TRB Installation PDF
TRB Installation PDF
TRB Installation PDF
High Efficiency
Models Oil Fired Hot Water Boiler
TRB4075
TRB4095
INSTALLATION, OPERATION &
TRB4110
TRB5100
MAINTENANCE MANUAL
TRB5115
TRB5135 FOR US SALES ONLY
TRB6130
TRB6145
TRB6165
TRB7165
TRB7180
TRB7190
Manufactured by:
Models
TRB4075
TRB5100
TRB6130
TRB7165
2
DIMENSIONS
DIMENSIONS
DIMENSIONS
Dimension
Flue Size Dimension "B"
"A" Inches
Sections Inches (cm)
Inches
(cm) (cm) Chimney Direct
Vent Vent
4 5 (13) 18 ⅜ (46.6) 1 ⅛ (32) ¾ (19)
5 5 (13) 21 ⅝ (54.8) 1 ⅛ (32) ¾ (19)
6 5 (13) 24 ⅞ (63.1) 1 ⅛ (32) ¾ (19)
7 6 (15) 28 ⅛ (71.3) ¾ (19) N/A
1 - Introduction............................................................................................................... 5
2 - Safety Information..................................................................................................... 6
3 - Before You Start......................................................................................................... 7
4 - Ratings & Capacities................................................................................................... 8
5 - Locating The Boiler..................................................................................................... 9
6 - Installation Requirements.......................................................................................... 10
7 - Fresh Air For Combustion........................................................................................... 11
8 - Boiler Assembly........................................................................................................ 13
9 - Boiler System Piping................................................................................................. 18
10 - Hydronic Piping...................................................................................................... 19
11 - Fuel Supply Piping.................................................................................................. 32
12 - Antifreeze In The System ........................................................................................ 33
13 - Electrical Connections.............................................................................................. 34
14 - Chimney And Venting Connections............................................................................ 35
15 - Filling Boiler........................................................................................................... 38
16 - Operating The Boiler - System Start-Up.................................................................... 39
17 - Oil Burner, Nozzle, & Air Settings.............................................................................. 46
18 - Maintenance.......................................................................................................... 53
19 - Oil Boiler / Burner Cleaning Instructions..................................................................... 55
20 - Troubleshooting...................................................................................................... 57
21 - Equipment And Accessories ..................................................................................... 59
Installation and Check Out Certificate .............................................................................. 63
! WARNING NOTICE
Installations of boilers and venting shall be done Surface rust on cast iron sections may be attributed
only by a qualified expert and in accordance with to manufacturing process as well as condensation
this manual. Installing or venting a boiler or any during storage. Surface rust is normal and does not
other oil appliance with improper methods or affect performance or life of boiler.
materials may result in serious injury or death due
to fire or to asphyxiation from poisonous gases
such as carbon monoxide which is odorless and
invisible.
Boilers include -
• Limit, 220° F maximum, operating control with integral
low water cut off.
• Temperature and pressure gauge
• 30 psi relief valve
• Drain valve
2.1 General
! WARNING
Boiler installation shall be completed by qualified agency.
Construction materials of appliance and products
of combustion and fuel contain alumina, silica,
! WARNING heavy metals, carbon monoxide, nitrogen
Fire, explosion, asphyxiation and electrical shock oxides, aldehydes and /or other toxic or harmful
hazard. Improper installation could result in death substances which can cause death or serious injury
or serious injury. Read this manual and understand and which are known to the State of California to
all requirements before beginning installation. cause cancer, birth defects and other reproductive
harm. Always use proper safety clothing,
! WARNING respirators and equipment when servicing or
Modification, substitution or elimination of factory working nearby the appliance.
equipped, supplied or specified components could
result in death or serious injury. ! WARNING
! WARNING Product contains fiberglass wool and refractory
ceramic fibers. Possible cancer hazard. May cause
Improper installation, adjustment, alteration, service irritation to skin, eyes and respiratory tract. To
or maintenance could result in death or serious avoid this hazard, wear a dust mask and gloves
injury. when handling fiberglass and ceramic fibers.
! CAUTION
Laceration, burn hazard. Metal edges and parts may IMPORTANT: Read the following instructions
COMPLETELY before installing!!
have sharp edges and/or may be hot. Use appropriate
personal protection equipment to include safety 2.3 Installation Shall Conform To Requirements
glasses and gloves when installing or servicing this Of Authority Having Jurisdiction Or In Absence
boiler. Failure to follow these instructions could result Of Such Requirements To ANSI/NFPA 31,
in minor or moderate injury. “Installation Of Oil Burning Equipment”.
Indicates a hazardous situation which, if not avoided, Additional manual reset low water cutoff and manual reset
high limit may be required.
WILL result in death or serious injury
*MAWP = Maximum allowable working pressure. This low pressure oil fired hot water boiler is constructed and
hydrostatically tested for maximum working pressure of 65 psi in accordance with the latest revision of the A.S.M.E.
(American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards for heating boilers.
Heating Capacity and AFUE based on 13.1% CO2 (13.5% CO2 at 0.95 GPH and 1.10 GPH, 13.2% CO2 on 7 section at
1.65 GPH), -0.02” w.c. draft in breech, and # 1 smoke or less. Testing is done in accordance with U.S. DOE (Department
of Energy) test procedure.
Heating Capacity indicates amount of heat available after subtracting losses up the stack. Remaining heat is available
to heat water. Small portion is heat from jacket and surfaces of boiler and this heat stays in structure. Net AHRI rating
represents portion of remaining heat applied to heat radiation or terminal units (i.e. finned tube baseboard, cast iron
radiators, radiant floor, etc.). Difference between Heating Capacity and Net AHRI Rating, called piping and pickup
allowance, establishes reserve for heating volume of water in system and offsetting heat losses from system piping. Net
AHRI ratings shown are based on piping and pickup factor of 15% in accordance with AHRI Standard as published by
Hydronics Institute.
Net AHRI rating of boiler selected should be greater than or equal to calculated peak heating load (heat loss) for building
or area(s) served by boiler and associated hot water heating systems. Consult manufacturer before selecting boiler for
installations having unusual piping and pickup requirements.
15”
RELIEF
VALVE
Fresh Air Duct Capacities For Ducts Supplying Fresh Air To Boiler In Tightly Constructed Houses
THROUGH LOUVERS
¼” Mesh Wood Metal
Fresh Air Screen Louvers Louvers
Duct Size
(Btuh)* (Btuh)* (Btuh)*
3 ½” x 12” 144,000 36,000 108,000
8” x 8” 256,000 64,000 192,000
8” x 12” 384,000 96,000 288,000
8” x 16” 512,000 128,000 384,000
*Btuh = British Thermal Units per hour based
on opening covered by ¼” mesh screen , wood
louvers, or metal louvers.
MOUNTING
PLUG
15. Check installation of liners and baffles (Not all
models). See Table 4, Page 16.
A. Check oval (4 section) or V-shaped (6 and 7 section)
liner. See Figures 9 & 10. Liner should be flush with
front edge of heat exchanger fins.
B. Flue way baffles (4, 5, 6 section only) are factory
installed in 3rd pass. Insure baffles are inserted
! WARNING in flue way such that position tab touches casting
between 2nd and 3rd Pass flue way. See Figure 11,
Burn and scald hazard. Relief valve could Page 14.
discharge steam or hot water during operation.
Check local codes for maximum distance from floor
Efficiency of boiler is based on insertion of flue way baffles
or allowable safe point of discharge. Installation of in 4, 5 and 6 section units. Baffles will generate lower
relief valve shall be consistent with ANSI/ASME Boiler gross stack temperatures entering chimney. This has the
and Pressure Vessel Code, Section IV. potential under certain operating conditions to cool flue
gases below dew point, creating condensation on interior
chimney and chimney connector surfaces. Remove baffles
14. Install Relief Valve. See Figure 9.
to increase stack temperature if there are any signs of
A. DO NOT pipe in area where freezing can occur. DO
condensation in chimney or chimney connector. Removing
NOT install shutoff valves, plugs or caps.
baffles alone may not address condensation depending on
B. Locate 3/4”NPT x 90° street elbow. Install elbow other boiler and heating system operating conditions.
using 3/4” NPT tapping in supply piping. Install
elbow with outlet facing directly up. Install relief NOTICE
valve with outlet facing horizontally. Flue gas condensate is corrosive, which requires
C. Pipe discharge of relief valve. Installation of relief special consideration and must be addressed
valve must be consistent with ANSI/ASME Boiler and immediately.
Pressure Vessel Code, Section IV.
NOTICE
Do not install valve between boiler and controls
manifold or relief valve.
LIMIT CONTROL
WITH INTEGRAL
LOW WATER
CUT OFF
THERMAL/ LWCO
WIRE
BURNER WIRING
RELIEF VALVE
BACK OF BOILER
Figure 14 - Circulator Wiring B. Use hand wrench to tighten door hardware and start
with non-hinged side. Use alternating tightening
method from non-hinged side to hinged side to
tighten door equally until sealed without applying
excessive torque. Never tighten hinged side flange
bolt first or tighten either piece of hardware 100%
without using alternating tightening method described
above.
GREEN TO NOTICE
GROUND
BLACK When securing burner swing door, make sure door is
SCREW
TO drawn-in equally on both sides.
YELLOW
WHITE
Failure to follow the prescribed procedure could
TO cause thread damage to casting or a leak in the
WHITE door seal. If hinged side is tightened before the
unhinged side, the hinged side of door cannot
NOTICE be drawn to provide an air-tight seal. Applying
Ensure all conduit is secured to prevent contact with excessive torque will only cause thread damage.
flue pipe
DRAIN
VALVE
9.1 Connect System Supply And Return Piping 9.2 Bypass Piping
To Boiler See Piping Diagrams for illustrations for this section.
Connect system supply and return piping to correct boiler Bypass piping may be required for applications listed
fittings. below. Failure to do so may cause damage due to thermal
Size system circulator to supply sufficient flow (GPM) to shock and sustained condensation within the boiler.
allow 20°F temperature differential in system. Connect Protect boiler from sustained operation of return water
circulator harness to circulator per Figure 12 and furnished temperatures lower than 130°F (54C). Occasionally,
wiring diagram. temperatures as low as 70°F (21C) may return back to
When sizing system circulator, use single most restrictive boiler when a zone that has not been activated for some
zone to determine maximum pressure drop. time is opened. However, most residential systems with
finned-tube (aluminum-copper) baseboard radiation
1. Boiler used in connection with refrigeration systems, contain low volume of water and will not adversely affect
install boiler so chilled medium is piped in parallel with
boiler. Systems with finned-tube baseboard radiation
heating boiler using appropriate valves to prevent
typically do not require bypass.
chilled medium from entering boiler. See Figure 28,
Page 19. Bypass piping details shown in piping diagrams must be
2. If boiler is connected to heating coils located in air used for any one of following conditions:
handling units exposed to refrigerated air, equip boiler • All large water content systems, including cast iron
piping with flow control valves to prevent gravity standing radiators, cast iron baseboard, converted
circulation of boiler water during operation of cooling two-pipe steam systems, converted gravity circulation
system. systems and other similar systems.
3. Limit control includes low water cutoff function, sensing
water level at control well in top of the rear boiler • Any system, including finned-tube baseboard, with
section. Periodic inspection and testing is necessary priority domestic hot water zone.
per instructions provided with limit control. Install ¾ inch bypass line as shown in piping diagrams for
4. When installation of boiler is for new heating system, systems identified above.
install all radiation units (panels, radiators, baseboard, Bypass valve cannot protect boiler from sustained
or tubing) and supply and return mains. After heating condensing operation for low temperature applications such
system piping and components have been installed, as radiant floor heating. These types of system require
make final connection of system piping to boiler. active controls that prevent return of cold return water to
Recommend mount circulating pump on supply side boiler.
piping, such that it pumps away from expansion tank. Refer to Radiant Professional’s Alliance (RPA)
5. Hot water boiler installed above radiation level must www.radiantprofessionalsalliance.org for piping
be equipped with low water cut off device. This boiler recommendations for non-condensing boiler applications.
is factory equipped with low water cutoff. Periodic
inspection is necessary, per manufacturer’s specific
instructions.
6. When connecting cold water supply to pressure
reducing valve, make sure clean water supply is
available. When water supply is from well or pump,
install sand strainer at pump.
Figure 18 Piping And Wiring Single Zone System With Domestic Hot Water DHW Priority
DHW Heater
FIGURE 18
INDIRECT WATER TANK
HEATER, AQUASTAT
CONTROL
OR THERMOSTAT
T-STAT
THERMOSTAT
PRIORITY
ZONE ZONE 2
COMMON
DATA PORT +
ELECTRONIC T 1 T
W R T 2 T
W R
FUSE 24 VAC @ 1 VA
HYDROSTAT
ZONE 1 ZONE 2
6 TO 7 INCH LBS
PRIORITY ON TO EXTRA
ZONE MODULE
X-X
PRIORITY ON
ARM-2P
CONTROL
WITH
PRIORITY X1 X1 X2 X2 L 1 N L 2 N L N
ISOLATED ISOLATED PRIORITY ZONE 2
SWITCH SWITCH 120VAC CIRCULATORS
120 VAC
CIRC
DHW
TO OIL
CIRC
BURNER
L
120 VAC
N
Figure 19 - M
ulti-Zone Piping and Wiring With Zone Valves And Domestic Hot Water Priority
(With Zone Valve)
SEE FIGURE
(CONSULTER 20
LA FIGURE 20)
ON
AZ-4CP
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
PRI ZONE 1 ZONE 2 ZONE 3 ZONE 4
L
120 VAC
N
Figure 20 - Piping And Wiring Multizone System With Zone Valves And Domestic Hot Water
Priority (With Circulator)
ON
AZ-4CP
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
PRI ZONE 1 ZONE 2 ZONE 3 ZONE 4
CIRC ZONE
VALVE
ZONE ZONE
TO OIL VALVE VALVE
BURNER DHW
CIRC
L
120 VAC
N
Figure 21 - Piping and Wiring Multi-Zone System With Circulators And Domestic Hot Water
Priority
T-STAT T-STAT
THERMOSTATS
DATA PORT PRIORITY
ZONE ZONE 2 ZONE 3 ZONE 4 COMMON
+
ELECTRONIC
FUSE
Z TW 1 T R TW 2 T R TW 3 T R TW 4 T R 24 VAC
@ 1VA
+
+
24AC
PRIORITY ON
HYDROSTAT
MODEL 3250 30 VA TO EXTRA
ZONE MODULE
COMMON
X-X
ZR-ZC
PRIORITY ON
+
ARM-4P
CONTROL WITH
PRIORITY
X X L 1 N L 2 N L 3 N L 4 N L N
ISOLATED
SWITCH ZC ZR PRIORITY ZONE 2 ZONE 3 ZONE 4
120 VAC
CIRC CIRC
TO OIL DHW
BURNER CIRC
CIRC
L
120 VAC
N
Figure 22 Primary/Secondary Piping And Wiring With Circulators And Domestic Hot Water
MAX = 4 X DIAMETER
CLOSELY - SPACED TEES
BOILER
PUMP
T-STAT T-STAT
THERMOSTATS
DATA PORT PRIORITY
ZONE ZONE 2 ZONE 3 ZONE 4 COMMON
+
ELECTRONIC
FUSE
Z TW 1 TR TW 2 T R TW 3 TR TW 4 TR
24 VAC
@ 1VA
+
24AC
PRIORITY ON
HYDROSTAT
MODEL 3250 30 VA TO EXTRA
ZONE MODULE
COMMON
X-X
ZR-ZC
PRIORITY ON
+
ZONE 1 ZONE 2 ZONE 3 ZONE 4
ARM-4P
CONTROL WITH
PRIORITY
X X L 1 N L 2 N L 3 N L 4 N L N
ISOLATED
SWITCH ZC ZR PRIORITY ZONE 2 ZONE 3 ZONE 4
120 VAC
CIRC CIRC
CIRC
TO OIL
BURNER RELAY
120VAC COIL
120VAC CONTACTS
DHW
CIRC
BLR
CIRC
L
120 VAC
N
Figure 23 - Piping And Wiring Primary/Secondary Multi Zone System Piping With Zone Valves
And Domestic Hot water (With Zone Valve)
BOILER
PUMP
ON
AZ-4CP
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
PRI ZONE 1 ZONE 2 ZONE 3 ZONE 4
BLR
CIRC
L
120 VAC
N
Figure 24 - Piping And Wiring Primary/Secondary Piping With Zone Valves And Domestic Hot
Water (With Circulator)
ZONE VALVE
MAX = 4 X DIAMETER
CLOSELY - SPACED
TEES
ON
AZ-4CP
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
PRI ZONE 1 ZONE 2 ZONE 3 ZONE 4
CIRC ZONE
VALVE
ZONE ZONE
VALVE VALVE
TO OIL RELAY DHW
24VAC COIL
BURNER 120VAC CONTACTS CIRC
BLR
CIRC
L
120 VAC
N
FROM SYSTEM
TO SYSTEM
V1 V2
SYSTEM
CIRCULATOR
WATER INLET
EXPANSION
TANK BOILER ALTERNATE
CIRCULATOR
LOCATION
WATER INLET
EXPANSION
TANK
BOILER ALTERNATE
CIRCULATOR
LOCATION
PRESSURE
10 - HYDRONIC PIPING
Figure 27 - Bypass Piping (4-Way Valve Option with Circulator On Supply Side
TO SYSTEM
FROM SYSTEM
WATER INLET
EXPANSION
TANK
BOILER ALTERNATE
CIRCULATOR
LOCATION
Figure 28 Recommended Piping For Combination Heating and Colling (Refrigeration) System
4-WAY MIXING
WATER CHILLER
SHUT-OFF FLOW CONTROL
CHECK VALVE VALVE HOSE BIB
VALVE VALVE
BOILER
SHUT OFF SHUT OFF
VALVES VALVES
AIR CUSHION
TANK
CIRCULATOR
14.2 Chimney and Chimney Connector • Over-fire Draft - Measure pressure at 1/4” NPT test port.
Three pass boilers have higher pressure drop than single
1. Chimney connector should be kept as short as possible.
pass. Table 9 shows expected pressure drop between
Horizontal length of chimney connector should not be
over-fire and breech. Total pressure drop is difference
greater than 10 feet.
between over-fire draft and breech draft. For example,
2. Type L Vent pipe or other suitable material may be if over-fire draft = 0.05 INWC and breech draft = - 0.05,
used for chimney connector if flue temperature is less total pressure drop = 0.05 - (-0.05) = 0.10 INWC. See
than 570° F. Figure 33, Page 37.
3. 4,5 & 6 section boilers are equipped with a sheet metal
flue collar for attaching 5" diameter chimney connector.
Attach chimney connector to flue collar with 3 standard Table 9 - Pressure Drop Between
sheet metal screws (field supplied). Over-Fire & Breech
4. 7 section boilers are equipped with a cast iron flue Sections Inches WC
collar for attaching 6" diameter chimney connector.
Attach chimney connector to flue collar using furnished 4 0.03-0.05
drill bit to drill holes for furnished screws. Vent 5 0.05-0.08
Connection Kit (drill bit and screws) furnished in
6 0.09-0.16
accessory carton. Predrill to avoid cracking cast iron
flue collar. 7 0.07-0.16
5. Inspect chimney and connector annually for signs of
debris and corrosion. Loose mortar at base of chimney
may be sign of condensate damage to chimney. 14.4 Stack Temperature
6. Inspect base of chimney for any signs of seepage. 1. Higher stack temperature, greater amount of draft
generated. Lower stack temperature not only reduces
Discoloration may be a sign of chimney damage. Have
amount of draft created but also increases possibility
repaired immediately.
flue gases could condense in chimney connector or
7. Contact qualified service agent immediately to examine stack.
damage and correct. Operation of damaged chimney 2. Consult NFPA 31 and CSA B139 for information for
may cause venting failure and force flue gases into appropriate choice of venting materials. Chimney may
living space. have to be lined to create sufficient draft, or chimney
8. If chimney is to be re-lined, use recommendations in may have to be lined to prevent corrosion of masonry
NFPA31, Appendix E or CSA B139. chimney. Consult qualified service agency for chimney
requirements in your area.
3. Baffles – Efficiency of boiler is based on insertion of
flue baffles supplied with 4,5 & 6 section units. Baffles
14.3 Draft are installed in 3rd pass (two inner flueways). Refer to
“8 - Boiler Assembly” on page 13 for baffle installation.
• Natural draft generated through chimney is dependent
Remove baffles to increase stack temperature.
on several factors including, chimney height,
temperature of flue gases, cross section area of 4. Remove baffles if any signs of condensation in chimney
chimney, chimney wall insulation value, dilution air and or chimney connector. Removing baffles may not
total volume of flue gases. Operate boiler for at least 5 address condensation.
minutes before measuring draft.
Tight, smooth,
Must slope up correctly sized
at least 1/4
inch per foot of
Sealed in Draft Regulator
horizontal run Vane
thimble
Tight clean-out
door
Balanced Crimped
Weight End
! WARNING NOTICE
Fire, burn, asphyxiation hazard. Turn off service Boiler maximum operating pressure is posted on
switch to boiler to prevent accidental firing of ASME data label located on front lower leg of boiler.
burner outside combustion chamber. Disconnect Never exceed this pressure. Do not plug relief
burner power cord from wire harness in front jacket. valve.
Tighten swing door fastener completely when
L. It may be necessary to clean air vent assembly
service is complete. Failure to follow instructions in
after few days of operation.
this manual and understand all requirements could
result in death or serious injury. 3. Check controls, wiring and burner. Verify all
connections are tight and burner is rigid, all electrical
1. Inspect Installation Before Starting Burner. connections have been completed and fuses installed,
and oil tank is filled and oil lines have been tested.
A. Verify venting, water piping, oil piping, and
electrical system are installed properly. Refer to
installation Instructions contained in this manual.
B. Confirm all electrical, water and oil supplies
are turned off at source and vent is clear from
obstructions.
2. Fill Heating System With Water.
A. Failure to clean system can result in clogged air
vents, circulator damage and seized zone valves.
7 TEST/SETTINGS Button
To Test Low Water Cut-Off: Press and hold Test/
1 TEMP ACTIVE Indicates Limit Control is powered Settings button for 5 seconds. Display will read LCO.
and temperature function is active. LWCO TEST LCO
2 TEMP HI TEMP Illuminates when boiler water Red Low Water light should illuminate and burner circuit
temperature reaches high limit setting. Remains lit until (B1 and B2) should de-energize. Note: Control must
water temperature falls 10°F. Limit control prevents burner be installed with Electro-Well for low water cut-off
operation while this LED is on. See Differential explanation functionality.
page 27.
To View Current Settings: Press and release Test/
3 LWCO ACTIVE Indicates low water cut-off (LWCO)
Settings button in short intervals to sequentially display the
function of limit control is active. Boiler is factory equipped following settings:
with Hydrolevel electro-well, enabling control’s low water
cut-off function. LED will be on at all times when control is
powered.
Important: If control well is replaced with a well other than
Electro-Well, LED will not illuminate indicating control is not
providing low water cut-off functionality.
! WARNING
Burn and scald hazard. Do not add water until boiler
has fully cooled. Failure to follow these instructions
could result in death or serious injury.
4 LWCO LOW WATER Illuminates if boiler is in low
water condition. Limit control will prevent burner operation
during this condition.
Important: System must be checked by a qualified service Display will return to boiler temperature (default) if Test/
agency prior to resuming operation. Settings button is not pressed for 5 seconds.
NOTICE ! WARNING
Instructions are for Beckett AFG with Beckett Fire, burn, asphyxiation hazard. Do not loosen
Genisys primary control. For other burners, refer to or remove any oil line fittings while burner is in
manufacturer’s manual. operation. Failure to follow these instructions could
Nozzle and air settings are given in Table 14 page result in death or serious injury.
50.
! WARNING
For direct vent installation guide, see Direct Vent
Fire, burn, asphyxiation hazard. Do not attempt
Addendum.
to start burner when oil has accumulated in
16.9 Oil Burner combustion chamber or unit is full of vapor, or
hot. Check operation of all boiler controls before
1. Prepare Oil Burner Before Starting.
installation of boiler is completed. Failure to follow
A. Check burner air band, air shutter and head setting
these instructions could result in death or serious
(if equipped), readjust if necessary. See “17 - Oil
Burner, Nozzle, & Air Settings” on page 46.
injury.
B. Open all oil line valves.
3. Preliminary Oil Burner Adjustments
C. Attach a plastic hose to fuel pump vent fitting and
provide a pan to catch the oil. A. Adjust Draft Regulator for breech draft of -0.05
(preferred) to 0 inches water column after chimney
has reached operating temperature and while burner is
2. Prime Pump and Start Oil Burner running.
A. Open bleed port fitting on fuel pump. B. Use smoke tester and adjust air if necessary for
B. Initiate a call for heat minimum smoke (not to exceed trace) with minimum
I. After burner starts, press and hold reset button for of excess air. Check using suitable instrumentation to
approximately 15 seconds until yellow light turns confirm CO2 of 11 to 13%. If flame appears stringy
on. Indicates button has been pressed long enough. instead of solid fire, try another nozzle of same type.
Flame should be solid and compact.
II. Release reset button. Yellow light turns off and
burner starts up again. C. Turn off burner and remove pressure gauge. Install
gauge port/bleeder plug and tighten. Start burner
III. At burner startup, click reset button while igniter is
still on. This transitions control to dedicated pump again.
priming mode, during which the motor, igniter and 4. Final Burner Adjustments: Final burner
valve are powered for four minutes. Yellow light will adjustments must be made using combustion test
be on. instruments.
C. Bleed pump until all froth and bubbles are purged. A. Check breech draft to verify between 0.00” WC and
I. If desired, terminate call for heat or hold reset -0.05” WC, or otherwise adjust draft to -0.05” WC (or
button for at least one second to exit pump priming less than zero.)
mode and return to standby mode. B. After operating 10 minutes to warm up boiler, use
II. At end of four minutes, yellow light will turn off and combustion test equipment to take smoke reading in
control will automatically return to standby mode. flue pipe between boiler and draft regulator. Smoke
III. If prime is not established during four minute pump reading should be zero to trace (Shell Bacharach
priming mode, return to step 2.B.III. to re-enter Scale).
pump priming mode. Repeat steps 2.C.I. to 2.C.II. C. New boiler may require more than 10 minutes to
until pump is fully primed and oil is free of bubbles. burn clean due to oil film on new heat exchanger.
D. Terminate call for heat. Close bleed port fitting on fuel If smoke reading is zero, gradually close burner’s
pump. air adjustment to obtain smoke reading showing
trace smoke reading. Once smoke reading is trace,
E. Adjust oil pressure.
measure CO2 and as insurance margin increase air to
I. When checking fuel unit’s operating pressure, sufficiently reduce CO2 by 1/2% to 1%.
reliable pressure gauge may be installed in either
bleeder port or nozzle port. D. If clean fire cannot be obtained, it is necessary to
verify burner head alignment. If fire continues to be
II. Initiate call for heat.
smoky, replace nozzle.
III. Locate oil pressure adjusting screw and turn screw
to obtain proper pump pressure, refer to “17 - Oil
Burner, Nozzle, & Air Settings” on page 46.
42 P/N 240009350 Rev. J [09/01/2017]
16 - OPERATING THE BOILER - SYSTEM START-UP
E. Once burner is completely adjusted, start and stop VI. Open hand valve in oil line.
burner several times to assure good operation with no VII. Click reset button and verify red light in reset
fluttering or rumbling. Verify there are no oil leaks, button shuts off and burner lights.
record nozzle size, oil pressure, combustion readings,
and air settings on tag or label attached to burner or, VIII. End call for heat.
boiler.
! WARNING
Figure 37 - CAD Cell Location
Electrical shock hazard. Following safety checks shall
be completed by qualified agency. Failure to do so
could result in death or serious injury.
NOTICE
Control contains no field serviceable parts. Do not
attempt to take it apart. Replace entire control if
operation is not as described.
Figure 39 - B
eckett Electrode Tip Adjustments Figure 40 - B
eckett Electrode Tip Adjustments Standard
Standard Dimensions (L1, V1) Heads Dimensions (L2) Heads
Figure 41 -B
eckett Check/Adjustment "Z" Figure 42 Beckett Check/Adjustment "Z"
Dimensions L1 & L2 Heads Dimensions - V1 Heads
Turbulator Setting
A. Loosen nut (1) turn SCREW (2) until INDEX MARKER
(3) is aligned with correct index number as per
Burner Settings Table.
B. Tighten RETAINING NUT (1).
NOTE: Zero and four are scale indicators only.
From left to right, first line is 4 and last line 0. On some
models, scale indicators are 0 and 3.
TABLEAU 13a : RÉGLAGES PRÉLIMINAIRES DU BRÛLEUR BECKETT AVEC ÉVACUATION PAR CHEMINÉE
4075 L2 3.375U 2.625 0.75 Oval Delavan 0.65x60B 140 N/A 0 7 87.0
4095 L2 3.375U 2.625 0.95 Oval Delavan 0.85x60B 125 N/A 1 10 85.0
4110 L1 N/A 2.625 1.10 Oval Hago 0.90x60B 150 N/A 1 10 84.0
5100 L2 3.375U 2.625 1.00 None Delavan 0.85x60B 140 N/A 2 10 87.0
5115 6 Slot N/A 2.5 1.15 V5 Hago 1.00x60B 140 N/A 1.5 N/A 85.0
5135 6 Slot N/A 2.5 1.35 V5 Delavan 1.10x60B 150 N/A 2.0 N/A 84.0
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instruments.
4075 6 Slot 2.5" 0.75 Oval Delavan 0.60x60B 150 1.5 0.65" WC 87.0
4095 6 Slot 2.5" 0.95 Oval Hago 0.75x60B 155 4.0 0.65" WC 85.0
5100 6 Slot 2.5" 1.00 None Delavan 0.75x45B 175 4.0 0.85" WC 87.0
5115 6 Slot 2.5" 1.15 V5 Hago 1.00x60B 140 1.8 0.85" WC 85.0
5135 6 Slot 2.5" 1.35 V5 Delavan 1.10x60B 150 2.5 0.85" WC 84.0
6130 6 Slot 2.5" 1.30 V6 Danfoss 1.00x45B 175 2.0 0.65" WC 87.0
Timings
Pre-purge 15 seconds
Post-purge 30 seconds
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test
instruments.
4075 Reverse 2.75" 0.75 Oval Delavan 0.65x60W 150 1 3.6 87.0
4095 Standard 1.75" 0.95 Oval Delavan 0.75x90B 175 3 5.3 85.0
4110 Standard 1.75" 1.10 Oval Delavan 1.00x90B 125 1 3.1 84.0
5100 Standard 2.75" 1.00 None Delavan 0.75x60B 175 1 2.4 87.0
5115 Standard 1.75" 1.15 None Delavan 1.00x80B 130 2 2.8 85.0
5135 Standard 1.75" 1.35 None Delavan 1.20x80B 125 3 3.4 84.0
Timings
Pre-purge 12 seconds
Riello Riello
ECR Oil ECR Oil
Boiler Oil Boiler Oil
Burner Part Burner Part
Model Burner Model Burner
Number Number
Model Model
4075 Reverse 2.75 po 0.75 Oval Delavan 0.65x60W 150 3 5.0 0.25" WC 87.0
4095 Standard 1.75 po 0.95 Oval Delavan 0.75x90B 175 1 4.0 0.25" WC 85.0
4110 Standard 1.75 po 1.10 Oval Delavan 1.00x90B 125 2 5.0 0.25" WC 84.0
5100 Standard 2.75 po 1.00 None Delavan 0.75x60B 175 1 5.0 0.80" WC 87.0
5115 Standard 1.75 po 1.15 None Delavan 1.00x80B 130 2 5.8 0.80" WC 85.0
5135 Standard 1.75 po 1.35 None Delavan 1.20x80B 125 4 5.8 0.80" WC 84.0
6130 Standard 2.75 po 1.30 V6 Delavan 1.00x4 B 175 2 8.0 0.90" WC 87.0
Timings
Pre-purge 12 seconds
Post-purge 30 seconds
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test instru-
ments.
Rated
Pump
Boiler Insertion Firing Combustion Nozzle Nozzle Air Band AFUE
Pressure Head Bar
Model Depth Rate Liner Mfr. Type Setting Efficiency
[PSI]
[%]
4075 3.00" 0.75 OVAL DANFOSS 0.60x60AS 160 0.60/0.65 25% 87.0
4095 3.00" 0.95 OVAL DELAVAN 0.75x45W 160 0.75 35% 85.0
4110 3.00" 1.10 OVAL DELAVAN 0.85x60A 165 0.75 50% 84.0
5100 3.00" 1.00 NONE HAGO 0.75x60B 175 0.75 35% 87.0
5115 3.00" 1.15 NONE DELAVAN 0.85x45A 180 0.85/1.00 40% 85.0
5135 3.00" 1.35 NONE DANFOSS 1.10x60AB 150 1.10/1.25 45% 84.0
Timings
Pre-purge 15 seconds
Post-purge 15 seconds
ECR Oil
Carlin
Boiler Burner
Burner
Model Part
Model
Number
If vent pipe shows any signs of leaking or deterioration, Remove control well from top of rear boiler section every
replace it immediately. five years and clean any scale or sediment deposits from all
parts exposed to boiler water.
If it shows any signs of soot build up, clean vent pipe and
have burner settings and combustion checked by qualified
service agency.
Steps to inspect, clean and/or replace control well: • Continue to circulate water for few hours.
1. Turn off electric service to boiler controls. • Stop firing boiler.
2. Drain boiler water to level below tapping for control • Drain system in a manner and to a location that hot
well. water can be discharged safely.
• Remove plugs from all available returns and wash
3. Remove low water cut-off/limit sensor from control
water side of boiler as thoroughly as possible, using
well.
high-pressure water stream.
4. Unscrew control well from tapping.
• Refill system with fresh water.
5. Inspect portion of control well exposed to water for
scale or sediment buildup.
3. Add appropriate boiler water treatment compounds
as recommended by your qualified water treatment
6. Light deposits may be removed by wiping control well company.
with damp cloth. Wiping probe with cloth soaked in
vinegar will remove more tenacious lime deposits.
4. Testing pH /alkalinity. After boiler and system have
been cleaned and refilled as previously described, test
7. Clean pipe threads of probe to remove old, hardened pH of water in system. Use pH test kit. pH should
pipe dope and other foreign matter. be higher than 7 but lower than 11. Add appropriate
8. Apply moderate amount of good quality pipe dope to water treatment chemicals, if necessary, to bring pH
pipe threads on control well, leaving two end threads within range. Care must be excercised to eliminate all
bare. Do not use PTFE (Teflon) tape. free oxygen in system.
9. Reinstall control well into tapping. 5. Boiler is now ready to be put into service.
10. Reinsert low water cutoff/limit sensor in control well
and secure with grommet.
11. Fill system with water and purge. 18.10 Frequent Water Addition
12. Restore electric service to boiler. Frequent water additions, although unusual for water
13. Fire burner to heat water in boiler 180°F to drive off boilers, are sign a of leaky system. Excessive amounts of
free oxygen. make up water supplied to boiler can significantly shorten
life of boiler. Repair leak and consult with your water
14. Warning – before returning boiler to service: Follow treatment specialist for recommendations.
low water cut-off test procedure in Figure 36, Page 41.
FLUE BRUSH
FLUE BRUSH
BRISTLE
BRUSH
VACUUM
HOSE
21.1 Limit Relay Control (provided) 21.6 Conventional Expansion Tank (Not
Water temperature limit control in limit relay is adjustable. Provided)
See Limit instructions for how to set limit temperature. In a properly assembled system, expanding water flows
into an expansion tank.
21.2 Drain Valve (provided)
• Expansion tank should be sized correctly because
Drain valve is manually operated valve, means of draining improperly installed or sized expansion tank may result
all water from boiler and heating system. Installed in in frequent lifting of relief valve or other heating system
casting below burner door. problems.
21.3 Circulator • It is important to install tank higher than top of boiler.
Connecting pipe from boiler to expansion tank shall rise
• Forced hot water systems require circulator.
continuously up to expansion tank so that air can rise
• Separate circulator or zone valve is required for each into expansion tank.
zone, if there are two or more zones. Circulator must
• Expansion tank is partially filled with air. Air compresses
have capacity to provide circulation required by heating
as water expands, thus forming an air pressure
system.
cushion. This “spring-like” cushion serves to maintain
• Circulator should be connected to supply main and correct operating water pressure regardless of water
must be wired into boiler’s electrical system. “9 - Boiler temperature. This assures a “full measure” of water, even
System Piping” on page 16, for piping configurations in highest radiation unit of the system.
with circulator located on supply main piping using zone
• Tank also serves as trap for excess air in the system. Air
circulators or zone valves.
can cause noises in pipes and inefficient circulation in
• When piping is arranged with zone circulators and no radiators if left in piping system.
bypass piping, circulator provided with boiler may be
• It is possible for a tank to become “waterlogged” (filled
used as zone circulator. Both piping arrangements allow
with water). It can also become overfilled with air when
circulator to pump away from expansion tank and show
filling system with new water. Fittings on tank and in line
how piping should be arranged to allow heating system to
to tank are for bleeding off excess air and water.
be easily purged of air.
• Circulator can be installed on return side of boiler, if 21.7 Diaphragm Expansion Tank (Not Provided)
preferred. Diaphragm type expansion tank takes place of conventional
21.4 Main Air Vent: (Not Provided) expansion tank.
Before system is filled with water, there is air in pipes and • Carefully read instructions packed with your tank
radiation units. Some air will be trapped as system is filled. assembly. Expansion tank should be sized and installed
It is possible to eliminate most of this air through air vents correctly. Improperly installed or sized expansion tank
on radiation units. Main air vent will speed and simplify this may result in frequent lifting of relief valve or other
process. Main air vent should be installed on highest point heating system problems.
in supply main. • Tank typically comes with 10-12 psi air charge. Same as
pressure produced in system by automatic fill valve set
21.5 Automatic Fill Valve (Not Provided) to fill boiler to 10-12 psi with fresh water. When system
Hot water system must be filled with water. Adding new is first filled, tank will fill partially with water. As water is
water, when needed can be done manually (by use of hand heated, and system pressure increases, water expands
valve in water supply line). This requires regular attention into tank and compresses air in the tank. This compressed
to system’s needs. Automatic fill valve or pressure reducing air cushion permits water in the system to expand as
valve accomplishes this without attention. Install in supply temperature changes and assures “full measure” of water,
line on hot water boilers only. Valve operates through even in highest radiation unit of system.
water pressure differentials. It does not require electrical • Diaphragm type expansion tank can be mounted on air
connection. purger fitting or at any other convenient place in supply
or return line. It is recommended to locate diaphragm
type expansion tank in supply line with circulator located
after expansion tank. This configuration allows circulator
to “pump away” from expansion tank for improved air
elimination and system performance.
• Air eliminator fitting or air purger is not provided. Air
eliminator fitting or air purger is used to help remove
air from system before it reaches radiators. It should be
installed in supply line. Air left in system can cause noises
in pipes and inefficient circulation in radiators.
3 10
2
Head (feet)
5
m Head
0
US GPM 5 10 15 20
3
m /h 1 2 3 4 5
Model Watts Volts Amps Capacitor
UP 15-42F 85 115 0.74 10 µF/180 V*
*Fourni avec la pompe
60
INSTALLATION AND CHECK-OUT CERTIFICATE
Installer (Company)
Address
Phone
Installer’s Name
Signature
UTICA BOILERS
2201 Dwyer Avenue
Utica NY 13501
web site: www.ecrinternational.com