Ieee Battery Protection
Ieee Battery Protection
Ieee Battery Protection
4, JULYIAUGUST 1991
Abstract-Growing emphasis on operating reliability is lead- 2) Whereas care is taken to keep other electrical equip-
ing both utility and industrial/commerciaI power system opera- ment free from chemical contaminants or corrosive
tors to confront a long-neglected system protection issue: proper
fault protection for large batteries. Full-load current from a
liquids, the battery inherently requires those potentially
large UPS battery may reach thousands of amperes, with fault destructive agents to do its work. Fumes, corrosion,
currents 10-12 times as high. Battery destruction during a major and possibly explosive conditions all are essential parts
fault can acid-contaminate an entire building, escalating damage of the electrical installation, rather than being carefully
far beyond battery cost or equipment downtime alone. Etisting excluded
IEEE standards, the NEC, other published standards, and sup- 3) The battery is a distributed power source. Its many
plier literature offer little help in applying fuses (seldom mar-
keted with specific dc current or voltage ratings) or circuit
interconnected components take up a wide area, rather
breakers td battery circuits. Often, no protective devices at all than being concentrated within a single compact assem-
are proqided because of a fear of their nuisance operation. Of bly like an alternator or engine. Those components
special concern is the “internal” fault that may go undetected must be readily separable, meaning that numerous “in-
by devices at a battery’s main terminals. This paper will outline ternal” connections are fully exposed to the environ-
some u,ser experience, bring together existing recommendations,
ment and to careless handling and not encased by a
and perhaps stimulate development of useful standard practices.
protective insulation system that can be left undis-
turbed.
WHYBATTERIES
AREDIFFERENT 4) Cell action cannot be shut off by throwing a switch,
closing a valve, or braking some machine to a stop.
A MONG THE energy sources available to modem indus-
trial and commercial power systems, a large storage
battery is unique. Until recently, batteries having terminal
Voltage-and the possibility for destructive short-cir-
cuit current-remains present at the terminals of each
cell, whatever switches are opened or connectors re-
voltages of 250 or more, with capacities of thousands of moved.
ampere hours, were confined to major utility substations or
large switchgear installations in industrial plants such as In addition, unlike other power sources, batteries will
refineries. Today, however, these power sources are becom- usually cause major, widespread damage to other equipment,
ing widely used in data processing facilities. They may be by as well as endangering personnel, when a major failure does
far the highest energy equipment on the premises. The poten- occur.
tial for catastrophic damage from battery failure is often
unappreciated by system designers or users. Within the IEEE Consequences of Battery Failure
and other standards-making agencies, no comprehensive
guidelines exist for the protection of battery circuits from Batteries supplying major loads up to several thousand
such damage. kilowatts at 400-500 V are no longer found only in heavy
Because of their predominance in the United States, the industrial facilities with competent plant engineering and
batteries considered in this paper are of the lead-acid type electrical maintenance staffs. They are going into office com-
[l]. But, similar protective measures are equally important to plexes where the big selling point is that the battery’ is
the nickel-cadmiud type. “maintenance free. (Users neglected their batteries enough
”
Large battery circuit protection is rendered both more as it was; now, their neglect seems to be encouraged by
important and more difficult by the following ways in which product marketing. Put the battery in place, says one sup-
plier, “and put it out of your mind.” Prospective users of
this source of electrical energy differs from others:
large battery systems may find that advice pleasant to hear
1) When it’s needed, it must perform. The control or UPS but would be wise not to take it too seriously [2].) Personnel
battery is the “last resort.” There’s no time to warm it capability in such facilities may be quite limited.
up; it must carry full load at once because nothing else Available short-circuit current can be tens of thousands of
is available. amperes. Faults are not in the “spark” category; rather,
vaporization of large conductors is possible. This current
Paper IPSD 90-11, approved by the Power Systems Protection Committee depends not only upon external circuitry, and battery termi-
of the IEEE Industry Applications Society for presentation at the 1990
Industrial and Commercial Power Systems Annual Technical Conference, nal voltage at the time of fault, but also upon such internal
Detroit, MI, April 29-May 1. Manuscript released for publication January battery conditions as electrolyte level and the state of charge.
21, 1991. The basis for calculating ‘ ‘available” short-circuit current is
The author is with the Electrical Engineering Division, Wisconsin Electric
Power Co., Milwaukee, WI 53201. the so-called “one-minute current” rating of the battery-the
IEEE Log Number 9144793. discharge amperes that will lower cell voltage to 1.75 within
60 sec. Assume a 250-V (nominal) battery capable of sustain- protection available. ” When that “cable” becomes a 0.5 by
ing a 100-kw load for 1 hr. The 1-hr ampere rating of the 5 in busbar, prudence dictates that it not be given the role of
battery will be 100000/250 or 400 A. For one typical make a fuse.
of cell, the 1-min current will be about twice that, or 800 A. Chapter 6 of the Orange Book goes on to indicate how
Leaving aside the minor corrections for state of charge or large battery short-circuit currents can be. But no guidelines
temperature and ignoring intercell connection resistance, the are offered for selection of either fuses or circuit breakers to
calculated short-circuit current would typically be 7000 to protect against such current. The only circuit diagram pro-
10000 A. Large UPS loads today range as high as several vided shows a breaker protecting the battery charger and not
thousand kilowatts so that short-circuit currents of 100 000 A the battery itself. None of the numerous bibliographical
or more are theoretically possible. references touches on the subject.
In practice, as a battery manufacturer has pointed out, Several IEEE standards, such as 450, 484, and 485, are
“one or more intercell connectors will go open circuit within concerned with design and installation of large storage batter-
10 to 15 s.” Unfortunately, that might not interrupt the flow ies. Only one, No. 946 [4], deals with circuit protection for
of fault current any more than vaporized busbars or cables battery systems (written for nuclear generating station appli-
will interrupt an arcing burndown fault in 480-V switchgear. cations, and then only in general terms, it is now being
In battery circuits, as in ac distribution systems, the high-cur- revised to cover other power plants as well). Other docu-
rent “bolted fault” is less likely than the low-current sus- ments, such as NFPA 70B on electrical equipment mainte-
tained burndown. Just as destruction is prolonged and en- nance, NFPA 110 on emergency power sources, or the
larged by the heat and sprayed conductive particles during various NEMA battery standards dealing almost entirely with
the ac fault, in the battery system the scattering of conductive testing, are silent concerning fault protection.
electrolyte escalates the damage. Article 480 of the National Electrical Code applies to “all
What’s more, the rapid spread of acidic smoke can quickly stationary installations of storage batteries. It says nothing
”
bring about catastrophic damage to electronic equipment far about battery circuit protection. At least one pertinent UL
from the fault itself. As an example, a manufacturing plant apparatus standard is in preparation but offers little specific
basement contained a UPS and its battery supply. The batter- advice (UL 1778, drafted in March 1989 for public com-
ies were in a separate, cut-off room, equipped with exhaust ment, titled “Uninterruptible Power Supply Equipment”). A
ventilation, smoke detectors, and automatic sprinklers. Above few paragraphs of this 215-page draft dealt with battery
that, on the first floor, was a large computer room plus other supply circuit protection for UPS installations. Either circuit
offices. breakers or fuses were allowed. Paragraph 25.22 stated “The
At 9:05 one Saturday evening, a smoke detector alarm was battery supply circuit shall be provided with acceptable rated
recorded, followed 3 min later by a sprinkler waterflow dc overcurrent protection to reduce the risk of fire and
alarm. The Fire Department arrived within 4 min to find that electric shock resulting from overload or short-circuit condi-
a short circuit in one battery string had caused a small tions.” The “acceptable rating” was to protect against ex-
explosion and fire, ultimately damaging 15 cells, that the plosion, flame, molten metal, and cracking or bursting of
sprinklers had already extinguished. But the entire basement battery cases, but just how such ratings were to be arrived at
was filled with smoke-necessitating the subsequent cleaning was not specified. Test procedures were not given.
of all the electrical equipment at a cost of $100000. Without
the prompt alarm, plus the battery room separation from the FUSES
IN BATTERY
CIRCUITS
computers, that loss would have been far greater-and this The only definitive book on fuse application [5] devotes
was an exceptionally well-designed and well-equipped instal- nearly 200 pages to the behavior and application of fuses in
lation. all sorts of electric circuits-except battery circuits. The
The extensive application literature available from large word “battery” does not even appear in the book’s index.
UPS suppliers usually offers much detail on battery/charger Whether or not fuses are used at all to protect a battery,
sizing, installation, and maintenance. The following is typical and if so, how the fuses are selected, are matters for individ-
user information: ‘‘The battery represents a significant por- ual engineering judgement in each application. But the deci-
tion of the cost of a UPS package. . . since the battery is the sion can be much more complex in a battery circuit than in an
sole source of power during an outage no shortcuts should be ac power system. That complexity stems from the basing of
taken regarding maintenance and care for the battery. Yet
” modem power fuse technology primarily on ac circuit behav-
these publications are silent concerning circuit protection for ior. Fuses do not work the same way in a dc circuit. Because
this essential back-up power source. low-voltage, high-current dc circuits were so seldom encoun-
tered in industrial or commercial facilities until recently, little
Lack of Protection Guidelines market demand existed to support the testing needed to
Do existing standards offer guidelines concerning battery establish dc fuse ratings or to develop fuses best suited to dc
protection? Almost nothing is published on the subject. As usage. Although the rapid growth in power electronics is
the IEEE Orange Book [3] says in Chapter 6 (“Protection”), changing that, much work remains to be done.
“an area of battery protection often overlooked is overcur-
rent protection. . . a designer should be aware that without dc versus ac Fuse Ratings
overcurrent protection a battery can be damaged and, in some Cautions the “Overcurrent Protection Handbook” issued
cases, the battery cable may inadvertently be the only fuse by one international fuse manufacturer, “A-c rated fuses
660 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 21, NO. 4, JULYIAUGUST 1991
Current
Fig. 1. Fault current versus time in a battery circuit (dashed curves) Number o f time constants following fault
compared with the initial fault current in an ac circuit (solid curve). initiation
Fig. 2. The solid curve is a plot of the time constant function given in the
text. For each time constant period, the circled point represents the RMS
fuse is designed to interrupt when that rate has been present current reached up to the end of that period.
for a time normally much less than half a cycle (Fig. 1).
In the illustration, the shaded area expresses the energy tance, thus
passing on downstream from the fuse for the duration of the i = ( v / ~- )A E - ( R / L ) ~
fault-the "let-through" energy. When the same fuse is used
in a dc circuit, containing some inductance even when a in which A is a constant dependent upon the circuit current
battery is the energy source and the load includes neither flowing at the instant of fault initiation. From that equation,
transformers nor motors, the situation is quite different. short-circuit current should follow a rate-of-rise curve such
Current rise rate is now determined by the circuit L / R ratio. that at the end of one time constant, the current will have
When inductance L is relatively low, current will rise almost reached 63% of its eventual maximum; after two time con-
in step with voltage. The latter does not follow a sinusoidal stants, 87%; and so on-see Fig. 2.
waveform rising at a rate by fixed frequency because no Here is an example of one method that has been used to
alternating frequency exists. Therefore, di / dt can become select battery protection fuses, based on use of such a curve:
extremely high. Result: The fuse blows even faster than in
the ac situation. Battery ampere hours = 330
Expected continuous current load = 48 A
Obviously, that's good, because let-through energy will be
One-minute current rating = 335 A.
held at a relatively safe, low level. What happens, though,
when the circuit inductance is high? Then we find a low Battery short-circuit current [7], [8] is calculated as
value of d i l d t . Fault current rises with time much more
slowly (Fig. 1). The resultant di / d t does not soon create an
arc voltage high enough to begin the arc extinction process.
= ( ampere rating ) (worst-case
1-min initial ) (4.4/K)
cell volts
Worse yet, when time tl is reached, the dc circuit offers no
current zero to promote interruption. Even though actual in which K is a temperature correction factor from IEEE 450
current is well below the peak value, it is able to persist so (1 .O may be used for this example). Thus:
long that the 12t let-through energy to the fault becomes
unacceptably high. I = (335)(2.33)(4.4) = 3440 A.
v)
V
r
0
WI
G
rz
r
0 10 20 30 40
W
r
L/R in milliseconds
c
Fig. 5 . Voltage derating curves for dc use of certain ac-rated fuses, as
0 supplied by one fuse manufacturer.
100 1000
Current in amperes
Fig. 3. Using a battery circuit fault current versus time plot (dashed line) Should the formula involving L / R be applied to the ultimate
to select a suitable fuse rating [lo].
value or to the transient peak?
Furthermore, accurate calculation of L and R is a difficult
*.5 task. The circuit may involve many relatively short lengths of
large cable, bundled in various ways, in differing proximity
to magnetic material such as cable trays. Resistance is vari-
able with battery conditions. All the values will be small so
that slight errors can have major effect.
Voltage Derating of Fuses
The arc voltage that a fuse must withstand will typically be
much higher than the system or source voltage. In a dc
circuit containing both R and L , voltage across the various
inductive and resistive portions will vary as current rises
during a fault. If L / R is high so that current rises slowly,
high voltages will develop across inductive elements of the
circuit, acting in a direction such as to maintain the current
0 o 10o 20o flow. Hence, dc use may subject the fuse to higher voltages
Elapsed time, milliseconds relative to the system level than would be true in ac service.
Fig. 4. One battery manufacturer [9] has suggested this variation in battery That gives rise to a “voltage derating” curve often (though
fault current accompanied by a drop in battery terminal voltage as shown.
This current variation does not suit the simple formula, involving an L / R
not always) used to govern application of ac power fuses in
time constant, cited in the text. dc circuits. Fig. 5 is an example. One supplier uses this
general rule: Rate the fuse for a dc voltage one half its
published ac voltage rating.
When those values are compared with melting curves for a A different concept of voltage derating is offered by an-
typical family of semiconductor fuses, we see from Fig. 3 other fuse supplier. The increased let-through energy prior to
that a 250-A fuse is the highest usable rating. Because the fuse operation is compounded by another effect that is also
maximum continuous current is only 48 A, a 50-A fuse could peculiar to dc behavior. The higher the current-whatever
be used. However, the fuse manufacturer recommends a fuse the time constant-the faster the fuse will operate because the
rating at least double the continuous current to minimize arc tends to establish itself at multiple locations within the
thermal fatigue of the fuse. Therefore, a 100-A rating is fuse chamber. In the absence of ‘a current zero, dc interrup-
selected. (Note: At least one other fuse supplier draws en- tion depends entirely upon the fuse’s ability to divide and
tirely different conclusions from similar curves, emphasizing cool the arc. Therefore, because a lower fault current estab-
that no universally accepted practice exists.) lishes an arc at only one location, extinguishment is more
Unfortunately, this usage of the L / R constant in discus- difficult than with the higher current.
sions of dc fuse behavior is not a true picture because it Unfortunately, just as in the 480-V ac system where the
assumes a constant voltage acting across a constant imped- relatively low-current burndown fault is now widely recog-
ance; hence, an ultimate value of fault current that is also a nized as the greatest hazard, UPS designers are well aware
constant. But battery voltage actually decays rapidly during that low-current battery system faults are more common than
the initial 5 or 10 ms of a fault. Thus, actual current is not a the bolted fault short circuit. A fuse that interrupts relatively
true exponential function but varies with time as in Fig. 4. less predictably on low current can therefore be particularly
Current does indeed stabilize at a value dependent upon troublesome.
battery voltage and circuit resistance. . . but not until after The approach taken by one manufacturer-unpublished,
passing through a transient peak well above that value. but based upon information available upon request-is to
NAILEN: BATTERY PROTECTION- WHERE DO WE STAND 663
VI
600 U
c
0
U
W
VI
575 --
rz,
0
550
L
-g
W
U.
a
+2
525 /
: L + L L J
500
0.01 0.02 0.05 0.1 0.2 0.5 1.0
TABLE I1
MOLDED-CASE
CIRCUIT
BREAKERRATINGSLISTED
BY VARIOUS
MANUFACTURERS
SHOWINGTHE WIDEVARIATIONI N DC
VERSUS
AC CAPABILITY
ac dc ac dc dc lac
240 1251250 10000 5000 0.5
240 250 18000 10000 0.56
240 250 65000 10000 0.15
240 250 22000 10000 0.45
240 250 10000 5000 0.50
240 250 25000 10000 0.40
600 250 -various-
6ooto1000 300 -various-
-
666 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 21, NO. 4, JULYIAUGUST 1991
ing repeated short-time (microseconds) current pulses from itself. When a fuse fails without load on the battery, how-
the battery. If a succession of such pulses is below a preset ever, the condition is likely to go undetected until an emer-
limit, the alarm operates. gency transfer to the battery fails to restore power. Whether
The choice of battery protection- particularly an either-or terminal or midpoint fuses are used, then, blown-fuse indica-
decision between fuses and monitors-is complicated for any tor switches should be provided to cause an alarm whenever
kind of standby system (such as an off-line UPS) by the any fuse opens. Such switches are a readily available fuse
normal absence of any load current. When a battery floats on accessory.
a charger, required to deliver load current only for infrequent Who is responsible for battery protection? Questioning
brief periods, neither thermal nor mechanical stress on com- those experienced in design or application of large battery
ponents is continually present. If it were, weak points would systems elicits conflicting answers. Says one, “In UPS sys-
show up gradually to be observed as they developed, and tem protection of the battery is largely left up to the user.”
timely corrective action could be taken while the problem Of the batteries installed in telecommunications or substation
was still minor. facilities, he added, “98% of them go in without any discon-
However, when the battery must instantly jump from float nect or fuse outside of the charger.” According to one
to peak overload, no one has any chance to respond to a trend battery supplier [7], “The designing engineer must review
alarm indicating that some problem is developing. If that the applicable codes and pertinent factors of the application
problem results in a fault, circuit interruption must be fast before deciding whether or not to install protective
and unequivocal. Whereas a fuse might not do that because devices. . . The designing engineer, however, generally
”
of uncertain selection criteria, a monitor can certainly never does not know what device application information is needed
do it. Even linking monitor output to a circuit breaker will or what is available. Says the battery system expert, “Here
not adequately limit fault let-through energy. are the types of fuses available; go ask the fuse manufacturer
what’s best to use.” The fuse manufacturer, in turn, says
PROTECTION PHILOSOPHY
what’s best to use depends upon the behavior of the battery
Either because of economics, uncertainty about the circuit.
prospects of failure, or the lack of any specific protection Probably few large UPS users are fully aware of the
guidelines in published industry standards, many large batter- overcurrent protection (if any) provided on their battery
ies are not being protected at all. Among these are two system. Nor do UPS manufacturers appear fully aware of the
experimental energy storage systems, one containing 8256 protective options. When asked how fuse or circuit breaker
cells in multiple 2OOO-V strings and the other containing 324 protection was selected, most manufacturers offered no reply.
-
cells, each of more than 2000 A hr capacity, able to supply When this paper was proposed, one of the engineers
0.5 MW. These, however, are carefully observed, well-con- consulted expressed the hope that solutions might be sug-
structed facilities that are still quite new. gested to battery problems that have generated “some real
There is precedent for omitting battery overcurrent protec- horror stories out there. ” Leaving large batteries unprotected
tive devices entirely on the premise that nuisance operation is no answer. For the present, the “real solution” appears to
(taking the battery out of circuit) is potentially more costly be the provision of carefully chosen battery protective de-
than a battery failure [7], [13]. Under NEC Section 430-31, vices to the maximum affordable extent, recognizing that a
for example, normal motor overload protection may be omit- major fault can spread damage far beyond the boundaries of
ted for fire pump drives because even though overloaded, the battery room or the battery circuit. In the long run, the
such a drive could be essential to the control of a fire that industry needs better standards for the selection and use of
could endanger lives and property if allowed to go unchecked. high-power dc protective equipment.
However, the two situations are not quite analogous, as In 1989, recognizing the growing importance of batteries
this comparison shows: in industrial and commercial power systems, the IEEE formed
Possible Consequences a new Standards Coordinating Committee, SCC-29, charged
Failure Nuisance Trip Only with overseeing and coordinating all standards written deal-
UPS Personnel hazard plus Little or no personnel or ing with installation, maintenance, and operation of station-
Battery extensive property loss property damage ary batteries. But although a number of such standards exist,
we clearly need a “protection standard” offering recommen-
Fire Personnel hazard plus Personnel hazard plus
dations concerning protective methods, and guidelines on
Pump extensive property loss extensive property loss
protective device selection, to fill an important gap in the
Thus, although great inconvenience and high monetary loss literature.
can result from a battery nuisance trip, the severity of the
consequences cannot normally be equated with those result- REFERENCES
ing from a serious battery fault-or from any unexpected [l] R. R. Fletcher, “Cell selection considerations,” Trans. IEEE En-
ergy Conv.,vol. EC-1, no. 4, pp. 69-72, Dec. 1986.
suspension in the operation of a fire pump. The more preva- [2] M. F. Migliaro, “Maintaining maintenance-free batteries,” in IEEE
lent opinion [4], [9], [ 151 is that battery systems should have Conf. Paper, Ind. Comm. Power Syst. Conf.(Chicago, IL), May
some sort of overcurrent protection. 1989.
[3] IEEE 446-1987, “Recommended practices for emergency and standby
Nuisance tripping that occurs while a battery carries load, power systems for industrial and commercial applications.”
inconvenient though that may be, will at least call attention to [4] IEEE 946-1985, “Recommended practice for the design of safety-
NAILEN: BATTERY PROTECTION-WHERE DO WE STAND 661
related dc auxiliary power systems for nuclear power generating and commercial switchgear installations,” Trans. IEEE Industry
stations.” Applications, vol. 1A-20, no. 3, pp. 667-671, May/June, 1984.
A. Wright and P. G. Newbery, Electric Fuses. London: Peter
Peregrinus, 1984.
T. M. Cmko, “Current-limiting fuse update-New developments: Richard L. Nailen (M’S-SM’68) was bom in
New style fuse for protection of semiconductor devices,” in IEEE San Jose, CA, on January 2, 1928. He received the
Conf. Paper Petrol. Chem. Industry Conf. (Dallas), Sept. 1977. B.E.E. degree with honors from the University of
“Stationary lead-acid battery systems,” Sect. 50.00, Exide Corp., Santa Clara, CA in 1950.
Form 7637, Jan. 1983. From 1953 to 1964, he was employed in the
F. L. Brennan, “DC distribution system,” Power Plant Electrical Motor Engineering Section, Westinghouse Electric
Reference Series, Electric Power Research Institute, vol. 9, 1987. Corp., Sunnyvale, CA, on electrical and mechani-
G. Walker, “Short circuit characteristics of lead acid batteries,” cal design of ac motors and generators through
unpublished Tech. Bull., C & D Battery Co., Jan. 1987. 19000 kVA. In 1964, he joined the Louis Allis
“Form 101 semiconductor fuse application guide,” Gould Shawmut, Co., Milwaukee, WI, from which he retired in
1981. 1985 as Engineering Specialist, Large Machinery
UL 198L, Standard f o r D-C Fuses f o r Industrial Use (2nd ed.), Engineering, where he was involved in design and application of induction
Mar. 1988. motors to 10000 hp. Now a Project Engineer with Wisconsin Electric Power
“Study of the auxiliaries for lead-acid battery systems for peaking Company in Milwaukee, he is concerned with application, maintenance,
power,” Final Rep. Westinghouse Electric Corp. for Energy Re- repair, and testing of all motors in the utility’s generating stations, as well as
search and Development Administration, U.S. Government Printing with utility customer problems involving motors and controls. He is the
Office, Dec. 1977. author of more than 300 published articles and 20 IEEE papers on motor
E. C. Korbeck, Jr. and J. W. Blankley, “Selection, use, and care of design and application, as well as many other subjects in electrical technol-
stationary batteries for paper mill service,” Trans. IEEE Ind. Gen. ogy, and the 1991 book, Managing Motors. He has presented numerous
Appl., vol. IGA-7, no. 6, pp. 742-749, Nov./Dec. 1971. University Extension courses, seminars, and workshops.
R. G. Brunner, “Auxiliary electrical equipment,” Power Plant Elec- Mr. Nailen is a member of the Petroleum and Chemical Committee of the
trical Reference Series, Electric Power Research Institute, vol. 7, IEEE, the Power Systems Engineering Committee, the Professional Commu-
1987. nications Society, Tau Beta Pi, the National Fire Protection Association, and
B. Bridger, Jr., “Control and auxiliary power systems for industrial is a registered Professional Engineer in the State of Wisconsin.