical refrigeration cycle consists of two isothermal and two isenthalpic or adiabatic steps at isobaric conditions.
Usually, the heat of vaporization isothermally transfers heat from the refrigeration to the process yielding a lower
temperature of the process fluid. The refrigerant vapors are compressed to raise the pressure adequately for
condensing by a heat sink. The heat sink is typically cooling water or ambient air; however, in cascade refrigeration
schemes the heat sink may be a higher-temperature refrigerant.
The heat sink is of sufficiently low temperature to condense the refrigerant totally and isothermally at the discharge
pressure of the refrigerant compressor. Condensed refrigerant, now in liquid form, is expanded isenthalpically across
a valve to lower the temperature of the liquid refrigerant. A portion of the refrigerant will flash into vapor across the
valve. This vapor is dead load in the chiller unless the refrigerant pressure is lowered in stages with economizers
installed to separate the liquid from the vapor. The remaining liquid will enter the chiller to continue the
refrigeration cycle (Fig. 3.10).
optimized by balancing the effect of compression ratio on horsepower (cost) against the increased revenues obtained
with colder process temperature.
It is preferential to control evaporator pressure and maintain constant chiller level to fully utilize heat transfer area.
Refrigerant levels in chillers should be held adequately high to cover all tubes, but not so high that refrigerant liquid
carries over into downstream scrubbers.
Some refrigeration system optimization opportunities may include:
• Maximize temperature difference across the chiller when cooling water is used
• Minimize pumping
• Cooling tower approach optimization
• Store refrigerant at night
• Always use the most efficient chiller combination
• Use efficiency information to initiate maintenance
Ideally, variable speed drives are preferred for refrigeration compressors to match horsepower consumed to amount
of refrigerant required. If several constant speed motors are used, then one compressor should be throttled and the
remaining compressors should be operated with the throttle valve wide open.
About ScienceDirect Remote access Shopping cart Advertise Contact and support
Terms and conditions Privacy policy
We use cookies to help provide and enhance our service and tailor content and ads. By continuing you
agree to the use of cookies.
https://www.sciencedirect.com/topics/engineering/chiller 20/21
11/9/2019 Chiller - an overview | ScienceDirect Topics
https://www.sciencedirect.com/topics/engineering/chiller 21/21