PROJECT

LOCATION
CLIENT
CONSULTANT
Date
Area or Sun Gain or
Item Factor Btu/Hour
Quantity Temp. Diff.
ROOM HEAT
ROOM SENSIBLE HEAT
Solar Gain - Glass
Glass - N SqFt x 28.00 F x 0.59 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x 163.00 F x 0.59 0.00
Glass - SE SqFt x F x 0.00
Glass - S SqFt x 14.00 F x 0.59 0.00
Glass - SW SqFt x F x 0.00
Glass - W SqFt x 163.00 F x 0.59 0.00
Glass - NW SqFt x F x 0.00
Skylight SqFt x F x 0.00
Solar & Transmission Gain - Walls & Roof
Wall - N SqFt x 17.00 F x 0.41 0.00
Wall - NE SqFt x F x 0.00
Wall - E SqFt x 36.00 F x 0.41 0.00
Wall - SE SqFt x F x 0.00
Wall - S 0.00 SqFt x 31.00 F x 0.41 0.00
Wall - SW SqFt x F x 0.00
Wall - W 0.00 SqFt x 46.00 F x 0.41 0.00
Wall - NW SqFt x F x 0.00
Roof 0.00 SqFt x F x 0.00
Transmission Gain - Except Walls & Roof
All Glass SqFt x 20.00 F x 0.00
Partition 0.00 SqFt x 15.00 F x 0.41 0.00
Ceiling 0.00 SqFt x 15.00 F x 0.41 0.00
Floor 0.00 SqFt x 15.00 F x 0.41 0.00
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 20.00 T.Diff x 1.08 0.00
Ventilation Air 0.00 CFM x 20.00 T.Diff x BF x 1.08 0.00
Internal Heat
People 0.00 Nos. x 0.00 Btu/Hour Per Person 0.00
Lighting 1.20 SqFt x 0.00 W/SqFt x 3.41 0.00
Equipments 1.00 SqFt x 0.00 W/SqFt x 3.41 0.00
Power kW/Hp x 0.00
Sub Total 0.00
Factor 5-10% 0.00
Effective Room Sensible Heat 0.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 20.00 Gr/Lb x 0.68 0.00
Outside Air 0.00 CFM x 20.00 Gr/Lb x BFx0.68 0.00
People 0.00 Nos. x 0.00 Btu/Hour Per Person 0.00
Sub Total 0.00
Factor 2.5 - 5% 0.00
Effective Room Latent Heat 0.00
EFFECTIVE ROOM TOTAL HEAT 0.00
OUTSIDE AIR HEAT
Sensible 0.00 CFM x 20.00 F(TD) x CF x 1.08 0.00
Latent 0.00 CFM x 20.00 Gr/Lb x CF x 0.68 0.00
OUTSIDE AIR TOTAL HEAT 0.00
GRAND SUB-TOTAL HEAT 0.00
Factor 1 - 3% 0.00
GRAND TOTAL HEAT 0.00
TONS=GRAND TOTAL HEAT/12000 0.00
FLOOR 15th
SPACE REFERENCE 0.00
AREA ( SqFt) 0.00
Height (Ft) 10.00
Volume (CuFt) 0.00
Estimate for Summer
W
Design Conditions DB (F) WB (F) RH (%) SH Gr/Lb
Ambient 106.00 100.00
Room 86.00 80.00
Difference 20.00 - - 20.00

By Pass Factor (BF) = 0.30


Contact Factor (CF = 1 - BF) = 0.70
CFM Ventilation
CFM Per Person 15.00 x 0.00 No 0.00
CFM Per SqFt 1.25 x 0.00 = 0.00
Air Change Per Hour (CFM) =
CFM Cu.ft 0.00 x 0.00 x1/60 = 0.00
CFM Infiltration
Swinging x cfm/door = 0.00
people 0.00 x 6.00 cfm/door = 0.00
Open Doors 0.00 x 30.00 cfm/door = 0.00
Crack (feet) x 20.00 cfm/ft = 0.00
0.00
Supply CFM from Machine
Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = #DIV/0!
Apparatus Dew Point (ADP)
Indicated ADP (°F) =
Selected ADP (°F) = 58.00
Dehumidified Rise
(Room DB - ADP) x CF = 19.60
DEHUMIDIFIED AIR QUANTITY
Effective Room Sensible Heat = 0.00 CFM
Dehumidified Rise x 1.08

= 0.00 L/s
TOTAL HEAT CAPACITY
Grand Total Heat = 0.00 TR
1.00 SENSIBLE HEAT CAPACITY
Grand Sensible Heat = 0.00 TR
12,000.00

2.00

3.00
4.00
Notes: